NORD TI 275271018 User Manual

Page 1
This document is only valid in combination with the operating instructions for the relevant frequency inverter.
Pos: 4 /Technis c h e Inf ormation en/ SK xUx - Bus - Erweiterung en/Powerl ink/SK CU 4-POL / 275271 0 18 / Basisinfor mationen [S K CU 4- POL] @ 4\mod_1378286286736_388.docx @ 92892 @ 555 @ 1
SK CU4-POL
Technical Information / Datasheet
POWERLINK - Internal bus interface
NOTICE
All of the information that is relevant for a safe start-up of this module and the frequency inverter is only available under these conditions.
Validity of the documents

Scope of supply

1 x Module SK CU4-POL 1 x System bus cable set grey / black 1 x 24 VDC cable set brown / blue 2 x Connecting screws M4 x 20, cross-head

Field of use

Internal interface for connecting a decentralised frequency inverter (SK 180E … SK 2xxE) to a POWERLINK field bus. It is connected to the inverter via the system bus, and can communicate directly with up to 4 frequency inverters. 2 digital inputs are available.

Technical data

Module
Temperature range -25°C … xx °C * Vibration resistance 3M7 Temperature class Class 3k3 Firmware version V1.2 R0 Protection class IP20 Hardware version AA Supply voltage 24 V ± 20 %, ≈ 100 mA
Reverse polarity protected
* The upper temperature limit depends on the frequency inverter and the operating mode à see "Derating"
Digital input - working area Low: 0 V … 5 V, High: 15 V … 30 V Digital input - specific dat a Ri = 10 kΩ, input capacity: 10nF, reaction time 1 ms, inputs
according to EN 61131-2 type 1
POWERLINK Bus module SK CU4-POL
1.1 LED - displays, derating, Error 10.9 4913 Rck TI 275271018 GB
version reason for change(s) issue name document speech
Page 2
POWERLINK Bus module – SK CU4-POL
motor used (IE1 / IE2 / ...) restrictions to the permissible ambient temperature must be taken into account. If the
bient temperature is exceeded, the module may heat up to an impermissible extent and switch off
S1
Motor
25°C
30°C
S3 ED 70 %, 10min
Motor
n. s.
40°C
S1
Wall (unventilated)
37°C
42°C
* The limits of the frequency inverter must not be exceeded (refer to the frequency inverter manual).
Diagnostic socket on the device (if available) or possibly
Bus specification
POWERLINK Max. 100 MBaud Cable Min. Ethernet CAT-5 Electrical isolation 500 V
Max. cable length 100 m between two modules
eff
Bus connection Screw terminals Shield Direct to PE bus termination performed automatically PE connection via PE screw connection Status display 6 LEDs in the terminal box Topology Star, tree, linear bus
Performance
Update interval for process data between module and frequency inverter ≈ 2.5 ms Parameter read access on the frequency inverter ≈ 25 ms Parameter write access with storage in EEPROM ≈ 70 ms Cycle times 400 µs … 60 ms
Pos: 5 /Technis c h e Inf ormation en/ SK xUx - Bus - Erweiterung en/Allge mein - Syste mübergreif end/Derati ng [SK CU 4 - ...] @ 4\mod_1378288335408_388.docx @ 92917 @ 5 @ 1

Derating

ATTENTION
Derating
Depending on the installation location of the module (SK 180E, SK 190E or SK 2xxE), the operating mode (S1, S3 ...) and the installation type (wall-mounting, motor -mounting) of the frequency inverter as well as the type of
permissible am with an error message (E104.0).
Maximum ambient temperature *
Operating mode Installation type SK 180E / SK 190E SK 2xxE
S3 ED 50 %, 10min Motor 40°C n. s.
S1 Wall (ve ntilated) 47°C 48°C
Pos: 6 /Technis c h e Inf ormation en/ SK xUx - Bus - Er weiterung en/Powerli n k /M erkmale [PO L Allgemein] @ 3\ mod_1377869060850_388.docx @ 92057 @ 5 @ 1

Module features

Hot Plugging (CN connection during operation) Yes Isochronous (PDO) Yes, Statistical Mapping Number of process data 12 Byte (SK TU3-…),
50 Byte (SK xU4-…) Asynchronous Data (SDO over ASND or UDP/IP) Yes Cross Traffic No, no direct communication between CN Addressing via DIP switch, module parameters possible Access for NORD diagnosis tool via
via frequency inverter and UDP Ethernet protocol
Pos: 8 /Technis c h e Inf ormation en/ SK xUx - Bus - Erweiterung en/Allge mein - Syste mübergreif end/Mont age [SK CU 4-xxx] @ 3\mod_1371811235059_388.docx @ 79455 @ 5 @ 1
2 TI 275271018 - 4913
Page 3
POWERLINK Bus module – SK CU4-POL
Potential
Contact
Designation
Description
E8
PHY1 RX-
Ethernet connection 1 Receive Data -
E6
PHY1 TX-
Ethernet connection 1 Transmission Data -
E5
PHY1 TX+
Ethernet connection 1 Transmission Data +
E4
PHY0 RX-
Ethernet connection 2 Receive Data -
E3
PHY0 RX+
Ethernet connection 2 Receive Data +
E2
PHY0 TX-
Ethernet connection 2 Transmission Data -
E1
PHY0 TX+
Ethernet connection 2 Transmission Data +
78
SYS -
System bus data line -
77
SYS +
System bus data line +
C1
DIN1
Digital input 1
C2
DIN2
Digital input 2
44
24V
Supply voltage (+24 V)
40
GND/0V
Reference potential (0 V / GND)
44
24V
Supply voltage (+24 V)
VI 24V
GND/0V
SYS +
SYS -
24V
GND/0V
SYS + SYS -

Installation

Installation location Within the connection unit of a frequency inverter (SK 1 80E, SK 190E, 2xxE) Mounting with screw fastenings
Pos: 13 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Al lgemein - S ystemüberg reifend/Ans chlüsse [ SK CU4 - ...] @ 4\ mod_1378291237620_388.docx @ 93067 @ 5 @ 1

Connections

Connection is via the terminal bar of the module
E7 PHY1 RX+ Ethernet connection 1 Receive Data +
1
Ethernet
2
40 GND/0V Reference potential (0 V / GND)
digital inputs
System bus level and
Schematic diagram - electrical connection
(Terminal designation on example of NORD frequency inverter SK 180E … SK 2xxE)
SK CU4-… SK 180E … SK 2xxE
Pos: 16 /T echnische I nformatio nen/SK xUx - Bus - Erweiterungen/Powerlink/Konfiguration [SK CU4-POL] @ 4\mod_1378290913534_388.docx @ 93041 @ 5 @ 1
TI 275271018 - 4913 3
Page 4
POWERLINK Bus module – SK CU4-POL
DIP switch
Meaning
12
11
10 9 8 7 6 5 4 3 2
1
Address
X X 0 0 0 0 0 0 0 0 X
0
X X 0 0 0 0 0 0 0 1 X 1 X X 0 0 0 0 0 0 1 0 X 2 X X 0 - - - - - - - X - X X 1 1 1 0 1 1 1 1 X
239 (largest permissible address)
0 System bus terminating resistor not set
1 System bus terminating resistor set
Access rights for remote maintenance
0 Only read access to parameters possible.
1 Read and write access to param et ers possible.
0 No control possible.
1 Control is possible.
remote maintenance. The type of access is
BS
green
Module status
BE
red
Network Error
2
L/A
green
Link/Activity
ON OFF

Configuration

The basic configuration of the module primaril y takes place via its DIP - switches. The DIP - switch settings are read after a "Power On" of the module.
No function
1. System bus (DIP 1)
The system bus mus t be terminated at both physica l ends.
2. IP address (DIP 2 - 9)
The node ID (the final byte of the IP address) c an be set via this switch and contr olled in parameter P185. The largest permissible node ID for CN is 239
3. Access rights for remote maintenance (DIP 10 – 12)
With the Ethernet protocol UDP, the m odule and the connected frequency inverter can be accessed via
1 … 12
determined via the DIP - switch with inputs 10 to 11.
Pos: 19 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Po werlink/L ED Anzeige n [SK CU4-POL] @ 4\mod_1378291275375_388.docx @ 93092 @ 5 @ 1

LED displays

The operating statuses of the module are visualised using LED indicators.
No. Name Colour Meaning
1
DS green Device status DE red Device error
Pos: 20 /T echnische I nformatio nen/SK xUx - Bus - Erweiterungen/Powerlink/LED Anzeigen- POWERLINK spezifische LED [POL Allgemein] @ 3\mod_1377869060362_388.docx @ 92032 @ @ 1
4 TI 275271018 - 4913
Page 5
POWERLINK Bus module – SK CU4-POL
BS
(Module status)
Meaning
OFF
No communication
Flashing gree n 1x
Pre Operational 1: Parameter communication active, no process data
Flashing gree n 2x
Pre Operational 2: as for Pre Operational 1
Flashing gree n 3x
Ready To Operate: Param ete r c om m unication active, restrict ed pr oces s data com m uni cation
Green ON
Operational: Parameter communication active, process data communication active
Flashing gree n (10 Hz)
Basic Ethernet: Parameter communication active via UDP, no process data
Flashing gree n (2.5 Hz)
Stopped: No communication
(Network Error)
OFF
No POWERLINK error
Red ON
General POWERLINK error
L/A
(Green LED)
Meaning
No bus connection (check cable connection)
Flashing gree n
Technology box connected and active
Green ON
Technology unit read y, but
OFF
OFF
Module not ready, no control voltage.
ON
OFF
Module ready, no error, at least one frequency inverter is communicating via the system bus
ON
Short flashing
One or more of the connected frequency inverters has fault status
Long flashing
OFF
Module ready and at least one other participant is connected to the system bus, but
Software incompatible (module software and FI software do not match - update required)
Long flashing
Short flashing
Long flashing
Short flashing
System bus is in status "Bus Off"
4
OFF
Short flashing
Module defective
POWERLINK-specific LEDs
BE
Meaning
OFF
Pos: 21 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Al lgemein - S ystemüberg reifend/LED Anzeigen- N ORD spezifische LED [EIP / POL / ECT / PNT Allgemein] @ 3\mod_1363773424248_388.docx @ 61815 @ @ 1
NORD-specific LEDs
DS
(Device status)
Long flashing Short flashing
Long flashing Short flashing
DE
(Device error)
Flash interval 1 x - 1s pause
Flash interval 2 x - 1s pause
Flash interval 3 x - 1s pause
Flash interval
x - 1s pause
Flash interval
1…7 - 1s pause
Pos: 22 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Al lgemein - S yst emübergr ei fe n d/Fehler mel dungen Ether net Baugru pp en allgemein [ SK x U x-EIP / POL - Allge mei n] @ 3\mod_1363779786491_388.docx @ 61865 @ 5 @ 1
• Module not ready, no control voltage.
• no bus activity available
Meaning
Long flash = 0.5 s on / 1 s off Short flash = 0.25 s on / 1 s off
Module ready, but
no frequency inverter connected to system bus (connection may be interrupted)
one or more system bus clients has address error
System bus is in status "Bus Warning"
Communication on system bus disrupted
No other clients available on system bus
Module not inserted correctly or no connection to the system bus
• Frequency inverter has no supply voltage
System bus is in status "Bus Off"
the system bus 24V power supply was interrupted during operation
No system bus 24V power supply
Module error
see parameter P170
System error, internal program sequence interrupted
EMC interference (observe wiring guidelines!)
TI 275271018 - 4913 5
Page 6
POWERLINK Bus module – SK CU4-POL
Error
Meaning
Remarks
100.0
EEPROM error
EMC fault, module defective
102.0
Timeout
via P151/P513 monitoring
103.0
System bus BUS OFF
No 24V supply to the bus, connections not correct
104.0
Module temperature > 97°C
SK CU4-… only, zpermissiv e internal temperature of the mo dule exceeded for approx. 60 sec.
550.1
DIP switch error
The DIP switches (IP address) could not be read correctly
560.0 …
560.9
Internal error
Module not r eady
561.0
General network error
561.1
Ethernet Watchdog timeout
561.2
Bus cable fault
Bus cable connection interrupted
561.3
IP address error
IP address of the module has been doubly assigned
563.0
Firmware version incompatible
The firmware version cannot be used for the device
Error (E010)
Meaning
Remarks
10.0
Connection error
Contact to SK xU4 lost
Switch-off of the supply voltage
10.2
Ethernet/IP Watchdog timeout
Telegram transfer error
Bus Master
10.3
Timeout by P151/P513
Telegram transfer error
10.4
IP address error
IP address of the module has been doubly assigned
10.5
Internal error
Module not r eady,
for SK CU4-… e.g.: Module temperature > 97°C
10.6
Bus cable fault
Bus cable connection interrupted
10.8
The connection between the inverter and the module had a timeout
Only SK TU3 module
10.9
Module missing (P1 20 )
Only SK xU4 module

Error messages

Error messages fr om the module - present errors or archived m ess ages relating t o the last error - can be read out via the module par ameter (P170). The error messages are lost if the m odule is switched off.
564.0 MAC address error
Errors which occur in relation to the module are depicted as follows in the error memory of the frequency inverter (P700 / P701).
10.1 ASIC errors Communication to Ethernet - ASIC lost
Pos: 23 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Al lgemein - Systemübergreifend/Parameter [SK xUx-... Allgemein - Freq uenzumric hter] @ 4\mod_1384953855694_388.docx @ 105781 @ 5 @ 1
Check the connections and links, program sequence and
Check the connections and links
• Check the Watchdog time
6 TI 275271018 - 4913
Page 7
POWERLINK Bus module – SK CU4-POL
Parameter [-Array]
Meaning
Remarks
P120 [-01]
Option monitoring
"Auto“ (default setting)
Only SK xU4
P509
Control word source
SK TU3-… on SK 5xxE: "Ethernet TU” SK xU4-… on SK 180/SK 2xxE: "System bus"
P543 [-01 …-03 (-05)]
Bus actual values (1 …3 (… 5))
Possible settings according to (P418) and P546 … P548
P700 [-01] / P701
Current / last failures
Information parameters
P740 / P741
Process data bus In / Out
Information parameters
P745
Module version
Information parameters
Only SK TU3
P748
CANopen / System bus status
Information parameters
Parameter [-Array]
Meaning
Remarks
-TU3-
-TU4-
-CU4-
P150
Set relays
Set DOUT directly or control via BUS
X
P151
External bus time-out
Monitoring of SK xU4 bus module
X X
P152
Factory setting
Reset module parameters
X X X
P153 [-01 …-02]
Minimum system bus cycle
Reduction of the b us load on the s ystem bus cause d by the module
X X
P160
Node ID/IP address 4
X X X
P162 [-01 …-32]
Device name
Name of the module in the POWERLINK network
X X X
P163
FI sets bus error
"1"= Error message in case of fault, "0" = Status message
X X X
P164 [-01 …-04]
IP Gateway
Default setting: -01 … -04 : 192 / 168 / 100 / 254
X X X
P165
POWERLINK cycle
For synchronisation with Manage Node
X X X
P171 [-01 … -03]
Software version
Firmware version / Revision
X X X
P172
Configuration
Module type
X X X
P173
Module status
Status of system bus or connected FI
X X X
P174
Status of digital inputs
Image of the switching status of DIN
X X
P175
State of relays
Image of the switching status of DOUT
X
P176 [-01 … ]
Process data bus In
Information parameters
X X X
P177 [-01 … ]
Process data bus Out
Information parameters
X X X
P178
Internal temperature
Information parameters
X
P181 [-01 … -06]
MAC address
Information parameters
X X X
P182
NMT State
Information parameter (CN status)
X X X
P183
NMT Error
Information parameter (CN error)
X X X
P184 [-01 … -06]
NMT State-change count
Information parameter (cause of change of status)
X X X
P185 [-01 …-04]
Current IP address
Information parameters
X X X
P186 [-01 …-04]
Present IP subnet mask
Information parameters
X X X

Parameters

Frequency inverter: The following frequency inverter parameters must be adapted for setting up communication between the frequency inverter and the bus module (for details see frequency converter manual).
P510 [-01 … -02] Setpoint source P513 Time-out Monitoring of the SK TU3 bus module Only SK 5xxE
and P543 … P545 P546 [-01 …-03 (-05)]
P745 Module status Information parameters Only SK TU3
Pos: 24 /T echnische I nformatio nen/SK xUx - Bus - Erweit er u ng e n/Powerli n k /P ar a meter [POL Al l g e mei n] @ 3\mod_1377869061310_388.docx @ 92082 @ @ 1
Bus target values (1 …3 (… 5)) Possible settings according to (P400)
"Auto“ (default setting)
BUS module: The module provides a selection of appropriate parameters for setting or displaying special operating values. Parameters can be adapted using the NORDCON software or an SK PAR-3H / -3E param eter box. All parameters can still be read an d written by the bus master via POWERLINK.
P154 [-01 …-02] Access to option card I/O Administration of read a nd writ e rights to the IO of t he
module Alternative to setti ng the arra y valu e [-04]: D IP-switch,
à The value from the DIP-switch has priority
X X
P170 [-01 … -02] Present errors Displaying module errors X X X
Pos: 25 /T echnische I nformatio nen/SK xUx - Bus - Erweit erungen/Al lgemein - S ystemüberg reifend/Par ameterzug riff und Di agnose [Bus BG - Allg e mei n] @ 3\mod_1363794074590_388.docx @ 61915 @ 5 @ 1
TI 275271018 - 4913 7
Page 8
POWERLINK Bus module – SK CU4-POL
Access via RJ12-SK 5xxE
Access via RJ12-Bus diagnosis
connection unit
Access via RJ12-Frequency
verter diagnosis socket , if
connected to module via system
Software
Name
Software
Meaning
Document
Name
Document
Meaning
BU 0000
Description of NORD CON software
BU 0200
SK 2xxE frequency inverter manual
BU 0040
ParameterBox manual
BU 2200
Description of POWERLINK bus communic a tio n
BU 0180
Frequency inverter manual SK 180E, SK 190E

Parameter access and diagnosis

The NORD CON software and optional control units s uch as the SK PAR-3H par ameter box provide convenient access to the parameters of the module and allow status information to be read out.
SK TU3- SK TU4- SK CU4- / SK TU4-
diagnosis socket
socket ­SK TI4-TU-BUS(-C)
Pos: 29 /T echnische I nformatio nen/SK xU x - Bus - Erwei terungen/ Powerlink /Weiterführ ende Do kumentation en und Sof tware [SK C U4-POL] @ 4\mod_1378291287192_388.docx @ 93117 @ 5 @ 1

Further Documentation and Software (www.nord.com)

XDD file
Device file (characteristics and parameters)
=== Ende der Liste für Textmar ke Inhalt ===
NORD CON
in
bus.
Parameterisation and diagnostic software
8 TI 275271018 - 4913