Job:
XFyre™ - Type WH
Engineer:
Contractor:
Prepared By: Date:
Model: Indoor/Outdoor:
95% Thermal Efficiency at Full Rate, Up to 99% at Part Load
Indoor/Outdoor Construction Standard
PVC, CPVC, or Stainless Venting Certified
Soft Start, Electronic Modulation, 5:1 Turndown
LCD Status Display and Full Diagnostics and Fault Memory
Footprint: Less Than 8-1/3 ft
Zero Clearance to Combustibles
Meets NOx Requirements Thru 2012 (< 20 ppm)
Maximum Outlet Water Temperature: 175°F
Maximum System Temperature: 175°F
Limited 25 Year Thermal Shock Warranty
Limited Five-Year Heat Exchanger Warranty
Heat Exchanger
All Stainless Steel Construction with
Copper Connections
Gasketless Heat Exchanger Design
ASME H Stamped
160 PSIG Working Pressure
National Board Approved
ASME Pressure Relief Valve
125 PSIG – Standard
PSIG – Optional
Temperature and Pressure Gauge,
Shipped Loose
Control
120V, 60Hz, 1Ø, Power Supply
Digital Operating Control with LCD
display.
0-10 VDC input for BMS
Cascade up to 8 water heaters
Spark Ignition (DSI)
Remote Flame Sensor
High Limit, Manual Reset, Fixed,
175ºF
Auto Limit, Fixed, 200ºF
Alarm Dry Contact Connection
On/Off Power Switch
Flow Switch
Blocked Vent Pressure Switch
Boiler, DHW & System Pump
Contacts
Water Temperature Sensors (3)
2
Burner
Ultra-Low NOx: Less than 20 PPM
Gas Train
Fuel
Natural Gas
Propane
Zero Governor Regulator
Dual-Seat Combination Valve
Electronic Modulating Firing Mode
(WH7)
Construction
Indoor/Outdoor Construction
Front Controls Enclosed
PolyTuf Powder Coat Finish
Rear Connections (Electrical, Gas, Vent,
Combustion Air)
Top Connections (Water)
Design Certified ANSI Z21.10.3/
CSA 4.3
Combustion Air Filter
Condensate Trap
Venting (PVC-CPVC-Stainless)
Vent Termination
Indoor, Vertical – Option D-11
Indoor, Horizontal – Option D-15
Outdoor
Extractor - Optional
By others
Not required
Condensing Water Heaters
Models 300-850
Proudly Made in the USA
Multi-Boiler System Controllers
B-36 TempTracker Mod+ Hybrid Digital
Controller, 2-4 water heaters
B-37 TempTracker Mod+ Hybrid Digital
Controller, 5-10 water heaters
B-38 TempTracker Mod+ Hybrid Digital
Controller, 11-16 water heaters
Options
D-21 TruSeal™ Combustion Air Inlet
(Mounted)
D-22 TruSeal™ Combustion Air Inlet
(Loose)
P- Pump: HP, 120V, 1∅,
60Hz
Bronze/SS
S-1/S-2 High/Low Gas Pressure
Switches, Manual Reset
Z-12 Condensate Neutralizer Kit
Regulatory Agency Requirements
Catalog No.: 3500.17B Effective: 11-02-10 Replaces: 12-15-09
XFyre – Type WH
Models 300-850 Model
CLEARANCES
Front 24” 24”
Rear 24” 24”
Right 0” 0”
Left 0” 0”
Top 12” 24”
Floor 0” -Vent 1” --
Certified
Minimum
Service
Minimum
Model
(WH7-)
MBTUH Dimensions (in.)
K
Ø
T
C/A
Ø
V
Input Output
A
Length
E
F
MountingG NPT H NPT
Flue
Ship
Weight
(Lbs.)
Foot-
Print
2
(Ft
Amps*
)
300 300 285 28-1/4 16-1/2 27-9/16 3/4 1-1/2 4 4 3 410 4.3 3
400 399 379 30-3/4 16-1/2 29-3/4 1 2 4 4 3 465 4.7 4
500 500 475 37-1/4 16-1/2 36-1/4 1 2 4 4 3 505 5.7 4
700 700 665 47-3/4 28 47-1/16 1-1/4 2 6 6 19-3/8 550 7.3 5
850 850 808 54-1/4 28 53-9/16 1-1/4 2 6 6 19-3/8 580 8.3 5
Ratings shown are for elevations up to 2,000 feet. For installations at elevations
above 2,000 feet, please consult the factory for additional instructions.
Catalog No.: 3500.17B Effective: 11-02-10 Replaces: 12-15-09
* Current draw is for heater only.
(Supply breaker must have delayed trip.)