NORD TI 276997120 User Manual

under strict compliance with the safety and warning instructions which they contain. All of the information that is
Enclosed package for creating protection against contact (not SK 5xxE-452-340-A
SK 5xxE-552-340-A
8
45 kW / 55 kW
Technical Information / Datasheet
Pos: 1 /Tec hnische Inf ormation en/Drosseln /SK DCL-950/120-C / 276997120 / Basisinformationen [SK DCL-950/120-C] @ 4\mod_1388745773880_388.docx @ 110002 @ 5555 @ 1
SK DCL-950/120-C
Part number: 276 997 120
Link circuit choke
NOTICE
This document is only valid in combination with the operating instructions of the relevant frequency inverter and relevant for a safe start-up of this module and the frequency inverter is only available under thes e condi tion s.
Validity of this document

Scope of delivery

1 x Module SK DCL-950/120-C 1 x
IP20)
Shrink tube

Usage area

Link circuit choke to im prove mains quality. Due to its principle of oper ation, distortions of the mains voltage caused by the fr equency inverter are c onsiderably reduced b y the use of a link circuit chok e. The harmonic com ponent of the current is reduced to approx. 40% and the power factor (lam bda) is increased. The module is installed in the immediate vicinity of the frequency inverter.

Frequency inverter assignment

Permissible frequency inverters (FI) FI size FI power

Technical data

General
Temperature range -10 … 50°C Temperature class F (VDE) / Class 155 (UL) Protection class IP00 Fastening 4 x M6 Weight 12.5 kg
Link circuit choke SK DCL-950/120-C
1.0 Erstausgabe / first issue 1014 Rck TI 276997120 GB
version reason for change(s) issue name document speech
Link circuit choke – SK DCL-950/120-C
Housing dimensions
L x W x H [mm]
146 x 145 x 205
No.
Designation
Connection*
Type
Torque
* Connection cross-section 50 mm²
Number of phases
1
Inductance
mH
0.5 ± 10%
Rated current
A =
120 Power dissipation
W
110
injury or damage to adjacent components, an adequate minimum distance must be maintained or appropriate Installation orientation
Floor-standing or on the rear wall of the control cabinet.
Fastening
With screw fastenings
Note
Protection against contact
Adequate protection against accidental contact must be ensured during installation. This protection can, for
Dimensions
Fastening L x W [mm] 100 x 95
Connections
1 Intermediate
circuit
2 Earth lead PE M8 12.0 Nm
-DC, CP M8 12.0 Nm
Electrical data
Rated voltage V = 950 Resistance of windings mΩ 4.2
Pos: 3 /Technis c h e Inf ormation en/ D r osseln/Mo ntage [Zwisc henkreisdr ossel - SK 5xxE] @ 4\mod_1389000368910_388.docx @ 110111 @ 5 @ 1

Installation

DANGER!
Do not work on live components (observe the 5 safety rules!) Failure to comply with this will result in serious or fatal injuries in case of contact.
Electric shock
5 safety rules:
• Disconnect
• Secure against switching on
• Check for no voltage
• Earth and short circuit
• Cover or guard adjacent live components
CAUTION
When in operation, the surface temperature of the device may reach temperatures of approx. 105 °C. To avoid protective devices must be provided.
Danger of burns
Installation l ocation Inside a control cabinet near to the frequency inerter. Note the load bearing
capacity of the mounting plate!
example, be by use of the enclosed shrink tube.
2 / 3 TI 276997120 - 1014