NORD TI 275281206 User Manual

IO-Extension
SK TU4-IOE-M12
1.0
4912
Rck
TI 275281206
GB
version
issue
name
document
speech
SK TU4-IOE-M12
Part Number 275 281 206
IO Extension
NOTICE
Validity of this document
This document is only valid in conjunction with the operating manual supplied for the respective frequency inverter. It is essential that all the relevant information is available for the safe commissioning of this module and the frequency inverter.
1 x
Module
SK TU4-IOE-M12
Required accessories:
1 x
Bus connection unit including:
SK TI4-TU-BUS Part No. 275 280 000)
1 x
System bus cable kit
grey / black
1 x
24 VDC cable kit
brown / blue
1 x
Gasket
2 x
Grommet
22 mm x 9.5 mm
4 x
Hexagon socket
M4 x 20
Temperature range
-25 °C … 50 °C
Vibration resistance
3M7
Temperature class
Class 3K3
Firmware version
V1.2 R0
Protection class
IP55
Dimensions [mm]*
HxWxD 95 x 136 x 99**
* Module mounted on the BUS connection unit ** 108 mm with cover caps on the M12 connection
Name
Terminal
Data
Module power supply (load capacity)
15/11
24 VDC ± 20 %, reverse polarity protected (≤ 3 A)
Power consumption of module
15/11
140 mA
Digital input - operating range
19,20,25,26
Low: 0 V … 5 V, High: 15 V … 30 V
Digital input - specific information
19,20,25,26
Ri = 8,1 kΩ, input capacitance: 10 nF
Pos: 5 /Technische Informationen/IO - Er weiterung/SK TU4-IOE-M12 / 275281206 / Basisinformationen [SK TU4-IOE-M 12] @ 2\mod_1353501890944_388.docx @ 51620 @ 666 @ 1
Technical Information / Datasheet

Scope of supply

Field of use

External IO extension for mounting on, or in the immediate vicinity of a decentralised frequency inverter (SK 2xxE). This can be connected to the inverter via the system bus. Four digital inputs, 2 digital outputs, 2 analog inputs and 1 analog output are available.

Technical Data

IO-Extension – SK TU4-IOE-M12
Name
Terminal
Data
Scan rate 1 ms, reaction time 1 ms
Digital output - 24 VDC power supply
35/31
≤ 1000 mA (input)
Digital output - operating range
33.34
Low = 0 V, High = 24 V; max. 500 mA
Analog input - reference voltage
1
10 VDC ±0,1 V, ≤ 20 mA (output)
Analog input - differential input version
3/5; 4/6
Resolution: 12 Bit, accuracy: 0.1 V
Analog output - load capacity
9
≤ 10 mA (Mode: 0/2 … 10 V) ≤ 20 mA (Mode: 0/4 … 20 mA, at 5 V)
Analog output - specific information
9
Resolution: 10 Bit, accuracy: 0.25 V
Installation location
on the left or right on the connection unit of the frequency inverter, alternatively: near to the inverter by means of the SK TIE4-WMK-TU wall-mounting
kit
Fastening
With screw fasteners
NOTICE
Sealing
When installing (module, cable glands, plug connectors), take care that there is a good seal, in order to prevent the entry of moisture and the danger of corrosion and short circuits. With IP66 modules (SK TI4-TU-...-C) the membrane valve (supplied) must be screwed in, in order to prevent the accumulation of condensation.
1.
Switch off the mains.
2.
Remove the two M25 caps on the required side of the frequency inverter (right / left).
3.
Remove the printed circuit board (with terminal bar) from the SK TI4-TU-…. connection unit.
4.
Install the SK TI4-TU- ... with the enclosed seal on the SK 2xxE using the 4 enclosed bolts.
5.
Insert both of the enclosed grommets in the M25 cable glands (to protect the internal wiring between the module and the frequency inverter).
6.
Replace the printed circuit board (See point 3) and carry out the electrical connections.
SK TI4-TU--C version devices: remove the top M20 cable gland (however not at the diagnostic inlet) and insert the enclosed membrane valve into this screw fitting.
7.
Fit and screw on the SK TU4 module.
Pos: 7 /Technische Informationen/IO - Er weiterung/Montage [SK TU4-IOE-xxx] @ 2\mod_1353315135994_388.docx @ 512 51 @ 6 @ 1

Installation

Installation steps for motor installation
2 TI 275281206 - 4912
IO-Extension – SK TU4-IOE-M12
1.
Switch off the mains.
2.
Attach the enclosed seal to the SK TI4-TU ... and place it on the wall-mounting kit. Tightly screw the 2 oval-head screws (enclosed with the wall-mounting kit) into the (countersunk) holes in the wall­mounting kit from the outside.
3.
Insert and tighten the 2 bolts (enclosed with the wall-mounting kit) from the inside into the freely accessible holes in the rear wall.
4.
Install the unit at the installation site and make the electrical connections (maximum cable length 20m)
5.
Fit and screw on the SK TU4 module.
Information
Contacts
The connection between the module and the connection unit is made by means of a pin connector. Terminals in the terminal bar of the connection unit with an identical potential are connected by fitting the module and connection unit together.
1.
No function, M20 x 1.5
2.
Diagnostic access, RJ12 socket
3.
M20 x 1.5 cable gland (1 on the left and 1 on the right): incoming or outgoing cable, e.g. for system bus or 24V supply
4.
M25 x 1.5 cable gland (2x): For wiring between the optional module and the frequency inverter
in case of direct attachment.
5.
M16x1.5 cable gland (4x): For wiring of sensors, actuators, etc. Direct mounting.
Installation steps for wall-mounting
Details of BUS connection unit
TI 275281206 - 4912 3