NORD TI 275900190 User Manual

Page 1
This document is only valid in combination with the operating instructions for the relevant frequency inverter. All
Pos: 1 /Technis c h e Inf ormation en/ SK xUx - Bus - Er weiterung en/PROFIN ET IO/SK T U3-PNT / 275900190 / Basisinformationen [SK TU3 -PNT] @ 4\mod_1385370630863_388.docx @ 106376 @ 555 @ 1
SK TU3-PNT
Technical Information / Datasheet
Part number: 275 900 190
PROFINET IO® - External Bus – Interface
NOTICE
of the information that is relevant for a safe start-up of this module and the frequency inverter is only available under these conditions.
Validity of this document

Scope of delivery

1 x Module SK TU3-PNT

Field of use

Technology unit for connecting a frequency inverter (SK 5xxE) to a PROFINET IO field bus. The module must be directly plugged into the technology slot of the frequency inverter.

Technical data

Module
Temperature range 0 °C … 40 °C Vibration resistance 2M1 Temperature class Class 3K3 Firmware version V1.2 R0 Protection class IP20 Hardware version AA
Supply voltage 24 V ± 20 %, ≈ 100 mA
Dimensions [mm] H x W x D: 27 x 73 x 101
Reverse polarity protected
PROFINET IO Bus module SK TU3-PNT
1.0 Erstausgabe / first issue 4913 Rck TI 275900190 GB
version reason for change(s) issue name document speech
Page 2
PROFINET IO Bus module – SK TU3-PNT
Isochronous real time communication of synchronised
Transmission and receiver cables are automatically
diagnosis socket on the device (if available) and possibly
Bus specification
EtherNet/IP Max. 100 MBaud Cable Min. Ethernet CAT-5 Electrical isolation 500 V
Max. cable length 100 m between two
eff
modules Bus connection 2 x RJ45 Shield via RJ sockets High­bus termination performed automatically Resistive & capacitive to
PE Status display 8 LEDs PE connection via PE post-type connector Topology* Star, tree, ring, linear bus (rating less than 24 V)
Performance
Update interval for process data between module and frequency inverter ≤ 2.5 ms Parameter read access on the frequency inverter ≈ 15 ms Parameter write access with storage in EEPROM ≈ 25 ms Cycle times ≥ 1 ms
Pos: 8 /Technis c h e Inf ormation en/ SK xUx - Bus - Er weiterung en/PROFIN ET IO/Mer kmal e [PNT Allge mei n] @ 4\mod_1385365458675_388.docx @ 106301 @ 5 @ 1

Module features

Communication RT (Real Time)
à Real time communication of process data
IRT (Isochronous Real Time)
à process data
Addressing Automatic address assignment via IO controller using DCP
(Discovery Configuration Protocol) Data transfer via Switched Ethernet Autonegotiation Negotiation of transfer parameters Autocrossover
crossed in the switch as necessary Conformity classes CC-B, and CC-C Access for NORD diagnosis tool via
via frequency inverter and
Ethernet protocols UDP or TCP/IP
Pos: 9 /Anleit ung en/Elektr onik/FU und St arter/3. /4. A nzeige und Be di e n ung [BU 0500 / BU 0200]/SK 5xxE/3.2 Übersicht der Technologieboxen -2- Montage @ 1\mod_1340712929975_388.docx @ 28340 @ 5 @ 1
2 / 8 TI 275900190 - 4913
Page 3

Installing

mains voltage, observe the
Push the control terminals cover down
with an upward turning movement. If
RJ45 Pin
Signal
Description
1
TX+
Transmission Data +
3
RX+
Receive Data +
6
RX-
Receive Data -
Terminal
Name
Description
45
+ 24 V
24 V supply
PROFINET IO Bus module – SK TU3-PNT
Note
Installing the technology unit
Modules should not be inserted or removed unless the device is free of voltage. The slots may only be used for the intended modules.
Installation of a technology unit separate from the frequency inverter is not possible. It must be connected directly to the frequency inverter.
The technology units must be installed as follows:
1. Switch off the waiting period.
2. slightly or remove.
3. Remove the blank cover, by loosening the release on the lower edge and pulling off
necessary, the attachm ent screw next to the release must be removed.
4. Hook the technology unit onto the upper edge slots and press in lightly until it engages. Ensure full contact with t he connector strip and fasten with the screws if necessary (separat e packet).
5. Close the control terminal cover again.
Pos: 12 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/PR OFINET IO /Anschlüss e [SK TU3-PN T] @ 4\mod_1384961413371_388.docx @ 105864 @ 5 @ 1

Connections

The two Ethernet l ines are connected ex clusiv ely via t he two RJ4 5 sock ets on th e front. If the m odule is the final participant on the line, one RJ45 socket can remain unoccupied.
( 1 ) RJ45 socket detail ( 2 ) Power supply detail
2 TX- Transmission Data -
46 GND Earth
Pos: 17 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/PR OFINET IO /Konfigura tion [SK TU 3-PNT] @ 4\mod_1385046026103_388.docx @ 106024 @ 5 @ 1
TI 275900190 - 4913 3 / 8
Page 4
PROFINET IO Bus module – SK TU3-PNT
DIP switch
Meaning
12
11
10 9 8 7 6 5 4 3 2
1
X X
X
No function
Access rights for remote maintenance
0 Only read access to parameters possible.
1 Read and write access to param et ers possible.
0 No control possible.
1 Control is possible.
0 TCP/IP open connection.
and the connected frequency inverter can be
No.
Name
Colour
Meaning
RUN
green
Ethernet State
BF
red
Ethernet Error
DS
green
Device status
Link
green
Link
Activity
yellow
Activity
OFF
ON
12 … 1

Configuration

Configuration of the module for remote maintenance is carried out via the DIP switches. The DIP - switch settings are read after a "Power On" of the module.
1 Secure TCP/IP connection.
1. (DIP 1 - 9) No function
2. Access rights for remote maintenance (DIP 10 – 12) Via the Ethernet pr otocols T CP and UDP th e m odule
accessed using remote maintenance. The type of access is determ ined via the DIP - switch with input s 10 to 12.
Pos: 20 /T echnische I nformatio nen/SK xUx - Bus - Erweiterungen/PROFI N ET IO/LED Anzeigen [SK TU3-PNT] @ 4\mod_1385046540406_388.docx @ 106099 @ 5 @ 1

LED indicators

The operating statuses of the module are visualised using LED indicators.
1
DE red Device error
2
Pos: 24 /T echnische I nformatio nen/SK xUx - Bus - Erweiterungen/PROFIN ET IO/LED Anzeigen- PROFINET spezifische LED [PNT Allgemein] @ 4\mod_ 1385130089638_388.docx @ 106275 @ @ 1
4 / 8 TI 275900190 - 4913
Page 5
PROFINET IO Bus module – SK TU3-PNT
RUN
(Ethernet State)
Meaning BF
(Ethernet Error)
Meaning
OFF
No operating voltage Initialisation
OFF
No error
Flashing gree n
No process data communication
Flashing red
Green ON
Parameter communication active Process data communication active
Red ON
Ethernet error à there is no physical
1sec pause)
Link
(Green LED)
Activity
(Yellow LED)
Meaning
OFF
OFF
Module not ready, no control voltage.
ON
OFF
No bus activity
ON
Flashing
Bus connection (cable connection) to another Ethernet device exists
Bus activity present
Meaning
Short flash = 0.25 s on / 1 s off
OFF
OFF
Module not ready, no control voltage.
ON
OFF
Module ready, no error, at least one frequency inverter is communicating via the system bus
Long flashing
OFF
Module ready and at least one other participant is connected to the system bus, but
Software incompatible (module software and FI software do not match - update required)
Long flashing
Short flashing
System bus is in status "Bus Warning"
Frequency inverter has no supply voltage
Long flashing
Short flashing
System bus is in status "Bus Off"
Long flashing
Short flashing
Long flashing
Short flashing
4
Module error
PROFINET-specific LED
No connection to PROFINET IO controller No parameter communication
(Blinking)
Pos: 25 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Al lgemein - S ystemüberg reifend/LED Anzeigen- N ORD spezifische LED [EIP / POL / ECT / PNT Allgemein] @ 3\mod_1363773424248_388.docx @ 61815 @ @ 1
NORD-specific LEDs
DS
(Device status)
ON Short flashing
DE
(Device error)
Double-flashing
red
(2 x 0.25 s,+
• No bus connection (check cable connection)
• Bus connection (cable connection) to another Ethernet device exists
Long flash = 0.5 s on / 1 s off
Module ready, but
• One or more of the connected frequency inverters has fault status
No process data communication à e.g. wrong GSDML file
connection to a further participant PROFINET or FI timeout,
(see also P151, P513)
Flash interval
1 x - 1s pause
Flash interval
2 x - 1s pause
Flash interval
3 x - 1s pause
Flash interval
x - 1s pause
OFF Short flashing
Flash interval
1…7 - 1s pause
Pos: 26 /Techni sche Infor mationen/ SK xUx - Bus - Erweiterungen/PROFINET IO/Fehlerm eldungen Profinet Baugruppen allgemein [SK xUx-PNT - Allgemein] @ 4\mod_1384961728468_388.docx @ 105889 @ 5 @ 1
no frequency inverter connected to system bus (connection may be interrupted)
one or more system bus clients has address error
Communication on system bus disrupted
No other clients available on system bus
Module not inserted correctly or no connection to the system bus
the system bus 24V power supply was interrupted during operation
System bus is in status "Bus Off"
No system bus 24V power supply
see parameter P170
System error, internal program sequence interrupted
EMC interference (observe wiring guidelines!)
• Module defective
TI 275900190 - 4913 5 / 8
Page 6
PROFINET IO Bus module – SK TU3-PNT
Error
Meaning
Remarks
100.0
EEPROM error
EMC fault, module defective
102.0
Timeout
via P151/P513 monitoring
104.0
Module temperature too high
only SK CU4-…, permissible internal temperature of the bus module exceeded for approx. 60 sec
560.0 …
Internal error
Module not ready
561.0
General network error
561.1
Ethernet Watchdog timeout
561.2
Bus cable fault
Bus cable connection interrupted
561.3
IP address error
IP address of the module has been doubly assigned
563.0
Firmware version incompatible
The firmware version cannot be used for the device
564.0
MAC address error
Error (E010)
Meaning
Remarks
10.0
Connection error
Contact to SK xU4 lost
10.1
ASIC errors
Communication to Ethernet - ASIC lost
Reduce the temperature of the module (only SK CU4-…)
• Check the Watchdog time
10.4
IP address error
IP address of the module has been doubly assigned
10.5
Internal error
Module not ready for operation, configuration error
10.6
Bus cable fault
Bus cable connection interrupted
and the module had a timeout
10.9
Module missing (P120)
Only SK xU4 module

Error messages

Error messages fr om the m odule - present error s or archived m ess ages relating t o the last error - can be read out via the module par ameter (P170). The error messages are lost if the m odule is switched off.
103.0 System bus BUS OFF No 24V supply to the bus, connections not correct
560.9
Errors which occur in relation to the module are depicted as follows in the error memory of the frequency inverter (P700 / P701).
10.2 Ethernet Watchdog timeout Telegram transfer error
10.3 Timeout by P151/P513 Telegram transfer error
10.8 The connection between the inverter
Pos: 27 /T echnische I nf ormatione n/ SK xUx - Bus - Erw eiterunge n/Allgemei n - Systemübergreifend/Parameter [SK xUx-... Allgemein - Fr equenzumr ichter] @ 4\mod_1384953855694_388.docx @ 105781 @ 5 @ 1
Switch-off of the supply voltage
• Check the connections and links, program sequence and Bus Master
• Check the connections and links
Only SK TU3 module
6 / 8 TI 275900190 - 4913
Page 7
PROFINET IO Bus module – SK TU3-PNT
Parameter [-Array]
Meaning
Remarks
P120 [-01]
Option monitoring
"Auto“ (default setting)
Only SK xU4
P509
Control word source
SK TU3-… on SK 5xxE: "Ethernet TU” SK xU4-… on SK 180/SK 2xxE: "System bus"
P510 [-01 … -02]
Setpoint source
"Auto“ (default setting)
P513
Time-out
Monitoring of the SK TU3 bus module
Only SK 5xxE
P543 [-01 …-03 (-05)]
Bus actual values (1 …3 (… 5))
Possible settings according to (P418) and P546 … P548
P700 [-01] / P701
Current / last failures
Information parameters
P740 / P741
Process data bus In / Out
Information parameters
P745
Module version
Information parameters
Only SK TU3
P745
Module status
Information parameters
Only SK TU3
P748
CANopen / System bus status
Information parameters
Parameter [-Array]
Meaning
Remarks
-TU3-
-TU4-
-CU4-
P150
Set relays
Set DOUT directly or control via BUS
X
P151
External bus time-out
Monitoring of the SK xU4 bus module
X X
P152
Factory setting
Reset module parameters
X X X
P153 [-01 …-02]
Minimum system bus cycle
Reduction of the bus load on the system bus caused by the module
X X
P154 [-01 …-02]
Access to option card I/O
Administration of r ead and write rights to the IO of the module
X X
P160 [-01 … 04]
IP address
X X
X
P161 [-01 …-04]
IP subnet mask
X X
X
save by entering "0" as the final ch ar ac ter
P163 [-01 …-07]
Alarm test
Sets a diagnostic alarm
X X X
P170 [-01 … -02]
Present errors
Displaying module errors
X X X
P171 [-01 … -03]
Software version
Firmware version / Revision
X X X
P172
Configuration
Module type
X X X
P173
Module status
Status of system bus or the connected FI
X X X
P175
Digital output state
Image of the switching status of DOUT
X
P176 [-01 … ]
Process data bus In
Information parameter
X X X
P177 [-01 … ]
Process data bus Out
Information parameter
X X X
P178
Internal temperature
Information parameter
X
P180 [-01 … -07]
PPO-Type
Information parameter
X X X
P181 [-01 … -06]
MAC address
Information parameter
X X X
P185 [-01 …-04]
Present IP address
Information parameter
X X X
P186 [-01 …-04]
Current IP subnet mask
Information parameter
X X X

Parameters

Frequency inverter: The following frequency inverter parameters must be adapted for setting up communication between the frequency inverter and the bus module (for details see frequency converter manual).
and P543 … P545 P546 [-01 …-03 (-05)]
Pos: 28 /T echnische I nformatio nen/SK xUx - Bus - Erweit er u ng e n/PROFINET IO/Paramet er [PNT Allg e mei n] @ 4\mod_1385367612358_388.docx @ 106326 @ @ 1
Bus target values (1 …3 (… 5)) Possible settings according to (P400)
BUS module: The module provides a selection of appropriate parameters for setting or displaying special operating values. Parameters can be adapted using the NORDCON software or an SK PAR-3H / -3E param eter box. Via PROFINET IO, all parameters c an still be read and written via the bus master.
P162 Device name Up to 240 character s (ASCII – Code 45 … 1 22),
P174 Status of digital inputs Image of the switching status of DIN X X
X X X
Pos: 29 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/All gemein - S ystemüberg reifend/Par ameterzug riff und Di agnose [Bus BG - Allg e mei n] @ 3\mod_1363794074590_388.docx @ 61915 @ 5 @ 1
TI 275900190 - 4913 7 / 8
Page 8
PROFINET IO Bus module – SK TU3-PNT
Access via RJ12-SK 5xxE
Access via RJ12-Bus diagnosis
connection unit
Access via RJ12-Frequency
verter diagnosis socket , if
connected to module via system
Software
Name
Software
Meaning
GSDML file
Device characteristics and parameters
NORD CON
Parameterisation and diagnostic software
Document
Name
Document
Meaning
BU 0000
Description of NORD CON software
BU 0505
SK 54xE frequency inverter manual
BU 0040
ParameterBox manual
BU 0590
Description of PROFINET IO bus communication
BU 0500
SK 500E - SK 535E frequency inverter manual

Parameter access and diagnosis

The NORD CON software and optional control units s uch as the SK PAR-3H parameter box provide convenient access to the parameters of the module and allow status information to be read out.
SK TU3- SK TU4- SK CU4- / SK TU4-
diagnosis socket
socket ­SK TI4-TU-BUS(-C)
Pos: 31 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/PRO FINET IO/ Weiterführ ende Doku mentation en und Soft ware [SK TU 3-PNT] @ 4\mod_1385375410283_388.docx @ 106553 @ 5 @ 1

Further Documentation and Software (www.nord.com)

=== Ende der Liste für Textmar ke Inhalt ===
in
bus.
8 / 8 TI 275900190 - 4913