Nordyne E3 User Manual

Downfl ow, Upfl ow Electric Furnaces
Owners Manual/Installation Instructions
E3 Series (Air Conditioner/Heat Pump Air Handler)
IMPORTANT: Read this owner information to become familiar with the capabilities and use of your heating appliance. Keep this literature where you will have easy access to it in the future. If a problem occurs, check the instructions and follow recommenda­tions given. If these suggestions don’t eliminate your problem, call the appropriate NORDYNE distributor. A distributor service list is included with this appliance.
WARNING:
Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance. Improper installation, adjustment, alteration, service or maintenance can cause injury, property damage, or death. Refer to this manual. For assistance or additional information consult a qualifi ed dealer or service agency. To avoid personal injury or property damage, ask a service technician to inspect the furnace and to replace any part of the control system which has been under water.
SECTION 1. OWNER INFORMATION OPERATING INSTRUCTIONS Before Operating System
Before operating your heating/cooling system (see Figure 1), make sure that:
• Control panel covers are closed.
• Blower and/or relay control plugs are plugged in.
• Fan switch is set to “AUTO” (E3EH units only).
CAUTION:
No user serviceable parts inside control panel. DO NOT OPEN.
• Circuit breakers are in “ON” position.
• All power supply switches for furnace and outside unit (if installed) are turned on.
• Furnace door is closed and properly latched.
Refer to the owner’s manual supplied with the optional heat pump or air conditioner for further information.
CAUTION:
For optional A/C or H/P systems, always wait at least fi ve minutes after the system shuts off before restarting the system. Observe this procedure when operating the system per the following instructions.
2
10 20 30
Temperature Selector
Temperature Scales
System Switch (optional sub-base)
Fan Switch (optional sub-base)
50 60 70 80 90
SYSTEM
HEAT OFF COOL
VENTILATE
ON AUTO
Indoor Coil (optional)
Coil Air Filters
(used with indoor coil)
Furnace Air Filter
(NOT used with
coil air filters)
Blower
Circuit Breakers
Data Label
Control Panel
Cover (left)
Figure 1. Furnace Parts Identifi cation
Product Type
E - Electric Furnace
Generation
EB - A/C Blower Equipped Relay
EX - Multi-Speed, X13 Motor
Used with Platinum Series
3 - Third Series
Product Identifier
Control Panel Cover (right)
E 3 EB - 010 H
Electrical Code
H - 240-1-60
Primary Capacity
010 - 10 kw 012 - 12 kw 015 - 15 kw 017 - 17 kw 020 - 20 kw 023 - 23 kw
Model Identifi cation
3
To Operate System in Cooling Mode
NOTE: The “FAN ON/FAN AUTO” (fan switch)
and “HEAT/OFF/COOL” (system switch) are located either on your thermostat (if it’s supplied with a sub-base) or on the relay box added to your furnace.
1. Make sure blower selector switch is on “Auto.”
2. Set fan switch to “AUTO.”
3. Set system switch to “COOL.”
4. Set thermostat temperature selector to desired comfort level.
To Operate System in Heating Mode
1. Make sure blower selector switch is on “Auto.”
2. Set fan switch to “AUTO.”
3. Set system switch to “HEAT.”
4. Set thermostat temperature selector switch to desired comfort level.
NOTE: Allow at least one hour for the room tem­perature to stabilize before you make a second adjustment to the thermostat setting. Once the desired comfort level is established, make only small adjustments to the thermostat setting to meet changing temperature conditions.
To Operate Blower Continuously
1. Set blower selector switch to “ON” for summer air circulation only (see Figure 1),
OR
2. If thermostat is equipped with optional heating/cooling sub-base or relay box (see Figure 1), set fan switch to “ON.”
To Balance Air Distribution
1. On a typical day, set thermostat selector to desired comfort level and operate system for several hours with all air registers open.
2. With system on, check temperature in all rooms.
3. Partially close registers in rooms that are too warm (in heating mode) or too cool (in cooling mode) and in rooms that are infrequently occupied.
4. Re-check room temperature and adjust registers as needed.
To Shut Off System
1. Make sure blower selector switch is on “Auto”.
2. Set thermostat temperature selector to lowest temperature setting, OR...
3. For thermostats with optional sub-base (see Figure 1), or for systems with relay box, set system switch to “OFF.”
WARNING:
To prevent hazard of electrical shock and injury from moving parts, be certain the thermostat is off and the furnace circuit breaker(s) are in the “OFF” position before servicing. Close and properly latch the outer door after doing the following recommended maintenance.
MAINTENANCE INSTRUCTIONS
Regularly NOTE: If a cooling coil is installed, furnace
fi lter is not used.
1. Replace furnace air fi lter (see Figure 1), OR...
2. Remove coil fi lters, wash, and allow to dry. Re-install coil fi lters to original positions.
3. Vacuum or wipe clean interior of furnace cabinet.
4. Clean all lint and dust from around fur­nace.
Every Six Months
1. Vacuum or wipe away any dust or lint on blower motor.
Before Each Heating Season NOTE: If a cooling coil is installed, furnace
fi lter is not used.
1. Replace furnace air fi lter (see Figure 1),
OR
2. Remove coil fi lters, wash, and allow to dry. Re-install coil fi lters to original positions.
3. Have a qualifi ed serviceman inspect all furnace components and fi eld wiring and clean and service heating system as needed. If this furnace was installed with aluminum power supply wiring, have ser­viceman periodically check all connections to prevent possible equipment failure and/or fi re hazard. Do not attempt any service function yourself which requires opening furnace control panel covers.
4
BEFORE YOU CALL A SERVICEMAN
1. Make sure thermostat temperature selector is set above room temperature for heating or below room temperature for cooling. If thermostat is equipped with heating/cool­ing sub-base, make sure system switch (see Figure 1) is set to “HEAT” for furnace operation or set to “COOL” for optional air­conditioning operation.
2. Check main household service panel to see if appropriate circuit disconnect(s) for appliance power supply is on.
3. Refer to instructions under Before Operating System for pre-operation checks.
4. Refer to instructions under Before Each Heating Season for maintenance proce­dures and recommended service checks.
5. Refer to owner’s manual provided with optional air conditioner or heat pump (if installed) for service and maintenance.
NOTE: All servicing of this heating appliance other than the normal maintenance described in this section must be done by authorized trained service personnel. Do not open the control panels (see Figure 1) at any time.
Please specify the complete model and serial numbers shown on the furnace data label (see Figure 1) for all warranty service and when or­dering replacement parts or optional equipment. Refer to the replacement parts list provided with the furnace for part numbers.
OPTIONAL AIR CONDITIONER AND HEAT PUMP
Your E3 Series electric furnace is approved for use with an optional central air conditioner or a heat pump. To adapt this heating appliance to a “total comfort system,” contact your nearest NORDYNE distributor.
SECTION 2. INSTALLER INFORMATION GENERAL
These instructions and specifi cations are pri­marily intended to assist qualifi ed individuals experienced in the proper installation of home heating and air conditioning appliances. Some local codes require licensed personnel for the installation and service of this type of equip­ment. Approved installation, operation, and maintenance of this central heating system appliance must be in accordance with the listed specifi cations contained in these instructions and other documents supplied with the furnace and/or optional air conditioning equipment. Refer to local authorities having jurisdiction for further information.
Before beginning installation, read these instruc­tions thoroughly. Follow all warnings and cautions in the instructions and on the unit.
Improper installation, service adjustment, or maintenance can cause explosion, fi re, electri­cal shock or other conditions which may result in personal injury or property damage. Unless otherwise noted in these instructions, use only factory-authorized kits and accessories when modifying this product.
Overview of E3 Furnace
E3E(-) Series electric furnaces are available in two models. E3EH models are equipped with the standard two-speed blower. E3EH models can be easily converted for use with NORDYNE split­system air conditioners and heat pumps. E3EB models are air-conditioning ready; that is, they are equipped with a multi-speed (four-speed) blower, blower relay, and cabinet insulation kit. See Table 3 for cooling and heat pump availability with factory installed blower.
Optional air conditioners and heat pumps are listed by Underwriters’ Laboratories (UL) or Environmental Testing Laboratories (ETL) and certifi ed by ARI and the Canadian Standards Association (CSA), or Warnock Hersey or ETLC. These cooling systems include energy-sav­ing components to provide maximum cooling performance at electrical energy usage levels established by federal standards. Refer to the operation instruction label on your furnace for the optional air conditioning equipment approved for your heating appliance.
For typical unducted return air downfl ow applica­tions, an air-conditioner or heat-pump coil can be installed by mounting the coil directly on top of the furnace without adding sheet metal cavities or cutting and trimming wood panels.
A return air grille for closet or alcove installations is available. For downfl ow alcove installations, the grille (with frame provided) may be attached to the top of the furnace and all paneling and trim fl ushed to it. This installation provides an access door for future installation of NORDYNE air conditioning or heat pump coils on top of the furnace.
5
Power entrance for all models may be through the right side or through the bottom of the unit (when viewing the unit in a downfl ow position).
UNIT CHECKOUT
Before installing this furnace:
1. Inspect unit for possible shipping damage. If shipping damage is found, fi le claim with transportation company.
2. Record furnace model number and serial number (see furnace data label) for future reference.
3. Carefully read all instructions supplied with optional equipment to be installed with furnace.
CODES, SPECIFICATIONS, AND REQUIREMENTS
Furnace Codes
Installation and wiring of this furnace, as well as the design and construction of the home duct system, must be in accordance with one or more of the following codes:
• HUD MANUFACTURED HOME CONSTRUC-
TION AND SAFETY STANDARD (Title 24, Part 3280)
• American National Standards (ANSI) A119.11, C1-NFPA 7 (National Electrical Code)
• CANADIAN STANDARDS (C.S.A.) Z240.6.1, and Z240.9.1.
All local codes having jurisdiction shall also apply.
Air Duct Codes and Specifi cations
Air ducts must be installed in accordance with National Fire Protection Association standards NFPA 90A and NFPA 90B, these instructions, and all applicable local codes.
• Materials: Air ducts must be aluminum, tin plate, galvanized sheet steel, or other approved materials for outlet or return air ducts.
• Construction: Snap-Lock or Pittsburgh-Lock seams are preferred. All other types of seams must be made tight to prevent leakage.
• Sizing: Supply duct system must be designed for proper air distribution. Static pressure measured externally to furnace shall not ex­ceed static pressure rating listed on furnace nameplate.
• Location of Openings: Duct system must be designed so that no supply registers are lo­cated in duct system directly below furnace.
Listing agency(s)
Approved Installation Confi gurations
Accessibility for Servicing Minimum of 18"(46cm) required in front of unit.
Minimum Clearance to Combustibles
Minimum return air opening required (total free area)
Return air grille (closet or alcove installation)
May vary by model, check the unit data label for applicable agency listing mark.
Approved for: single/multistory residential or mobile/ modular/manufactured structures. Upfl ow, downfl ow, (freestanding/closet/alcove)
0" from all surfaces of furnace cabinet, ducts, optional coil housing and plenum connector. No separate subbase required for installations on combustible ooring.
200 in (1290 cm ) heating only* 235 in (1516 cm ) A/C or H/P up to 4 ton installed 250 in (1613 cm ) A/C or H/P up to 4 ton w/1" clearanced installed 390 in (2516 cm ) A/C or H/P up to 5 ton installed *or return air grille and frame assembly p/n 902989 or wall mount grille p/n 902999
Use return air grille and frame assembly P/N 902989 or equivalent for alcove installation. Use wall mount return air grilled P/N 902999 or equivalent for closet installation. 155 in (1000 cm ) must be added for 5 ton A/C or H/P system.
Table 1. Miscellaneous Listings & Installation Requirements
6
Return Air Codes and Requirements
Unducted return air systems may be used for closet or alcove installations.
NOTE: Applicable installation codes may limit the furnace to installation in a single-story residence only. Furnace installations other than closet or alcove installations require ducted return air systems.
Air return to the furnace must have a minimum free area opening (see Table 1).
Acceptable fl oor or ceiling return air systems for closet installations with return air entering through an opening in the closet fl oor or ceiling must meet all of the following requirements:
• Return air opening into closet, regardless of its location, must not be smaller than size specifi ed on unit data label.
• If located in fl oor of closet, return air opening must be provided with means of preventing its inadvertent closure by a fl at object placed over opening.
• Materials located in return air duct system must have a fl ame-spread classifi cation of 200 or less.
• Noncombustible pans having 1” upturned fl anges must be located beneath openings in a fl oor-return duct system.
• Wiring materials located in retur n duct system must conform to NEC Article 300-22(c).
• Gas piping must not run in or through return air duct system.
• If return air opening is located below top of furnace, a minimum clearance must be provided between opening and furnace (see “Accessibility for servicing” in Table 1).
Closed-Off Space Requirements
Living space not served by, and closed off from, the return air ducts to the furnace by doors, sliding partitions, and other means must be provided with permanent, uncloseable openings in the doors or partitions to allow air to return to the furnace from all parts of the home. Return air grilles, with a minimum open area of one square inch for every fi ve square feet of living space closed off from the furnace, must be provided in the door or room partition.
OPTIONAL EQUIPMENT
Contact your nearest NORDYNE distributor for a complete list of electric furnace accessories.
Return Air Grille
A return air grille and frame assembly (see Figure
2) is available for use in unducted return air instal­lations. In downfl ow alcove installations, the grille and frame assembly may be mounted directly to the top of the furnace. In closet installations, a wall mount grille is available for attachment to a door or wall.
Optional Automatic Furnace Damper #901083 -
Furnace may (not required) be equipped with the optional automatic damper when a packaged air conditioner is installed and connected to the warm air duct system. This damper prevents cooled air from discharging through the furnace cabinet, causing excessive cooling of the immedi­ate area. Refer to instructions supplied with the damper for details.
Multi-Speed Blower Conversion Package (4 or 5 ton):
Upgrade blower packages are available for adding air conditioning or heat pump systems. See furnace “Options and Compatibility” label for systems available.
TYPICAL INSTALLATION OF DOWNFLOW SYSTEMS OR PLATINUM SYSTEM
The following steps describe installation instruc­tions for an under-the-fl oor supply duct system with a return air system that can be either unducted or ducted. Duct connectors (Table 4) are recommended for this application. NOTE: Before installing this furnace, consider all clearances for the installation and future servicing of the furnace. Refer to Table 1.
Return Air and Filtering Systems
Furnaces may be installed with unducted or ducted return air. For unducted return air systems, either the optional grille and frame assembly or the optional wall mount grille is rec­ommended. For ducted return air systems with air conditioners or heat pumps, either providing an access panel in the duct or using the optional coil cabinet is recommended. The duct system must be properly sized so as to account for any additional external static pressure produced from the chosen fi ltering method.
7
20" (508 mm)
Cabinet
Insulation
Upflow Coil Cabinet
23 3/4" (603 mm)
29" (737 mm)
1
2
3
4
7
8
27" (686 mm)
29" (737 mm)
20"
(508 mm)
23 3/4"
(603 mm)
Item Number
(See Figure)
Description
4-Speed Blower
1
4 Ton - See notes: 1 & 5 5 Ton - See Note: 1
2 3
4
5
6
A.C./H.P. Relay Control See Note: 1 Cabinet insulation Kit See Notes: 1 & 5 A-Coil Conversion Kit See Note: 2
Coil Cabinet See Note: 3
Upfl ow Stand See Note: 4
7 A/C and H/P Indoor Coils 8
Notes:
1) For A/C and H/P use.
2) Includes coil fi lters.
3) For upfl ow or downfl ow installations.
4) For upfl ow A/C or H/P installations (includes one fi lter; use fi lter from furnace to complete fi ltering system in this acces­sory).
5) Standard in EB models.
Return Air Grille and Frame
Table 2. Optional Air Conditioning and
Heat Pump Equipment
11/16"
20-1/8"
(511 mm)
3"
(76 mm)
24 3/4” (628 mm)
Figure 3. Optional Rear Mounting Plate
(17 mm)
(P/N 389080)
NOTE: See Table 2 for descriptions
Figure 2. Optional Accessories
8
Upflow Stand
and notes
20” (508 mm)
20” (508 mm)
Electric Furnace Models
Rated Heating Output, Btuh
(see note 1)
Watts (Total kw, Heating
Elements and Blower)
Supply Voltage 240 Volts/60Hz/1-Phase
Heating Elements,
No.(Total kw)
Blower Wheel Size 10.5" Dia., 8" Wide
Motor Speed,
H.P. Rating, Amps
Test ESP, in. w.c. Max 0.3
Optional Cooling Available with
factory installed blower
Optional Heat Pump Available
with factory installed blower
Air Filter (Standard) 16" x 20" x 1" (nominal)
Furnace Dimensions Width-20" (508mm), Height-29" (737mm) (see note 2), Depth-24 1/2" (623mm)
Table 3. Unit Specifi cations
E3EH
010H 012H 015H 017H 020H 023H
35,000 41,000 53,000 57,000 70,000 75,000
10.4 12.0 15.4 16.6 20.4 22.0
2 (10.0) 2 (11.6) 3 (15.0) 3 (16.2) 4 (20.0) 4 (21.6)
2 Speed, 1/5 HP, 2.0
2.0 - 3.0 Ton (see note 3)
2.0 - 3.0 Ton (see note 3) n/a (see note 3)
Electric Furnace Models
Rated Heating Output, Btuh
(see note 1)
Watts (Total kw, Heating
Elements and Blower)
Supply Voltage 240 Volts/60Hz/1-Phase
Heating Elements,
No.(Total kw)
Blower Wheel Size
Motor Speed,
H.P. Rating, Amps
Test ESP, in. w.c. Max 0.3
Optional Cooling Available with
factory installed blower
Optional Heat Pump Available
with factory installed blower
Air Filter (Standard) 16" x 20" x 1" (nominal)
Furnace Dimensions Width-20" (508mm), Height-29" (737mm) (see note 2), Depth-24 1/2" (623mm)
Electric Furnace Models
Rated Heating Output, Btuh
(see note 1)
Watts (Total kw, Heating
Elements and Blower)
Supply Voltage 240 Volts/60Hz/1-Phase
Heating Elements,
No.(Total kw)
Blower Wheel Size 10.5" Dia., 8" Wide
Motor Speed,
H.P. Rating, Amps
Test ESP, in. w.c. Max 0.3
Optional Cooling Available with
factory installed blower
Optional Heat Pump Available
with factory installed blower
Air Filter (Standard) 16" x 20" x 1" (nominal)
Furnace Dimensions
1. Heating output rated at listed voltage. For outputs at voltages other than 240V, multiply Btuh rating by the following factors: x 0.92 (230V), x 0.84 (220V), x 0.75 (208V)
2. Height is 56” with return air grille installed, 58” with coil cabinet and 72” with coil cabinet and upfl ow stand.
3. The factory installed blower for the EH models can be replaced with a multi-speed blower allowing the units to accept up to 5 tons of air conditioning or 4 tons heat pump.
4. The factory installed blower for the EB models can be replaced with a multi-speed blower allowing the units to accept up to 5 tons of air conditioning.
010H 012H 015H 017H 020H 023H 023H 5-Ton
35,000 41,000 53,000 57,000 70,000 75,000 75,000
10.4 12.0 15.4 16.6 20.4 22.0 22.0
2 (10.0) 2 (11.6) 3 (15.0) 3 (16.2) 4 (20.0) 4 (21.6) 4 (21.6)
4 Speed, 1/3 HP, 2.9
2.0 - 4.0 Ton (see note 4) 2.0 - 5.0 Ton
010H 012H 015H 017H 020H
35,000 41,000 53,000 57,000 70,000
11.4 13.0 16.4 17.6 21.4
2 (10.0) 2 (11.6) 3 (15.0) 3 (16.2) 4 (20.0)
Multi-Speed, 3/4 HP, 6.0
2.0 - 4.0 Ton
2.0 - 4.0 Ton
Width-20" (508mm), Height-29" (737mm) (see note 2)
Depth-24 1/2" (623mm)
E3EB
2.0 - 4.0 Ton
E3EX
11" Dia.,
8" W
4 Spd,
3/4HP 3.8
Amps
9
NOTE: Refer to the instructions supplied with
A
B
19”
(483 mm)
19"
(483 mm)
TOP VIEW
X
Reducer
*Felt Seal
Corner
Spacers
C
*OPENING TO DUCT A= 13-1/4" (337 mm)
B= 10-3/4" (274 mm) WITH PLATE (C) REMOVED OPENING BECOMES 13-1/4” x 13-1/4”
*Indicates only applicable for Finger Tab Duct Connector
x
SUPPLY AIR DUCT
FLOOR CAVITY
Frame
Top of
Furnace
Fasteners (4)
Grille
Furnace Filter
(not used with
A/C or H/P)
any additional accessories for further installa­tion details.
(see Figure 3) supplied with the duct connec­tors is recommended for use with this type of installation.
Filtering Methods - Non-Ducted Return Air
1. Without A/C or H/P uncased coil:
- use the fi lter supplied with the furnace; ensure that the fi lter is installed mat side down between the fi lter retainer and furnace top (see Figure 4).
2. With A/C or H/P uncased coil:
- use the optional coil fi lters; the fi lter sup­plied with the furnace is not used; REMOVE AND DISCARD THIS FILTER.
3. With optional coil housing:
- see coil cabinet instructions for specifi c fi ltering methods.
Filtering Methods - Ducted Return Air
1. Without optional coil housing:
- install a fi lter with a minimum unrestricted medium area of 324 square inches in the duct above the coil that is accessible for monthly cleaning or replacement by hom­eowner.
2. With optional coil housing:
-install a fi lter with a minimum unrestricted medium area of 324 square inches in the duct above the coil that is accessible for monthly cleaning or replacement by hom­eowner.
Selecting Duct Connector
Non Platinum Duct Connector
1. Determine depth of fl oor cavity from surface of fl oor to top of supply air duct (see Figure
5).
2. Select appropriate model from Table 4 which matches X-dimension of fl oor cavity. To maximize air delivery, remove reducer (C in Figure 5) to obtain largest open area that will fi t duct/fl oor construction.
NOTE: Duct connectors may be
installed in any one of four positions.
Platinum Duct Connector
1. The 14” round duct connector (903896) is designed to connect directly to a 14” fl ex­duct.
Optional Duct Connectors for Downfl ow Systems
Duct connectors are recommended for heated air distribution in under-the-fl oor duct systems. With this system, furnaces may be installed on combustible fl ooring without a separate sub­base. Also, the furnace rear mounting plate
10
Figure 5. Duct Connector Selection (Non-Platinum)
Figure 4. Grille Support Frame and Grille
Assembly
Preparing Floor Opening(s)
2-3/8" MIN (60 mm)
"
6-1/4
23-3/4"
(603 mm)
20
"
3/4"
"10
14-1/2"
(368 mm)
3" (76 mm)
"4-1/4 "5
"3-3/8
REAR WALL OF ENCLOSURE
Furnace Outer Door
Optional Supply Wire
Entrance
Optional
Refrigerant
Line
(Not required
for Platinum)
Center Line
17"
(432 mm)
14-1/2"
(368 mm)
16-5/8"
(422 mm)
(254 mm)
(86 mm)
(127 mm)
(108 mm)
(159 mm)
(19 mm)
(508 mm)
3-3/4"
(95 mm)
Furnace Outline
A/C Or HP
1. Mark fl oor opening(s) as shown in Figure
6. Provide minimum clearances at rear and right side walls of closet or alcove for installation of furnace and wiring.
2. Cut fl oor opening on outside edge of marked line so that opening is slightly larger than area marked.
3. Additional provisions may be necessary for optional air conditioning or heat pump if refrigerant lines are installed elsewhere than at the front of the furnace.
4. The refr igerant and entrance supply opening dimensions may be adjusted ± 1/2”.
Installing Duct Connector
NOTE: The duct connector is designed for use
on ducts down to 12” wide. On typical ducts, the fi nger tab duct connector may be installed using Method B. On narrow ducts, there may be insuffi cient clearance to bend the tabs on two sides of the fi nger tab duct connector. In such
If "X"
oor cavity is:
English
Metric
(mm)
Use Duct Connector
Model Part Number Finger
Tab
Screw
Down
7/8" 22 901987 904008
2" 51 901988 904009 4 1/4" 108 901989 904010 6 1/4" 159 901990 904011 8 1/4" 210 901991 904012
10 1/4" 260 901992 904013 12 1/4" 311 901993 904014
Table 4. Floor Cavity Sizes
cases, use Method C or D. For screw down duct connector use method E. For Platinum models always use method A.
Method A - Platinum Series
NOTE: Flex duct used must have a minimum
temperature rating of 200
° F and meet all
other applicable codes and standards.
1. Place duct connector through opening in fl oor. See Figure 9.
2. Connect 14” supply duct.
Figure 6. Downfl ow Floor Cutout Locations (nominal dimensions)
11
Rear Wall
Cut-out Area
Optional Supply Entrance
Mounting Plate
Floor Opening
Refrigerant Line Opening
Supply Air Duct
Cut Duct Opening 1/16th. Larger Than Plenum Connector
Rear Wall
Secure Duct Connector & Mtg Plate With 2 Flat Head Screws or Nails At Dimpled Locations
Refrigerant Line Opening
Supply Air Duct
Mounting Plate
Plenum
Bend Connector Tabs Under Duct Opening
Figure 7. Rear Mounting Plate
Figure 8. Duct Connector (Non Platinum)
Method B
1. Place duct connector through fl oor opening with bottom tabs resting on top of supply air duct. Mark cutout area around inside of tabs.
2. Remove duct connector and cut out duct opening slightly larger than area marked.
3. If using optional rear mounting plate (sup­plied with duct connector), install it to back edge of fl oor opening (see Figure 7). Re­install duct connector in fl oor opening. A shim may be used, if necessary, to ensure the furnace is level.
12
4. Secure duct connector to fl oor with two fl at-head fasteners at dimpled locations (see Figure 8).
5. Secure connector to duct by bending bottom tabs under and up against duct surfaces (see Figure 10).
Method C
1. Attach tabs to sides of duct (one on each side) using sheet metal fasteners or other method, ensuring that the duct connector is secure and sealed to the duct (see Figure
11).
2. Seal the duct fl ap edges with an approved tape or compound for a leak-free joint.
Figure 9. Platinum Duct Connector
Mounting Plate
Duct
Connector
Secure Duct Connector and Mounting Plate with 2 Flat-Head Screws or Nails
14" Supply Connection
TABS
DUCT
1. INSERT DUCT CONNECTOR INTO DUCT CUT-OUT
TABS
DUCT
2. BEND BOTTOM TABS OVER AND ONTO THE UNDER-
NEATH DUCT SURFACE
Method D
1. Score and cut top of metal duct as indicated in Figure 12, Step 1 or Step 2. If using Step 1, also cut out metal from the shaded area “A”.
2. Fold the duct fl ap “B” up (see Figure 12, Step 3).
3. At the front-to-back of duct run (see Figure 12, area “A”), bend the duct connector tabs and secure them directly to the duct.
4. At area “B”, bend the duct connector tabs up and back over, around the duct connector (see Figure 12, step 3).
5. Fold/form the duct fl ap against the side of the duct connector and attach as shown (see Figure 12, Step 4). Use at least three staples on each duct fl ap OR... if a 2X block/joist is not provided, use at least two sheet metal fasteners on each duct fl ap.
6. Seal the duct fl ap edges with an approved tape or compound for a leak-free joint.
Method E
1. Apply a bead of caulking, mastic, or other approved sealant around bottom side of 1/2” fl ange and restrictor plate, when ap­plicable.
Figure 10. Duct Connector Installation B
13
2. Locate the duct connector over duct and
Staple Folded Duct
Flap (typ) to side of
Duct Connector
Duct
STEP 4.
Cut- Out Area "A"
STEP 1.
"B"
"B"
Cut- Out
Area"A"
Fold Back Flap "B"
Fold Back Flap "B"
Top of Duct
"A" "A"
"B"
"B"
Fold Back Flap"B"
Cut
Lines
Duct
Fold Back Flap"B"
STEP 2.
STEP 3.
Bend Duct Connector Tabs Up
and Over- (along length of duct)
Duct Flap "B"
Duct
Duct
Duct Connector
Narrow Duct
carefully lower screw down duct connector into place.
3. Once duct connector is located on duct, temporarily hold in place while fastening duct connector to the fl oor using fl at head screws or nails. Be sure fl anges of duct connector stay in contact with the duct.
4. Screw duct connector to duct making sure a seal is made between the duct and the duct connector. Additional screws may be added if required.
5. Cut away duct along edge of duct connector fl ange allowing the center to drop into the duct. Remove section of duct with caution, as edges will be sharp.
Alcove Installation
1. Cut alcove rough openings to minimum dimensions shown in Figure 13.
2. Attach frame assembly with four fasteners (provided or equivalent) into pre-punched holes on top of furnace (see Figure 5).
3. At manufacturers discretion, if additional securing is required attach each side of frame assembly to alcove opening using holes provided.
4. Attach return air grille to frame assembly by hooking grille over fl ange on top of frame and into channel on bottom.
Closet Installation
NOTE: For closet installations, the return air
grille mounting frame is not used since the furnace is located inside the closet (see Figure 14 and 15).
1. Cut return air opening in desired position in door or wall, preferably above top of fur­nace. Refer to Table 1 for return air opening requirements.
2. Insert four fasteners, securing grille to door or wall.
Figure 11. Alternate Duct
Connector Installation C
Furnace Installation
1. Install 240V supply circuit(s) and 24V wir­ing to closet or alcove (see Figure 16 for appropriate locations).
14
Figure 12. Alternate Duct Connector Installation D
Furnace
Front
18" Nearest Wall or Partition
Holes (4)
Wall-Mount
Return Air Grille
Coil Air
Filters
Wall
Panel
A/C or H/P
Coil
24 3/4"
(629 mm)
Return
Air
Grille
27"
(686 mm)
(1423 mm)
29"
( 737 mm)
56"
Closet
20"
Floor
(508 mm)
Figure 13. Typical Alcove Installation Figure 14. Typical Closet Installation
Door
2. Remove refrigerant line knockouts in fur­nace only when installing indoor coil of an air conditioner or heat pump system, or for hook-up of a VentilAire accessory when the furnace is used in the upfl ow position. Refer to instructions supplied with accessory equipment.
3. Remove unit front door and slide back until bottom slots in rear of unit engage with both tabs of optional rear mounting plate, OR... If mounting plate is not used, an equivalent method of securing the rear of the unit may be used as long as it prevents displacement during transport if used in a manufactured home.
NOTE: The furnace does not need to be hard up against the rear mounting plate. The tabs will engage into the slots and allow approximately 1/2” of furnace adjustment front to back and right to left.
4. Secure front of unit with one or more fas­teners at mounting hole(s) provided or at tie-down tab (see Figure 16).
5. See Electrical System Installation to com­plete furnace installation.
Provide min. 235 sq. in. (1516 cm ) open free area in front or side wall or in top of closet door
0" Side Clearance to Furnace Cabinet
6"
(152 mm)
Standard Closet Installation
Provide min. 250 sq. in. (1613 cm2 ) open free area in front or side wall or in top of closet door
0" Side Clearance to Furnace Cabinet
1"
(25 mm)
CLOSET DOOR
TYPICAL INSTALLATION OF UPFLOW SYSTEMS
The following steps describe installation instruc­tions for an overhead supply duct system with a return air system that can be either over the fl oor (unducted) or through the fl oor (ducted).
CLOSET DOOR
Special 1" Clearance
Figure 15. Closet Installation
15
Low Voltage Wire Entrances
Power
Supply
Wire
Entrances
Blower Selector
Switch (EH Only)
Refrigerant Line Knockouts
Low Voltage Wire Entrances
Refrigerant
Line Knockouts
Blower Selector
Switch (EH Only)
DOWNFLOW INSTALLATION UPFLOW INSTALLATION
Power Supply Wire Entrances
Tie-Down Tab
(See Inset)
Tie Down Tab
Figure 16. Downfl ow and Upfl ow Installations
NOTES:
• Before installing this furnace, consider all
clearances for the installation and future servicing of the furnace. Refer to Table 1.
• The 2 Wire Relay Control is NOT recom-
mended for upfl ow applications, instead, the AC/HP Relay Control (4-7 wire) should be used when converting some models to accept an air conditioner. See Relay Control installation instructions for further details.
Upflow Duct Connector
Furnace
Filter (one obtained
Upflow Stand
Figure 17. Over-the-Floor Return Air Sys-
tem with Upfl ow Stand
from furnace)
Return Air and Filtering Systems
Furnaces may be installed with unducted or ducted return air. For unducted systems with air conditioners or heat pumps, the following optional equipment is recommended: upfl ow stand, coil cabinet, upfl ow duct connector, and wall mount grille. For ducted systems with air conditioners or heat pumps, the following optional equipment is recommended: coil cabinet and upfl ow duct connector.
NOTE: Refer to the instructions supplied with any additional accessories for further installa­tion details.
Filtering Methods - Non-Ducted Return Air
1. Without optional upfl ow stand: (see Figure
18)
-install a fi lter with a minimum unrestricted medium area of 324 square inches below the coil cabinet/furnace assembly that is accessible for monthly cleaning or replace­ment by the homeowner
2. With optional upfl ow stand: (see Figure 17)
Stand must use two fi lters; one is supplied
with the stand and the other MUST be removed from the furnace and placed in the stand - see upfl ow stand instructions for additional details.
Filtering Methods - Ducted Return Air
1. Install a fi lter with a minimum unrestricted
medium area of 324 square inches below the coil cabinet/furnace assembly that is accessible for monthly cleaning or replace­ment by the homeowner
16
Applications and Furnace
Coil Cabinet
Air Filter
Braced Mounting Platform
Front Grille
Non-combustible Pan or Enclosure
WALL
FLOOR
Installation
NOTE: Remove refrigerant line knockouts in
furnace only when installing indoor coil of an air conditioning or heat pump system.
Refer to instructions supplied with accessory equipment.
Over-the-Floor Return Air System (Non-Ducted)
1. If fl oor underneath furnace is made of com­bustible material, locate a pan fabricated of non-combustible material with 1” upturned fl anges under furnace return air opening (see Figure 18).
2. Use optional upfl ow stand with fi lters or con­struct a suitably braced mounting platform in closet (see Figure 17 or 18).
3. Install 240V supply circuit(s) and 24V wir­ing to closet (see Figure 16 for appropriate locations).
4. Position optional coil cabinet onto upfl ow stand or mounting platform and secure with three or more fasteners.
5. Position furnace in upfl ow mode onto coil cabi­net and secure with two or more fasteners.
6. Use optional upfl ow duct connector or fi eld supplied connector to attach furnace to overhead supply duct. (see Figure 17)
7. Install return air grille in closet preferably at same level as upfl ow stand or below mounting platform (see Figure 18).
NOTE: Be certain to provide an adequate free return air area as described under Return Air Codes and Requirements and Closed-Off Space Requirements.
3. Install 240V supply circuit(s) and 24V wir­ing to closet (see Figure 16 for appropriate locations).
4. Position optional coil cabinet over fl oor cutout and secure with three or more fasteners.
5. Position furnace onto coil cabinet and secure with two or more fasteners.
6. Use optional upfl ow duct connector or fi eld supplied connector to attach furnace to overhead supply duct (see Figure 17).
ELECTRICAL SYSTEM INSTALLATION
WARNING:
To avoid the risk of electrical shock, personal injury or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical power supply.
Codes, Specifi cations, and Re­quirements
The wiring, installation, and electrical hookup of this furnace must comply with the National Electrical Code (or the Canadian Electrical Code) and all regulations of local authorities having jurisdiction. See Table 9a & 9b for minimum circuit ampacity, maximum over-current protection, and recommended wire size. See the unit wiring diagram for other wiring details. Supply-circuit requirements are as follows:
Through-the-Floor Return Air System (Ducted)
1. Prepare Floor Opening(s): a. Mark fl oor opening(s) as shown in Figure
19. Provide minimum clearances at rear and left side walls of closet for installation of furnace and wiring.
b. Cut fl oor opening on outside edge of
marked line so that opening is slightly larger than area marked.
c. Additional provisions may be necessary
for optional air conditioning if refrigerant lines are installed other than at the front of the furnace.
2. If return air duct is made of combustible
material, locate a pan fabricated of non­combustible material with 1” upturned fl anges under furnace return air opening.
Figure 18. Over-the-Floor Return Air
System
17
1 3/4" MIN
(45 mm)
23 3/4"
(604 mm)
3/4"
(20 mm)
20"
(508 mm)
17 1/2"
(445 mm)
14" (356 mm)
5 3/4"
(147 mm)
3 1/8"
(80 mm)
3"
(73 mm)
Furnace
Outer Door
For Optional A/C Or H/P
REAR WALL OF ENCLOSURE
CENTER LINE
Furnace Outline
18 5/8" (474 mm)
Figure 19. Upfl ow Floor Cutout Locations (nominal dimensions)
• -010 model is factory-wired for single-branch supply circuit only.
• -012 models are factory-wired for single­branch supply circuit (single-circuit kit in­stalled). Dual-branch circuit can be used by removing factory-installed single-circuit kit (see Figures 20 and 21).
• -015, -017, -020 and -023 models are factory-wired for dual-branch supply circuit. Single-branch circuit can be used by installing optional single-circuit kit .
IMPORTANT:
Note: Circuit breakers installed within this unit are for short-circuit protection of the internal wiring and to serve as a disconnect. Circuit breakers installed within this unit DO NOT provide over-current protection of the supply wiring and therefore may be sized larger than the branch circuit protection.
18
Connecting Supply Service Wires
1. Remove right-hand control panel (when viewing in downfl ow position).
2. Locate power supply hole plugs in side of unit and in bottom of unit. Remove appropriate plug(s) or knockout opening applicable to recommended wire size(s).
3. Install listed cable connector(s) in opening(s). If metal-sheathed conduit is used for incom­ing power line(s), provide an approved metal clamp on conduit and secure it in entrance knockout.
4. Insert supply service wire(s) through cable connector(s) and connect wires to circuit breakers (Figures 20 and 21).
NOTE: To install single-circuit kit, perform
step 5. If single-circuit kit installation is not necessary, go to step 6.
5. To install single-circuit kit: a. Loosen lugs at supply side of circuit
breakers.
b. Remove cover from single-circuit kit (if
supplied).
c. Insert metal buss bars of kit into lugs of
circuit breaker.
d. Tighten lugs securely (45 in.-lbs. recom-
mended).
Optional Single Circuit Adaptor Kit
Circuit Breaker
Bracket
60A
60A
ON
ON
OFF
OFF
Circuit
Breaker
Wire
Assemblies
(Factory
Installed)
Supply Service Wire Connection With Single Circuit Adaptor Kit
6. Connect ser vice ground wire(s) to grounding lug(s) provided. One ground is required for each supply circuit used.
WARNING:
To avoid personal injury or property damage, make certain that the motor leads cannot come into contact with non-insulated metal components of the unit.
Blower Installation:
1. Turn off all electrical supply circuits to the furnace at the main service panel.
2. Remove furnace front door and switch furnace circuit breaker(s) to “OFF”.
3. Disconnect the motor plug from the control panel receptacle.
4. Remove one screw from left side of blower and three screws from right side of blower; slide blower forward and remove.
5. Install new blower ensuring the side fl anges engage under side mounting tabs (three on one side, one on the other) and the long tab in the rear.
6. Replace screws previously removed from blower.
7. Connect the motor plug to the control panel receptacle.
8. Switch circuit breaker(s) to “ON”, reinstall furnace front door, and turn on electrical supply circuits to the furnace.
Selecting Blower Speed
See Table 5 for the lowest speed approved for the heating output of the unit. Since the blower leads connect to the control box, blower speed selection is accomplished through use of the proper color-coded blower lead located inside the control box. The speed(s) set by the factory may be different from that shown on the wiring diagrams. See the unit control box for blower speed(s) set at factory.
Figure 20. Installation of Optional Single Circuit Adaptor Kit
Breaker
Assemblies
(Factory
Installed)
Circuit Breaker
Bracket
Circuit
Wire
Figure 21. Installation of Supply Service Wires
60A
OFF
ON
60A
OFF
ON
Supply Service
Wire Connection
Without Single Circuit Adaptor Kit
19
IMPORTANT:
If a relay box is installed, blower speeds for heating and cooling are set inside the relay box (see instructions included with relay box). The blower speed inside the furnace control box must be set to low or medium-low. Never change to a heating speed lower than that shown in Table 5.
Changing Blower Speed
E3EH: The selected heating blower lead is at-
tached to the wire lead attached to terminal 2 of the blower selector switch. a. Remove blower lead from the wire lead off
of terminal 2. b. Choose desired speed. c. Attach new blower lead to wire lead off
terminal 2 of blower selector switch.
E2EB: The selected heating blower lead is at­tached to terminal 6 on blower relay. The selected cooling blower lead is attached to terminal 4 on blower relay. a. Remove heating blower lead from terminal
6 on blower relay. b. Choose desired speed and install new
blower lead onto terminal 6 of blower relay
for new heating speed. c. Remove cooling blower lead from terminal
4 on blower relay. d. Install new blower lead onto terminal 4 of
blower relay for new cooling speed.
E3EX: The selected heating blower lead is at­tached to terminal 6 on blower relay and is the red wire attached to the motor pin terminals 1-3. The selected cooling blower lead is attached to
terminal 4 on blower relay and is the blue wire attached to the motor pin terminals 1-3.
a. Remove heating and cooling leads from
motor terminals 1-5.
b. Choose desired speeds and seat terminal
back into motor terminals 1-5.
Same Speed, Heating and A/C: Use loose white jumper wire supplied with unit and jumper between terminals 5 & 2 on blower relay. On E3EX, remove one wire from motor terminals 1-5, while leaving one wire on the required blower speed.
See Table 6 for blower performance data.
Installing Control Circuit Wiring
NOTE: Installation of a fi ve-wire thermostat
circuit is recommended to provide for future addition of a heat/cool thermostat.
1. Install the 24V control-circuit cable through plastic bushing at either side of furnace.
a. For models without a relay box, connect
wires to furnace at blower plug pigtails (see wiring diagrams). Secure all connections with wire nuts.
b. For units with a relay box installed, make
wiring connections at relay box low-voltage terminal board. (See relay box installation instructions.)
2. Route control circuit wiring to wall thermostat and outdoor section, if installed. (See relay box installation instructions if applicable.)
3. Set anticipator per Table 7 or per the mark­ing on the unit.
4. See Figure 31 (non-Platinum) and Figure 32 (Platinum) for E3EB thermostat connec­tions.
20
Plug/Receptacle Position Pin1 Pin2 Pin3 Pin4 Pin5
2 Speed Blower Low High - - ­4 Speed Blower Low Med-LO Med-Hi High ­Control Box Blower Lead Red Yellow Blue Black -
Minimum approved speed
for 010 and 012 models
Multi-Speed, E3EX Low Med-Lo Med Med-Hi High
Table 5. Furnace Blower Speed Data
Minimum approved speed for 015, 017, 020, 023 models
SYSTEM CHECKOUT Checking Installation
1. Refer to appropriate wiring diagram and recheck all wiring connections. Ensure that all connections are tight.
2. Check blower motor and relay box con­nectors for proper connection.
3. Reinstall control box cover(s).
4. Switch circuit breaker(s) to “ON” position.
5. Set furnace blower selector switch (see Figure 16) to “AUTO” (EH Units only).
6. Replace outer furnace door.
7. Check all duct connections and tape for air leakage.
Standard E3EH Blower with Filter, @ 0.3" ESP
Pin No. Speed CFM
#1 Low 840
#2 High 1160
4-Ton Blower with Coil and Coil and Filters, @ 0.3" ESP
Furnace
Model
Thermostat
Anticipator Setting
010, 012 0.2
015, 017, 020, 023 0.4
Table 7. Anticipator Settings
ALL MODELS CLOSET ALCOVE
Front ** 6" 18" Back 0" 0" Sides 0" * 0" * Top 0" 0" Top and Sides of Duct 0" 0" Bottom of Duct 0" 0"
** Service Clearance * For upfl ow application using upfl ow stand, 1” minimum per
side.
Table 8. Clearances
Pin No. Speed CFM
#1 Low 880
#2 Med.-Low 1170
#3 Med.-High 1310
#4 High 1460
5-Ton Blower, with Coil and Coil Filters, @ 0.3" ESP
Pin No. Speed CFM
#1 Low 990
#2 Med.-Low 1320
#3 Med.-High 1620
#4 High 1790
Multi-Speed, X13, Blower, with Coil and Filters, @ 0.3" ESP
Pin No. Speed CFM
#1 Low 880
#2 Med.-Low 1000
#3 Med 1170
#4 Med.-High 1260
#5 High 1460
Table 6. Blower Performance
21
Model
Number
E3E(*)
-010H
-012H
-015H
-017H
-020H
-023H
Model
Number
E3EX
-010
-012
-015
-017
-020
Replacement furnace for E2E(*)-015HB
E2E(*)-
015HBR
Supply
Circuit
Single 45.5 60 57 4 6 10
Single 52.1 70 65 4 6 8 Dual "A" 28.0 40 35 8 8 10 Dual "B" 24.2 30 30 10 10 10
Single 66.3 90 83 2 4 8 Dual "A" 45.5 60 56 4 6 10 Dual "B" 20.8 30 26 10 10 10
Single 71.3 90 89 2 4 8 Dual "A" 48.8 60 60 4 6 10 Dual "B" 22.5 30 28 10 10 10
Single 87.1 125 109 0 2 6 Dual "A" 45.5 60 57 4 6 10 Dual "B" 41.7 60 52 4 6 10
Single 93.8 125 117 0 2 6 Dual "A" 52.1 60 60 4 6 10 Dual "B" 41.7 60 56 4 6 10
Supply
Circuit
Single 47.7 60 57 4 6 10
Single 54.3 70 67 4 6 8 Dual "A" 30.2 40 35 8 8 10 Dual "B" 24.2 30 30 10 10 10
Single 66.0 90 83 2 4 8 Dual "A" 46.0 60 57 4 6 10
Dual "B" 20.0 30 25 10 10 10
Single 71.5 90 89 2 4 8 Dual "A" 51.0 60 60 4 6 10 Dual "B" 22.5 30 28 10 10 10
Single 86.0 125 109 0 2 6 Dual "A" 46.0 60 57 4 6 10 Dual "B" 40.0 60 50 4 6 10
Single 67.1 90 83 2 4 8 Dual "A" 35.5 50 44 6 8 10 Dual "B" 31.7 40 39 8 8 10
Total
Amperes
Total
Amperes
* Can be H or B
Maximum
Over-current
Rating
Maximum
Over-current
Rating
Minimum
Circuit
Ampacity
Minimum
Circuit
Ampacity
Copper Wire Size - See
Caution Below
60°C
(e.g., Romex)
Copper Wire Size - See
Caution Below
60°C
(e.g., Romex)
(e.g., SEU)
(e.g., SEU)
90°C
90°C
Ground
Wire Size
Ground
Wire Size
Low
Voltage
Thermostat
Wire Size
2-Wire system maximum wire
lengths: 24 Ga.= 55' 22 Ga.= 90'
20 Ga.= 140' 18 Ga.= 225'
4 or more
Wire systems
maximum wire
lengths: 24 Ga.= 25' 22 Ga.= 45' 20 Ga.= 70'
18 Ga= 110'
Low
Voltage
Thermostat
Wire Size
2-Wire system maximum wire
lengths: 24 Ga.= 55' 22 Ga.= 90'
20 Ga.= 140' 18 Ga.= 225'
4 or more
Wire systems
maximum wire
lengths: 24 Ga.= 25' 22 Ga.= 45'
Replacement
furnace for
E2E(*)-015HB
CAUTION: When sizing the wire, you must follow the guidelines of the latest revision of the NEC. NM-B wire is equivalent to “Romex” cable. SEU is equivalent to service entry cable. For NEC type NM-B wire, you must size the wire using 60C ratings per NEC article 326.
* Minimum overcurrent protection per NEC 424-3b not to be less than 125%
of total amps for fi xed resistance heat.
Table 9a. Electrical Specifi cations
Circuit "A" Circuit "B"
Model Number
E3E(*)
Wire Gauge
and Type
Breaker
Size
Wire Gauge
and Type
Breaker
Size
-012H #8 NM-B 40 amp #10 NM-B 30 amp
-015H #6 SEU 60 amp #10 NM-B 30 amp
-017H #6 SEU 60 amp #10 NM-B 30 amp
-020H #6 SEU 60 amp #6 SEU 60 amp
-023H #6 SEU 60 amp #6 SEU 60 amp
Replacement furnace for E2E(*)-015HB
E2E(*)-015HBR #8 SEU 50 amp #8 NM-B 40 amp
Table 9b. Recommended Electrical Application Guide
for Dual Circuit Installations**
** Alternate wiring combinations can be used. Refer to the latest revision of the NEC for these
appropriate alternate combinations.
22
Legend:
240V
Cont 1
C
L
IFM
CB-A CB-A
Transformer
LS
Btm - 10.0
ML
12345
IFR
Red
Blue
E
Cont 1
IFR
Cont
1
24V
Red Pig-Tail
White Pig-Tail
IFR
Green Pig-Tail
Grey Pig-Tail
Yellow
MH
H
6
Black
Grey
Org.
White Jumper Wire
(See note 7)
Fuse
CB – Circuit Breaker
E – Heater Element
IFR – Fan Relay
Cont – Contactor
Line
Voltage
Supply
Circuit A
ON
60A
OFF
GRD Ground
RED
RED
CIRCUIT
BLACK
BLACK
– Fan Plug
LS – Limit Switch
IFM – Fan Motor
BREAKER
replaced with 105°C thermoplastic copper wire of
the same gauge.
ground.
5) If any wire in this unit is to be replaced it must be
6) Not suitable for use on systems exceeding 120V to
7) This wire is used with some accessories. See
sizes.
NOTES:
1) See unit data label for recommended supply wire
box refer to installation instructions.
2) Thermostat anticipator setting: 0.20 Amps.
3) To change blower speed on units without a relay
4) Refer to furnace and/or relay box installation for
C
accessory Installation Instructions for further de-
thermostat connections.
WARNING:
RED
6
45
BLACK
GREEN
BLACK
GREY
FUSE
TRANSFORMER
Switch circuit breakers to
the OFF position before
servicing the furnace.
ORANGE
BLOWER
2
5
1
BLUE
RELAY
4
6
3
3
2
1
RED
YELLOW
WHITE
3
6
5
2
RED
L
ML
MH
H
YELLOW
BLUE
4
1
BLACK
BLACK
Figure 26. E3EB 010H Wiring Diagrams
ORANGE
GREEN
240V
COM
VIOLET
GREY
24V
WHITE
TOP ELEMENTS, 10.0 KW
BLACK
CONTACTOR
GREY
2
RED
4
BLACK
1
3
RED
ELEMENTS
LIMITS
RED
23
WARNING:
240V
Cont 1
C
H
L
IFM
CB-A
CB-A
CB-B
CB-B
Transformer
LS
Btm - 11.6
ML
MH
12345
IFR
Red
Yellow
Blue
E
IFR
Cont
1
24V
Red Pig-Tail
White Pig-Tail
IFR
Green Pig-Tail
Grey Pig-Tail
6
Black
Grey
Org.
White Jumper Wire
(See note 7)
E
Fuse
Switch circuit breakers to
the OFF position before
servicing the furnace.
replaced with 105°C thermoplastic copper wire of
the same gauge.
ground.
5) If any wire in this unit is to be replaced it must be
6) Not suitable for use on systems exceeding 120V to
7) This wire is used with some accessories. See
2) Thermostat anticipator setting: 0.20 Amps.
3) To change blower speed on units without a relay
box refer to installation instructions.
4) Refer to furnace and/or relay box installation for
sizes.
NOTES:
1) See unit data label for recommended supply wire
24
tails.
accessory Installation Instructions for further de-
C
thermostat connections.
– Fan Plug
LS – Limit Switch
IFM – Fan Motor
RED
Legend:
CB – Circuit Breaker
E – Heater Element
IFR – Fan Relay
Cont – Contactor
RED
BLACK
BLUE
GREY
GREEN
FUSE
TRANSFORMER
240V
COM
GREY
ORANGE
BLUE
YELLOW
L
ML
MH
H
RED
BLACK
123
456
BLACK
ORANGE
123
456
YELLOW
BLUE
RELAY
BLOWER
4
2
5
6 3
1
RED
WHITE
Figure 27. E3EB 012H Wiring Diagrams
Line
ON
60A
OFF
BLACK
VIOLET
Vol ta ge
Circuit B
GREY
24V
Dual
Supply
Ground
GRD
RED
WHITE
60A
BLACK
Line
Circuit A
ON
OFF
Vol ta ge
Ground
GRD
CIRCUIT
BREAKERS
TOP ELEMENTS, 11.6 KW
BLACK
OR
2
RED
4
1
3
RED
ELEMENTS
GREY
Single
ON
60A
OFF
Supply
LIMITS
BLACK
CONTACTOR
(optional)
ON
60A
OFF
BLACK
RED
Ground
GRD
WARNING:
240V
Cont 1
C
H
L
IFM
CB-A
CB-A
CB-B
CB-B
Transformer
LS
Btm -
5.0/5.4
Top -
10.0/10.8
ML
MH
12345
IFR
Red
Yellow
Blue
E
Cont 1
IFR
Cont 2
LS
Cont
2
Cont
1
24V
Red Pig-Tail
White Pig-Tail
IFR
Green Pig-Tail
Grey Pig-Tail
6
Black
Grey
Org.
White Jumper Wire
(See note 7)
E
Fuse
Switch circuit breakers to
the OFF position before
servicing the furnace.
thermostat connections.
replaced with 105°C thermoplastic copper wire of
the same gauge.
ground.
5) If any wire in this unit is to be replaced it must be
6) Not suitable for use on systems exceeding 120V to
7) This wire is used with some accessories. See
Legend:
accessory Installation Instructions for further de-
C
– Fan Plug
LS – Limit Switch
IFM – Fan Motor
CB – Circuit Breaker
E – Heater Element
IFR – Fan Relay
Cont – Contactor
ORANGE
BLUE
3
2
L
ML
MH
H
YELLOW
1
RED
BLACK
60A
ON
OFF
BOTTOM ELEMENT, 5.0/5.4 KW
(optional)
Single
Supply
ON
60A
OFF
RED
ELEMENTS
LIMITS
WHITE
Ground
GRD
BLACK
Dual
Supply
Line
BLACK
RED
GREEN
ORANGE
3
6
5
4
456
12
RED
BLUE
GREY
RED
WHITE
GREY
BLACK
YELLOW
Circuit B
ON
60A
OFF
Line
Vol ta ge
RED
Ground
GRD
RED
60A
BLACK
Vol ta ge
Circuit A
ON
OFF
BLACK
Ground
OR
GRD
CIRCUIT
BREAKERS
2
RED
ELEMENTS, 10.0/10.8 KW
TOP
BLACK
1
3
4
RED
sizes.
NOTES:
1) See unit data label for recommended supply wire
2) Thermostat anticipator setting: 0.40 Amps.
box refer to installation instructions.
3) To change blower speed on units without a relay
4) Refer to furnace and/or relay box installation for
FUSE
VIOLET
240V
TRANSFORMER
24V
BLACK
COM
BLACK
GREY
WHITE
RELAY
BLOWER
4
2 5
6
1
3
BLACK
Figure 28. E3EB 015H, E3EB 017H Wiring Diagrams
GREY
CONTACTOR
GREY
CONTACTOR
RED
25
IFR – Fan Relay
240V
Cont 2
C
H
L
IFM
CB-A
CB-A
CB-B
CB-B
Transformer
LS
Top -
10.0/11.6/7.6
Btm - 10.0/7.6
ML
MH
12345
IFR
Red
Yellow
Blue
E
E
Cont 2
IFR
Cont 2
Cont 2
LS
Cont
2
Cont
1
24V
Red Pig-Tail
White Pig-Tail
IFR
Green Pig-Tail
Grey Pig-Tail
6
Black
Grey
Org.
White Jumper Wire
(See note 7)
Fuse
E – Heater Element
Legend:
CB – Circuit Breaker
– Fan Plug
IFM – Fan Motor
Cont – Contactor
LS – Limit Switch
replaced with 105°C thermoplastic copper wire of
the same gauge.
ground.
5) If any wire in this unit is to be replaced it must be
6) Not suitable for use on systems exceeding 120V to
7) This wire is used with some accessories. See
accessory Installation Instructions for further de-
WARNING:
!
Switch circuit breakers to
ORANGE
C
L
ML
MH
H
RED
BLUE
YELLOW
the OFF position before
3
2
1
BLACK
servicing the furnace.
56
4
56
4
123
RED
YELLOW
BLUE
WHITE
Dual
Supply
Line
Voltage
Circuit B
ON
60A
OFF
BLACK
RED
BLACK
RED
RED
GREY
ORANGE
GREEN
BLACK
FUSE
VIOLET
GREY
Ground
GRD
RED
WHITE
Line
Circuit A
60A
OFF
RED
BLACK
Voltage
Ground
ON
GRD
CIRCUIT
2
4
RED
TOP ELEMENTS, 10.0/11.6/7.6 KW
CONTACTOR
OR
BREAKERS
BLACK
1
3
RED
ELEMENTS
Single
ON
60A
OFF
BLACK
RED
BOTTOM ELEMENT, 10.0/7.6 KW
Supply
2
4
RED
(optional)
ON
60A
OFF
1
LIMITS
3
ELEMENTS
CONTACTOR
Ground
GRD
BLACK
WHITE
NOTES:
1) See unit data label for recommended supply wire
sizes.
2) Thermostat anticipator setting: 0.40 Amps.
3) To change blower speed on units without a relay
box refer to installation instructions.
Figure 29. E3EB 020H, 023H, and 023H - 5 Ton, E2EB-015HBR Wiring Diagrams
26
4) Refer to furnace and/or relay box installation for
thermostat connections.
240V
RELAY
BLOWER
2
4
5
6
1
3
BLACK
BLACK
TRANSFORMER
GREY
24V
COM
GREY
GREY
BLACK
RED
Figure 30. E3EX 010H
Notes :
1) See unit data label for recommended supply wire sizes.
2) Thermostat anticipator setting : 0.40 Amps
3) To change blower speed on units without a relay box installed refer to installation instructions
4) Refer to furnace and/or relay box installation instructions for thermostat connections.
5) If any wire in this unit is to be replaced it must be replaced with 105° C thermoplastic copper wire of the same gauge.
6) Not suitable for use on systems exceeding 120V to ground.
7) Refer to Installation Instructions for complete wiring diagram.
8) Heating and cooling may be wired on the same speed using the provided jumper wire.
"A" (BOTTOM)
FUSE
GREEN
BLUE
RED
ORANGE WHITE
BLACK
RED RED
RED
RED
BLACK
RED
GRAY
BLUE
GRAY
BLACK
WHITE
ORANGE
VIOLET RED
BLUE
RED
WHITE
GRAY
BLACK
RED
BLACK
BLACK
BLACK
CONTACTOR
240V COM
24V
ELEMENTS
LIMIT
T1
T2
T3
T4
T5
G
N
L
C
X13
123 456
123 456
152
463
BLOWER RELAY
WHITE
GREEN
Notes :
1) See unit data label for recommended supply wire sizes.
2) Thermostat anticipator setting : 0.40 Amps
3) To change blower speed on units without a relay box installed refer to installation instructions
4) Refer to furnace and/or relay box installation instructions for thermostat connections.
5) If any wire in this unit is to be replaced it must be replaced with 105° C thermoplastic copper wire of the same gauge.
6) Not suitable for use on systems exceeding 120V to ground.
7) Refer to Installation Instructions for complete wiring diagram.
8) Heating and cooling may be wired on the same speed using the provided jumper wire.
"A" (BOTTOM)
FUSE
GREEN
BLUE
RED
ORANGE WHITE
BLACK
RED
RED
RED
RED
BLACK
GRAY
GRAY
BLACK
WHITE
ORANGE
VIOLET RED
WHITE
GRAY
BLACK
RED
BLACK
BLACK
BLACK
CONTACTOR
240V COM
24V
ELEMENTS LIMIT
T1
T2
T3
T4
T5
G
N
L
C
X13
"B" (TOP)
WHITE
123
456
123
456
15
2
4
63
BLOWER RELAY
RED
BLUE
BLUE
RED
GREEN
Figure 31. E3EX 012H
27
Notes :
1) See unit data label for recommended supply wire sizes.
2) Thermostat anticipator setting : 0.40 Amps
3) To change blower speed on units without a relay box installed refer to installation instructions
4) Refer to furnace and/or relay box installation instructions for thermostat connections.
5) If any wire in this unit is to be replaced it must be replaced with 105° C thermoplastic copper wire of the same gauge.
6) Not suitable for use on systems exceeding 120V to ground.
7) Refer to Installation Instructions for complete wiring diagram.
8) Heating and cooling may be wired on the same speed using the provided jumper wire.
"A" (BOTTOM)
FUSE
RED
GREEN
BLUE
RED
ORANGE
WHITE
BLACK
RED
GRAY
WHITE
WHITE
GRAY
BLACK
WHITE
ORANGE
VIOLET RED
GREEN
WHITE
GRAY
BLACK
RED
BLACK
WHITE
CONTACTOR
240V COM
24V
ELEMENTS LIMIT
ELEMENTS LIMIT
T1
T2
T3
T4
T5
G
N
L
C
X13
(11)
"B" (TOP)
RED
RED
RED
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
RED
RED
RED
123
456
123
456
1
52
4
63
BLOWER RELAY
RED
BLUE
BLUE
RED
Figure 32. E3EX 015/017H
Notes :
1) See unit data label for recommended supply wire sizes.
2) Thermostat anticipator setting : 0.40 Amps
3) To change blower speed on units without a relay box installed refer to installation instructions
4) Refer to furnace and/or relay box installation instructions for thermostat connections.
5) If any wire in this unit is to be replaced it must be replaced with 105° C thermoplastic copper wire of the same gauge.
6) Not suitable for use on systems exceeding 120V to ground.
7) Refer to Installation Instructions for complete wiring diagram.
8) Heating and cooling may be wired on the same speed using the provided jumper wire.
"A" (BOTTOM)
FUSE
RED
GREEN
BLUE
RED
ORANGE
WHITE
BLACK
RED
GREY
WHITE
WHITE
GREY
BLACK
WHITE
ORANGE
VIOLET RED
GREEN
WHITE
GREY
BLACK
RED
BLACK
WHITE
CONTACTOR
240V COM
24V
ELEMENTS LIMIT
ELEMENTS LIMIT
T1
T2
T3
T4
T5
G
N
L
C
X13
(11)
"B" (TOP)
RED
BLACK
BLACK
BLACK
BLACK
BLACK
RED
RED
123
456
123
456
1
52
463
BLOWER RELAY
RED
BLUE
BLUE
RED
RED
28
Figure 33. E3EX 020H
5-Wire Thermostat
W Y RC RH G
4-Wire Thermostat
W Y R G
Wire nuts
White
Grey
Red
E3EB FURNACE Control Wiring
2-Wire Thermostat
W R
Wire nuts
White
Red
Grey
E3EB FURNACE Control Wiring
Figure 34. E3EB Thermostat Connection
Wire from furnace to Platinum unit
PLATINUM
Red and white t-stat wire connected by OEM
Ye l l o w
Green
Unstripped
Wires
Green
Black
To A/C
Wire nuts
Wire nuts
White
Grey
Red
E3EB FURNACE Control Wiring
Heat Pump Thermostat
G R W2 C E O Y
Green
White
Red
Grey
E3EB FURNACE Control Wiring
Typical AC
Green White Red Yellow or Blue
FURNACE
Grey White Red Green
Green
To A/C
To H/P
Yellow or Blue
RGW
Y
THERMOSTAT
White Green Red
Wire from thermostat to furnace
Platinum installer disconnects white and red t-stat wires
PLATINUM Grey or Green White Orange or Red Ye l l o w
Wire from furnace to Platinum unit
Green White Red Yellow or Blue
Typical HP
FURNACE
Grey White Red Green
Yellow or Blue
R
GW
Y
THERMOSTAT
White Green Red
Wire from thermostat to furnace
Figure 35. E3 Furnace Low Voltage Wiring if Installed with Platinum Series Models
29
Furnace Inspection Report
Please Write In Appropriate
Response
Electrical Wiring (If single circuit, write “N/A” in circuit B) Circuit A Circuit B Breaker Size? Furnace Wire Size? Thermostat Wire Size?
Please Circle Appropriate
Response
Electrical Is the furnace grounded properly? Yes No N/A Is wiring routed safely with approved connectors? Yes No N/A
Closet Installation Is front clearance a minimum of 6 inches? Yes No N/A Is return air opening a minimum of 235 sq. inches? Yes No N/A Is front clearance less than 6 inches (minimum of 1 inch)? Yes No N/A Is return air opening a minimum of 250 sq. inches? Yes No N/A Does the furnace have the 5-ton AC coil installed? Yes No N/A Is the return air opening a minimum of 390 sq inches? Yes No N/A
Plenum (Base) Connector Is mounting plate secured properly? Yes No N/A Is furnace locked and secured in front? Yes No N/A Is plenum free of debris? Yes No N/A
Has plenum opening been reduced in size to accommodate offset? Has plenum spacer been removed if duct size is large enough? Yes No N/A
Testing Is someone in the plant trained to perform duct tests? Yes No N/A
VentilAire III __ IV__ Is VentilAire duct connected properly to furnace? Yes No N/A Is depressurization vent (if required) installed properly? Yes No N/A Is roof assembly installed properly? Yes No N/A Is roof assembly a minimum of 3 inches from any other vents? Yes No N/A
General Is fi lter in place? Yes No N/A Is owner’s packet included? Yes No N/A
Checked storage area for damage to product and proper storage? Is installation in accordance with installation instructions? Yes No N/A
Yes No N/A
Yes No N/A
Comments:
30
31
INSTALLER: Do Not Discard These Instructions
After completing the installation, return these instructions
to the Homeowner’s Package for owner-user’s future reference.
Complies with H.U.D. Manufactured Home Construction & Safety Standards.
O’Fallon, MO
¢708827H¤
7088270
7088270
Specifi cations and illustrations subject to change
without notice and without incurring obligations.
Printed in U.S.A. (07/08)
Loading...