SK CU4-POL
Technical Information / Datasheet
Part number: 275 271 018
POWERLINK - Internal bus interface
NOTICE
All of the information that is relevant for a safe start-up of this module and the frequency inverter is only available
under these conditions.
Validity of the documents
Scope of supply
1 x Module SK CU4-POL
1 x System bus cable set grey / black
1 x 24 VDC cable set brown / blue
2 x Connecting screws M4 x 20, cross-head
Field of use
Internal interface for connecting a decentralised frequency inverter (SK 180E … SK 2xxE) to a
POWERLINK field bus. It is connected to the inverter via the system bus, and can communicate
directly with up to 4 frequency inverters. 2 digital inputs are available.
Technical data
Module
Temperature range -25°C … xx °C * Vibration resistance 3M7
Temperature class Class 3k3 Firmware version V1.2 R0
Protection class IP20 Hardware version AA
Supply voltage 24 V ± 20 %, ≈ 100 mA
Reverse polarity protected
* The upper temperature limit depends on the frequency inverter and the operating mode à see "Derating"
Digital input - working area Low: 0 V … 5 V, High: 15 V … 30 V
Digital input - specific dat a Ri = 10 kΩ, input capacity: 10nF, reaction time 1 ms, inputs
according to EN 61131-2 type 1
POWERLINK Bus module SK CU4-POL
1.1 LED - displays, derating, Error 10.9 4913 Rck TI 275271018 GB
version reason for change(s) issue name document speech
POWERLINK Bus module – SK CU4-POL
motor used (IE1 / IE2 / ...) restrictions to the permissible ambient temperature must be taken into account. If the
bient temperature is exceeded, the module may heat up to an impermissible extent and switch off
* The limits of the frequency inverter must not be exceeded (refer to the frequency inverter manual).
Diagnostic socket on the device (if available) or possibly
Bus specification
POWERLINK Max. 100 MBaud Cable Min. Ethernet CAT-5
Electrical isolation 500 V
Max. cable length 100 m between two modules
eff
Bus connection Screw terminals Shield Direct to PE
bus termination performed automatically PE connection via PE screw connection
Status display 6 LEDs in the terminal box
Topology Star, tree, linear bus
Performance
Update interval for process data between module and frequency inverter ≈ 2.5 ms
Parameter read access on the frequency inverter ≈ 25 ms
Parameter write access with storage in EEPROM ≈ 70 ms
Cycle times 400 µs … 60 ms
Pos: 5 /Technis c h e Inf ormation en/ SK xUx - Bus - Erweiterung en/Allge mein - Syste mübergreif end/Derati ng [SK CU 4 - ...] @ 4\mod_1378288335408_388.docx @ 92917 @ 5 @ 1
Derating
ATTENTION
Derating
Depending on the installation location of the module (SK 180E, SK 190E or SK 2xxE), the operating mode (S1,
S3 ...) and the installation type (wall-mounting, motor -mounting) of the frequency inverter as well as the type of
permissible am
with an error message (E104.0).
Maximum ambient temperature *
Operating mode Installation type SK 180E / SK 190E SK 2xxE
S3 ED 50 %, 10min Motor 40°C n. s.
S1 Wall (ve ntilated) 47°C 48°C
Pos: 6 /Technis c h e Inf ormation en/ SK xUx - Bus - Er weiterung en/Powerli n k /M erkmale [PO L Allgemein] @ 3\ mod_1377869060850_388.docx @ 92057 @ 5 @ 1
Module features
Hot Plugging (CN connection during operation) Yes
Isochronous (PDO) Yes, Statistical Mapping
Number of process data 12 Byte (SK TU3-…),
50 Byte (SK xU4-…)
Asynchronous Data (SDO over ASND or UDP/IP) Yes
Cross Traffic No, no direct communication between CN
Addressing via DIP switch, module parameters possible
Access for NORD diagnosis tool via
via frequency inverter and UDP Ethernet protocol
Pos: 8 /Technis c h e Inf ormation en/ SK xUx - Bus - Erweiterung en/Allge mein - Syste mübergreif end/Mont age [SK CU 4-xxx] @ 3\mod_1371811235059_388.docx @ 79455 @ 5 @ 1
2 TI 275271018 - 4913
POWERLINK Bus module – SK CU4-POL
Ethernet connection 1 Receive Data -
Ethernet connection 1 Transmission Data -
Ethernet connection 1 Transmission Data +
Ethernet connection 2 Receive Data -
Ethernet connection 2 Receive Data +
Ethernet connection 2 Transmission Data -
Ethernet connection 2 Transmission Data +
Reference potential (0 V / GND)
VI 24V
GND/0V
SYS +
SYS -
24V
GND/0V
SYS +
SYS -
Installation
Installation location Within the connection unit of a frequency inverter (SK 1 80E, SK 190E, 2xxE)
Mounting with screw fastenings
Pos: 13 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Al lgemein - S ystemüberg reifend/Ans chlüsse [ SK CU4 - ...] @ 4\ mod_1378291237620_388.docx @ 93067 @ 5 @ 1
Connections
Connection is via the terminal bar of the module
E7 PHY1 RX+ Ethernet connection 1 Receive Data +
1
Ethernet
2
40 GND/0V Reference potential (0 V / GND)
digital inputs
System bus level and
Schematic diagram - electrical connection
(Terminal designation on example of NORD frequency inverter SK 180E … SK 2xxE)
SK CU4-… SK 180E … SK 2xxE
Pos: 16 /T echnische I nformatio nen/SK xUx - Bus - Erweiterungen/Powerlink/Konfiguration [SK CU4-POL] @ 4\mod_1378290913534_388.docx @ 93041 @ 5 @ 1
TI 275271018 - 4913 3