Nordyne CMF2 80-PG Convertible, CMF2 80-PO Convertible Owner's Manual

Counterflow Gas or Oil Heating Appliance
Owners Manual/Installation Instructions
CMF2 80-PG Convertible (65, 75, and 85 KBTU/H Inputs), CMF2 80-PO Convertible (65, 75, and 85 KBTU/H Inputs)
Read all instructions carefully before beginning the installation. Read all labels and tags on the furnace carefully and follow all precautions outlined on those labels and tags.
GENERAL
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
!
WARNING:
Improper installation, alteration, ser­vice or maintenance can cause injury or property damage. Refer to this manual for assistance or consult a qualified installer, service agency, or the gas supplier for additional infor­mation.
FOR YOUR SAFETY
WHAT TO DO IF YOU
SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Rated CMF2-PG CMF2-PO
BTUH 80 CONV. 80 CONV.
Input 75,000 75,000
Output 56,000 60,000
CMF2 furnaces are high quality, direct vent furnaces used for manufactured housing, rec­reational vehicle, and residential These furnaces are offered in either power gas (designated by PG) or power oil (designated by PO) models. The power gas models are de­signed for operation with either natural or pro­pane (LP) gas.
The CMF2 series is convertible from power oil to power gas, and vice versa. Furthermore, the firing rate of the CMF2 80 Convertible Series can be changed using a certified NORDYNE conversion kit field-installed by a qualified service technician. Refer to the “Firing Rate Conversion” section later in these instructions for more information on the firing rate change.
These furnaces are certified to the UL307 standards (UL 307A for oil models; UL 307B for gas models), and can be installed in a variety of applications, as shown in Table 1. This furnace is not to be used for temporary heating of buildings or structures under construction.
!
WARNING:
This furnace must be installed by a quali­fied installing agency and in accordance with applicable local codes and ordi­nances that govern this type of equip­ment. Failure to properly install the fur­nace, base assembly, and venting sys­tem as described herein may damage the equipment and/or the home, can create a fire or asphyxiation hazard, violates U.S. listing requirements, and will void the warranty. This furnace is NOT approved for installation with split system air con­ditioning. Use a NORDYNE packaged air conditioning system.
applications.
INSTALLATION REQUIREMENTS ........................................................................................... 3
Equipment Check .................................................................................................................3
Requirements and Codes .................................................................................................... 3
Important Note ..................................................................................................................... 3
Combustion Air and Ventilation Requirements .................................................................... 4
Venting Requirements – Manufactured Housing Installations ........................................... 4
Venting Requirements – Residential Installations ............................................................... 5
Unit Location and Clearance Requirements ....................................................................... 7
UNIT INSTALLATION ................................................................................................................ 7
MA-200 Base Installation ..................................................................................................... 8
MA-100 Universal Base Installation .................................................................................... 8
Combustion Air Duct/Pipe Installation ................................................................................. 8
Damper Installation .............................................................................................................. 9
Installation of Furnace onto the MA-200 Base .................................................................... 9
Installation of Furnace onto the MA-100 Base .................................................................... 9
CB-200 Cottage Base Installation ....................................................................................... 9
Closet Installation of the Furnace ...................................................................................... 10
Chimney Installation ........................................................................................................... 13
Installation of Ventilaire III or IV Air Quality Package ........................................................ 13
FUEL CONNECTIONS ............................................................................................................. 13
Oil Piping Installation – PO Series Only ............................................................................ 14
Fuel Line Hook-Up ............................................................................................................. 14
HookUp Procedure ............................................................................................................ 14
How to Eliminate Air Leaks ................................................................................................ 16
Fuel Oil Type ...................................................................................................................... 16
ELECTRICAL WIRING ............................................................................................................. 16
General ............................................................................................................................... 16
Line Voltage Requirements ................................................................................................ 16
Line Voltage Connections .................................................................................................. 16
Room Thermostat Requirements ...................................................................................... 16
Room Thermostat Connections ........................................................................................ 17
FAN AND LIMIT CONTROLS .................................................................................................. 17
Fan Limit Switch ................................................................................................................. 17
Supply Air Limit Switch ....................................................................................................... 17
Auxiliary Limit ..................................................................................................................... 17
MAINTENANCE ........................................................................................................................ 18
Air Filters ....................................................................................................................
Combustion Air and Venting System ................................................................................. 18
LIGHTING AND OPERATING INSTRUCTIONS FOR CMF2 PG DIRECT IGNITION GAS
BURNERS ......................................................................................................................... 18
Operating Instructions for PG Direct Ignition Burner ....................................................... 18
To Turn Off Gas to the Appliance ..................................................................................... 18
Checking the Input of the Furnace .................................................................................... 19
Measuring the inlet Gas and Manifold Pressures ............................................................ 19
Gas Burner Controls ......................................................................................................... 20
Natural Gas to LP Conversion .......................................................................................... 20
Adjusting the Burner .......................................................................................................... 21
LIGHTING AND OPERATING INSTRUCTIONS FOR CMF2 PO OIL BURNERS .............. 22
Start-Up Procedure ........................................................................................................... 22
Air-Bleed Procedure - Single Pipe Installation ................................................................... 22
Oil Burner Shutdown Procedure ....................................................................................... 22
Flame Adjustment .............................................................................................................. 22
Electrode Setting ................................................................................................................ 22
SWITCHING FROM INTERRUPTED TO INTERMITTENT IGNITION CONTROL ............. 22
FIRING RATE CONVERSION .................................................................................................. 23
FURNACE OPERATING SEQUENCE .................................................................................... 23
ADJUSTING HEAT DISTRIBUTION ....................................................................................... 24
SERVICE GUIDE FOR FURNACES WITH PGB POWER BURNER WITH DIRECT
IGNITION-GAS GUN ........................................................................................................ 24
TROUBLESHOOTING ............................................................................................................. 26
TABLE OF CONTENTS
........ 18
!
WARNING:
Do not use this appliance if any part has been submerged under water. Immedi­ately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been submerged under water.
Installations (Manufactured Home Sites, Communities, and Set-ups), ANSI 225.1.
All residential installations (Refer to Table 1) must conform with these instructions, all applicable local building codes, ANSI Z223.1/ NFPA 54 (National Fuel Gas Code), ANSI/ NFPA 31 (Installation of Oil-Burning Equipment), ANSI/NFPA70 (National Electrical Code), and NFPA 211 (Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances).
INSTALLATION REQUIREMENTS
Equipment Check
All units are securely packaged at the time of shipment and should be carefully inspected upon arrival for damage. Claims for damages (apparent or concealed), shortage in shipment, or nondelivery should be filed immediately against the carrier by the consignee. The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The manufacturer will not accept claims for transportation damage.
Requirements and Codes:
Installer shall be familiar with and comply with all codes and regulations and applicable to the installation of these heating appliances and related equipment.
All manufactured housing installations must conform with these instructions, all applicable local codes, ANSI Z223.1/NFPA 54 (National Fuel Gas Code), ANSI/NFPA 31 (Installation of Oil Burning Equipment), ANSI/NFPA 70 (National Electrical Code), the Manufactured Home Construction and Safety Standard, Title 24 CFR, part 3280, or when this standard is not applicable, the standard for Manufactured Home
The National Fuel Gas Code is available by writing:
American National Standards Institute, Inc.
1430 Broadway New York, NY 10018
NFPA publications are available by writing:
National Fire Protection Association
Batterymarch Park Quincy, ME 02269
IMPORTANT NOTE
The Commonwealth of Massachusetts re­quires compliance with regulation 248 CMR
4.00 and 5.00 for installation of through – the – wall vented gas appliances as follows:
(a) For direct-vent appliances, mechanical-
vent heating appliances or domestic hot water equipment, where the bottom of the vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfied:
1. If there is not one already present, on each floor level where there are
Type of Ducted Direct Vent Furnace Flue Products
Installation Applica tion System Requir ed Bas e Us ed Exhaus te d By
Manufactured
Housing or Yes Yes
Recreational Vehicle
Residential
Residential
Residential
†Residential is only defined as a s ingle-story non-manufac tured housing installation.
*Refer to the "Venting Requirements " section later in these instructions for more details on properly v enting this appliance through an existing chimney.
Yes
Yes
No
Yes
Yes
No
Table 1
MA-100 or MA-200
Universal Base
MA-100 or MA-200 NORDYN E SRJ Roofjack or
Universal Base an Existing Chimney*
CB-200A Cottage NORDYNE SRJ Roofjack or
Base an Existing Chimney*
CB-200A Cottage NORDYNE SRJ Roofjack or
Base an Existing Chimney*
NORDYNE SRJ
Roofjack Only
3
bedroom(s), a carbon monoxide de­tector and alarm shall be placed in the living area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall be located in the room that houses the appliance or equipment and shall:
a. Be powered by the same electrical
circuit as the appliance or equip­ment such that only one service switch services both the appliance
and the carbon monoxide detector; b. Have battery back-up power; c. Meet ANSI/UL 2034 Standards and
comply with NFPA 720 (2005 Edi-
tion); and d. Have been approved and listed by a
Nationally Recognized Testing Labo-
ratory as recognized under 527
CMR.
3. A Product-approved vent terminal must be used, and if applicable, a Product­approved air intake must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.
b. Be either hard-wired or battery pow-
ered or both; and
c. Shall comply with NFPA 720 (2005
Edition).
3. A Product-approved vent terminal must be used, and if applicable, a Product­approved air intake must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.
Combustion Air and Ventilation Requirements
Provisions for adequate combustion air and ventilation air must be in accordance with the ANSI Z223.1/NFPA 54, (National Fuel Gas Code), ANSI/NFPA 31 (Installation of Oil Burning Equipment), and all applicable local codes.
Depending upon the type of installation (See Table 1), the CMF2 furnace can draw the combustion air either from outside the home (direct vent) or from the space being conditioned. A direct vent system is one in which the flue products are exhausted to and the combustion air is drawn from outside the house. A direct vent system can also be referred to as a sealed combustion system.
4. A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the location of vent terminal. The plate shall be of sufficient size to be easily read from a distance of eight feet away, and read “Gas Vent Directly Below”.
(b) For direct-vent appliances, mechanical-
vent heating appliances or domestic hot water equipment where the bottom of the vent terminal and the air intake is installed above four feet above grade the following requirements must be satisfied:
1. If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide de­tector and alarm shall be placed in the living area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall:
a. Be located in the room that houses
the appliance or equipment;
4
For direct vent applications either the combustion air duct provided with the MA Series base kit or the direct vent kit can be used. The direct vent kit must be ordered separately. Only for a special CB-200A cottage base installation can the CMF2 draw the combustion air from the conditioned space. The CB-200A cottage base kit must be ordered separately. Refer to the replacement parts listing provided with the furnace to order the direct vent kit or the cottage base kit. Follow the instructions provided with the kits for proper installation.
When unsure about combustion air supply availability, a direct vent system should be used. For small rooms, confined spaces, tight construction or similar situations in which the combustion air requirements of the furnace might not be met, a direct vent system must be used. The air openings in the door of the unit and the warm air registers from the ductwork or base must not be restricted.
Combustion air must not be drawn from a contaminated atmosphere. Excessive exposure to contaminated combustion air will
result in safety and performance related problems. Some examples of chemical contaminants are chlorine, fluorine, and sulfur, which can be found in a wide variety of some common commercial and household products.
The installation of the furnace must allow for an adequate supply of combustion air. The combustion air opening of the furnace must be designed and located to prevent blockage by snow.
When drawing the combustion air from underneath the home, ensure that a vent or duct of at least 18 square inches of free area is provided from outside. Check to ensure that the combustion air opening is unobstructed. When using the combustion air duct, ensure that it extends through the floor. When using the direct vent kit, the combustion air opening must be located in the same pressure zone as the flue exit of the roof jack or chimney. Refer to the instructions provided with the direct vent kit for more information.
!
WARNING:
When venting through a chimney, check the chimney for soot, leaks, obstruc­tions, and proper installation.
The materials used to construct the venting system must be capable of withstanding exposure to temperatures of at least 700 degrees F. The existing chimney servicing this furnace must be vertical. Horizontal distances to an existing chimney must be as short as possible, and the connecting pipe must slope upward to the chimney at not less than a 45 degree angle. The total length of the sloping pipe must not exceed 6 feet. The venting system must have no obstructions or sharp bends where soot and other foreign matter can accumulate.
If an inspection determines that the chimney is obstructed, the chimney must be cleaned. Furthermore, the connecting flue pipe must be cleaned or replaced.
Venting Requirements — Manufactured Housing Installations
For all manufactured housing applications, the CMF2 furnace must be vented using the SRJ series roofjack. The instructions for selecting the proper roofjack for your installation are detailed later in these instructions.
Venting Requirements — Residential Installations
!
WARNING:
This furnace is not to be connected to a chimney flue serving a separate appli­ance designed to burn solid fuel.
For residential applications (Refer to Table 1), the CMF2 furnace may be vented through the SRJ series roofjack or through an existing chimney. If the SRJ roofjack is to be used, then the instructions for selecting the proper roofjack for your installation are detailed later in these instructions. If venting through an existing chimney, then the venting system used must be in accordance with these instructions, all applicable local building codes, ANSI Z223.1/ NFPA 54 (National Fuel Gas Code), ANSI/ NFPA 31 (Installation of Oil-Burning Equipment), and NFPA 211 (Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances).
For ONLY a CMF2 power oil furnace installation vented into an existing chimney, a barometric damper can be installed at the vent connection of the furnace to regulate the draft. The barometric damper must be properly installed per the manufacturer’s instructions. Refer to all
Flashing Barrel
Ceiling Plate
Ventilation Knock-Out
Return Air Grille and Filter
Power Supply Connection
Access Door
Base Pan
Fuel Line
Feeder Duct
Combustion Air Duct
Vent
ROOF JACK
ASSEMBLY
FURNACE
ASSEMBLY
Combustion Air Adapter (Not Shown) is to be Installed Over Combustion Air Duct
DUCT
CONNECTOR
Figure 1. Typical Furnace Installation for
Manufactured Housing Applications
5
applicable codes to determine whether or not a barometric damper can be used for your CMF2 power oil furnace installation. The barometric damper used must be installed such that air from the conditioned space can only enter the flue passageway. Do not use a double acting barometric damper. All flue pipe joints should be fastened with sheet metal screws for rigidity.
The chimney height, required draft, and number of appliances served by the chimney must be in accordance with all applicable codes. To prevent down draft, the chimney should extend at least two feet above the peak of the roof.
Closet Alcove
ALL MODELS Ins ta llation Installation
Sides 0" 0" Back 0" 0" Front 6"** 18" Top 17" 17" Vent 6" 6" Duct within 3' from Furnace 1/4" 1/4" Plenum 1" 1" Roof Jack Barrel 0" 0"
** See Item K in the "Closet Installation of
Furnace" section later in these instruc­tions for clearance less than 6".
Table 2. Minimum Clearances
to Adjacent Materials
It is recommended that the furnace flue serve no other appliances. When the chimney serves only the furnace, the flue area must be sized according to all applicable codes. The minimum internal area of the flue must be equal to at least the area of the furnace flue exit.
When two or more appliances must vent through a common flue, the area of the common flue should be sized in accordance with all applicable codes.
When an existing furnace is removed or replaced in a venting system, then the venting system may not be properly sized to vent the attached appliances. The venting system must be checked to ensure proper venting. Improperly sized venting systems can result in the formation of condensate, leakage, spillage, etcetera. Refer to the ANSI Z223.1/NFPA 54, (National Fuel Gas Code), and ANSI/NFPA 31( Installation of Oil Burning Equipment) for correcting any improperly operating venting system.
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:
(a) Seal any unused openings in the venting
system.
9-1/8
Feeder Duct
12-1/8
Flue
Location
Opening
7-1/8 X 2-3/16 Knock-outs
Combustion Air
FRONT
18-1/4
12-1/8
8-3/8
24-1/8
(b) Inspect the venting system for proper size
and horizontal pitch, as required in the ANSI Z223.1/NFPA 54, (National Fuel Gas Code) and ANSI/NFPA 31 (Installation of Oil Burning Equipment), and these instruc­tions. Determine that there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
(c) In so far as is practical, close all building
doors and windows and all doors between the space in which the appliance(s) con­nected to the venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not con­nected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
Figure 2. MA-200 Base Pan
6
(d) Follow the lighting instructions. Place the
appliance being inspected in operation. Adjust thermostat so appliance shall oper­ate continuously.
(e) Test for draft hood equipped appliance
spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
(f) After it has been determined that each
appliance connected to the venting sys­tem properly vents when tested as out­lined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previ­ous conditions of use.
Slit 4 Corners
Base
Bend Over Tabs
Flange
Slit 4 Corners
Flange
Bend Over Tabs
Bend Down 4 Sides
Heater Duct Below Joists
Bend Down 4 Sides
Base
Heater Duct Below Joists
Floor
Joists
TRANSITION
DUCT
Floor
Joists
(g) If improper venting is observed during any
of the above tests, the venting system must be corrected.
Unit Location and Clearance to Adjacent Material Requirements
The unit must be installed in a level position. The furnace must be installed with the minimum clearances from adjacent materials as stated in Table 2. Additional clearance should be provided to permit servicing of filters, blower, motors, controls, combustion air connections, and vent connections.
UNIT INSTALLATION
These instructions are intended for the use of qualified individuals specially trained and experienced in installation of this type equipment and related system components. Installation and service personnel are required by some governing bodies to be licensed. Persons not qualified should not attempt to install this equipment or interpret these instructions.
MA-200 Base Installation
The MA-200 base is designed for O.E.M. and replacement installation of the CMF2 series furnace (see Figures 2 and 3). The warm air duct system should be designed so the duct static pressure external to the furnace does not exceed the static pressure listed on the furnace data label.
Figure 3. Transition and Offset Ducts
Feeder Duct
12-1/8
7-1/8 X 2-3/16 Knock-outs
Opening
24-1/2
12-1/8
Combustion Air
18-1/4
Use the base pan to mark the 12-1/8" x 12-1/ 8" center opening for the feeder duct. When the 4" offset feeder duct is used, the floor opening will be offset 4 inches from the opening in the main duct. If using the combustion air duct, select and knock out the combustion air open­ing to be used. Then mark the 2-1/4" x 7-1/4" opening for the combustion air duct.
Cut This Line
Bend Over
1"
Base
Heat Duct Below Joists
Feeder Duct
Along This Line
Floor
Joists
Figure 4. MA-100 Universal Base,
Bottom Panel
Figure 5. Feeder Duct Installation
7
Cut the opening for the feeder duct 14-1/8" x 14­1/8" in flooring (cutting opening 1" larger all the way will allow the flanges on the underside of the base pan to fit in the opening).
the feeder duct. If using the combustion air duct, select and knock out the combustion air open­ing to be used. Then mark the 2-1/4" x 7-1/4" opening for the combustion air duct.
If using the combustion air duct, cut the opening for the duct about 1/8" larger than the marking on the floor. Be sure to cut through all insulation and the bottom board so that the combustion air duct is unobstructed to outside air.
Drill an approximate 1" diameter hole for the fuel line through the floor and bottom board to the outside. Fuel lines are not supplied with the furnace. They should be installed to comply with all applicable codes.
Drop transition or offset feeder duct upside down through the floor opening and center the top of the feeder duct in 14-1/8" x 14-1/8" floor opening. Using the feeder duct as a guide, mark and cut a 12" x 12" opening in the distribution duct. (See Figure 3)
Insert the feeder tabs into the main duct and bend them over tightly so that the main duct edges are trapped between flanges and tabs. Metal tape may also be used to ensure an air tight connection. Install the base pan around the feeder duct with the (2) screws through the holes towards the rear of the base pan.
Slit the corners of the feeder duct down to the top of the base pan. While the top of the distri­bution duct is pulled up with one hand, bend down each side of the feeder duct tightly to the base with the other hand. Trim the metal to allow a one inch flange over the top of the base pan and seal that flange with the metal tape.
If a “V” or “U”-box crossover system is to be used, see the instructions provided with the crossover system.
MA-100 Universal Base Installation
The MA-100 base is designed primarily for replacement installation of the CMF2 series furnace where the manufactured home duct system may be small and restrictive to proper air flow. The MA-100 base provides approxi­mately four (4) inches of additional plenum space before the discharge air enters the manu­factured home duct system. (See Figures 4 and
5)
Use the bottom panel of the base assembly to mark the 12-1/8" x 12-1/8" center opening for
8
Cut the opening for the feeder duct 14-1/8" x 14­1/8" in flooring (cutting opening 1" larger all the way around 12-1/8" x 12-1/8" template mark­ing). This will allow the four flanges on the underside of the panel to fit into the opening.
If using the combustion air duct, cut the opening for the duct about 1/8" larger than the marking on the floor. Be sure to cut through all insulation and the bottom board so that the combustion air duct is unobstructed to the outside air.
Drill a 1" hole for the fuel line through the floor and bottom board to the outside. Fuel lines are not supplied with the furnace. They should be installed to comply with local codes.
Put the bottom base panel in place (See Figure
5). Drop the transition feeder duct upside down through the opening and mark a 12" x 12" opening to be cut into the distribution duct. Remove the bottom panel and transition feeder duct; then cut the opening into the distribution duct.
Install the feeder duct by bending the tabs inside the heat duct and using the metal tape to insure an airtight connection.
Set the bottom base panel over the feeder duct. Slit the corners of the feeder duct down to the top of the base. While the top of the distribution duct is pulled up with one hand, bend down each side of the feeder duct tightly to the base with the other hand. Trim the metal to allow one inch flange over the top of the base and seal that flange with the metal tape.
Secure the top panel to the floor with two (2) screws through the front flange.
If a “V” or “U”-box crossover system is to be used, see the instructions provided with the crossover system.
Combustion Air Duct/Pipe Installation
The CMF2 furnace must draw the combustion air from outside, except for special installations (See Table 1). This can be accomplished either by using the 2”X7” rectangular combustion air duct provided in the MA series base kits or using the direct vent kit.
When the rectangular combustion air duct is to be used, install the combustion air duct through the selected knockout in the base. For direct vent applications, the rear knock-out in the furnace base cannot be used. After the combustion air duct has been positioned, install the combustion air adapter. This adapter will transition the 2”X7” opening of the combustion air duct to the 2” diameter of the burner flexible tubing. This adapter is included in the MA series base kits. For retrofit applications in which the MA series base is already installed, the combustion air adapter can be ordered as a kit. Refer to the Replacement Parts List for more details on ordering this kit. Secure the adapter with either wood or metal fasteners (field provided), depending upon the particular installation. Ensure that the gasket for the adapter is positioned properly before installing the adapter. Attach the flexible hose from the burner to the combustion air adapter using the provided metal hose clamp.
When the direct vent kit is used, follow the instructions provided with the kit. Note: The direct vent kit should be installed before positioning the furnace on the base.
Damper Installation
An automatic shut-off damper is available (see replacement parts list). An automated shut off damper is required when the home is air con­ditioned by a self-contained unit. This damper is designed to fit in the feeder duct cavity, directly under the furnace. A damper is required to prevent chilled air from flowing over the furnace heat exchanger. For proper installa­tion, refer to the instructions provided with the damper.
Open the access door. Fasten the front of the furnace and the base to the floor with #8 x 1/2" long sheet metal screws.
Using the provided hose clamp, secure the flexible combustion air tubing from the burner to the combustion air adapter.
Installation of Furnace onto the MA-100 Base
Tilt the furnace forward and carefully work the furnace back over the MA-100 Universal base.
Lift the furnace as necessary when positioning the unit over the base assembly to prevent any damage to the feeder duct assembly and com­bustion air adapter, if present.
Be sure the furnace is positioned all the way to the back of the base assembly.
Open the furnace door and fasten the furnace to the base using #8 x 1/2" long sheet metal screws.
Using the provided hose clamp, secure the flexible combustion air tubing from the burner to the combustion air adapter.
CB-200A Cottage Base Installation
The CMF2 can be installed on a CB-200A cottage base in certain applications, as described earlier in these instructions (See Table 1). Refer to the Replacement Parts List
Installation of Furnace onto the MA-200 Base
Lift the furnace over the base so that the flange at the back comes to rest on the inside rails of the base.
Raise the front of the furnace to clear the gasket on the bottom of the furnace and slide the back until the rear flange drops into the channel at the rear of the base. Be careful not to damage the combustion air adapter, if present, while posi­tioning the unit.
Be sure that the furnace is all the way back so as to engage the tabs on the rear flange on the base.
Figure 6. Closet Installation
9
Loading...
+ 19 hidden pages