Newport INFCP Quick Start Manual

INFCP and INFCP-xxxB
Process Meter
Using This Quick Start Manual
Use this Quick Start Manual to set up your Process Meter and begin operation. Information is provided on how to:
• Connect ac power • Set basic options for operation
• Connect the sensor • Scale the meter.
IMPORTANT:For complete information on all setup options, please refer to the Operator’s Manual.
Mount the Unit
1. Cut a panel opening using the dimensions shown to the right.
2. Position the unit in the opening, making sure the front bezel is flush with the panel.
3. Install retaining clips on both sides of the meter and tighten against the panel.
Wiring
1. Remove the panel at the back of the unit.
2. Locate the TB1 connector.
3. Insert the correct wire in each terminal as shown in the following figure and tighten the lockdown screws.
4. Tug gently on the wires to verify the connections.
Connect the Sensor
1. Locate the TB2 connector on the rear of the unit.
2. Attach the sensor wires and tighten the lockdown screws. The diagram below shows the wiring for 4–20 mA sensors with internal excitation.
3. Tug gently on the wires to verify the connections.
4. Replace the panel at the back of the unit.
NOTE: Refer to the Operator's Manual for setup requirements for other sensor types.
Current Input Connections (4–20 mA)
with Internal Excitation
Using the Configuration Menu
To configure the meter, you use the buttons on the front panel.
To: Take This Action:
Display the Press the MENU button. The first function Configuration Menu on the menu, INPT, displays. Select a submenu 1. Press MENU until the function you function want is shown.
2. Press /TARE.
The information you can change flashes.
Select a value 1. Press /MAX to display the option for that submenu you want. function 2. Press MENU to store it.
STRD quickly flashes, indicating that the selection has been stored in memory.
Then the next menu function displays. Go back to previous Press RESET once. menu function Exit the Press RESET twice. The unit displays Configuration RST as it reinitializes. When a numeric
Menu value displays, the unit is in run mode.
(Optionally, you can press MENU to
move through all the menu functions
until the unit reinitializes.)
NOTE: This Quick Start Manual includes specific configuration parameters for transducers with an output range of 4–20 mA and 24 V excitation. Other sensor types may require different parameters or additional ones. When this is the case, we refer you to the Operator's Manual for detailed instructions.
2
34
Warning: Do not connect AC power to your device until you have completed all input and output connections. This device must only be installed by a specially trained electrician with corresponding qualifications. Failure to follow all instructions and warnings may result in injury!
AC Powered Unit Connections
DC Powered Unit Connections
To Set the Input Type
1. Press MENU until the unit displays:
2. Press /TARE. The unit displays:
3. For this application you want 0-20. If 0-20 is not
displayed, press /MAX until it appears. Other choices are 100M, 50M, 10V and 5V.
NOTE: Refer to the Operator's Manual for more information on changing ranges.
4. Press MENU to select the sensor shown. The meter displays the next menu item. If you changed input type, the meter displays:
To Set the Decimal Point
1. If it's not already shown, press MENU until the unit displays:
2. Press /TARE. The unit displays:
3. Press /MAX to move the decimal point to the desired location. The choices are FFFF, F.FFF, FF.FF, and FFF.F.
4. Press MENU to select the decimal point position shown. The unit displays:
MENU SUBMENU /TARE DESCRIPTION
INPT 100M, ±50M,!1 0V , !±5V , 0-20*Input DEC.P FFFF*, F.FFF, FF.FF, FFF.F Decimal Point RD.S.O IN!1, RD!1, IN!2 , RD!2 Scale and Offset RD.CF R.1=T*, R.1=N
Reading Configuration
R.2=0, R.2=1, R.2=2 , R.2=3, R.2=4
*
R.3=F*, R.3=U COLR GRN, RED, AMBR Display Color S1.CF S.1=A*, S.1=B
Setpoint 1 Configuration
S.2=U*, S.2=L S2.CF S.1=A*, S.1=B
Setpoint 2 Configuration
S.2=U*, S.2=L S1.DB 0003
*
Setpoint 1, Deadband
S2.DB 0003
*
Setpoint 2, Deadband
OT.CF O.1=E*, 0.1=D Analog Output
O.2=C*, 0.2=V
Configuration
O.3=A*, 0.3=P
O.4=D, 0.4=R
O.5=F, 0.5=H P.BND 0000 shown if 0.3 = P Proportional Band M.RST 0000 shown if 0.3 = P Manual Reset OT.S.O RD!1, OUT1 , RD!2, OUT2
Output Scale & Offset
LK.CF RS=E*, RS=D
Lockout Configuration
SP=E*, SP=D
L3=0*, L3=1 BRIT M.BrT, L.BrT, H.BrT
Display Brightness
External Fuse Required:
Time-delay, UL248-14 listed Time-lag, IEC 127-3 recognized
175 mA (115 Vac line) 125 mA (115 Vac line) 80 mA (230 Vac line) 63 mA (230 Vac line)
10-32 Vdc, 7.5 W
DEVICE
* Factory Default Settings
When using DC power, do not use internal excitation or Isolated Analog Output for high color brightness. For low or medium brightness, internal excitation is limited to 24 V @ 25 mA, 5 V, 10 V, 12 V @ 35 mA.
In order to maintain the same degree of protection as the AC units, always use a Safety Agency Approval DC source with the same Overvoltage Category and Pollution Degree.
For immediate technical or application assistance please call:
Newport Electronics, Inc.
2229 South Yale Street • Santa Ana, CA • 92704 • U.S.A.
TEL: (714) 540-4914 • FAX: (714) 546-3022
Toll Free: 1-800-639-7678 • http://www.newportUS.com • e-mail:info@newportUS.com
ISO 9001 Certified
Newport Technologies, Inc.
976 Bergar • Laval (Quebec) • H7L 5A1 • Canada
TEL: (514) 335-3183 • FAX: (514) 856-6886
Toll Free: 1-800-639-7678 • http://www.newport.ca • e-mail:sales@newport.ca
Newport Electronics, Ltd.
One Omega Drive • River Bend Technology Centre
Northbank, Irlam • Manchester M44 5BD • United Kingdom
Tel: +44 161 777 6611 • FAX: +44 161 777 6622
Toll Free: 0800 488 488 • http://www.newportuk.co.uk • e-mail:sales@newportuk.co.uk
Newport Electronics B.V.
Postbus 8034 • 1180 LA Amstelveen • The Netherlands
TEL: +31 20 3472121 • FAX: +31 20 6434643
Toll Free: 0800 0993344 • http://www.newport.nl • e-mail: sales@newport.nl
Newport Electronics spol s.r.o.
Rudé armády 1868, 733 01 Karviná 8 • Czech Republic
TEL: +420 69 6311899 • FAX: +420 69 6311114
Toll Free: 0800-1-66342 • http://www.newport.cz • e-mail: sales@newport.cz
Newport Electronics GmbH
Daimlerstrasse 26 • D-75392 Deckenpfronn • Germany
TEL: 49 7056 9398-0 • FAX: 49 7056 9398-29
Toll Free: 0800 / 6397678 • http://www.newport.de • e-mail: sales@newport.de
Newport Electronique S.A.R.L.
9, rue Denis Papin • 78190 Trappes • France
TEL: +33 130 621 400 • FAX: +33 130 699 120
Toll Free: 0800-4-06342 • http://www.newport.fr • e-mail: sales@newport.fr
Mexico and Latin America
TEL: 001-800-826-6342 • FAX: 001 (203) 359-7807
En Español: 001 (203) 359-7803
®
Safety Consideration
This device is marked with the international Caution symbol.
The instrument is a panel mount device protected in accordance with Class I of EN61010-1 (AC units) and Class III (DC units). Remember that the unit has no power-on switch. Building installation should include a switch or circuit-breaker that must be compliant to IEC 947-1 and 947-3.
SAFETY:
• Do not exceed voltage rating on the label located on the top of the instrument housing.
• Always disconnect power before changing signal and power connections.
• Do not use this instrument on a work bench without its case for safety reasons.
• Do not operate this instrument in flammable or explosive atmospheres.
• Do not expose this instrument to rain or moisture.
EMC:
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wire close to the instrument if EMC problems persist.
Scaling Without Known Loads (Continued)
To define the maximum load (IN!2 and RD!2
):
1. Repeat steps 3–9 above, entering the values for IN!2 and RD!2 .
2. Once you've completed all steps, the unit displays:
To begin operation: Reinitialize the unit (press RESET twice or press MENU until RST flashes on the
display). When a numeric reading appears, the unit is operational.
Determining Reading Offset
The run mode reading for meters scaled without known loads may reflect an offset. For example, say you set
RD!1
to 0 and
RD!2
to 100, but when the minimum load is applied, a
negative value of –1.5 displays on the front panel. To adjust the display reading:
1. With zero load applied, note the reading on the display.
2. Subtract that amount from the RD!1 and RD!2 values you originally entered.
In the example, the offset would be –1.5. If RD!1 is to read 0 in run mode, it must be reentered as 1.5. RD!2 must likewise be reentered as 101.5 if the meter is to read 100 when the maximum load is applied.
3.
Repeat the steps for "Scaling Without Known Loads," but when the values for IN!1 and IN!2 display, do not change them. Instead, press MENU to move to the prompts for RD!1 and RD!2 and make the necessary changes.
4. Reinitialize the unit and resume operation.
Scaling Without Known Loads
For 4–20 mA sensors, the values for the minimum and maximum input loads are always as follows:
• Minimum load (IN!1)— 2000
• Maximum load (IN!2)— 9999. If your installation uses a different sensor type, you must calculate the values for IN!1 and IN!2 before proceeding with the steps below. Use the formula provided in the Operator's Manual.
To define the minimum load
(
IN!1 and RD!1
):
1. If it's not already shown, press MENU until the unit displays:
2. Press /TARE. The unit displays:
3. Press /TARE again. The unit displays the last setting for IN!1. (The first digit flashes.)
4. Change IN!1 as necessary:
Press 䊱/MAX to set or change the digit's current value. Continue to press
/MAX until the meter displays the desired value for the flashing digit. Values can range from 0 to 9. For the first digit, you can also enter a minus sign (–) or –1.
• Press 䊳/TARE to scroll to the digit(s) you want to change.
5. Press MENU to store IN!1.
The unit displays:
6. Press /TARE. The unit displays the
last setting for RD!1. (The first digit flashes.)
7. Change RD!1 as necessary:
• Press 䊱/MAX until the meter displays the desired value for the flashing digit. Values can range from 0 to 9. For the first digit, you can also enter a minus sign (–) or –1.
• Press
/TARE to scroll to the digit(s) you want to change.
8. Press MENU to store the value
shown for RD!1. The unit displays:
Scaling With Known Loads (Continued)
6. Press MENU to store IN!1. The unit
displays:
7. Press /TARE. The unit displays the
last setting for RD!1.
8. Change RD!1 as necessary:
• Press 䊳/TARE to scroll to the digit(s) you want to change (it flashes on the display).
• Press 䊱/MAX to change the value of the flashing digit. Values can range from 0 to 9. For the first digit, you can also enter a minus sign (–) or –1.
9. Press MENU to store the value shown
for RD!1. The unit displays:
To identify the maximum known load (IN!2 and RD!2
):
1. Apply the maximum known load (100%).
2. Repeat steps 4–9 for IN!2 and RD!2.
Once you've completed all steps, the unit displays:
To begin operation:
Reinitialize the unit (press RESET twice or press MENU until RST flashes on the display). When a numeric reading appears, the unit is operational.
Scaling With Known Loads
To identify the minimum known load (IN!1 and RD!1
):
1. If it's not already shown, press MENU until the unit displays:
2. Apply the minimum known load (0%).
3. Press /TARE. The unit displays:
4. Press /TARE again. The unit displays the last setting for
IN!1
.
5. Press /TARE again. The unit displays the actual reading being received from the sending device.
5678
MQS3597/N/0801
Warranty/Disclaimer
NEWPORT Electronics, Inc. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year from the date of purchase. In addition to NEWPORT’s standard warranty period, NEWPORT Electronics will extend the warranty period for one (1) additional year if the warranty card enclosed with each instrument is returned to NEWPORT.
If the unit should malfunction, it must be returned to the factory for evaluation. NEWPORT’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by NEWPORT, if the unit is found to be defective it will be repaired or replaced at no charge. NEWPORT’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of being damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of NEWPORT’s control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.
NEWPORT is pleased to offer suggestions on the use of its various products. However, NEWPORT neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by NEWPORT, either verbal or written. NEWPORT warrants only that the parts manufactured by it will be as specified and free of defects. NEWPORT MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive and the total liability of NEWPORT with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall NEWPORT be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by NEWPORT is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, or used on humans, or misused in any way, NEWPORT assumes no responsibility as set forth in our basic WARRANTY / DISCLAIMER language, and additionally purchaser will indemnify NEWPORT and hold NEWPORT harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
Direct all warranty and repair requests/inquiries to the NEWPORT Customer Service Department. BEFORE RETURNING ANYPRODUCT(S) TO NEWPORT, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM NEWPORT’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the following information available BEFORE contacting NEWPORT:
1. P.O. number under which the product was PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the product.
FOR NON-WARRANTY REPAIRS, consult NEWPORT for current repair charges. Have the following information available BEFORE contacting NEWPORT:
1. P.O. number to cover the COST of the repair,
2. Model and serial number of product, and
3. Repair instructions and/or specific problems relative to the product.
NEWPORT’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.
NEWPORT is a registered trademark of NEWPORTElectronics, Inc.
© Copyright 2001 NEWPORT Electronics, Inc. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without prior written consent of NEWPORT Electronics, Inc.
PATENT NOTICE:
The “Meter Case Bezel Design” is a trademark of NEWPORT Electronics, Inc., registered in the U.S.. This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577; 6,243,021 / CANADA 2052599; 2052600 /
ITALY 1249456; 1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150; 2048066 / UK PATENTNo. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. OTHER INTERNATIONALPATENTS PENDING.
Return Requests/Inquiries
This device is marked with the international caution symbol. It is important to read the Setup Guide before installing or commissioning this device as it contains important information relating to safety and EMC.
WARNING: These products are not designed for use in, and should not be used for, patient connected applications.
It is the policy of NEWPORT to comply with all worldwide safety and EMC/EMI regulations that apply. NEWPORT is constantly pursuing certification of its products to the European New Approach Directives. NEWPORT will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct but NEWPORT Electronics, Inc. accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
TRADEMARK NOTICE:
a
®
, , , , ,
and the “Meter Case Bezel Design”
are trademarks of NEWPORTElectronics, Inc.
EWP
RT
®
NEWP
RT
®
To Scale the Meter
You can scale the meter in one of two ways:
1. With a known load — This method uses input (load) information sent from another device such as a scale or a simulator for voltage or current.
2. Without a known load — This involves calculating the load based on transducer specifications and manually entering it to the meter.
For both methods, you must first identify the minimum input load IN!1 and the corresponding display reading you want RD!1. Then you identify the maximum input load IN!2 and its corresponding display reading RD!2.
The decimal point is for display purposes only — you set it where you want it to display for your application. When entering IN!1 and IN!2 values, ignore any decimal point on the display. However, you must enter RD!1 and RD!2 values with the decimal point in the desired position.