Nordyne E2EH-012-HB, E2EH-010-HB, E2EH-015-HB, E2EH-015-HR, E2EH-017-HB Owner's Manual & Installation Instructions

...
Downflow, Upflow Electric Furnaces
Owners Manual/Installation Instructions
E2EH-xxx HB Series E2EB-xxx HB Series
(Air Conditioner/Heat Pump Air Handler)
IMPORTANT: Read this owner information to become familiar with the capabilities and use of your heating appliance. Keep this literature where you will have easy access to it in the future. If a problem occurs, check the instructions and follow recommenda­tions given. If these suggestions don’t eliminate your problem, call the appropriate NORDYNE distributor. A distributor service list is included with this appliance.
!
WARNING:
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Improper installation, adjustment, alteration, service or maintenance can cause injury, property damage, or death. Refer to this manual. For assistance or additional information consult a qualified dealer or service agency. To avoid personal injury or property damage, ask a service technician to inspect the furnace and to replace any part of the control system which has been under water.
SECTION 1. OWNER INFORMATION
OPERATING INSTRUCTIONS
Before Operating System
Before operating your heating/cooling system (see Figure 1), make sure that:
• Control panel covers are closed.
• Blower and/or relay control plugs are plugged in.
• Fan switch is set to “AUTO” (E2EH units only).
• Circuit breakers are in “ON” position.
!
CAUTION:
No user serviceable parts inside control panel. DO NOT OPEN.
• All power supply switches for furnace and outside unit (if installed) are turned on.
• Furnace door is closed and properly latched.
Refer to the owner’s manual supplied with the optional heat pump or air conditioner for further information.
Temperature Selector
10 20 30
50 60 70 80 90
SYSTEM
HEAT OFF COOL
VENTILATE
ON AUTO
Temperature Scales
Fan Switch (optional sub-base)
System Switch (optional sub-base)
Coil Air Filters
(used with indoor coil)
Furnace Air Filter
(NOT used with
coil air filters)
Blower Selector Switch (EH only)
Blower
Indoor Coil (optional)
Product Type
E - Electric Furnace
Generation
2 - Second Series
Product Identifier
EH - Heat Only
EB - A/C Blower Equipped
A/C or H/P Relay Box
(optional)
Circuit Breakers
Data Label
Control Panel
Cover (left)
Control Panel Cover (right)
Figure 1. Furnace Parts Identification
E 2 EB - 010 HB
Model Revision
(R=replacement)
Electrical Code
H - 240-1-60
Primary Capacity
010 - 10 kw 012 - 12 kw 015 - 15 kw 017 - 17 kw 020 - 20 kw 023 - 23 kw
2
Model Identification
!
CAUTION:
For optional A/C or H/P systems, always wait at least five minutes after the system shuts off before restarting the system. Observe this procedure when operating the system per the following instructions.
To Operate System in Cooling Mode
NOTE: The “FAN ON/FAN AUTO” (fan switch)
and “HEAT/OFF/COOL” (system switch) are located either on your thermostat (if it’s supplied with a sub-base) or on the relay box added to your furnace.
for several hours with all air registers open.
2. With system on, check temperature in all
rooms.
3. Partially close registers in rooms that are
too warm (in heating mode) or too cool (in cooling mode) and in rooms that are infre­quently occupied.
4. Re-check room temperature and adjust
registers as needed.
To Shut Off System
1. Make sure blower selector switch is on
“Auto”.
2. Set thermostat temperature selector to low-
est temperature setting, OR...
3. For thermostats with optional sub-base (see
Figure 1), or for systems with relay box, set system switch to “OFF.”
1. Make sure blower selector switch is on “Auto.”
2. Set fan switch to “AUTO.”
3. Set system switch to “COOL.”
4. Set thermostat temperature selector to desired comfort level.
To Operate System in Heating Mode
1. Make sure blower selector switch is on “Auto.”
2. Set fan switch to “AUTO.”
3. Set system switch to “HEAT.”
4. Set thermostat temperature selector switch to desired comfort level.
NOTE: Allow at least one hour for the room temperature to stabilize before you make a second adjustment to the thermostat setting. Once the desired comfort level is established, make only small adjustments to the thermostat setting to meet changing temperature condi­tions.
!
WARNING:
To prevent hazard of electrical shock and injury from moving parts, be certain the thermostat is off and the furnace circuit breaker(s) are in the “OFF” position before servicing. Close and properly latch the outer door after doing the following recommended maintenance.
MAINTENANCE INSTRUCTIONS
Regularly NOTE: If a coil is installed, furnace filter is not
used.
1. Replace furnace air filter (see Figure 1), OR...
2. Remove coil filters, wash, and allow to dry. Re-install coil filters to original positions.
3. Vacuum or wipe clean interior of furnace cabinet.
4. Clean all lint and dust from around furnace.
To Operate Blower Continuously
1. Set blower selector switch to “ON” for sum­mer air circulation only (see Figure 1), OR...
2. If thermostat is equipped with optional heat­ing/cooling sub-base or relay box (see Figure 1), set fan switch to “ON.”
To Balance Air Distribution
1. On a typical day, set thermostat selector to desired comfort level and operate system
Every Six Months
1. Vacuum or wipe away any dust or lint on blower motor.
Before Each Heating Season NOTE: If a coil is installed, furnace filter is not
used.
1. Replace furnace air filter (see Figure 1), OR...
2. Remove coil filters, wash, and allow to dry. Re-install coil filters to original positions.
3
3. Have a qualified serviceman inspect all furnace components and field wiring and clean and service heating system as needed. If this furnace was installed with aluminum power supply wiring, have ser­viceman periodically check all connections to prevent possible equipment failure and/ or fire hazard. Do not attempt any service function yourself which requires opening furnace control panel covers.
BEFORE YOU CALL A SERVICEMAN
1. Make sure thermostat temperature selec­tor is set above room temperature for heat­ing or below room temperature for cooling. If thermostat is equipped with heating/cool­ing sub-base, make sure system switch (see Figure 1) is set to “HEAT” for furnace operation or set to “COOL” for optional air­conditioning operation.
2. Check main household service panel to see if appropriate circuit disconnect(s) for appliance power supply is on.
3. Refer to instructions under Before Operat­ing System for pre-operation checks.
4. Refer to instructions under Before Each Heating Season for maintenance proce­dures and recommended service checks.
5. Refer to owner’s manual provided with optional air conditioner or heat pump (if installed) for service and maintenance.
NOTE: All servicing of this heating appliance other than the normal maintenance described in this section must be done by authorized trained service personnel. Do not open the control panels (see Figure 1) at any time.
Please specify the complete model and serial numbers shown on the furnace data label (see Figure 1) for all warranty service and when ordering replacement parts or optional equip­ment. Refer to the replacement parts list pro­vided with the furnace for part numbers.
Optional air conditioners and heat pumps are listed by Underwriters’ Laboratories (UL) or Environmental Testing Laboratories (ETL) and certified by ARI and the Canadian Standards Association (CSA), or Warnock Hersey or ETLC. These cooling systems include energy-saving components to provide maximum cooling per­formance at electrical energy usage levels es­tablished by federal standards. Refer to the operation instruction label on your furnace for the optional air conditioning equipment approved for your heating appliance.
SECTION 2. INSTALLER INFORMATION
GENERAL
These instructions and specifications are pri­marily intended to assist qualified individuals experienced in the proper installation of home heating and air conditioning appliances. Some local codes require licensed personnel for the installation and service of this type of equip­ment. Approved installation, operation, and maintenance of this central heating system appliance must be in accordance with the listed specifications contained in these instructions and other documents supplied with the furnace and/or optional air conditioning equipment. Refer to local authorities having jurisdiction for further information.
Before beginning installation, read these in­structions thoroughly. Follow all warnings and cautions in the instructions and on the unit.
Improper installation, service adjustment, or maintenance can cause explosion, fire, electri­cal shock or other conditions which may result in personal injury or property damage. Unless otherwise noted in these instructions, use only factory-authorized kits and accessories when modifying this product.
OPTIONAL AIR CONDITIONER AND HEAT PUMP
Your E2 Series electric furnace is approved for use with an optional central air conditioner or a heat pump. To adapt this heating appliance to a “total comfort system,” contact your nearest NORDYNE distributor.
4
Overview of E2 Furnace
E2E(-) Series electric furnaces are available in two models. E2EH models are equipped with the standard two-speed blower. E2EH models can be easily converted for use with NORDYNE split-system air conditioners and heat pumps. E2EB models are air-conditioning ready; that is, they are equipped with a multi-speed (four­speed) blower, blower relay, and cabinet insu­lation kit. See Table 3 for cooling and heat pump availability with factory installed blower.
For typical non-ducted return air downflow applications, an air-conditioner or heat-pump coil can be installed by mounting the coil directly on top of the furnace without adding sheet metal cavities or cutting and trimming wood panels.
A return air grille for closet or alcove installations is available. For downflow alcove installations, the grille (with frame provided) may be attached to the top of the furnace and all paneling and trim flushed to it. This installation provides an ac­cess door for future installation of NORDYNE air conditioning or heat pump coils on top of the furnace.
Power entrance for all models may be through the right side or through the bottom of the unit (when viewing the unit in a downflow position).
UNIT CHECKOUT
Before installing this furnace:
1. Inspect unit for possible shipping damage. If shipping damage is found, file claim with transportation company.
2. Record furnace model number and serial number (see furnace data label) for future reference.
3. Carefully read all instructions supplied with optional equipment to be installed with furnace.
CODES, SPECIFICATIONS, AND REQUIREMENTS
Furnace Codes
Installation and wiring of this furnace, as well as the design and construction of the home duct system, must be in accordance with one or more of the following codes:
• HUD MANUFACTURED HOME CON-
STRUCTION AND SAFETY STANDARD (Title 24, Part 3280)
• American National Standards (ANSI)
A119.11, C1-NFPA 7 (National Electrical Code)
• CANADIAN STANDARDS (C.S.A.) Z240.6.1,
and Z240.9.1.
May vary by model, check the unit data label for
Listing agency(s)
appli cable agency listing mark. Approved for: single/multistory residential or mobil e/modular/manufactured structures. Upflow,
Approved Installation Configurations
downflow, (freestanding/closet/alcove)
Accessibility for Servicing Minimum of 18" (46 cm) required in front of unit. Mini mum Cl earance to Combustibles
0" from all surfaces of furnace cabinet, ducts, optional coil housing and plenum connector. No separate subbase required for installations on
combustible flooring. Minimum return air 200 in. opening required (total free area) 235 in
250 in
2
(1290 cm2) heating only*
2
(1516 cm2) A/C or H/P up to 4-ton installed.*
2
(1613) cm2 A/C or H/P up to 4 ton w/1"
clearance installed.
2
390 in.
(2516 cm2) A/C or H/P up to 5 ton installed. *or return air grille and frame assembly p/n 902989 or wall mount grille p/n 902999. Use return air grill e and frame assembly P/N 902989-
Return air g rille
or equivalent for alcove installation. Use wall mount return air grilled P /N 902999- or
(closet or alcove installation)
equivalent for closet installation. 155 in.
2
(1000 cm2) must be added for 5-to n A /C or H/P system.
Table 1. Miscellaneous Listings & Installation Requirements
5
All local codes having jurisdiction shall also apply.
Air Duct Codes and Specifications
Air ducts must be installed in accordance with National Fire Protection Association standards NFPA 90A and NFPA 90B, these instructions, and all applicable local codes.
• Materials: Air ducts must be aluminum, tin plate, galvanized sheet steel, or other ap­proved materials for outlet or return air ducts.
• Construction: Snap-Lock or Pittsburgh-Lock seams are preferred. All other types of seams must be made tight to prevent leak­age.
• Sizing: Supply duct system must be designed for proper air distribution. Static pressure measured externally to furnace shall not ex­ceed static pressure rating listed on furnace nameplate.
• Location of Openings: Duct system must be designed so that no supply registers are located in duct system directly below furnace.
Return Air Codes and Requirements
Non-ducted return air systems may be used for closet or alcove installations.
NOTE: Applicable installation codes may limit the furnace to installation in a single-story resi­dence only. Furnace installations other than closet or alcove installations require ducted return air systems.
• Wiring materials located in return duct sys­tem must conform to NEC Article 300-22(c).
• Gas piping must not run in or through return air duct system.
• If return air opening is located below top of furnace, a minimum clearance must be pro­vided between opening and furnace (see “Accessibility for servicing” in Table 1).
Closed-Off Space Requirements
Living space not served by, and closed off from, the return air ducts to the furnace by doors, sliding partitions, and other means must be provided with permanent, uncloseable open­ings in the doors or partitions to allow air to return to the furnace from all parts of the home. Return air grilles, with a minimum open area of one square inch for every five square feet of living space closed off from the furnace, must be provided in the door or room partition.
OPTIONAL EQUIPMENT
Contact your nearest NORDYNE distributor for a complete list of electric furnace accessories.
Return Air Grille
A return air grille and frame assembly (see Figure 2) is available for use in non-ducted return air installations. In downflow alcove in­stallations, the grille and frame assembly may be mounted directly to the top of the furnace. In closet installations, a wall mount grille is avail­able for attachment to a door or wall.
Air return to the furnace must have a minimum free area opening (see Table 1).
Acceptable floor or ceiling return air systems for closet installations with return air entering through an opening in the closet floor or ceiling must meet all of the following requirements:
• Return air opening into closet, regardless of its location, must not be smaller than size specified on unit data label.
• If located in floor of closet, return air opening must be provided with means of preventing its inadvertent closure by a flat object placed over opening.
• Materials located in return air duct system must have a flame-spread classification of 200 or less.
• Noncombustible pans having 1" upturned flanges must be located beneath openings in a floor-return duct system.
6
Optional Automatic Furnace Damper #901083 -
Furnace may (not required) be equipped with the optional automatic damper when a pack­aged air conditioner is installed and connected to the warm air duct system. This damper pre­vents cooled air from discharging through the furnace cabinet, causing excessive cooling of the immediate area. Refer to instructions sup­plied with the damper for details.
Multi-Speed Blower Conversion Package (4 or 5 ton):
Upgrade blower packages are available for adding air conditioning or heat pump systems. See furnace “Options and Compatibility” label for systems available.
)
4
23 3/4"
(603 mm)
Cabinet
Insulation
8
Item
Number
7
(Se e Fi g. Descri ptio n
1 4-Speed Blower
27" (686 mm)
4 Ton - See Notes: 1 & 5 5 Ton - See Note: 1
2 A.C./H.P. Relay Control
See Not e: 1
3 Cabinet Insul at i on K i t
1
2
29" (737 mm)
3
4 "A" -Coi l Conversi on Ki t
5 Coil Cabi net
See Not es : 1 & 5
See Not e: 2
See Not e: 3
6 Upflow St and
See Not e: 4
20"
(508 mm)
20" (508 mm)
29" (737 mm)
Notes:
1) For A/C and H/P use.
2) Includes coil filters.
3) For upflow or downflow installations.
4) For upflow A/C or H/P installations (includes
5) Standard in EB models.
7 A/ C and H/ P Indoor Coils 8 Return A i r G rille and
Frame A ssem bl y
one filter; use filter from furnace to complete filtering system in this accessory).
23 3/4" (603 mm)
Upflow Coil Cabinet
20" (508 mm)
14" (357 mm
23 3/4" (603 mm)
Filters (one obtained from furnace)
Upflow Stand
NOTE: See Table 2 for descriptions
and notes
Figure 2. Optional Accessories
Table 2. Optional Air Conditioning and
Heat Pump Equipment
11/16"
20-1/8"
(511 mm)
3"
(76 mm)
(17 mm)
Figure 3. Optional Rear Mounting Plate
(P/N 389080)
7
g
g
g
g
3.8 Amps
4 Spd, 3/4HP
11" Dia., 8" W
2.0 - 5.0 Ton
023H 023H 5-Ton
75,000 75,000
22.0 22.0 4 (21.6) 4 (21.6)
240 Volts/60Hz/1-Phase
0.3
2.0 - 4.0 Ton
speed blower allowing the units to accept up to 5 tons of air conditioning or
4 tons heat pump.
speed blower allowing the units to accept up to 5 tons of air conditioning.
3. The factory installed blower for the EH models can be replaced with a multi-
4. The factory installed blower for the EB models can be replaced with a multi-
E2EH E2EB
010H 012H 015H 015HR 017H 020H 023H 010H 012H 015H 015HR 017H 020H
8
Electric Furnace Models
10.4 12.0 15.4 16.6 16.6 20.4 22.0 10.4 12.0 15.4 16.6 16.6 20.4
35,000 41,000 53,000 57,000 57,000 70,000 75,000 35,000 41,000 53,000 57,000 57,000 70,000
(see note 1)
Output, Btuh
Rated Heatin
Supply Voltage
Elements and Blower)
Watts (Total kw, Heatin
2 (10.0) 2 (11.6) 2 (15.0) 3 (16.2) 3 (16.2) 4 (20.0) 4 (21.6) 2 (10.0) 2 (11.6) 2 (15.0) 3 (16.2) 3 (16.2) 4 (20.0)
Elements,
No.(Total kw)
Heatin
Blower Wheel Size 10.5" Dia., 8" Wide
2 Speed, 1/5 HP, 2.0 4 Speed, 1/3 HP, 2.9
2.0 - 3.0 Ton (see note 3) 2.0 - 4.0 Ton (see note 4)
Motor Speed,
Available with
H.P. Rating, Amps
Test ESP, in. w.c. Max
factory installed blower
Optional Coolin
2.0 - 3.0 Ton (see note 3) n/a (see note 3)
Air Filter (Standard) 16" x 20" x 1" (nominal)
Furnace Dimensions Width-20" (508mm), Height-29" (737mm) (see note 2), Depth-24 1/2" (623mm)
with factory installed blower
Optional Heat Pump Available
240V, multiply Btuh rating by the following factors: x 0.92 (230V), x 0.84
1. Heating output rated at listed voltage. For outputs at voltages other than
Table 3. Unit Specifications
(220V), x 0.75 (208V)
coil cabinet and upflow stand.
2. Height is 56" with return air grille installed, 58" with coil cabinet and 72" with
TYPICAL INSTALLATION OF
)
DOWNFLOW SYSTEMS OR PLATINUM SYSTEM
The following steps describe installation in­structions for an under-the-floor supply duct system with a return air system that can be either non-ducted or ducted. Duct connectors (Table 4) are recommended for this application. NOTE: Before installing this furnace, consider all clearances for the installation and future servicing of the furnace. Refer to Table 1.
Return Air and Filtering Systems
Furnaces may be installed with non-ducted or ducted return air. For non-ducted return air systems, either the optional grille and frame assembly or the optional wall mount grille is recommended. For ducted return air systems with air conditioners or heat pumps, either providing an access panel in the duct or using the optional coil cabinet is recommended. The duct system must be properly sized so as to account for any additional external static pres­sure produced from the chosen filtering method.
AND DISCARD THIS FILTER.
3. With optional coil housing:
- see coil cabinet instructions for specific filtering methods.
Filtering Methods - Ducted Return Air
1. Without optional coil housing:
- install a filter with a minimum unrestricted medium area of 324 square inches in the duct above the coil that is accessible for monthly cleaning or replacement by home­owner.
2. With optional coil housing:
-install a filter with a minimum unrestricted medium area of 324 square inches in the duct above the coil that is accessible for monthly cleaning or replacement by home­owner.
Optional Duct Connectors for Downflow Systems
Duct connectors are recommended for heated air distribution in under-the-floor duct systems. With this system, furnaces may be installed on
NOTE: Refer to the instructions supplied with any additional accessories for further installa­tion details.
Filtering Methods - Non-Ducted Return Air
1. Without A/C or H/P uncased coil:
- use the filter supplied with the furnace; ensure that the filter is installed mat side down between the filter retainer and fur­nace top (see Figure 4).
2. With A/C or H/P uncased coil:
- use the optional coil filters; the filter sup­plied with the furnace is not used; REMOVE
FLOOR CAVITY
x
SUPPLY AIR DUCT
*Felt Seal
Corner
Spacers
Reducer
C
*Indicates only applicable for Finger Tab Duct Connector
*OPENING TO DUCT A= 13-1/4" (337 mm)
B= 10-3/4" (274 mm) WITH PLATE (C) REMOVED OPENING BECOMES 13-1/4” x 13-1/4”
Frame
Fasteners (4)
Grille
Furnace Filter
(not used with
A/C or H/P
Figure 4. Grille Support Frame and Grille
Assembly
TOP VIEW
19”
(483 mm)
A
B
19"
X
(483 mm)
Top of
Furnace
Figure 5. Duct Connector Selection (Non-Platinum)
9
combustible flooring without a separate sub­base. Also, the furnace rear mounting plate (see Figure 3) supplied with the duct connec­tors is recommended for use with this type of installation.
Selecting Duct Connector
Non Platinum Duct Connector
1. Determine depth of floor cavity from sur­face of floor to top of supply air duct (see Figure 5).
2. Select appropriate model from Table 4 which matches X-dimension of floor cavity. To maximize air delivery, remove reducer (C in Figure 5) to obtain largest open area that will fit duct/floor construction. NOTE: Duct connectors may be installed in any one of four positions.
Platinum Duct Connector
1. The 14” round duct connector (903896) is designed to connect directly to a 14” flex­duct.
If “X” Use Duct Connector
floor cavity is: Model Part Number
Englis h Me t r i c ( m m ) Finger T ab Screw Dow n
7/8" 22 901987 904008
2" 51 901988 904009 4 1/4" 108 901989 904010 6 1/4" 159 901990 904011 8 1/4" 210 901991 904012
10 1/4" 260 901992 904013 12 1/4" 311 901993 904014
Table 4. Floor Cavity Sizes
Preparing Floor Opening(s)
1. Mark floor opening(s) as shown in Figure
6. Provide minimum clearances at rear and
right side walls of closet or alcove for
installation of furnace and wiring.
2. Cut floor opening on outside edge of marked line so that opening is slightly larger than area marked.
3. Additional provisions may be necessary for optional air conditioning or heat pump if refrigerant lines are installed elsewhere than at the front of the furnace.
4. The refrigerant and entrance supply open­ing dimensions may be adjusted ± 1/2”.
2-3/8" MIN (60 mm)
(432 mm)
23-3/4"
(603 mm)
(95 mm)
3/4"
(19 mm)
Furnace Outer Door
17"
3-3/4"
REAR WALL OF ENCLOSURE
Center Line
14-1/2"
(368 mm)
14-1/2"
(368 mm)
Optional Supply Wire
Entrance
(Not required
for Platinum)
(108 mm)
A/C Or HP
Optional
Refrigerant
"4-1/4 "5
(127 mm) "10
(254 mm)
Line
(86 mm)
20
"
(508 mm)
"3-3/8
6-1/4
(159 mm)
Furnace Outline
16-5/8"
(422 mm)
3" (76 mm)
"
Figure 6. Downflow Floor Cutout Locations (nominal dimensions)
10
Loading...
+ 22 hidden pages