NEC 616 User Manual

NEC
Electra – 616
(With Addendum-001)
CONTENTS
Page
110
120
130
Installation Site Requirements
110.1
Physical Environment of Equipment
. . . . . . . . . . . . . . . . . . . . . . .
Electrical and Grounding Requirements
120.1
120.2
Other
130.1
130.2
130.3
Specifications
140.1
1402
140.3
440.4
140.5
140.6
140.7
140.8
140.9
140.10 Dialing Specification
140.11
AC Power Requirements Grounding Requirements
Considerations
Electrical Noise Generators Pre-installation Site Survey Additional Equipment
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Capacity
Cabling Requirements Power Requirements Surge Protection Environmental Conditions CO/PBX Line Type
Dimensions and Weight Network and Control Visual and Audible lndhtions
. . . . . . . . . . . . . . . . . . . . . . .
_ .
External Equipment Interfacing
. . . . . . . . . . . . . . . .
. . . . . . .
. . . . .
1100-1
100-l
100-2
100-2
c
150
160
List of Equipment
150.4
150.2
General Information
Equipment Description
System Configuration
160.1 1602
To Determine Required Equipment
To Determine
. . . . ..*........a...*............
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Equipment
100-5
100 -7
p
SECTION 100 GENERAL INSTALLATION
110
110.1 Physical Environment of Equipment
chosen for mounting the central equipment (Key Service unit>.
1. The KSU should normally be wall-mounted to protect
2. The KSU should not be located directly beneath pipes
3. The area in which the KSU is located must be free of:
Installation
Site Requirements
The following conditions should be met at the site
against accident or flooding. Where possible
use
of a
wooden backboard is recommended for this purpose.
due to the possibility of leaks or condensation causing damage.
120.2 Grounding Requirements
The
KSU must be well-grounded. If a good conduit ground is not present at the dedicated AC outlet, the following steps should be taken:
1. Provide a suitable waterpipe ground in accordance with the local operating (telephone) company procedures.
2. If no waterpipe is available, a ground rod should be installed in accordance with local operating company
procedures.
3. In the case where a ground other than conduit ground is used a grounding terminal is provided on the ES-6 -1 as shown below in Figure 120- 1.
corrosive or inflamable gases, excessive chemical or in-
dustrial dusts, and other materials which could cause hazard to personnel or to the proper functioning of the equipment.
‘1
4. Heat and humidity must be within the limits found in Section 140 “Specifications” in this manual.
t’
5. Although its virtually noiseless operation allows a wide choice of installation sites, care should be taken that the KSU not present a hazard to office traffic. For
/
#
T
PS-6-l PSU
I I
//
purposed of economy a central location (to minimize cabling) is often preferable.
720 Electrical and Ground Requirements
120.1 AC Power Requirements
1. They system should have a dedicated 117V AC outlet separately fused for 15 AMPS.
2. The
AC
outlet should be a standard 12SV three-prong
type which provides conduit ground.
3. The AC power must be within the limits found in Sec­tion 140 “Secifications” in this manual.
4.
If the AC outlet is subject to power surges, it is re­commended that the best locally available AC surge protection be installed.
Fig. 120-l Qutsideview of ES-G-1
Page 108-l
/
Other Consideratiaons
130.1 Electrical Noise Generators
Certain
equipment, such as welding machines,
thyrister-driven power supplies, large electrical motors, etc.
generate electrical noise. As a stored program machine the
Electra-616 System is vulnerable to this noise. When this type of machine is present at an instahation, the following precautionary steps are urged:
Locate KSU, telephone sets, and cabling away from
1. these machines.
2. If cables must pass near these machines, use shielded cabIe with the shield grounded.
3. Ensure all machines of this type are well-grounded to a separate ground to minimize noise interference.
130.2
Pre-installation Site Survey
Since a pre-installation survey is generally required
to plan for application and installation, a check of the
matters covered so far in this section at this time will pre-
vent later problems.
130.3 Additional Equipment
In addition to electronic station equipment and the KSU and their contents, other equipment is required. This includes cables, modular connecting jacks, quick­connect blocks (or smimlar apparatus), etc. This additional equipment must be locally supplied.
140 Specifications
140.1 System Capacity
The Electra-616 system capacity is as follows: CO/PBX Lines Intercom Paths Internal and External Paging Station Sets BLF Consoles
Path
6max.
2 max. 1 max.
16 max.
2 max.
Door Phones 2 max.
140.2 Cabling Requirements
1.
Cabling required for Key Telephone Sets, BLF Con­soles, Door Phones is as follows:
1) Required Cable
-
Key Telephone Set: Twisted 2-pair cable
-
BLF Console:
-
Door Phone:
Twisted 1 -pair cable Twisted 1 -pair cable
2) Maximum Loop Resistance and Cable Length at 24AWG
-
Key Telephone Set: 40 ohms, 700 ft. (21Om)
-
BLF Console:
-
Door Phone:
40 ohms, 700 ft. (21Om) 40 ohms, 700 ft. (210m)
3) Maximum Cable Length at 22AWG
*
Key Telephone Set: 1,150 ft. (35Om)
-
BLF Console:
-
Door Phone:
1,150 ft. (35Om) 1,150 ft. (35Om)
- “g-‘ : >;
a;
3
. ..+
.5>
__._
‘P
^
‘2:
.+iy
:,.
:ig;
‘?:9
._>.
;y
,’
Lt..
:;
:
x
.k.
7,
Page 100-2
2. BLF Consoles require a local power supply (provided with each unit), which plugs into a 117V AC outlet. The cable provided with these units is 6 feet in length.
I
3. Fuse Replacement
Replace fuses in accordance with Table 140- 1.
Table
140-l Fuse Specifications For PS-6-1 and KSI-S
(~__-___-.~-___./
Note:
7his is NOTa recommendation that more than one
set of protectors be installed on CO lines at instaila-
tion premises. Improper installation of additional
protection can be a serious safety hazard.
. .
‘*a
Note 1: FI is 1/4”x I-1/4”size normal blown glass tube or
ceramic fuse. Buss 3A G 125 V., 4A fuse.
Note2:
140.3 Power Requirements
KSI-S Fl - F8 are 13/64” c 45164” (S mm x 20 mm) size normal blown glass tube fuse. Buss GMA I25 V., O.SA fuse.
Do not install any ‘slow blow” fuses in the ES-6-I KSU.
1. AC Input
- 117V
AC f 1 O%, SO or 60Hz + 1 O%, single phase
. Max. current draw: 4.OA
*
Dedicated outlet separately fused at 15A max.
2. Power Supply Outputs (PS-6 - 1)
DC Voltage
+5v + 0.25v
+12v 5 O.5V
+24V it 1 .QV
+41v * l.OV
Max. current
4.OA
1.2A
2.OA
1.4A
3. BLF Console Power Supply
Output Voltage: Max. Output Current:
140.4 Surge Protection
9vDC
0.3A
If an installation is subject to AC power surges it is recommended that the most effective locally available form of surge protection be supplied. CO Lines are protected by the local operating (telephone) company. It is recommend­ed that the most effective locally available form of protec­tion be installed on CO/PBX lines by the local operating (telephone) company.
140.5
Environmental Conditions
1. Temperature: pperating:
+32” F- 104°F (O”C-
40°C)
Recommended long term: +50”F- 90°F
2. Humidity:
Operating 10 - 90 percent
140.6 CO/PBX
Line Type
CO/PBX Line Type: 2 wire, loop start
140.7 Dimensions and Weight
ES-6-I KSU W/PSU
ET-6-I TEL
490(W) x 195S(D)x 421(H)mm, 40 Lbs (I 8kg)
210(W) x 222(D) x 82(H)mm,
2.9 Lbs (1300g)
EB-6-1 BLF
75(W) x 222(D) x 82(H)mm,
1.3 Lbs (600g)
DP-6-1 Door Phone
140.8 Network and Control
100(W) x 132(D) x 31.5(H)mm,
0.4 Lbs (200g)
1. Control
.
Control:
.
Central processor:
.
Microprocessor in keyset:
Stored program 8085A pCOM43N (4 bit one-
chip microcomputer)
.
Clock (KSU-keyset):
.
Transmission data:
33kHz 9 bits
(from KSU to keyset)
.
Scanning time for each
Every SO msec.
keyset:
.
Number of cable pairs from 2 pair wire for keyset
KSU to each station:
.
For keyset, one pair:
Voice and signalling
one pair: Data sending and re-
ceiving
.
For Door Phone, one pair: Voice and signalling
.
For BLF, one pair:
Data receiving
Page 100-3
2.
Network
-
Matrix:
Single stage, non block­ing C-MOS switch ar-
ray
. Keyset network:
Electronic circuit using
custom LSI (Equivalent
to 500 type standard network)
- Transmitter and Receiver
:
Dynamic type (Equivalent to 500 type standard telephone transmitter and receiver)
3. Transmission
- Cross talk attenuation:
More than 75 dB for
300-3, SOOkHz
- Insertion loss,
station to trunk:
140.9 Visual and Audible
Less than 1.8 dB at
IkHZ
Indications
1. Visual
Lamp indications of a Keyset are as follows:
* Idle condition:
-
Busy CO/PBX and
Not lit
Steady light
intercom path:
-
Incoming CO/PBX and
Flashing light at 601PM
intercom call:
* Call hold CO/PBX:
Winking light at
‘120IPM
-
I-Hold indication
Intermittent wink light
(CO/PBX):
* Hold reminder:
2. Audible Indication
I) CO/PBX call
-
Incoming call on CO/PBX (idle):
Flashing light at 6OOIPM
483Hz/64SHz modu­lated by lOHz, 1
ON/1 sec. OFF
*
Incoming call on
CO/PBX (Receiver off
hook):
*
Hold reminder:
1200Hz/580Hz
1200Hz,
0.5 sec. ON/O.5 sec. OFF
sec.
2)
Intercom call
-
Calling signal for
called station:
* Ringback tone:
-
Busy tone:
- Call waiting tone:
- Override tone:
-
Error tone:
* Store speed dial tone:
140.10 Dialing Spxification
1.
Dial Pulse Address Signalling
a) Pulse rate:
b) Percent break:
c) Interdigital interval:
2. DTMF Address Signalling
Frequencies:
a>
Nominal Low Group
Frequencies (Hz) 852 7
Frequency deviation:
Voice signaIling after tone burst (580Hz,
0.75 sec.) 580Hz,O.75 sec. 580Hz,
0.5 sec. ON/OS sec. OFF
1200Hz,
0.5 sec. ON/O.5 sec. OFF
58OHz, 0.75 sec.
1200Hz,
0.25 sec. ON/O.25 sec.
OFF
580Hz
10 pps or 20 ppS
61 t 3 percent
800 msec.
Two sinusoidal signals, one from a high group of three frequencies and one from a low group of four frequen-
cies.
Nominal High Group
Frequencies (Hz)
1209 1336 1477
---
69J 1 2 3
770 4
5 6 8 9
w*
0
Within * 1.5%
7
#
Page 100-4
.-,_ ,.
c) Signal level
d) Duration of two
e) Interdigital time:
3. Dialing Memories
a) Last COjPBX Number
b) Speed Dialing-Station:
c) Speed Dialing-System:
140.11
1.
External Paging
-
?
-
2. Output to External Amplifier for External Paging
-
-
3. BGM Input to PBS-S
4. MOH Input
-
Minimum level per
frequency: Low group:
High group:
frequency signal:
Redial:
External Equipment Interfacing
Output power:
Required speaker inpedance:
Output power: Output impedance:
-
Input level:
-
Required output
impedance of
amplifier:
Input level
Required output
impedance of signal source
:
-1OdBm
- 8dBm
60 msec. min.
00 msec. min.
16 digits max.
(including pause)
16 numbers (16 digits,
including any pauses)
4q numbers (16 digits, including any pauses)
1 watt
600 ohms
-1.5 dBm 600 ohms
1
watt (nominal)
600 ohms
lm watt (nominal)/8
ohms 8 ohms
150
150.1 General Information
List of Equipment
1. The Key Service Unit (ES-6-1 KSU) comes equipped with two common control cards {CPU-S KTU, CLK-S KTU), a power supply (PS-6-1 PSU), and an Installation Service Manual (ND- 173 14). A wall mounting bracket is also supplied for wall mounting the KSU. All other equipment must be ordered accord­ing to application requirements. All customer-provided optional equipment (external amplifier, MOH music source, speakers, etc.) must be locally provided.
150.2 Equipment Description
1.
ES-6-1 KSU (Key Service Unit) is the Key Service Unit. This steel cabinet houses two common cards, Power Supply and various Key Telephone Units (KTUs). It provides service for up to 6 CO/PBX lines,
16 Keysets, 2 Door Phones, 2 BLFs and various system
options.
2.
PS-6-1 PSU is the Power Supply required for the
ES-6-l KSU. The PS-6-
1 is
provided mounted in the ES-6-l KSU and supplies the required voltages to KTUs installed within, and station equipment con­nected to the ES-6-1 KSU.
3.
CPU-S KTU (Central Processing Key Telephone Unit) is composed of three sections: the Central Processor, The ROM section for storing the generic programmed instructions, and the RAM section for storing system configuration and day to day data. The CPU-S KTU conains an 8085A 8 bit microprocessor which ex­ecutes many different functions under the control sequence of programmed instructions stored in ROM. The CPU-S KTU is provided installed in the ES-6-l KSU.
CLK- I KTU (Clock Generator Key Telephone Unit) is
4. composed of 5 sections: The I/O section distributes the data signals sent to or from the CPU. It provides an amplifier for internal paging, clocking for rotary dial pulse signalling and a control circuit for external CO/PBX signal!ing. The Tone source section of the CLK generates the signal for COjPBX ringing in the system.
DCI-S KTU (Dial Pulse Converter Interface Key
5. Telephone Unit) provides circuits to serve up to 3 CO/PBX lines and contains circuitry for CO/PBX ring detection, hold and control functions. It also sends rotary dial pulse signalling to CO/PBX lines in accord­ance with dialing from keysets. A DCI-S KTU and a MFI -S KTU can be mixed in a system.
.
Page 100-5
6. MFI-S KTU (Dual-Tone Multip Frequency Interface Key Telephone Unit) provides circuits to serve up to 3 CO/PBX lines, and contains circuitry for CO/PBX ring detection, hold and control functions. It also sends DTMF dial signalling to CO/PBX lines in accordance with dialing from keysets. A MFI-S KTY and a DCI-S KTU can be mixed in a system.
. 7.
KSI-S KTU (Keyset Interface Key Telephone Unit) provides data control to the Electronic Key Telephone set (ET-6-l). Each KSI-S KTU provides circuits to serve up to 8 Electronic Key Telephone Sets.
SWM-S KTU (Switch Matrix Key Telephone Unit)
8. contains a 8 x 12 semi-conductor switching matrix for connection of keysets to CO/PBX lines, intercom paths, door phones, and paging trunks. Each SWM-S con­nects 8 keysets to 3 CO/PBX fines, 2 door phones, 2 intercom paths and internal and external paging trunks. Each SWM-S provides a talk battery supply for up to 8 ET-6- 1 Telephones.
ET-6- 1 Telephone is a fully-modular push button dial
9. electronic key telephone set with 35 nonlocking buttons, a 2 digit LED display and a speaker and micro­phone for voice page and handsfree answerback on ICM calls. 6 of the buttons are CO/PBX line buttons,
13 buttons are function buttons, and 16 buttons are used both for DSS (Direct Station Selection) and Station Speed Dialing. Each keyset requires 2 pair cabl­ing to the Main Distribution Frame (MDF).
AHR-S KTU (Automatic Hold Release Key Telephone
10. Unit) serves up to 6 CO/PBX lines. This option provides for restoration of a held line to idle status when the outside party abandons the call. A timed disconnect signal must be sent from the central office or PBX to activate this feature. One AHR-S KTU can be installed in the ES-6- 1 KSU for this feature.
When any combination of these features is
required in
the system, one PBS-S KTU must be installed in the ES-6-l KSU.
r-- --­j
I i-
12.
-----
Note:
7Yhis security feature should not he used a$ a
sOurce of protection.
failure, for example. will not result
cation.
-- --..-.-_-_.
A power otrtoge or component
prirrwry
in ,gn alarm indi_
DPH-S KTU (Door Phone Key Telephone Unit) contains amplifiers and voice switching circuits to provide a 2-way communication to keysets in the sys­tern. It can also be used as a monitor phone in areas where monitoring of audible activity is desired. This KTU can serve up to 2 door/monitor phones and can provide a tone to signal assigned keysets programmed to ring when the door phone is activated.
13.
DP-6-l Door Phone is a speaker unit with a speaker, microphone, and a control button to provide two-way communication to any keyset in the system. With the DPH-S KTU installed in the KSU up to two door phones can be connected at the Main Distribution Frame (MDF). One pair cabling is required for each door phone.
DB -6 - 1 BLF is a modular Electronic Busy Lamp Field
14
withe 21 LEDS. 16 LEDS show station status, 1 LED each shows paging status (both internal and external), Night Transfer, and BLF Power On status. 2 LEDs
show the status of the door phones. The EB-6- 1 comes equipped with a local power supply with a 117V AC plug and requires 1 pair cabling to the Main Distri­bution Frame (MDF).
. .
11
PBS-S KTU (External Paging/Busy Lamp Field/ Security Key Telephone Unit) provides circuitry for three optional features. It contains a l-watt amplifier and a control circuit for single-zone external paging. For applications where a l-watt amplifier is insuffi­cient, a locally provided high power amplifier may be used in addition to the PBS-S KTU. The Busy Lamp Field circuitry to detect a signal from an external source which activates an audible alarm in idle key­sets and a visual alarm in the display of all keysets. Two security circuits are provided for this purpose.
Page 100-6
160 System Configuration
160.1 To
Determine Required Equipment
1. Determine how many electronic key telephones are re­quired in the system. Refer to Table A if the number of keysets are 8 or less. Refer to Table B if the number of keysets are more than 8.
2. Determine how many CO/PBX lines are required. The result will tell you which line of the selected table to
use. See Table 160-l.
Table 160-l
TABLE A:
COIPBX LINES
I
160.2 To Determine Optional Equipment
Total Number of Keysets is 1 - 8
OCIS/MFIS
/
l-3
I
4-6
Note:
I
Power Failure hansfer is provided in ES-6-I KSU for CO/PBX Lines 1 and 2.
SWMS
/
1
1 1
/
I
2
KSI-S
1 t
I
1
1. Required KTUs for options are:
Required Quantities of KThls
TABLE B: Tota! Number of Keysets is 9 - 16
1 CO/PBX LINES
I
I
l-3
4-6
/
I
DCIWMFIS
2
1 svw-s
i
2
2 2
KSIS
I
.I
2
I
I
OPTION
Automatic Hold Release
Door Phone
External Paging
_-_--_+
t-
BLF Console
Security Alarm
Note:
One PBS-S KTU 2 security alarm circuits.
Table 160-2
AHR-S 1
DPH-S 1 2 Door Phones
PBS-S
PBS-S
PBS-S
provides circuits for external
I
1
!
1
1
paging.
2 BLF consoles, and
2 BLF Consoles
I
6
Page 100-7
/---
CQlP0X \
123
1 2
456
---_------__
-I I I I
1 I
I I I I I I
I
I I
I
I
DOOR PHONE 1 DOOR PHONE 2
EXT. SPEAKER
SECURITY CONTROL EQUIPMENT
SWM 2
[ 13 installed in ES&l KSU
Fig.
160-l
System Block Diagram
i
I I
PS-6-!
---I-l
I
I I
Page 100-8
SECTION
200

HARDWARE INSTALLATION

CONTENTS
Page
f
installation of the Key Service Unit
210.1
210.2
Wall Mounting the KSU
Floor Mounting the KSU
Connecting and Testing the Power Supply
Installation
230.1
230.2
230.3
230.4 230 5
MDF Installation
240.1
240.2
of KTUs
General Information
Installing Basic KTUs Installing Common KTUs Installing Optional KTUs
Volume Controls
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ZOO-6
CO/PBX Connection Station Cabling Connection
Installing Station Equipment
250.1
250.2 250 3
ET-6-l Installation EB-6-1 Installation DP-6-l installation
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 200-g
200-1
200-z
200-3
installing Options
260.1
260.2
260.3
260.4
260.5
260.6
260.7
260.8
260.9
Music On Hold External Paging Speaker
External Background Music when PBS-S KTU is Used External Tone Ringer External Paging Amplifier External Background Music when External Amplifier
is Used Power Failure Telephones Security Control Equipment External Amplifier Control
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
200-14
SECTION 200 HARDWARE INSTALLATION
. .
2
I (
210
210.1 Wall Mounting the KSU
1.
Installation of the
The ES -6-l
KSU is supplied with a wall mounting
Key
Service
Unit
bracket. The bracket should be mounted on a back­board secured in a manner capable of holding the weight of the KSU. With the mounting tabs of the bracket facing upward, install appropriate screws into the 6 holes of the bracket. Loosen the securing screw located in the upper right position of the bracket.
Align the mounting slots of the KSU with the mount-
2.
ing tabs of the bracket, and push down to seat the
KSU
securely.
Remove the front cover of the KSU, and locate and
3.
tighten the securing .screw through the hole provided above the J 1 connector.
SECURING SCREW \
\
0
210.2
Floor Mounting the KSU
The same bracket that is provided for wall mounting
1. can also be used to anchor a floor mounted KSU. Set
the bracket on a level surface with the 6 screw holes
down and the securing screw facing up and the floor
mounting slot to the right.
Loosen the securing screw located in the rear right
2. position of the bracket.
Engage the mounting tabs on the bracket into the slots
3.
on the bottom of the KSU and push forward to seat
the KSU securely.
Locate and tighten the securing screw through the hold
4. provided on the bottom panel of the KSU.
0
0
-
FLOOR MOUNTING SLOT
Fig. 210-l Front View of hbunting Bracket
Page
220 Connecting and Testing the Power Supply
Note 1:
Note 2: Before proceeding, ensure that the PS-6-I Power
1.
Remove the 9-pin connectorended cable of the power supply from the connector of the KSU.
2.
Plug the AC cord of the power supply into an AC outlet. Set PSU Power switch to on position. The PSU Power Indicator Lamp should to the figure below:
Verify that the AC outlet is supplying 11% AC and provides good conduit ground. If there is a problem with the AC voltage, have it corrected. If there is no conduit ground, provide alternate
ground as explained in Section 120, “Grounding Requirements”, of this manual.
Cord is unplugged. The PS-6-I Power Switch
should be off, and its power indicator lamps should
light.
Use a voltmeter,
+41v
7
+24V
t
1
03
I
I@/
e3
I
I@I
I I
cl3
e3
H
,
Fig. 220-2 View of TBI Terminal Block
When measuring DC voltages, note that each voltage has its own reference ground.
6. The Power Supply Switch must be set in the Offposi­tion before proceeding with installation.
+12v
+5v
+41G
+24G
+12G
+5G
+12G
+5G
I
Fig. 220-I Front View of g-pin Connector of PS-6-l
Set PSU Power Switch to Off Position
3.
Verify that step 3 has been completed before pro-
Note:
ceeding. Verify that PS-6-I Power Indicator Lamp
I
4.
5. Turn the PSU Power Switch on. DC voltage (under
is off:
Connect the 9-pin connectorended cable of the Power Supply Unit to the 9-pin connector of the KSU. Ensure that the looking tabs are engaged.
load) can now be read on the TBl terminal block located on the left side of KSU.
Note:
Veriyy that Step 6 has been completed before pro-
ceeding. Verify that PS-6-i Power indicator Lamp-
is oft
1
I
@)
Page 200-2
F--
230
230.1
1.
Installation of
Note: The following KTUs cannot be inserted or removed
with power on:
CPU-S
CLK-S
SWM-S
General Information
KTUs
KSI-S DPH-S DCI-S MFI-S
-_. _... .._ .._ _._. - .- .__J
PBS-S
AHR-S
The KTUs specified directly above cannot be inserted or removed -with power on. It is recommended that power be OFF during installation and during mainte­nance unless this will seriously inconvenience the user. This will prevent accidental damage to equipment.
are Smm by 20mm and are rated OSA 125V: one fuse for each keyset. The fuse provides protection on the data transmission pairs (DT and DR). When a fuse must be replaced refer to Section 140, “Fuse Replace­ment” of this manual.
3. SWM-SKTU An SWM -S KTU must always be installed in SWM 1.
An SWM-S KTU must be installed in SWM2 when either stations 9
- 16 and/or CO/PBX lines 4 - 6 are
to be connected.
Table 230-I
SWM -S
SLOT
Installing SWM-S KTUs
WHEN
T
The KTUs used in the Electra-616 system make ex­tensive use of CMOS technology. Care must be taken to avoid static discharge when handling these KTUs.
KTUs are provided with a guide slot to prevent mis­installation. KTU connectors are provided with a guide
key. These guide keys must not be removed.
230.2
Installing Basic MTUs
1
DC1 -S and MFI -S KTUs
When installing DCI-S and MFI-S KTUs there may
be more KTU circuits installed (since there are 3 per KTU) then will actually be used. Any non-used circuits should be programmed as “not installed” when pro­gramming for CO/PBX line assignment. See Section 300 “Programming”
of this manual for instructions on programming CO/PBX line assignment. This will avoid confusion when attempts to access unconnected CO/PBX lines are made. The DSI-S or MFI-S in the first designated KTU position (DCI/MFI 1) serve CO/ PBX lines 1 through 3. A DCI-S or MFI-S in the second designated KTU position (DCI/MFI 2) serve
CO/PBX lines 4 through 6. Refer to figure 230-2 for KTU positions in the Key Service Unit. See AHR-S KTU in Section 230 for information’on wiring change for providing Automatic Hold Release feature when AHR-S KTU is installed.
/ SWMl
SWM2
230.3 Installing &mmon KTUs
I.
/
For Stations 1
For Stations 9 -
CPU-S STU
- 8 and CO/PEX lines 1 - 3.
16 and/co CO/PBX lines 4 - 6.
Before programming the Network Plan Memory (NPM), ensure that the SW1 switch located on the CPU-S KTU is set to the ON position. This will provide battery back-up for the NPM, speed dial, and last number dialed memories when power is lost to the KSU. If there is a power failure and switch is left in the OFF position, the system will lose the contents of memory and return to the Resident System Program. For a description of the Resident System Program see Section 300 “Programming”. When the CPU-S KTU is removed for long-term storage, set the SW1 switch to the OFF position. This will prevent the battery from constantly discharging until it is no longer capable of holding a charge. The battery, when fully charged, will protect the memory for approximately 60 days.
back-up to the Electra-616 system during a power
failure.
I
KS1 -S KTU
2. There are two designated KS1 KTU positions within
the Key Service Unit. The KS1 -S in the first position (KS1 1) serves stations 1 through 8, while a KSI-S in the second position (KS1 2) serves stations 9 through
16. Located on each KS!-S KTU are 8 fuses which
Fig. 230-l
ON-
CPU-S Switch for Volatile Memory
-- OFF
SW1
Page
290-3
On the CPU-S KTU is a momentary switch for system reset. Depressing the reset switch causes any program changes to enter the working program and interrupts all system operation in progress.
D--M
2. CLK-S KTU
When DCI-S KTU(s) is installed ensure the switches SW1 and SW2 on the CLK-S KTU are set to appro-
priate positions. Refer to Table 230-2 below. The
switch settings are subject to the dialing specifications
of the CO or PBX. The switches have been set by the
manufacturer at 1Opps dial speed and at 39% make ratio.
Table 230-2
230.4
Rotary Dial Pulse Signalling Switch Settings
Dial Speed SW1
installing Optional KTUs
; :z; /
1. PBS-S KTU Install PBS-S KTU in ES-6-1 KSU when External
Paging,Busy Lamp Field and/or Security options are
required. Refer to Section 250.2 “EB-6-1 Installa-
tion” for BLF connection. When installing External Paging and/or Security options, see Section 260, Instal­ling Options”.
7
__ DPH-S KTU
When a DPH-S KTU is installed in the ES-6-l KSU, two DP-6-1 can be used as Door Phone or Monitor Phone separately. When Door Phone 1 is required as a Door Phone, set
the SW1 to the “D” position on the DPH-S KTU. (In the case of Door Phone 2, set the SW3 to the “D” position.) When Door Phone 1 is required as a Monitor Phone, set the SW1 to the “M” position on the DPH-S KTU. (In the case of Door Phone 2, set the SW3 to the “M” position.) and remove the straps Sl and S2 on the DPH-S KTU. (In the case of Door Phone 2, remove the straps S3 and S4). Then the voice from Key Set will be cut off when Door Phone is accessed, and the voice from DP-6-l is more amplified compared with
being used as Door Phone.
SW1
Fig. 230-2
Door Phone/Monitor Phone Select Switches
3. AHR-S KTU Located on each DCI-S and MFI-S KTUs are three
straps (one for each line circuit) that should be removed when AHR-S KTU is installed for Auto­matic Hold Release option. When AHR-S KTU is not installed, the straps should be left connected to the solder terminals. Refer to Figure 230-3 for terminal designations. The AHR-S will release a CO/PBX line which is on hold when the outside party abandons the call. A timed disconnect signal of more than 150 milli­seconds must be provided from the CO or PBX to enable this option (the AIIR-S does not recognize a reversal of polarity). The AHR-S KTU serves up to 6 CO/PBX lines and is installed in ES-6-l KSU. Remove the straps when AHR-S KTrJ is installed.
I
DCI-S 1
or
MFI-S 1
/
Line Circuit 3
Line Circuit 6
1
Page 200-4
Fig. 230-3
DCI-S and MFI-S AHR Straps
230.5 Volume Controls
1. AlI tones from the built-ii speaker in a keyset are controlled at the keyset by adjusting the volume dial located at the front of the keyset.
2.
System wide CO/PBX ring (station id!e) and intercom all call and zone paging are controlled by adjusting volume controls on the CLK-S KTU. Tone level is increased by turning the volume control clockwise.
All volumes are pre-adjusted by the manufacturer. Refer to Table 230-3.
Table 230-3 CLK Volume Controls
.ii,
L
TBl
---K
u
-
- I
OFF POWER FUSE
5A
- - -...-c2
-
-
-
n
N
3
z
a
8
4
J
-
-
8
2
;’
5
J
-
2
0
z
2
-
-
N
E
-
11
J2
Pl
:
J
L
I
Fig. 2304 ES-6-l KSU Card Layout
Page 200-5
- - ___-___-_
.%
-.
k&+.
240 MDF
240.1
The FCC approved USOC number for 50 position
1.
CO/PBX
Installation
Connection
miniature ribbon jack for connection of CO lines is IU21X. The CO lines are to be connected in sequence consecutively within this jack.
Use of 66BSO or 66M50 quick-connect type blocks is
+
2.
recommended for ease of trouble location and correc­tion. Use of bridging clips allows easy separation of
the system to determine cause of trouble.
PIN
26
1
27
2 2R
FUNCTION
1T
1R
2T
3. The following Table 240-1 gives complete information on 50 position connector pin number, lead function,
running
DCI/MFI slot:
240.2
Station
1. The following tables give complete information on KSU, cable, 50 position connection pin number, run­ning cable color, lead designation, station cable color,
intercom number assignment, KSI-S slot assignment, etc. for all stations. Refer to Table
Table 240-l
CO/PBX Connection Information
Pl Connector & Cable ES-6-l KSU
CABLE COLOR CiRCIJlT SLOT
WH-BL CO/PBX
BL-WH
WH-OR
OR-WH
CO/PBX
cable color, circuit designation, associated
Cabling Connection
240-2 and 240-3.
1
2
DCI/MFI
1
28 3T
3 3R
29
4T
4 4R
5T
,
5R
31 6T
6 6Fi
CO/PBX Connection:
I.
FCC approved connector USOC code is RJ21X. Connector-ended cable for CO/PBX lines to plug info ES-6-I KSU requires
2. Jack (Female) 50 position miniature ribbon connector.
WH-GN CO/PBX
GN-WH
WH-BR CO/PBX BR-WH
WH -SL SL-WH
The rest of PI Cable is spare and is
3
4
CO/PBX
5
not used.
DCI/.MF12
Page 200-6
Table 240-2 Station Connection Information
Jl - 52 Connectors and Cables ES-6-1 KSU
PIN
26 WH-EL
1
27
2
28
3 GN-WH
29
4
30 WH-SL
5 SL-WH
31
6 BL-RD
32 RD-OR
7
33 RD-GN
8 GN-RD
34 RD-BR
P
9 BR-RD
35 RD-SL
10 SL-RD
36 BK-BL 11 37 12 OR-BK
38 BK-GN 13 GN-BK
39 BK-BR
14
40 BK-SL
15 SL-BK
41
16 BL-YL
RUNNING
CABLE
BL-WH WH-OR OR-WH
WH-GN
WH-BR BR-WH
RD-BL
OR-RD
BL-BK BK-OR
BR-BK
YL-BL
STATION
CABLE
GN RD YL BK
GN RD YL BK
GN RD YL BK
GN
RD YL BK
GN RD YL BK
GN RD YL BK
GN RD YL BK
GN RD YL BK
KEY SET
LEADS
VT VR DT DR
VT VR DT DR
VT VR DT DR
VT VR DT DR
VT VR DT DR
VT VR DT
DR VT
VR DT DR
VT VR DT DR
SLOT
KSI
1
CABLE
Jl
(See Note)
STA.
1
(ATT)
STA.
2
STA.
3
STA.
4
STA.
5
STA.
6
STA.
7
STA.
8
SLOT
CABLE
(See
STA.
(ATT)
STA.
92
Note)
9
10
I----
STA.
17
STA.
12
KS!
STA.
15
STA.
16
Note: Two stations in rhe sysrem can be assigned as attendant srarions. Stations 1 and 9 are initialIy assigned
these positions. Sration 1 must be insralled for programming purposes.
Page 200-7
Table 240-3 Connector Running List
Pl
26 1T
1 1R BL-WH 1
27 2T
2 2R OR-WH 2
28 3T
3 3R GN-WH 3
29 4T WH-BR
4 4R BR-WH 4
30 5T WH-SL LIN
5R SL-WH 5
-6T _-_-__j.- . . . -.._
6R 1 BL-RD 1
32 RD-OR j
7
9 j
35 I
12 I
42 I
18 / GN-YL i
44 YL-BR /
19 BR-YL i
45 YL-SL
20 46 ._ssc-yL+.- VI-BL 21 BL-VI
22 48
47
23 49 e&._/_.___-.
24 BR-VI /
-50 + ____-. +- __. _-. v, _SL
25 I SL-VI :
WH-BL LIN
WH-OR LIN
WH-GN LIN
RD-BL
OR-RD /
/ BR-RD 1 / RD-SL /
1 OR-BK i
j YL-OR j 42
/
OR-VI
_-. -_-
VI -GN VI -OR
I
LIN
LIN
6
_._
26
1
27
2
28
3
29
4
30
5
31
6
32
7
33
8
34
9
35
IO
36
11
37
12
38
13
39
14 40 15
41
16
17
-­43
18
44
19
-­45
20
-_ 46
21
47
22
48
23
z-
24
--. 50
25
-
1VT
1VR
1DT 1DR 2VT
2VR
2DT
2DR 3VT
3VR
3DT
3DR 4VT
4VR
4DT
4DR
5VT
5VR
5DT
5DR
-­6VT
6VR 6DT 6DR 7VT 7VR
7DT
7DR
8VT
8VR
8DT
8DR 1BLT
1BLR
-.._- _..._
1 DVT
1 DVR
--_
1SE
1SEG MOH MOHG SKR SKRG
.._-_-.
BGM BGMG
_. .-..__...
ERA
ERB 1PFT 1PFR
_. _.
2PFT 2PER
Jl
WH-BL BL-WH WH-OR OR-WH WH-GN GN-WH WH-BR BR-WH WH-SL SL-WH RD-BL BL-RD RD-OR OR-RD RD-GN GN-RD RD-BR BR-RD RD-SL SL-RD BK-BL BL-BK BK-OR OR-BK BK-GN GN-BK BK-BR BR-BK BK-SL
SL-BK
YL-BL BL-YL YL-OR OR-YL
__-_-_-_
YL-GN GN-YL YL-BR BR-YL
---­YL-SL
SL-YL
VI-BL BL-VI VI -OR OR-VI
__._._.-_- .._.
VI-GN GN-VI VI-BR BR-VI VI-SL
SC-VI
TEL
1
TEL
2
TEL
3
TEL
4
TEL
5
TEL
6
TEL
TEL
8
BLF
1
-.--. -..-. ..- .
DOOR PHONE
1
SECURITY
MOH
EXT.
SPEAKER
--_-.----. -. BGM
--.-_--_ EXT. RINGER
CONTROL
POWER
FAILURE 1
__..-... ._ _--.
POWER
FAILURE 2
52
38 I 15VT BK-GN j
13 1 15VR 39 15DT, BK-ER ! 14 40
I
15 41
! 16DT I 1 16DR
‘6!--_.<
42 / 2BL.T j YL-OR j BLF
‘7 _I.?!% i. _.ck!_L... i.
23 49 / 24 ’
5o I 25 /
__~
GN-BK /
15DR / BR-SK /
16’0 1
16VR ; SL-BK i
-L-
BK-SL j
YL-BL / 16 BL-YL /
YL-GN / DOOR PHONE
/
GN-VI / VI-BR /
j BR-VI 1
/ VI-SL / I SL-VI ~
TEL
15
TEL
--
.-.--.----.--.
/
2
Page 200-8
250 IrkaIling Station Equipment
250.1 ET-6-l installation
The ET-6-l is a fully-modular electronic key tele­phone set. Each keyset requires 2pair cabling to the Main Distribution Frame (MDF). The maximum cable length is 700 ft. using standard 24 AWG cable and 1,150 ft. using standard 22 AWG cable. Refer to Section 140, “Cabling
Requirements”, of this manual. For keyset connection,
see Figures 250-I and 2.50-2 and Table 240-2.
STATION CABLE
DR (BK)
TO KSU
VR FIDI
VT (GN) _
a
Fig. 250-l Simplified Schematic - ET-6-7 Telephone Connection
J
VR VT DT
DR
ET-6-l TELEPHONE
MODULAR TERMINAL
Page 200-9
r
TO KSU
CABLE
_..._,.^ ..___ ___ _.....__..... -- .-.._ . -. ..__. -..
..-
-L,.-L-
Fig. 250-2
________--__
View of Modular Terminal for Connection of
J
MODULAR TERMINAL
ET-$-l Telephone
Page 200-10
?
&
2502 EB-6-l installation
The
EB-6 -1 is a modular electronic busy lamp field. Each unit is provided with a 9V DC 03A power supply for LED illumination. The power supply is to be plugged into a standard 117V AC outlet. Each BLF requires
1 -pair cabling to the main distribution frame (MDF). The maximum cable length is 700 ft. using standard 24 AWG cable and 1,150 ft. using standard 22 AWG cable. Refer to Section 140, “Cabling Requirements”, of this manual. For BLF connection, see Figures 250-3, 2504 and 250-S and Table 240-3.
RUNNING CABLE
BLR (BK)
TO KSU
BLT (Y L)
Fig.
2503
DR DT
EB-6-1 BLF
Simplified Schematic - EB-6-1 BLF Connection
Page 200-il
____..__
_._-
-
. . . . . ..- ._.--. _- .-_ ..I ._._
TO KSU
BLFCABLE
_-__-l-._-~-.C_~“~-~~
‘xL..?Au.-.. . . . . __.~,
I
I
MODULAR TERMINAL
I
I
_____-------
L
Fig. 2504 View of Modular Terminal for Connection of EB-6-1 BLF
-I
Page 200-12
TO POWER SUPPLY
/
Fig. 250-5 Power Supply Connection
EB-6-1
BLF
250.3 DP-6-1 Installation
The
DP-6-1 is a Door/Monitor phone unit. Each door phone requires 1 pair cabling to the Main Distribution Frame (MDF). The maximum cable length is 700 ft. using
standard 24 AWG cable and 1,150 ft. using standard 22 AWG cable. Refer to Section 140, “Cabling Requirements” of this manual. To prepare the door phone for wall mounting losen the set screw and remove the door phone unit from the mounting plate. Use the two screws provided or other appropriate fastners to fiiy connect to wall surface. For door phone cable connection, see Figure 2506 and Table 240-3. Refer to Section 340, ‘Programming Sheets” for Door Phone assignment.
SCREW SLOT POSITIONS
TO
Fig. 250-6
Rear View of DP-6-l Door Phone
Page 2m-13 ‘-_
260
installing Options
2605 External Paging Amplifier
260.1
Music On
Hold
Provision has been made to allow connection of a
locally provided external music source to provide Music-
On-Hold for held CO/PBX calls. Connection of the Music
Source is made at the Jl Block of the Main Distribution
Frame (MDF). The output signal level should be approxi-
mately 1 milliwatt with 8 ohms impedance. See Figure
260.3 and Table 240.3 for connection information to
260.2
External Paging Speaker
MDF .
When a PBS-S KTU is installed in the ES -6 - 1 KSU, external paging with meet-me answer can be provided. The PBS-S KTU contains a 1 -watt Amplifier and Control Circuit for one-zone paging (when a l-watt amplifier is insufficient, see Section 260.5.) The External Speaker should be locally-supplied in correspondence to the output impedance of 600 ohms. The Volume Control (VRl), located on the PBS-S, provides a way to increase or de­crease the output signal of the amplifier to the speakers. To adjust output signal, turn VR1 clockwise to increase signal, and counterclockwise to lower signal. An LED is provided on PBS-S KTU to indicate when paging is being used. When an External Page is answered (meet-me-answer), the PBS-S is released to allow access for another page. See Figure 2 60-3 and Table 240-3 for connection informa­tion to MDF.
The PBS-S
KTU contains a l-watt Amplifier and control circuit for external paging. For applications where 1 -watt is insufficient, an external amplifier may be used.
Provision has been made to allow connection of a locally­provided amplifier to the MDF for this purpose. The PBS-S KTU is required when an external amplifier is used. See Figure 2604 and Table 240-3 for connection information to the MDF.
260.6
External Background Music when External
Amplifier is Used
To provide for background music with an external
amplifier installed, set the SW4 switch
io
the “ON” posi­tion and the SW3 switch to the “OFF” position on the PBS-S KTU. When background music is not required set the SW3 switch to the “ON” position and the SW4 switch to the “OFF” position. Music will be cut off from the paging speakers when external paging is accessed. The output level and impedance of the music source should
match the input level and impedance of the external amplifier. See Figure 2604 and Table 240-3 for connec­tion information to the MDF.
c-.-..
ON
OFF
ON - - OFF
.
260.3 External Background Music when PBS-S KTU is
Used
When a PBS-S KTU is installed, an external locally­provided music source can be used to supply background music over the External Paging System. The recommended output of the music source is l-watt with 600 ohms im­pedance. When external paging is accessed music is cut off from the paging speaker. Connection is made on the Jl block of the MDF. See Figure 260-3 and Table 240-3 for connection information to MDF.
260.4 External Tone
Ringer
Provision has been made to allow connection of locally provided External Tone Ringer to supply common audible on all incoming CO/PBX calls. For this purpose a relay contact is prepared on the CLK-S KTlJ. which provides an interrupted closure (1 SEC. on/ 1 SEC. off) during the CO/PBX Ring Cycle. The signal of the tone ringer can be controlled by a locally provided control switch. See Figure 260-3 and Table 240-3 for connection information to MDF.
SW4
260-7
SW3
Fig. 260-I PBS-S Switches for BGM
Power
Failure Telephones
ET-6-l Ke:J Telephone Sets cannot be used to originate or answer calls during a commercial power failure. Locally-provided single line telephone sets can be installed for this purpose. The KSU provides automatic power failure for CO/PBX lines 1 and 2. No optional KTU is required. Connection of the Single Line Telephones is
made at the Jl block of the MDF. Single Line Telephones
with appropriate dials (rotary or DTMF) should be installed if the capability of dialing out during a power outage is desired. See Figtire 260-3 and Table 240-3 for connection information to MDF.
Page 200-14
26043 Security Control Equipment
260.9 External Amplifier Control
Provision has been made to allow connection of a locally-provided security control system. For this purpose the PBS-S KTU contains 2 individual control circuits that, when activiated, provide an audible alarm through all idle keyset speakers and a visual alarm on each keyset display. Each security circuit can be activiated by means of an external make (closed) or break (open) contact. The SW1 switch on the PBS-S KTU is used to set the desired break or make detection for security circuit one and the SW2 switch performs the same function for security circuit two.
For connection information to the MDF see Figure 260-3
and 260.4 and Table 240-3.
1M - - 18
piT=q
SW1
Fig. 260-2 PBS-S Security Control Switches
2M - - 20
p7i-l
SW2
A set of dry contacts is provided on the PBS-S KTU, which can be used to control an auxiliary relay for External Paging. Although this option is not required when an external amplifier is used, it may be desired in some applications. When an external page is activiated the EAS and EAM contacts are closed for the duration of the page. In the idle condition the closure is made between the EAS and EAB contacts. See Figure 2604 and Table 240-3 for connection information to the MDF.
Page 200 - 15
_. _. __.
-.- . .
CLK-S
Y L-BR
BR-Y L 1SEG
YLSL MOH
SL-YL MOHG
VI-BL SKR
BL-VI SKRG
VI-OR
OR-VI
1SE
BGM
BGMG
44
-oo-oo-
-o&a-
--Qc2Lo-
-o&o-
-o&o-
-4&o-
-oEoo-
-ocPoo-
-oEoo-
-o&*
-o&c
SECURITY 1 ACTIVATION CONTACT
---p&&i
EXTERNAL PAGING SPEAKERS (600.52)
POWER FAILURE CONNECTION FOR CO/PBX 1
VI-SL 2PFT
-o&*
25
-ac--Oo-
:
Jl BLOCK
OF MDF
(668-50 OR 66M-50)
Fig. 260-3 Connection of Optional Features
POWER FAILURE
CONNECTION
FOR COIPBX 2
..-
Page 200-16
Loading...
+ 62 hidden pages