SK TU4-EIP-C
Part number: 275 281 169
EtherNet/IP® - External bus – interface
Validity of document
This document is only valid in combination with the operating instructions for the relevant frequency inverter. All
of the information that is relevant for a safe start-up of this module and the frequency inverter is only available
under these conditions.
Scope of delivery
1 x Module SK TU4-EIP-C
4 x Hexagon socket M4 x 40 mm
Accessories required:
1 x Bus connection unit SK TI4-TU-BUS-C
TI 275280500 (Part No. 275 280 500)
Usage area
External technology box for connecting distributed frequency inverter (SK 180E … SK 2xxE) to a
EtherNet/IP field bus. The module can be fitted to or in the immediate vicinity of the frequency
inverter. It is connected via the system bus with the inverter and can respond directly with up to
4 frequency inverters. 8 digital inputs and 2 digital outputs are available.
Technical data
Module
Temperature range -25 °C … 50 °C Vibration resistance 3M7
Temperature class Class 3k4 Firmware version V1.1 R1
Protection class IP66 Hardware version AA
Supply voltage 24 V ± 20 %, ≈ 100 mA
Dimensions [mm]* H x W x D: 95 x 136 x 99
Reverse polarity
protected
* module fitted to BUS-connection unit
Depth: 108mm with covers on M12
-connection
EtherNet/IP Bus module SK TU4-EIP-C
1.1 LED - displays, technical datas, Error 10.9 4913 Rck TI 275281169 GB
version reason for change(s) issue name document speech
EtherNet/IP Bus module – SK TU4-EIP-C
DIP switches, module parameters, BOOTP and DHCP
diagnosis socket on the device (if available) and possibly
Digital input - working area Low: 0 V … 5 V, High: 15 V … 30 V
Digital input - specif ic dat a Ri = 10 kΩ, input capacity: 10nF, reac tio n ti m e 1 ms, inputs
according to EN 61131-2 type 1
Digital output - 24 VDC power supply ≤ 400 mA (input)
Digital output - working area Low = 0 V, High = 24 V; max. 200 mA
Bus specification
EtherNet/IP Max. 100 MBaud Cable Min. Ethernet CAT-5
Electrical isolation 500 V
Max. cable length 100 m between two
eff
modules
Bus connection 2 x M12 sockets Shield via M12 direct to PE
Bus termination Takes place automatically PE connection via PE screw connection
Status display 8 LEDs in the terminal box
Topology* Star*, ring, linear bus
* additional switch for "star" topology required
Performance
Update interval for process data between module and frequency inverter ≤ 5 ms
Parameter read access to frequency inverter ≈ 15 ms
Parameters write access with storage on EEPROM ≈ 25 ms
Cycle times ≥ 1ms
Pos: 6 /Technis c h e Inf ormation en/ SK xUx - Bus - Er weiterung en/EtherN et/IP/Mer kmale [EIP Al lgemein] @ 3\mod_1362996549668_388.docx @ 61397 @ 5 @ 1
Module features
IO messages (process data co nnec tion s) One "Exclusive Owner“
Max. 2 “Listen Only” connections
Type "Cyclic", min cycle time 1 ms
Explicit messages Yes
UCMM Supported
DLR Supported
Switch with two ports integrated
Addressing via
possible
Access for NORD diagnosis tool via
via frequency converter and
Ethernet protocols UDP or TCP/IP
Pos: 7 /Technis c h e Inf ormation en/ SK xUx - Bus - Er weiterung en/Allgem ein - System übergreif end/Montag e [SK TU4- xxx-xxx] @ 2\mod_1353315135994_388.docx @ 51251 @ 5 @ 1
Installation
The module must be attac h ed to t he s u ita ble c o nn ec tio n un it (S K TI4-TU- …) and connected using th e
four M4 x 40 mm provided hexagon socket c ollar screws. Installati on details can be found in the d ata
sheet for the relevant connection units.
Pos: 10 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Al lgemein - S ystemüberg reifend/Ans chlüsse - E thernetsei te - Variant e M12 [SK TU 4-...EIP/EC T/POL/A nschlüsse - Et hernetsei te - Variant e M12 [SK T U4-...EIP/ECT/P OL/PNT(-M12). ..-C)] @ 4\mod_1385383150995_388.docx @ 106697 @ 5 @ 1
2 TI 275281169 - 4913
Supply potential (+24 V, ≤ 200 mA)
Supply potential (+2 4 V, ≤ 200 mA)
Reference potential (0 V / GND)
Reference potential (0 V / GND)
Supply potential (+24 V, ≤ 200 mA)
Supply potential (+24 V, ≤ 200 mA)
Reference potential (0 V / GND)
Reference potential (0 V / GND)
Reference potential (0 V / GND)
Reference potential (0 V / GND)
Reference potential (0 V / GND)
Reference potential (0 V / GND)
Supply potential (+24 V - in) of the digital outputs
Reference potential (0 V / GND) of the digital outputs
Digital output 1 (+24 V, ≤ 200 mA)
Digital output 2 (+24 V, ≤ 200 mA)
Reference potential (0 V / GND) of the digital outputs
Reference potential (0 V / GND) of the digital outputs
Reference potential (GND)
Connections
The two Ethernet lines are connected exclusively via the two M12 sockets on the front. If the module is
the final subscriber on the line, one M12 socket can remain unoccupied. The use of EMC screw
connections is recommended.
EtherNet/IP Bus module – SK TU4-EIP-C
PIN assignment
M12-4 socket
("D“- coded):
Pos: 11 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Al lgemein - S ystemüberg reifend/Ans chlüsse - K lemmenleis te [SK TU 4(-C) - EtherNet B aug ruppen all g e mei n] @ 3\mod_1362998963057_388.docx @ 61424 @ @ 1
The connection to other signal and control lines takes place via the BUS - connection units.
1
Digital inputs
17 0V Refere nc e pot en ti al (0 V / GND)
2
System bus level and digital inputs
3
Digital outputs
4
Diagnosis
TI 275281169 - 4913 3