Erstausgabe / first issue
Interface converter connection extension
RJ12 RJ12
(L = approx. 10 cm)
DIP switch position for "master"
Direction of
communication
Technical Information / Datasheet
Pos: 1 /Technische Informationen/Ansc hlusserweiterungen [HAN, HQ,SK TIE]/U msetzer RS 232-RS485/SK TIE4-RS4 85-RS232 / 275274603 / Basisinform ationen [SK TIE4-RS485-RS232] @ 3\mod_1372666043302_388.docx @ 8024 3 @ 5555 @ 1
Scope of delivery
Field of use
Signal converter from RS 485 to RS 232. This is used to connect a device with an RS 232 interface to
another device with an RS 485 interface.
Use
The converter is intended for the following device combinations. The DIP switch must be set according
to the combination (see also "Configuration").
For SK 180E ... SK 5xxE series devices, no converter is required for communication with a PC, as the
devices are also equipped with an RS 232 interface. The converter only needs to be connected in
case one or more devices are to be connected to the PC via an RS 485 interface.
Technical data
Pos: 2 /Technische Informationen/Ansc hlusserweiterungen [HAN, HQ,SK TIE]/U msetzer RS 232-RS485/LED Anzeige n [SK TIE4-RS485-RS232] @ 3\mod_ 1372669872055_388.docx @ 80295 @ 5 @ 1
LED indicators
The operating statuses of the module are visualised using LED indicators.
Connection extension – SK TIE4-RS232-RS485
* Each LED indicates an intact communication direction. If an LED
does not illuminate, this indicates a fault or interruption in the relevant
communication direction.
Starter
(Interface: RS 232)
Connection cable
RJ12 – RJ12
(Enclosed with
converter)
Converter
SK TIE4-RS485-
RS232
Connection cable
RJ12 – RJ12
(enclosed with
ParameterBox)
ParameterBox
(Interface: RS 485)
( 1 ) Detail RJ12 – RS232
( 2 ) Detail RJ12 – RS485
Contacts 3 and 6 are
connected through! The load
must not exceed 500 mA!
Configuration of the converter is restricted to a DIP switch on
the front side of the converter. This determines the interface
on which the master is located.
No communication is possible if the DIP switch is not
set correctly.
Possible damage to devices
Care must be taken that only one participant takes on the master function. Failure to observe this may cause
damage to the relevant drivers.
Pos: 3 /Technische Informationen/Ansc hlusserweiterungen [HAN, HQ,SK TIE]/U msetzer RS 232-RS485/Anschlüsse [SK TIE4-RS485_RS232] @ 3\mod_137 2674444498_388.docx @ 80447 @ 5 @ 1
Connections
The converter is connected between e.g. the motor starter and the ParameterBox (see below).
Pos: 4 /Technische Informationen/Ansc hlusserweiterungen [HAN, HQ,SK TIE]/U msetzer RS 232-RS485/Konfiguration [SK TIE4-RS485-RS232] @ 3\mod_13 72670309640_388.docx @ 80376 @ 5 @ 1
Configuration
=== Ende der Liste für Textmarke Inhalt ===
2 TI 275274603 - 2713