NORD TI 275900150 User Manual

Pos: 3 /Technis c h e Inf ormation en/ SK xUx - Bus - Er weiterung en/EtherN et/IP/SK TU 3-EIP / 27 5900150 / B asisinform ationen [S K TU3-EIP] @ 3\ mod_1363943288231_388.docx @ 62307 @ 555 @ 1
SK TU3-EIP
Technical Information / Datasheet
EtherNet/IP® - External bus – interface
ATTENTION
This document is only valid in combination with the operating instructions for the relevant frequency inverter. All of the information that is relevant for a safe start-up of this module and the frequency inverter is only available under these conditions.
Validity of document

Scope of delivery

1 x Module SK TU3-EIP

Usage area

Technology box for connec ting a f requency inverter (S K 5xxE) t o a EtherNet/IP f ield bus. The m odule must be attached directly to the technology slot of the frequency inverter.

Technical data

Module
Temperature range 0 °C … 40 °C Vibration resistance 2M1 Temperature class Class 3k3 Firmware version V1.1 R1 Protection class IP20 Hardware version AA Supply voltage 24 V ± 20 %, ≈ 100 mA
Reverse polarity protected
Dimensions [mm] H x W x D: 27 x 73 x 101
EtherNet/IP Bus module SK TU3-EIP
1.1 LED - displays, technical datas, Error 10.9 4913 Rck TI 275900150 GB
version reason for change(s) issue name document speech
EtherNet/IP Bus module – SK TU3-EIP
DIP switches, module parameters, BOOTP and DHCP
diagnosis socket on the device (if available) and possibly
Bus specification
EtherNet/IP Max. 100 MBaud Cable Min. Ethernet CAT-5 Electrical isolation 500 V
Max. cable length 100 m between two
eff
modules Bus connection 2 x RJ45 Shield via RJ sockets high­bus termination Takes place automatically Ohmic & capacitive to PE Status display 8 LEDs PE connection via PE post-type connector Topology* Star*, ring, linear bus (rating less than 24 V) * additional switch for "star" topology required
Performance
Update interval for process data between module and frequency inverter ≤ 2.5 ms Parameter read access to frequency inverter ≈ 15 ms Parameters write access with storage on EEPROM ≈ 25 ms Cycle times ≥ 1ms
Pos: 6 /Technis c h e Inf ormation en/ SK xUx - Bus - Er weiterung en/EtherN et/IP/Mer kmale [EIP Al lgemein] @ 3\mod_1362996549668_388.docx @ 61397 @ 5 @ 1

Module features

IO messages (process data connections) One "Exclusive Owner“ Max. 2 “Listen Only” connections Type "Cyclic", min cycle time 1 ms Explicit messages Yes UCMM Supported DLR Supported Switch with two ports integrated Addressing via
possible
Access for NORD diagnosis tool via
via frequency converter and Ethernet protocols UDP or TCP/IP
Pos: 9 /Anl eitungen/El ektronik /FU und Star ter/3. /4. Anzeige u nd Bedien ung [BU 050 0 / BU 0200 ]/SK 5xxE/ 3.2 Übersic ht der Tec hnologieboxen -2- Monta ge @ 1\mod_1340712929975_388.docx @ 28340 @ 5 @ 1
2 TI 275900150 - 4913
Push the control terminals cover down
edge and pulling off
with an upward turning movement. If
RJ45 Pin
Signal
Description
1
TX+
Transmission Data +
2
TX-
Transmission Data -
3
RX+
Receive Data +
6
RX-
Receive Data -
Terminal
Name
Description
45
+ 24 V
24 V supply
46
GND
Earth

Installing

EtherNet/IP Bus module – SK TU3-EIP
Note
Installing the technology unit
Modules should not be inserted or removed unless the device is free of voltage. The slots may only be used for the intended modules.
Installation of a technology unit separate from the frequency inverter is not possible. It must be connected directly to the frequency inverter.
The technology units must be installed as follows:
1. Switch off the mains voltage, observe the waiting period.
2. slightly or remove.
3. Remove the blank cover, by loosening the release on the lower
necessary, the attachm ent screw next to the release must be removed.
4. Hook the technology unit onto the upper edge slots and press in lightly until it engages. Ensure full contact with t he connector strip and fasten with the screws if necessary (separate packet).
5. Close the control terminal cover again.
Pos: 12 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Et herNet/IP /Anschlüss e [SK TU3-E IP] @ 3\mod_1363958898449_388.docx @ 62382 @ 5 @ 1

Connections

The two Ethernet l ines are connected ex clusiv ely via t he two RJ45 sock ets on th e front. If the m odule is the final subscriber on the line, one RJ45 socket can remain unoccupied.
( 1 ) RJ45 socket detail ( 2 ) Power supply detail
Pos: 15 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Et herNet/IP /Konfigurati on [SK TU 3-EIP] @ 3\mod_1363947436882_388.docx @ 62357 @ 5 @ 1
TI 275900150 - 4913 3