SK CU4-EIP
Technical Information / Datasheet
Part number: 275 271 019
EtherNet/IP® - Internal bus – interface
NOTICE
This document is only valid in
of the information that is relevant for a safe start-up of this module and the frequency inverter is only available
under these conditions.
Validity of the documents
Scope of supply
1 x Module SK CU4-EIP
1 x System bus cable set grey / black
1 x 24 VDC cable set brown / blue
2 x Connecting screws M4 x 20, cross-head
Field of use
Internal interface for connecting decentralised frequency inverter (SK 180E … SK 2xxE) to a
EtherNet/IP field bus . It is connecte d to the inverter via the system bus and can respond directly with
up to 4 frequency inverter. 2 digital inputs are available.
Technical data
Module
Temperature range -25°C … xx °C * Vibration resistance 3M7
Temperature class Class 3k3 Firmware version V1.2 R0
Protection class IP20 Hardware version AA
Supply voltage 24 V ± 20 %, ≈ 100 mA
Reverse polarity
protected
* The upper temperature limit depends on the frequency inverter and the operating mode à see "Derating"
Digital input - working range Low: 0 V … 5 V, High: 15 V … 30 V
Digital input - specif ic dat a Ri = 10 kΩ, input capacity: 10nF, reaction time 1 ms, inputs
according to EN 61131-2 type 1
EtherNet/IP Bus module SK CU4-EIP
1.1 LED - Anzeigen / LED displays, Derating 4913 Rck TI 275900150 GB
version reason for change(s) issue name document speech
EtherNet/IP Bus module – SK CU4-EIP
motor used (IE1 / IE2 / ...) restrictions to the permissible ambient temperature must be taken into account. If the
bient temperature is exceeded, the module may heat up to an impermissible extent and switch off
DIP switches, module parameters, BOOTP and DHCP
diagnosis socket on the device (if available) and possibly
Bus specification
EtherNet/IP Max. 100 MBaud Cable Min. Ethernet CAT-5
Electrical isolation 500 V
Max. cable length 100 m between two
eff
modules
Bus connection Screw terminals Shield Direct to PE
bus termination performed automat ica lly PE connection via PE screw connection
Status display 6 LEDs in the terminal box
Topology Star, tree, linear bus
Performance
Update interval for process data between module and frequency inverter ≈ 2.5 ms
Parameter read access on the frequency inverter ≈ 25 ms
Parameter write access with storage in EEPROM ≈ 70 ms
Cycle times ≥ 1 ms
Pos: 5 /Technis c h e Inf ormation en/ SK xUx - Bus - Erweiterung en/Allge mein - Syste mübergreif end/Derati ng [SK CU 4 - ...] @ 4\mod_1378288335408_388.docx @ 92917 @ 5 @ 1
Derating
ATTENTION
Derating
Depending on the installation location of the module (SK 180E, SK 190E or SK 2xxE), the operating mode (S1,
S3 ...) and the installation type (wall-mounting, motor -mounting) of the frequency inverter as well as the type of
permissible am
with an error message (E104.0).
Maximum ambient temperature *
Operating mode Installation type SK 180E / SK 190E SK 2xxE
S1 Motor 25°C 30°C
S1 Wall (unventilated) 37°C 42°C
* The limits of the frequency inverter must not be exceeded (refer to the frequency inverter manual).
Pos: 6 /Technis c h e Inf ormation en/ SK xUx - Bus - Er weiterung en/EtherN et/IP/Mer kmale [EIP Al lgemein] @ 3\mod_1362996549668_388.docx @ 61397 @ 5 @ 1
Module features
IO messages (process data connections) One "Exclusive Owner“
Max. 2 “Listen Only” connections
Type "Cyclic", min cycle time 1 ms
Explicit messages Yes
UCMM Supported
DLR Supported
Switch with two ports integrated
Addressing via
possible
Access for NORD diagnosis tool via
via frequency converter and
Ethernet protocols UDP or TCP/IP
2 TI 275900150 - 4913
EtherNet/IP Bus module – SK CU4-EIP
Ethernet connection 1 Receive Data -
Ethernet connection 1 Receive Data +
Ethernet connection 1 Transmission Data -
Ethernet connection 1 Transmission Data +
Ethernet connection 2 Receive Data -
Ethernet connection 2 Receive Data +
Ethernet connection 2 Transmission Data -
Ethernet connection 2 Transmission Data +
Reference potential (0 V / GND)
Reference potential (0 V / GND)
VI 24V
GND/0V
SYS +
SYS -
24V
GND/0V
SYS +
SYS -
Pos: 8 /Technis c h e Inf ormation en/ SK xUx - Bus - Erweiterung en/Allge mein - Syste mübergreif end/Mont age [SK CU 4-xxx] @ 3\mod_1371811235059_388.docx @ 79455 @ 5 @ 1
Installation
Installation location Within the connection unit of a frequency inverter (SK 180E , SK 190E, 2xxE)
Mounting with screw fastenings
Pos: 13 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Al lgemein - S ystemüberg reifend/Ans chlüsse [ SK CU4 - ...] @ 4\ mod_1378291237620_388.docx @ 93067 @ 5 @ 1
Connections
Connection is via the terminal bar of the module
1
Ethernet
2
digital inputs
System bus level and
Schematic diagram - electrical connection
(Terminal designation on example of NORD frequency inverter SK 180E … SK 2xxE)
SK CU4-… SK 180E … SK 2xxE
Pos: 16 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Et herNet/IP /Konfigurati on [SK CU 4-EIP] @ 4\mod_1384951929342_388.d ocx @ 105681 @ 5 @ 1
TI 275900150 - 4913 3