For BTS 8420 radio cabinets with integrated power, locate the T1/E1 cables shipped
2
with the cabinet.
For the AWS 8420 and all versions of the BTS 8420 radio cabinet except the Digital
Only version with two Digital Shelves, ensure both ends of the T1 cables are labeled
“T1-1,” “T1-2,”and “T1-3” (as applicable) and connect them to the Integrated Power
Module on top of the BTS 8420/AWS 8420 radio cabinet.
How to route and connect T1/E1 cables to BTS
8420/AWS 8420 radio cabinet
For the BTS 8420 Digital Only version with two Digital Shelves, ensure that the T1
cables are labeled as follows: “T1-1 for Digital Shelf 1,” “T1-2 for Digital Shelf 1,”
“T1-3 for Digital Shelf 1,” “T1-4 for Digital Shelf 2,” “T1-5 for Digital Shelf 2,” and
“T1-6 for Digital Shelf 2,” as applicable. Connect the T1 cables to the Universal
Hatchplate on the BTS 8420 radio cabinet according to one of the figures below.
Refer to the figure immediately below if the Integrated Power Module bracket has
labels specifically designed for BTS 8420 Digital Only version with two Digital
Shelves.
Route the T1/E1 cable(s) to the location of the Z-IDC punchdown block (or
3
equivalent), if the NIU is located more than the 10 meter (33 foot) cable length from
the BTS 8420/AWS 8420 radio cabinet. Otherwise, route the T1/E1 cable(s) directly to
the NIU. Refer to the appropriate figure below.
Important! When performing the next step, secure the cable to the ladder rack
using standard procedures, including the use of cable ties.
Connecting cables to BTS 8420/AWS 8420 radio cabinet
Connect twisted-wire pairs in T1/E1 cables to appropriate Z-IDC punchdown blocks (or
equivalent) -- for AWS 8420 and all versions of BTS 8420 except Digital Only version with two
Digital Shelves.
How to route and connect T1/E1 cables to BTS
8420/AWS 8420 radio cabinet
Important! Z-IDC punchdown blocks are used only if the distance from the NIU to
the BTS 8420/AWS 8420 is greater than the 10 meter (33 foot) cable length.
Otherwise, T1/E1 connections are made directly to the NIU.
Each T1/E1 cable contains eight twisted-wire pairs. One end is terminated with a
25-pin, D-sub connector. The 25-pin, D-sub connector is connected to the BTS
8420/AWS 8420 radio cabinet. The end with loose wires is punched down at the
Z-IDC punchdown blocks (i.e., punchdown block 1-5 on the NIU) or equivalent.
When URCs are used in the Digital Shelf: T1-1 is connected to punchdown block 1
on the NIU, T1-2 is connected to punchdown block 2 on the NIU, and T1-3 is
connected to punchdown block 3 on the NIU.
Each T1/E1 cable supports up to four T1/E1 Voice lines or one Data line, as
follows:
•First cable (T1-1): One to four T1/E1 lines (one Data line or one to four Voice
lines, mutually exclusive) to punchdown block 1 on the NIU -- applies to URCs
or URC-IIs
•Second cable (T1-2): One to four T1/E1 lines (Voice only) to punchdown block
2 on the NIU -- applies to URCs or URC-IIs
•Third cable (T1-3): One to four T1/E1 lines (Voice only) to punchdown block 3
on the NIU -- applies to URCs or URC-IIs
Connect the T1/E1 twisted-wire pairs to the punchdown terminals on the EQUIPMENT
SIDE of the appropriate Z-IDC punchdown block (or equivalent) according to the
following procedure. See Step 10 for the Z-IDC punchdown block wiring tables.
Important! When performing the following procedure, note that line numbers have
already been assigned to signal pairs by the customer during site preparation (i.e.,
when the lines were punched down at the NETWORK SIDE of each Z-IDC
punchdown block).
Locate the cable marked T1-1 and Z-IDC punchdown block 1. For the location of the
punchdown blocks on the NIU, for all versions of the BTS 8420 radio cabinet except
the Digital Only version with two Digital Shelves, refer to“Layout of Z-IDC
punchdown blocks” (p. 5-13)
1.Data or Voice T1/E1 lines must be assigned to Z-IDC Punchdown Block 1 (URC or URC-II). Data and
Voice are mutually exclusive.
2.EXAMPLE 1-3 Lower = Block Number 1, Position 3, Lower
3.The Z-IDC positions 9 and 10 are not used. Unused T1/E1 cables at the customer’s NIU must not be
looped back towards the BTS 8420/AWS 8420 while the radio is in operation.
4.Use the T1-1 cable wire color code accordingly to punch down T1 cable (depends upon number of T1s
available) at customer provided punchdown block on NIU.
1.Only Voice T1/E1 lines may be assigned to Z-IDC Punchdown Block #2 (URC or URC-II, Position 2).
2.EXAMPLE 2-3 Lower = Punchdown Block #2, Position 3, Lower
3.Z-IDC positions 9 and 10 are not used. Unused T1/E1 cables, at the customer’s NIU, must not be looped
back towards the BTS 8420/AWS 8420 while the radio is in operation.
4.Use the T1-2 cable wire color code accordingly to punch down T1 cable (depends upon number of T1s
available) at customer provided punchdown block on NIU.
1.Only Voice T1/E1 lines may be assigned to Punchdown Block 3 (URC or URC-II, Position 3).
2.EXAMPLE 3-3 Lower = Block Number 3, Position 3, Lower
3.Z-IDC positions 9 and 10 are not used. Unused T1/E1 cables, at the customer’s NIU, must not be looped
back towards the BTS 8420/AWS 8420 while the radio is in operation.
4.Use the T1-3 cable wire color code accordingly to punch down T1 cable (depends upon number of T1s
available) at customer provided punchdown block on NIU.
Connecting cables to BTS 8420/AWS 8420 radio cabinet
Connect twisted-wire pairs in T1/E1 cables to appropriate Z-IDC punchdown blocks (or
equivalent) -- for BTS 8420 Digital Only version with two Digital Shelves.
How to route and connect T1/E1 cables to BTS
8420/AWS 8420 radio cabinet
Important! Each T1/E1 cable contains eight twisted-wire pairs. One end is
terminated with a 25-pin D-sub connector. The 25-pin, D-sub connector is
connected to the BTS 8420 radio cabinet. The end with loose wires is punched
down at the appropriate Z-IDC punchdown block (if applicable) or the punchdown
block provided by the customer at the NIU.
Z-IDC punchdown blocks are used only if the NIU is located more than the 10
meter (33 foot) cable length from the BTS 8420. Otherwise, T1/E1 connections
are made directly to the NIU.
If Z-IDC punchdown blocks are to be used, proceed with the steps which
follow.
When URCs or URC-IIs are used in the first Digital Shelf: T1-1 is connected to
punchdown block 1 on the NIU, T1-2 is connected to punchdown block 2 on
the NIU, and T1-3 is connected to punchdown block 3 on the NIU.
When URCs or URC-IIs are used in the second Digital Shelf: T1-4 is connected
to punchdown block 4 on the NIU, T1-5 is connected to punchdown block 5 on
the NIU, and T1-6 is connected to punchdown block 6 on the NIU.
Each T1/E1 cable supports up to four T1/E1 Voice or Data lines, as follows:
•First cable (T1-1): Data or Voice (one to four T1/E1 lines) (mutually exclusive)
to punchdown block 1 on NIU -- applies to URCs or URC-IIs
•Second cable (T1-2): One to four T1/E1 lines (Voice only) to punchdown block
2 on NIU-- applies to URCs or URC-IIs
•Third cable (T1-3): One to four T1/E1 lines (Voice only) to punchdown block 3
on NIU -- applies to URCs or URC-IIs
•Forth cable (T1-4): Data or Voice (one to four T1/E1 lines) (Mutually
exclusive) to punchdown block 4 on NIU -- applies to URCs or URC-IIs
•Fifth cable (T1-5): One to four T1/E1 lines (Voice only) to punchdown block 5
on NIU -- applies to URCs or URC-IIs
•Sixth cable (T1-6): One to four T1/E1 lines (Voice only) to punchdown block 6
on NIU -- applies to URCs or URC-IIs
Connect the twisted-wire pairs in the T1/E1 cables to the punchdown terminals on the
EQUIPMENT SIDE of the appropriate Z-IDC punchdown block (or equivalent)
according to the following procedure.
Important! When performing the following procedure, note that line numbers have
already been assigned to signal pairs by the customer during site preparation (i.e.,
when the lines were punched down at the NETWORK SIDE of the Z-IDC
punchdown blocks).
Locate the cable labeled “T1-1 for Digital Shelf 1” (T1-1) and Z-IDC punchdown
block 1. Refer to the figure on page 5-13 for the location of the punchdown blocks on
the NIU, for the Digital Only version with two Digital Shelves.“Layout of Z-IDC
punchdown blocks” (p. 5-14)
Locate the cable labeled “T1-4 for Digital Shelf 2” (T1-4) and punchdown block 4.
Repeat Steps 2-6. Punch down twisted-wire pairs 1-8 at punchdown block 4, according
to the appropriate table below. Cut off any excess wire.
Locate the cable labeled “T1-5 for Digital Shelf 2” (T1-5) and punchdown block 5.
Repeat Steps 2-6. Punch down twisted-wire pairs 1-8 at punchdown block 5, according
to the appropriate table below. Cut off any excess wire.
Locate the cable labeled “T1-6 for Digital Shelf 2” (T1-6) and punchdown block 6.
Repeat Steps 2-6. Punch down twisted-wire pairs 1-8 at punchdown block 6, according
to the appropriate table below. Cut off any excess wire.
Connect the T1/E1 cables according to the following tables.
The following tables list the twisted-wire pair connections for cables “T1-1 for Digital
Shelf 1,” “T1-2 for Digital Shelf 1,” “T1-3 for Digital Shelf 1,” “T1-1 for Digital Shelf
2,” “T1-2 for Digital Shelf 2,” and “T1-3 for Digital Shelf 2.” These cables (24 T1/E1
lines) are connected to the EQUIPMENT SIDE of each corresponding Z-IDC
punchdown block. Tx/Rx signal twisted wire-pair connections are shown for Positions
1,2,3 on the first Digital Shelf and Positions 1,2,3 on the second Digital Shelf.
Data or Voice, mutually exclusive, Digital Shelf 1
1.Data or Voice T1/E1 lines must be assigned to Z-IDC Punchdown Block 1 (URC or URC-II). Data and
Voice are mutually exclusive.
2.EXAMPLE 1-3 Lower = Block Number 1, Position 3, Lower
3.The Z-IDC positions 9 and 10 are not used. Unused T1/E1 cables at the customer’s NIU must not be
looped back towards the BTS 8420 while the radio is in operation.
4.Use the T1-1 cable wire color code accordingly to punch down T1 cable (depends upon number of T1s
available) at customer provided punchdown block on NIU.
1.Only Voice T1/E1 lines may be assigned to Z-IDC Punchdown Block #2 (URC or URC-II, Position 2).
2.EXAMPLE 2-3 Lower = Punchdown Block #2, Position 3, Lower
3.Z-IDC positions 9 and 10 are not used. Unused T1/E1 cables, at the customer’s NIU, must not be looped
back towards the BTS 8420 while the radio is in operation.
4.Use the T1-1 cable wire color code accordingly to punch down T1 cable (depends upon number of T1s
available) at customer provided punchdown block on NIU.
Voice only, Digital Shelf 1
Customer assigned T1/E1
Line Number. (Cable to be
punched down at Equipment
side of Z-IDC block by
customer.) See Note 1.
LINEWhite-Blue1Tx T3-1 Upper2
LINE
T1-3 cable wire color
code. To be punched
down at customer
provided punchdown
block at NIU. (See Note
4.)
Pair#Function
Tx/Rx
Tip/Ring
Equipment side of
Z-IDC punchdown
block 3, if applicable.
(See Note 2.) URC or
URC-II, Position 3.
1.Only Voice T1/E1 lines may be assigned to Punchdown Block 3 (URC or URC-II, Position 3).
2.EXAMPLE 3-3 Lower = Block Number 3, Position 3, Lower
3.Z-IDC positions 9 and 10 are not used. Unused T1/E1 cables, at the customer’s NIU, must not be looped
back towards the BTS 8420 while the radio is in operation.
4.Use the T1-3 cable wire color code accordingly to punch down T1 cable (depends upon number of T1s
available) at customer provided punchdown block on NIU.
Data or Voice, mutually exclusive, Digital Shelf 2
1.Data or Voice T1/E1 lines must be assigned to Z-IDC Punchdown Block 4 (URC or URC-II). Data and
Voice are mutually exclusive.
2.EXAMPLE 4-3 Lower = Block Number 1, Position 3, Lower
3.The Z-IDC positions 9 and 10 are not used. Unused T1/E1 cables at the customer’s NIU must not be
looped back towards the BTS 8420 while the radio is in operation.
4.Use the T1-4 cable wire color code accordingly to punch down T1 cable (depends upon number of T1s
available) at customer provided punchdown block on NIU.
Voice only, Digital Shelf 2
Customer assigned T1/E1
Line Number. Cable to be
punched down at Equipment
side of Z-IDC block, if
applicable. (See Note 1.)
LINEWhite-Blue1Tx T5-1 Upper2
LINE
T1-5 (SECB-2) wire
color code. To be
punched down at
customer provided
punchdown block at
NIU. (See Note 4.)
Pair#Function
Tx/Rx
Tip/Ring
Equipment side of
Z-IDC punchdown
block 5, if applicable.
(See Note 2.) Goes to
1.Only Voice T1/E1 lines may be assigned to Z-IDC Punchdown Block 5 (URC or URC-II, Position 2).
2.EXAMPLE 5-3 Lower = Punchdown Block 5, Position 3, Lower
3.Z-IDC positions 9 and 10 are not used. Unused T1/E1 cables, at the customer’s NIU, must not be looped
back towards the BTS 8420 while the radio is in operation.
4.Use the T1-5 cable wire color code accordingly to punch down T1 cable (depends upon number of T1s
available) at customer provided punchdown block on NIU.
Voice only, Digital Shelf 2
Customer assigned T1/E1
Line Number. Cable to be
punched down at Equipment
side of Z-IDC block by
customer, if applicable. (See
Note 1.)
LINEWhite-Blue1Tx T6-1 Upper2
LINE
T1-6 (User Relay) wire
color code. To be
punched down at
customer provided
punchdown block at
NIU. (See Note 4.)
Pair#Function
Tx/Rx
Tip/Ring
Equipment side of
Z-IDC punchdown
block 6, if applicable.
(See Note 2.) URC or
URC-II, Position 3.
1.Only Voice T1/E1 lines may be assigned to Punchdown Block 6 (URC or URC-II, Position 3).
2.EXAMPLE 6-3 Lower = Block Number 6, Position 3, Lower
3.Z-IDC positions 9 and 10 are not used. Unused T1/E1 cables, at the customer’s NIU, must not be looped
back towards the BTS 8420 while the radio is in operation.
4.Use the T1-6 cable wire color code accordingly to punch down T1 cable (depends upon number of T1s
available) at customer provided punchdown block on NIU.
This topic provides instructions for routing and connecting the User Alarm cable
(external and power, if applicable) to the BTS 8420/AWS 8420 radio cabinet. Each
indoor User Alarm cable consists of 16 twisted-wire pairs. The end, which is
terminated with a 37-pin D-sub, is connected to the BTS 8420/AWS 8420 radio
cabinet. The loose (not terminated) end is punched down at the NIU.
Connect User Alarm cable(s) to BTS 8420/AWS 8420 radio cabinet with integrated power
Perform the following steps when connecting User Alarm cable(s) to the BTS
8420/AWS 8420 radio cabinet with integrated power.
For the AWS 8420 and all versions of the BTS 8420 radio cabinet with integrated
1
power (except the BTS 8420 Digital Only version with two Digital Shelves), locate the
two User Alarm cable(s) shipped with the cabinet. Mark the first cable “Alarms 0-15”
at both ends. Mark the second cable (if there is one) with “Alarms 16-31“ at both
ends. For configurations with non-Alcatel-Lucent power, connect the “Alarms 16-31”
cable to the bracket on top of the Integrated Power Module. Refer to the figure below.
For the BTS 8420 Digital Only version with two Digital Shelves radio cabinet with
integrated power, locate the two User Alarm cable(s) shipped with the cabinet. Mark
the first cable “Alarms 0-15” at both ends. Mark the second cable (if there is one)
“Alarms 16-31“ at both ends. Connect the “Alarms 0-15” cable to the USER ALARMS
0-15 connector on the Integrated Power Module bracket. Connect the “Alarms 16-31”
cable to the USER ALARMS 16-31 connector on the Integrated Power Module
bracket. Refer to the figure below.
For BTS 8420/AWS 8420 radio cabinets without integrated power only, locate the User
1
Alarm cable(s) that are shipped with the cabinet. Label the first cable “Alarms 16-31”
at both ends. Label the second cable “Alarms 0-15” at both ends. Connect the “Alarms
16-31” cable to the Universal Hatchplate on the BTS 8420/AWS 8420 radio cabinet. If
using non-Alcatel-Lucent power, connect only “Alarms 0-15” cable to the Universal
Hatchplate on the BTS 8420/AWS 8420 radio cabinet. Refer to the figure of the
Universal Hatchplate below.
Connecting cables to BTS 8420/AWS 8420 radio cabinet
How to route and connect User Alarm cable(s) to indoor
BTS 8420/AWS 8420 radio cabinet
Connect User Alarm cable(s) to Z-IDC punchdown block(s) (or equivalent) -- for all BTS
8420/AWS 8420 radio cabinets except Digital Only version with two Digital Shelves.
Important! Z-IDC punchdown blocks are used only if the NIU is located more
than the 10 meter (33 foot) cable length distance from the BTS 8420/AWS 8420.
Otherwise, User Alarm connections are made directly to the NIU. The customer
may use the Z-IDC (or NIU) to collect alarm cables from various locations. Use
the following steps only if connecting to a Z-IDC. Otherwise, use only the tables to
determine how to make connections at NIU.
Use the following procedure to connect the User Alarm cables (External Alarms and
Power Alarms, if applicable) to the punchdown terminals on the EQUIPMENT side of
the Z-IDC punchdown block(s) (or equivalent), located at the NIU. (Refer to the figure
on Page 5-11 for a simplified wiring diagram of User Alarm cabling from the Z-IDC
punchdown blocks to the BTS 8420/AWS 8420 radio cabinet.)
Locate the cables labeled “Alarms 0-15” and “Alarms 16-31,” and Z-IDC punchdown
1
blocks 7,8,9,10 on the NIU. User Alarms 0-6 are connected to Z-IDC punchdown
block 7, User Alarms 7-15 are connected to Z-IDC punchdown block 8, User Alarms
16-23 are connected to Z-IDC punchdown block 9, and User Alarms 24-31 are
connected to Z-IDC punchdown block 10. (Refer to the figure on page 5-12 for the
Connect User Alarm cable(s) to Z-IDC punchdown block(s) (or equivalent) -- for BTS 8420
Digital Only version with two Digital Shelves.
Important! Z-IDC punchdown blocks are used only if the NIU is located more
than the 10 meter (33 foot) cable length distance from the BTS 8420. Otherwise,
User Alarm connections are made directly to the NIU. The customer may use the
Z-IDC (or NIU) to collect alarm cables from various locations. Use the following
steps only if connecting to a Z-IDC. Otherwise, use only the tables to determine
how to make connections at NIU.
Use the following procedure to connect User Alarm cables (i.e., external User
Alarms and Power Alarms) to the punchdown terminals on the EQUIPMENT side
of the Z-IDC punchdown block(s), or equivalent, on the NIU. Refer to the figure
on page 5-12 for a simplified wiring diagram of the User Alarm cabling from the
Z-IDC punchdown blocks to the BTS 8420 radio cabinet with two Digital Shelves.
Locate the cables labeled “Alarms 0-15” and “Alarms 16-31,” and Z-IDC punchdown
1
blocks 7,8,9,10 on the NIU. User Alarms 0-6 are connected to Z-IDC punchdown
block 7, User Alarms 8-15 are connected to Z-IDC punchdown block 8, and User
Alarms 23-31 are connected to Z-IDC punchdown block 10. (Refer to the figure on
page 5-13 for the location of the punchdown blocks.)
Refer to the figure on page 5-13 and the tables in Step 9. Connect the 0-6, 7-15, and
7
23-31 User Alarm twisted-wire pairs as follows:
•Connect User Alarm twisted-wire pairs 0-6 to the EQUIPMENT SIDE (see figure
below) of punchdown block 7. These go to terminals 1-7 on the punchdown block.
•Connect User Alarm twisted-wire pairs 7-15 to the EQUIPMENT SIDE (see figure
below) of punchdown block 8. These go to terminals 1-9 on the punchdown block.
•If applicable, connect Power Alarm twisted-wire pairs 16-22 to the EQUIPMENT
SIDE (see figure below) of punchdown block 9. These go to terminals 1-7 on the
punchdown block. (These Power Alarms are for non-Alcatel-Lucent power only.
Punch downs are not made for cabinets with integrated power.)
•Connect User Alarm twisted-wire pairs 23-31 to the EQUIPMENT SIDE (see
figure below) of punchdown block 10. These go to terminals 1-9 on the punchdown
block.
Connecting cables to BTS 8420/AWS 8420 radio cabinet
How to route and connect User Alarm cable(s) to indoor
BTS 8420/AWS 8420 radio cabinet
0-15 Alarm
Cable/
Connector
at BTS
8420 Radio
Cabinet
Alarms
0-15
(37-Pin
D-Sub)
Alarm Punchdown
Block (Z-IDC or
equivalent)
Z-IDC BLOCK 8
External User
Alarms
Alarm #Punchdown position
at Equipment side of
punchdown block.
(Z-IDC block and
position.) See Note.
Alarm wire color code. To
be punched down at
customer provided
punchdown block at NIU.
Pin#at
37-Pin D-Sub
User 7 Alarm8-1 UpperRed-Green8
8-1 LowerGreen-Red27
User 8 Alarm8-2 UpperRed-Brown9
8-2 LowerBrown-Red28
User 9 Alarm8-3 UpperRed-Slate10
8-3 LowerSlate-Red29
User 10 Alarm8-4 UpperBlack-Blue11
8-4 LowerBlue-Black30
User 11 Alarm8-5 UpperBlack-Orange12
8-5 LowerOrange-Black31
User 12 Alarm8-6 UpperBlack-Green13
8-6 LowerGreen-Black32
User 13 Alarm8-7 UpperBlack-Brown14
8-7 LowerBrown-Black33
User 14 Alarm8-8 UpperBlack-Slate15
8-8 LowerSlate-Black34
User 15 Alarm8-9 UpperYellow-Blue16
8-9 LowerBlue Yellow35
The following table lists the connections (external only), to the EQUIPMENT side of
Z-IDC punchdown block 10, for User Alarms 16-31. (User Alarms 16-22 are not
available for integrated power.)
This section describes how to connect T1/E1 lines when a Balun Block is used.
In the event the Balun Blocks provided to the customer are Alcatel-Lucent Balun
Blocks, instructions are provided to the installer for installing and connecting one to
three T1/E1 cables from the BTS 8420/AWS 8420 radio cabinet to one to three Balun
Blocks. The Balun Blocks must be located within the 10 meter (33 foot) cable length
distance from the BTS 8420/AWS 8420 radio cabinet. Four loose RJ-45 connectors
(shipped with the Balun Block) must be connected to the end of the T1/E1 cables that
connect to the Balun Block.
Contents
How to connect twisted-wire pairs in T1/E1 cable(s) to Balun Blocks5-62
This module provides instructions to the installer for installating and connecting one to
three T1/E1 cables from the BTS 8420/AWS 8420 radio cabinet to one to three Balun
Blocks. (The Balun Blocks are customer provided and installed.)
“Connect RJ-45 connectors to twisted-wire pairs in T1/E1 cable(s) ” (p. 5-64)
“Connect RJ-45 connectors to Balun Blocks” (p. 5-66)
Balun Block description
The customer is responsible for converting 75 ohm unbalanced coaxial cable to 120
ohm balanced twisted pair if the incoming facility provides 75 ohm unbalanced coaxial
cable. Conversion of 75 ohm unbalanced coaxial cable to 120 ohm balanced twisted
pair is accomplished with an Alcatel-Lucent Balun Block, or equivalent.
Important! The Balun Block must be installed within the 10 meter (33 foot) cable
length from the BTS 8420/AWS 8420 radio cabinet. The T1/E1 cable is connected
directly to the Balun Block. Four RJ-45 loose connectors are provided with each
Balun block and must be installed on each T1/E1 cable that goes from the BTS
8420/AWS 8420 to the Balun Block, during installation of the BTS 4400 radio
cabinet. Refer to the figure below.
NIU with primary
T1/E1
input lines
(From
Service
Protection
(Provided by
customer)
(Provided as part
of site preparation)
T1/E1 lines to
Balun Block
(Coaxial cable)
Balun
Block
(See
Notes
1 and 2)
Provider)
Note 1: Z-IDC block not required when Balun Block is used.
Note 2: Balun Block must be located not more than the 10 meter (35 foot)
cable length distance from radio cabinet.
Note 3: RJ-45 connectors installed on loose end of T1/E1 cables and connected to Balun Block
during installation of radio cabinet.
T1/E1 cable
(See Note 3)
To BTS 8420/AWS 8420
radio cabinet. [Maximum
distance = 10 meter
(33 foot) cable length.
Connecting cables to BTS 8420/AWS 8420 radio cabinet
The Step 7 table that follows, provides punchdown and wire color code information for
the T1/E1 cable that is to be connected from the Balun Block to the BTS 8420/AWS
8420 radio cabinet. The customer must label each Balun Block with the cable name of
the cable that is to be connected to it.
The table notes in the table that follows describe the three cable possibilities (one
Balun Block is required for each T1/E1 cable) and URC/URCII, Voice, and Data
assignments.
How to connect twisted-wire pairs in T1/E1 cable(s) to
Connecting cables to BTS 8420/AWS 8420 radio cabinet
How to connect twisted-wire pairs in T1/E1 cable(s) to
Connect RJ-45 connectors to twisted-wire pairs in T1/E1 cable(s)
The following figure shows the RJ-45 connector and its pins, which are numbered.
Balun Blocks
Use the following procedure to attach four RJ-45 connectors to the eight twisted-wire
pair in the T1-1 (first) T1/E1 cable (two twisted-wire pairs connect to each RJ-45
connector).
If applicable, locate the cable marked T1-3 and repeat Steps 2 through 5.
7
The following table provides the wire color codes for the twisted-wire pairs in the
T1/E1 cable so the RJ-45 connectors can be connected to cables T1-1, T1-2 and T1-3.
Cables T1-1, T1-2 and T1-3 are subsequently connected to the appropriate Balun
Block.
How to connect twisted-wire pairs in T1/E1 cable(s) to
Balun Blocks
The table applies to the T1/E1 connections from the BTS 4400 radio cabinet to the
Balun Block.
This chapter provides instructions for connecting AC, DC, and customer-supplied
power to the BTS 8420 radio cabinet with integrated power. (Note that the Integrated
Power Module is field installed.) Procedures are provided for:
•connecting customer-supplied power to a BTS 8420/AWS 8420 radio cabinet
(references DC and alarm connections)
•connecting AC power to a BTS 8420/AWS 8420 radio cabinet with integrated
power
Contents
•connecting first and second EZBFi battery frames to a BTS 8420/AWS 8420 radio
cabinet with integrated power
Installation of rectifiers in the Integrated Power Module is covered in Chapter 7,
“Component installation in Integrated Power Module”. Installation of batteries in the
EZBFi is covered in the EZBFi Modular Battery System Installation Manual for +24Vand -48V, 401-703-507.
Customer-supplied power6-2
Safety precautions6-3
Power wiring overview6-4
Installation of integrated power AC connections6-5
Wiring overview6-6
How to install the integrated power AC connections6-7
This section provides the references required for customer supplied power.
References
For AC/DC power and power system alarm requirements, refer to Appendix E in the
Alcatel-Lucent CDMA Base Station BTS 8420/AWS 8420 Indoor Site Preparation
Guidelines, 401-703-443.
Refer to the applicable vendor documentation if the requirements listed in the
applicable document have been met. Then use the chapter and page references given
below for instructions to connect the indoor radio cabinet and external punchdowns, if
applicable.
This chapter provides instructions for the power interconnections between the EZBFi
battery frames and the integrated power module on the integrated power version of the
radio cabinet, as well as the AC utility connection to the integrated power module.
Refer to the figure below for a key to the following numbered list.
1. AC utility connection to the integrated power module
2. DC cable connections between the first EZBFi battery base module and the
integrated power module
3. Fuse alarm cable connections between the first battery base module and the
integrated power module (combined with #4)
4. Thermal probe cable connection between the battery base modules and the
integrated power module (combined with #3)
5. DC cable connections between the first EZBFi battery base module and the second
EZBFi battery base module.
AC
1
ADD-ONBATTERY
MODULE AS
SECOND BASE
MODULE
THERMAL
PROBE
CABLES
4
3
REAR VIEW
SINGLE
SHELF
ADD-ON
BATTERY
MODULE
ADD-ON
BATTERY
MODULE
4
ADD-ON
BATTERY
MODULE
* Power alarm connections to the radio cabinet were covered in Chapter 5.
This section describes the instructions for making AC utility power connections to the
BTS 8420/AWS 8420 radio cabinet having an Integrated Power Module.
Note that grounding cables were installed in Chapter 4, “Transport, mount, and ground
cabinet” after placement and anchoring of the BTS 8420 radio cabinet.
Contents
Wiring overview6-6
How to install the integrated power AC connections6-7
AC utility power input enters the Integrated Power Module on the top of the unit. AC
power is connected to the AC terminal block. Refer to the following figure for an
overview illustration.
This procedure module provides instructions for the connection of the AC utility power
wires to a BTS 8420/AWS 8420 radio cabinet that is equipped with integrated power.
Since this procedure may be performed by a licensed electrician (depending upon local
regulations), these steps are supplied for reference only.
If the AC utility connections are to be performed by a licensed electrician, this activity
must be coordinated with the work of the BTS 8420 radio cabinet installers in order to
avoid unnecessary delays.
Step-by-step instructions are provided for the following tasks:
“Connect 1-inch AC flexible metallic conduit to Integrated Power Module on top of
BTS 8420/AWS 8420 radio cabinet” (p. 6-8)
“Route and connect AC wires in Integrated Power Module” (p. 6-11)
Safety precautions
Observe the following safety precautions
CAUTION
Equipment Damage / Inspection Failure
Damage to equipment, safety hazards, or failure to pass inspection can occur if all
applicable codes and regulations are not followed.
Follow all local codes and practices when performing the steps to connect AC to the
Integrated Power Module.
How to install the integrated power AC connections
DANGER
Electrical Energy Hazard
Electrical circuits can become energized, resulting in an electrical shock hazard.
Follow these rules:
1. Ensure that the circuit breaker for each AC input is turned OFF and tagged out.
2. Follow the procedures in the order provided. Always install earth ground
connection before connecting AC power to the Integrated Power Module.
Description of AC utility power connections
The BTS 8420 radio cabinet described in this chapter is equipped with an Integrated
Power Module. The Integrated Power Module accepts a 1-inch conduit (flexible
metallic or rigid per local code) for the AC power supply wires. The AC wires enter
through the top of the module. The Integrated Power Module is equipped with an AC
terminal block at the top interior left side of the Integrated Power Module, for
connecting the AC wires that power up to six rectifiers in the module. The customer
provides the AC service and the flexible metallic conduit as part of site preparation.
Before you begin
The AC cable should be installed from the service panel to the area of the Integrated
Power Module as part of site preparation. If this has not been done, contact your
supervisor and the customer contact.
Verify that the circuit breakers for the AC feeder wires are off, locked out, and tagged
at the AC service panel.
Verify that the GPS antenna, BTS 8420 radio cabinet and associated equipment have
been properly grounded.
Connect 1-inch AC flexible metallic conduit to Integrated Power Module on top of BTS
8420/AWS 8420 radio cabinet
Use the following procedure to connect the 1-inch AC flexible metallic conduit to the
Integrated Power Module on top of the cabinet.
Verify that the main panel breaker(s) that supply AC power are OFF and that clearly
label (tag out) the circuit breaker panel, stating that installers are working on the AC
wiring.
Remove the AC terminal block cover from the Integrated Power Module by
unscrewing the captivated Phillips head screw on the top. Refer to the following figure.
The location, color, function, and size of each wire in the AC input is shown in the
5
table below. Use a small flat blade screwdriver, in each terminal insertion slot, to
release each terminal input for insertion of the individual wires.
This procedure module provides instructions for installing the rectifiers in the
integrated power module.
Description of rectifiers and shelves
The rectifiers are shipped separately if the radio cabinet is equipped with an integrated
power module. You may want to refer to the installation instructions provided in the
integrated power module kit (109601302) at this point.
The integrated power module has one rectifier shelf. The rectifier shelf can support up
to six KS-24734 rectifiers.
The rectifiers must be installed, starting with Rectifier #1, as shown in the figure
below.
Semiconductor elements can be damaged by static discharges.
The following rules must be complied with when handling any module containing
semiconductor components:
•Wear conductive or antistatic working clothes (e.g., coat made of 100% cotton.
•Wear grounded ESD wrist strap.
•Wear shoes with conductive soles on a conductive floor surface or conductive work
mat.
•Leave the modules in their original packaging until ready for use.
•Make sure there is no difference in potential between yourself, the workplace, and
the package before removing, unpacking, or packing a module.
•Hold the module only by the grip without touching the connection pins, tracks, or
components.
How to install rectifiers in Integrated Power Module
•Place modules removed from the equipment on a conductive surface.
•Test or handle the module only with grounded tools on grounded equipment.
•Handle defective modules exactly like new ones to avoid causing further damage.
Number of required rectifiers
Use the following procedure to install the KS-24734 rectifier(s) in the radio cabinet.
The number of rectifiers is specified in the ERD and depends upon how many carriers
there are.
Install the rectifiers in the integrated power module
Use the following procedure to install the rectifier(s) for the integrated power module
on the radio cabinet.
Insert, from left to right, the required number of rectifier modules KS-24734 that are
1
needed to power the base station. Remove cover plates from slots 3 through 6, as
needed. Secure each rectifier by turning the latch mechanism CW with a flat head
screwdriver until it is fully seated. Do not over tighten. Refer to the figure below.
Verify that the GPS antenna is properly connected, as outlined in Chapter 5 of this
document. Verify that it meets all of the appropriate guidelines in accordance with the
following documents:
•Alcatel-Lucent CDMA Base Station BTS 8420/AWS 8420 Indoor Site Preparation
Guidelines, 401-703-443
•Grounding and Lightning Protection Guidelines for Alcatel-Lucent Network
Wireless System Cell Sites, 401-200-115
Important! The GPS antenna must be connected to the radio cabinet prior to
“Initial start up and system test.” Refer to Chapter 5, “Connecting cables to BTS
8420/AWS 8420 radio cabinet”.Donot connect RF (Tx and Rx) antenna jumper
cables.
Verify RF antennas not connected
The RF (Tx and Rx) antennas, if present, must not be connected until initial start-up
and system test has been performed.
Initial start-up and system test can be performed if the following tasks are completed:
•All cabinets are installed as specified in this document.
•The GPS antenna cable is connected.
•RF antenna jumper cables, if present, are not connected to the radio cabinet.
Important! The procedures for initial start-up and testing are not covered in this
document. Refer to CDMA Modcell and Base Station Integration EngineeringHandbook (IEH 238).
Important! It is recommended that the RF antenna jumper cables be connected to
the BTS 8420 radio cabinet after the BTS 8420 radio cabinet power cabinet has
been turned on and initial start-up and system test have been completed.
Overview
This procedure module provides instructions for installing the six RF antenna jumper
cables at the BTS 8420/AWS 8420 radio cabinet.
Contents
Step-by-step instructions are provided for the following tasks:
“Connect RF antenna jumper cables to BTS 8420/AWS 8420 radio cabinet” (p. 8-5)
“Route and connect indoor RF antenna jumper cables to customer provided DAS”
(p. 8-8)
Description of indoor RF antenna jumper cables
The BTS 8420 radio cabinet requires six RF antenna jumper cables. The RF antenna
jumper cables will be attached to the six RF antenna connections at the top rear of the
BTS 8420/AWS 8420 radio cabinet. Refer to figure after Step 5Step 5.
Each RF antenna jumper cable connects directly to an assigned antenna connection at
the customer provided DAS.
Connect RF antenna jumper cables to BTS 8420/AWS 8420 radio cabinet
Use the following procedure to connect the RF antenna jumper cables to the BTS
8420/AWS 8420 radio cabinet.
Important! When performing the next step, note that right angle connectors may
be used at the radio cabinet connections.
The radio cabinet is provided with six RF antenna jumper cables, terminated on both
ends with a straight DIN connector. Locate these cables in the RF antenna kit.
Torque the RF antenna jumper cable connections at the BTS 8420/AWS 8420 radio
4
S3D0
S2D1
S2D0
S1D1
S1D0
cabinet to 25 Nm (221 in-lb), using the method shown in the figure below.
221 - 250 lb-IN
25 - 30 N-m
32mm
22mm
22mm
Important! When connecting/disconnecting a Alcatel-Lucent RF coaxial jumper
cable assembly to/from any fixed panel mounted 7-16 DIN female receptacle, it is
highly recommended that the cable assembly be connected/disconnected as shown
in the figure below. Please note that the mating receptacle is not shown because it
is a fixed and secured interface. Wrenches for connecting/disconnecting the mating
RF coaxial jumper cable’s 7-16 DIN male plug, which is equipped with a rotating
coupling nut, are required.