Nordyne B3BV Installation Instructions Manual

Installation Instructions
B3BV Series Electric Furnaces
For HUD approved installations in manufactured homes and modular homes
These instructions are intended to assist qualified individuals experienced in the proper installation of heating and/or air conditioning appliances. Some local codes require licensed installation/service personnel for this type equipment. All installations must be in accordance with these instructions and with all applicable national and local codes and standards. Improper installation, service, adjustment, or maintenance can cause, fire, electrical shock or other conditions which may result in personal injury or property damage. Unless otherwise noted in the instructions, only factory authorized kits or accessories may be used when modifying this product.
INTRODUCTION
The B3BV Series electric furnaces are approved for use in HUD code manufactured homes (HUD Manufactured Home Construction and Safety Standard (Title 24, Part
3280)) and other modular home applications. The B3BV Series electric furnace may be installed in downflow or upflow applications
as “freestanding” units, and in closet or alcove installations. B3BV Series electric furnaces are supplied with factory installed electric heat. Approved
NORDYNE heat-pump/air conditioning coils may be installed in the field.
GENERAL INFORMATION
Codes
All electrical power wiring for the B3 series electric furnace must be installed in accor­dance with:
1) HUD Manufactured Home Construc­tion and Safety Standard
2) NFPA 70 - National Electric Code (NEC)
rules. Do not leave disconnected after servicing or adding A/C to the system.
RETURN AIR
In closet or alcove installations provide at least 235 square inches free opening for return air for B-cabinet (19 3/4" wide) models and 300 square inches for C­cabinet (22 1/2" wide) models.
NOTE : Circuit breakers installed in the B3 electric furnace are for short-circuit protection of the internal wiring and to serve as a unit disconnect. Circuit break-
ers installed in the B3BV electric furnace DO NOT provide over-current protection of the supply wiring. Over-current protec­tion of the supply wiring must be provided at the distribution panel and sized as shown in the installation instructions or on the unit data label, and per the NEC.
Location
Reference the installation instruction in­cluded with this unit for location require­ments.
Clearance
All electric heater kits less than 20 kw are approved for use in air handler installa­tions with zero-clearance to combustibles at any blower speed. For horizontal and upflow configuration, air handlers equipped with 20 kw electric heater kits are approved for installation with zero clearance to combustibles at any blower speed. When using a 20 kw electric heat kit in a downflow installation, the blower must be set for high speed for both heating and cooling.
VENTILATION
The B3BV electric furnace has a cut-out on each side for ventilation air. Use NORDYNE part number 914120 or 914427 adaptor with Ventilaire III or IV to supply the proper amount of ventilation air. The VentilAire connections must be made for the system to conform to H.U.D.
The return air opening can be located in a closet door or a sidewall. If the return air opening is directly adjacent to the side (or front) of the air handler, 6" minimum clear­ance must be provided between the side of the furnace and the return air opening. If no part of the return air opening is directly adjacent to the unit no clearance is re­quired.
If an upflow pedestal mounting stand is fabricated in the field it must be constructed strong enough to support the unit with all accessories installed (approximately 130 lbs. for B-cabinet models and 200 lbs. for C-cabinet models). The construction of the pedestal stand must also allow for at least 235 square inches free opening (300 square inches for C-cabinet models) in the application. Field fabricated upflow ped­estal mounting stands must be constructed of noncombustible materials.
Refer to the installation instruction included with this unit for other return air details.
SUPPLY AIR DUCTS
The duct system must be designed so that the external static pressure of the system does not exceed the maximum external static pressure indicated on the unit data label.
Downflow applications require the use of a plenum connector shown in Figure 1 or its equivalent if the supply air ducts pass through the floor of the structure. See Table 1 for plenum connectors available.
2
Description
Downflow Plenum Connect o r, 6. 25 "
Downflow Plenum Connect o r, 8. 25 "
Downflow Plenum Connector, 10. 25"
Cabinet Size
BC
913840 914969
913841 914970
913842 914971
INSTALLATION
Install the unit as directed in the Installa­tion Instructions. NOTE: Secure the unit to the structure using metal strap and/or fas­teners at the top of the unit and at the bottom of the unit.
POWER WIRING
!
W ARNING:
Upflow Pedes t al Mo un ting Stan d
Downflow Coil Adaptor
Table 1. Optional Accessory Kits
The plenum connectors are designed for use with trunk ducts having a minimum width of 12 in. If sufficient space is not available to adequately bend and secure plenum tabs it may be necessary to attach the connector to the duct using sheet­metal fasteners and seal with an approved foil tape.
Plenum connectors may be field con­structed but must meet requirements as stated in the unit installation instructions.
913872 913873
917343A 917344A
To avoid risk of electric shock, personal injury, or death, disconnect electrical power to the unit before performing any maintenance or service. The unit may have more than one electric power supply.
All wiring must comply with the current revision of the National Electric Code and must be sized for the minimum ampacities as listed on the unit data label or in Table
2. If a single circuit adaptor kit is used, it may
need to be re-configured for some appli-
13.25"
18.5" (B-Cab.)
21.25" (C-Cab.)
Figure 1. Plenum Adapter
3
Loading...
+ 5 hidden pages