NORD TI030276997071 User Manual

Technical Information
LINE FILTER SK CIF-323-40 Part No. 276997071
Overvoltage filter – CSA filter
Technical characteristics:
Voltage limitation filter pursuant to CSA 22.2 No. 14-5 / UL508C Ch. 48 for reduction of a 5 kV surge pulse (rising edge 1.2 µs/trailing edge 50 µs) to max. 300% of the amplitude of the rated voltage (230 VAC/240VAC for SK CIF 32340).
Module SK CIF-323-40 must be used in combination with a suitable mains choke only
(L
= 3 x 0.73 mH). The permanent current flowing through the choke must not be less than the
min
CAUTION!
resulting typical input current of the connected frequency inverter(s).
When using a single-phase frequency inverter (SK 2xxE-XXX-123-…) L1 and also L2/N must be wired to a choke. To do so, you can use a 2-phase (L (L
= 3 x 0.73 mH).
min
Note
With the use of a line choke, the effective input currents of the frequency inverters reduce to approximately the values of the output currents, depending on inductance and load. Several frequency inverters can be connected to a choke/filter combination. When doing so, the sum of input
currents must not exceed the rated/nominal current of the filter and/or the choke.
= 2 x 0.73 mH) or a 3-phase input choke
min
Area of application:
Frequency inverter SK 5xxE-250-323-A … SK 5xxE-112-323-A
SK 2xxE-250-323-A … SK 2xxE-401-323-A It is also possible to connect several frequency inverters to an appropriate filter. In this case, the resulting typical input current (see technical data of FI) is definitive.
SK 2xxE-250-123-A … SK 2xxE-111-123-A
Technical parameters:
Rated voltage [V] 1/3~ 200 … 240 ± 10% Mains voltages [V] 1/3~ 230 / 1/3~ 240 Rated frequency [Hz] 47 – 63 Rated current (FLA) [A] 40 (max.) (input/output current) max. line fuse [A] 60* Weight [kg] 0,74 Protection class IP 20 Ambient temperature [°C] 0 … +50 Operating mode S1 – 100% duty cycle Certifications CE; cURus; RoHS
* Class, type and rating of fuse according to connected frequency inverters
TI030276997071V1_1
1/2
Connections:
Input and output Screw/plug-in terminal 0.5 … 25 mm² L1/L2/L3/PE
Terminal screw tightening torque 2.5 Nm (22 lb-in)
Schematic circuit diagram of electrical connection:
Line Filter-CSA SK CIF-323-40 / SK CIF-340-60 - Installation hints
1U1 (L1) 1V1 (L2) 1W1 (L3)
Line choke SK CI1-460/x-C
- optional for SK CIF-340-60 Netzdrossel SK CI1-460/x-C
- optional für SK CIF-340-60
Netz Filter-CSA SK CIF-323-40 / SK CIF-340-60 - Montagehinweise
1U2 (L11) 1V2 (L21) 1W2 (L31) PE (PE1)
Fastening element Befestigungselement 4x für M4
L1 (L12) L2 (L22) L3 (L32) PE (PE2)
Mains supply ­Inverter
Netzanschluss ­Frequenzumrichter
NS 35/7,5
SK CIF-340-60
Optional: Modifications for on-wall mounting
- Remove fixing screws
- Remove side frames
- Screw on alternate side frames
- Plug fastening elements in
SK CIF-323-40
Optional: Umbau aus Wandmontage
- Befestigungsschrauben lösen
- Seitenteile abnehmen
- Seitenteile für Wandmontage aufsetzen
- Befestigungselemente anstecken
SK CIF-340-60
SK CIF-323-40
Installation data:
Dimensions: [mm] L 180.5 x W 126 x D 71 (Snap-on rail mounting) L 204,5 x B 126 x T 57
Scope of delivery:
Voltage limitation filter without additional accessories with 4 off removable fastening elements for on-wall mounting.
UL/cUL approval(supplement to specifications in the frequency inverter manual):
"Use 75°C Copper Conductors Only"
"Connection of copper cable with an insulation rating of at least 75°C" (only refers to connection cables (mains and motor cables but not control cables)
These products are intended for use in a pollution degree 2 environment“
"The product is suitable for operation in a pollution degree 2 environment"
“Total SCCR of the combination (drive and transient surge suppression device) will be determined by the max. SCCR rating of the drive according the drive manual or label, type and rating of the Branch Circuit Protection.”, or equivalent. Protection as described in drive manual, for example type J, T fuses or inverse time trip type circuit breaker.
The total short-circuit current rating of the combination (SK CIF and frequency inverter) is determined by the maximum short­circuit current rating of the connected frequency inverter. Protection as described in the frequency inverter manual by approved lead cut-outs or circuit breakers.
(on-wall mounting)
Getriebebau NORD GmbH & Co. KG
Tel.: +49 45 32 - 40 10 · Fax: +49 45 32 - 40 12 53 · www.nord.com
Rudolf-Diesel-Straße 1 · D-22941 Bargteheide
1.0 First edition 03.11.10 Rck
1.1 Supplement to UL/cUL approval conditions, tightening torques in lb-in 24.02.12 Rck
Version Change Date Name Document Page
Overvoltage filter
TI 030 276997071 2/2
Loading...