Nedap N V LWBRDG Users Guide

EN–US
Language
Luxon Bridge
1. Before you start, check the package contents
Luxon Bridge DIN-rail clips (2x) Blind plug for cable gland (2x) Installation guide
Installation of electrical components must be completed by a certified electrician as per local codes and regulations.
2. Mounting
1. Mount the Luxon Bridge to a wall or other flat mounting surface
using pan-head screws, max 4.5mm diameter.
2. Alternatively, in case of DIN-rail mounting, click the DIN-rail clips into the rear of the Luxon Bridge.
3. Wiring
Connect the Luxon Bridge to mains power. (100-347Vac 50/60Hz)
during installation.
Make sure the mains power source is not powered
Connect the required sensor or switch to an I/O port.
p/n 9986294
www.nedap-luxon.com
1. Open the wiring compartment after loosening the two screws on the front.
Switch, low
C1 C2 0V
Switch, mains
S
ensor
(ac sensor
-- --
2. Enter the mains cable through the left wire gland.
3. Connect L and N wire to corresponding terminals, no earth connection required.
4. If applicable, connect the switched mains line to the Sensor input.
5. Enter the sensor and/or switch cable using the smaller two cable glands.
6. Connect the wires to the correct I/O terminals, see section 5 for details.
7. Mount the wiring compartment cover.
8. Unused cable glands can be closed using a blind plug.
4. Quick test
Testing power supply and testing correct operation of connected sensor and/or switch.
1. Switch on the mains power
2. The green led (mounted internally) must light up
3. Trigger the sensor, the green led must flash three times
4. Operate the switch, the green led must flash three times.
5. If applicable, operate the mains switch, the green led must flash three times.
5. Compatible sensors and switches
Overview of compatible sensors and switches and their connections
For possible sensors see Luxon Portal: https://portal.nedap-luxon.com.
Connection → Signal wire 24V Supply
wire Device ↓ Nedap motion sensor Commercial 24V motion sensor Light sensor C1
C1 --- 0V
C1 C2 0V
C2 0V
0V wire
voltage
voltage
In case a second low voltage sensor or switch shall be connected, use C3 and C4 terminals.
Report which sensor is connected to which I/O port, this information is required during commissioning.
www.nedap-luxon.com
input, reference to mains N, max. 347Vac)
Loading...
+ 1 hidden pages