chosen for mounting the central equipment (Key Service
unit>.
1. The KSU should normally be wall-mounted to protect
2. The KSU should not be located directly beneath pipes
3. The area in which the KSU is located must be free of:
Installation
Site Requirements
The following conditions should be met at the site
against accident or flooding. Where possible
use
of a
wooden backboard is recommended for this purpose.
due to the possibility of leaks or condensation causing
damage.
120.2 Grounding Requirements
The
KSU must be well-grounded. If a good conduit
ground is not present at the dedicated AC outlet, the
following steps should be taken:
1. Provide a suitable waterpipe ground in accordance with
the local operating (telephone) company procedures.
2. If no waterpipe is available, a ground rod should be
installed in accordance with local operating company
procedures.
3. In the case where a ground other than conduit ground
is used a grounding terminal is provided on the ES-6 -1
as shown below in Figure 120- 1.
corrosive or inflamable gases, excessive chemical or in-
dustrial dusts, and other materials which could cause
hazard to personnel or to the proper functioning of the
equipment.
‘1
4. Heat and humidity must be within the limits found in
Section 140 “Specifications” in this manual.
t’
5. Although its virtually noiseless operation allows a wide
choice of installation sites, care should be taken that
the KSU not present a hazard to office traffic. For
/
#
T
PS-6-l PSU
I I
//
purposed of economy a central location (to minimize
cabling) is often preferable.
720 Electrical and Ground Requirements
120.1 AC Power Requirements
1. They system should have a dedicated 117V AC outlet
separately fused for 15 AMPS.
2. The
AC
outlet should be a standard 12SV three-prong
type which provides conduit ground.
3. The AC power must be within the limits found in Section 140 “Secifications” in this manual.
4.
If the AC outlet is subject to power surges, it is recommended that the best locally available AC surge
protection be installed.
Fig. 120-l Qutsideview of ES-G-1
Page 108-l
/
130
Other Consideratiaons
130.1 Electrical Noise Generators
Certain
equipment, such as welding machines,
thyrister-driven power supplies, large electrical motors, etc.
generate electrical noise. As a stored program machine the
Electra-616 System is vulnerable to this noise. When this
type of machine is present at an instahation, the following
precautionary steps are urged:
Locate KSU, telephone sets, and cabling away from
1.
these machines.
2. If cables must pass near these machines, use shielded
cabIe with the shield grounded.
3. Ensure all machines of this type are well-grounded to a
separate ground to minimize noise interference.
130.2
Pre-installation Site Survey
Since a pre-installation survey is generally required
to plan for application and installation, a check of the
matters covered so far in this section at this time will pre-
vent later problems.
130.3 Additional Equipment
In addition to electronic station equipment and
the KSU and their contents, other equipment is required.
This includes cables, modular connecting jacks, quickconnect blocks (or smimlar apparatus), etc. This additional
equipment must be locally supplied.
140 Specifications
140.1 System Capacity
The Electra-616 system capacity is as follows:
CO/PBX Lines
Intercom Paths
Internal and External Paging
Station Sets
BLF Consoles
Path
6max.
2 max.
1 max.
16 max.
2 max.
Door Phones 2 max.
140.2 Cabling Requirements
1.
Cabling required for Key Telephone Sets, BLF Consoles, Door Phones is as follows:
1) Required Cable
-
Key Telephone Set: Twisted 2-pair cable
-
BLF Console:
-
Door Phone:
Twisted 1 -pair cable
Twisted 1 -pair cable
2) Maximum Loop Resistance and Cable Length at
24AWG
-
Key Telephone Set: 40 ohms, 700 ft. (21Om)
-
BLF Console:
-
Door Phone:
40 ohms, 700 ft. (21Om)
40 ohms, 700 ft. (210m)
3) Maximum Cable Length at 22AWG
*
Key Telephone Set: 1,150 ft. (35Om)
-
BLF Console:
-
Door Phone:
1,150 ft. (35Om)
1,150 ft. (35Om)
- “g-‘
: >;
a;
3
. ..+
.5>
__._
‘P
^
‘2:
.+iy
:,.
:ig;
‘?:9
._>.
;y
,’
Lt..
:;
:
x
.k.
7,
Page 100-2
2. BLF Consoles require a local power supply (provided
with each unit), which plugs into a 117V AC outlet.
The cable provided with these units is 6 feet in length.
I
3. Fuse Replacement
Replace fuses in accordance with Table 140- 1.
Table
140-l Fuse Specifications For PS-6-1 and KSI-S
(~__-___-.~-___./
Note:
7his is NOTa recommendation that more than one
set of protectors be installed on CO lines at instaila-
tion premises. Improper installation of additional
protection can be a serious safety hazard.
. .
‘*a
Note 1: FI is 1/4”x I-1/4”size normal blown glass tube or
ceramic fuse. Buss 3A G 125 V., 4A fuse.
Note2:
140.3 Power Requirements
KSI-S Fl - F8 are 13/64” c 45164” (S mm x 20
mm) size normal blown glass tube fuse. Buss GMA
I25 V., O.SA fuse.
Do not install any ‘slow blow” fuses in the ES-6-I
KSU.
1. AC Input
- 117V
AC f 1 O%, SO or 60Hz + 1 O%, single phase
. Max. current draw: 4.OA
*
Dedicated outlet separately fused at 15A max.
2. Power Supply Outputs (PS-6 - 1)
DC Voltage
+5v + 0.25v
+12v 5 O.5V
+24V it 1 .QV
+41v * l.OV
Max. current
4.OA
1.2A
2.OA
1.4A
3. BLF Console Power Supply
Output Voltage:
Max. Output Current:
140.4 Surge Protection
9vDC
0.3A
If an installation is subject to AC power surges it is
recommended that the most effective locally available form
of surge protection be supplied. CO Lines are protected by
the local operating (telephone) company. It is recommended that the most effective locally available form of protection be installed on CO/PBX lines by the local operating
(telephone) company.
140.5
Environmental Conditions
1. Temperature:
pperating:
+32” F- 104°F (O”C-
40°C)
Recommended long term: +50”F- 90°F
2. Humidity:
Operating 10 - 90 percent
140.6 CO/PBX
Line Type
CO/PBX Line Type: 2 wire, loop start
140.7 Dimensions and Weight
ES-6-I KSU
W/PSU
ET-6-I TEL
490(W) x 195S(D)x 421(H)mm,
40 Lbs (I 8kg)
210(W) x 222(D) x 82(H)mm,
2.9 Lbs (1300g)
EB-6-1 BLF
75(W) x 222(D) x 82(H)mm,
1.3 Lbs (600g)
DP-6-1
Door Phone
140.8 Network and Control
100(W) x 132(D) x 31.5(H)mm,
0.4 Lbs (200g)
1. Control
.
Control:
.
Central processor:
.
Microprocessor in keyset:
Stored program
8085A
pCOM43N (4 bit one-
chip microcomputer)
.
Clock (KSU-keyset):
.
Transmission data:
33kHz
9 bits
(from KSU to keyset)
.
Scanning time for each
Every SO msec.
keyset:
.
Number of cable pairs from 2 pair wire for keyset
KSU to each station:
.
For keyset, one pair:
Voice and signalling
one pair: Data sending and re-
ceiving
.
For Door Phone, one pair: Voice and signalling
.
For BLF, one pair:
Data receiving
Page 100-3
2.
Network
-
Matrix:
Single stage, non blocking C-MOS switch ar-
ray
. Keyset network:
Electronic circuit using
custom LSI (Equivalent
to 500 type standard
network)
- Transmitter and
Receiver
:
Dynamic type
(Equivalent to 500 type
standard telephone
transmitter and
receiver)
3. Transmission
- Cross talk attenuation:
More than 75 dB for
300-3, SOOkHz
- Insertion loss,
station to trunk:
140.9 Visual and Audible
Less than 1.8 dB at
IkHZ
Indications
1. Visual
Lamp indications of a Keyset are as follows:
* Idle condition:
-
Busy CO/PBX and
Not lit
Steady light
intercom path:
-
Incoming CO/PBX and
Flashing light at 601PM
intercom call:
* Call hold CO/PBX:
Winking light at
‘120IPM
-
I-Hold indication
Intermittent wink light
(CO/PBX):
* Hold reminder:
2. Audible Indication
I) CO/PBX call
-
Incoming call on
CO/PBX (idle):
Flashing light at
6OOIPM
483Hz/64SHz modulated by lOHz, 1
ON/1 sec. OFF
*
Incoming call on
CO/PBX (Receiver off
hook):
*
Hold reminder:
1200Hz/580Hz
1200Hz,
0.5 sec. ON/O.5 sec.
OFF
sec.
2)
Intercom call
-
Calling signal for
called station:
* Ringback tone:
-
Busy tone:
- Call waiting tone:
- Override tone:
-
Error tone:
* Store speed dial tone:
140.10 Dialing Spxification
1.
Dial Pulse Address Signalling
a) Pulse rate:
b) Percent break:
c) Interdigital interval:
2. DTMF Address Signalling
Frequencies:
a>
Nominal
Low Group
Frequencies (Hz) 852 7
Frequency deviation:
Voice signaIling after
tone burst (580Hz,
0.75 sec.)
580Hz,O.75 sec.
580Hz,
0.5 sec. ON/OS sec.
OFF
1200Hz,
0.5 sec. ON/O.5 sec.
OFF
58OHz, 0.75 sec.
1200Hz,
0.25 sec. ON/O.25 sec.
OFF
580Hz
10 pps or 20 ppS
61 t 3 percent
800 msec.
Two sinusoidal signals,
one from a high group
of three frequencies
and one from a low
group of four frequen-
cies.
Nominal High Group
Frequencies (Hz)
1209 1336 1477
---
69J 1 2 3
770 4
5 6
8 9
w*
0
Within * 1.5%
7
#
Page 100-4
.-,_ ,.
c) Signal level
d) Duration of two
e) Interdigital time:
3. Dialing Memories
a) Last COjPBX Number
b) Speed Dialing-Station:
c) Speed Dialing-System:
140.11
1.
External Paging
-
?
-
2. Output to External Amplifier for External Paging
-
-
3. BGM Input to PBS-S
4. MOH Input
-
Minimum level per
frequency:
Low group:
High group:
frequency signal:
Redial:
External Equipment Interfacing
Output power:
Required speaker
inpedance:
Output power:
Output impedance:
-
Input level:
-
Required output
impedance of
amplifier:
Input level
Required output
impedance of signal
source
:
-1OdBm
- 8dBm
60 msec. min.
00 msec. min.
16 digits max.
(including pause)
16 numbers (16 digits,
including any pauses)
4q numbers (16 digits,
including any pauses)
1 watt
600 ohms
-1.5 dBm
600 ohms
1
watt (nominal)
600 ohms
lm watt (nominal)/8
ohms
8 ohms
150
150.1 General Information
List of Equipment
1. The Key Service Unit (ES-6-1 KSU) comes equipped
with two common control cards {CPU-S KTU,
CLK-S KTU), a power supply (PS-6-1 PSU), and an
Installation Service Manual (ND- 173 14). A wall
mounting bracket is also supplied for wall mounting
the KSU. All other equipment must be ordered according to application requirements. All customer-provided
optional equipment (external amplifier, MOH music
source, speakers, etc.) must be locally provided.
150.2 Equipment Description
1.
ES-6-1 KSU (Key Service Unit) is the Key Service
Unit. This steel cabinet houses two common cards,
Power Supply and various Key Telephone Units
(KTUs). It provides service for up to 6 CO/PBX lines,
16 Keysets, 2 Door Phones, 2 BLFs and various system
options.
2.
PS-6-1 PSU is the Power Supply required for the
ES-6-l KSU. The PS-6-
1 is
provided mounted in the
ES-6-l KSU and supplies the required voltages to
KTUs installed within, and station equipment connected to the ES-6-1 KSU.
3.
CPU-S KTU (Central Processing Key Telephone Unit)
is composed of three sections: the Central Processor,
The ROM section for storing the generic programmed
instructions, and the RAM section for storing system
configuration and day to day data. The CPU-S KTU
conains an 8085A 8 bit microprocessor which executes many different functions under the control
sequence of programmed instructions stored in ROM.
The CPU-S KTU is provided installed in the ES-6-l
KSU.
CLK- I KTU (Clock Generator Key Telephone Unit) is
4.
composed of 5 sections: The I/O section distributes the
data signals sent to or from the CPU. It provides an
amplifier for internal paging, clocking for rotary dial
pulse signalling and a control circuit for external
CO/PBX signal!ing. The Tone source section of the
CLK generates the signal for COjPBX ringing in the
system.
DCI-S KTU (Dial Pulse Converter Interface Key
5.
Telephone Unit) provides circuits to serve up to 3
CO/PBX lines and contains circuitry for CO/PBX ring
detection, hold and control functions. It also sends
rotary dial pulse signalling to CO/PBX lines in accordance with dialing from keysets. A DCI-S KTU and a
MFI -S KTU can be mixed in a system.
.
Page 100-5
6. MFI-S KTU (Dual-Tone Multip Frequency Interface
Key Telephone Unit) provides circuits to serve up to 3
CO/PBX lines, and contains circuitry for CO/PBX ring
detection, hold and control functions. It also sends
DTMF dial signalling to CO/PBX lines in accordance
with dialing from keysets. A MFI-S KTY and a DCI-S
KTU can be mixed in a system.
. 7.
KSI-S KTU (Keyset Interface Key Telephone Unit)
provides data control to the Electronic Key Telephone
set (ET-6-l). Each KSI-S KTU provides circuits to
serve up to 8 Electronic Key Telephone Sets.
SWM-S KTU (Switch Matrix Key Telephone Unit)
8.
contains a 8 x 12 semi-conductor switching matrix for
connection of keysets to CO/PBX lines, intercom paths,
door phones, and paging trunks. Each SWM-S connects 8 keysets to 3 CO/PBX fines, 2 door phones, 2
intercom paths and internal and external paging
trunks. Each SWM-S provides a talk battery supply for
up to 8 ET-6- 1 Telephones.
ET-6- 1 Telephone is a fully-modular push button dial
9.
electronic key telephone set with 35 nonlocking
buttons, a 2 digit LED display and a speaker and microphone for voice page and handsfree answerback on
ICM calls. 6 of the buttons are CO/PBX line buttons,
13 buttons are function buttons, and 16 buttons are
used both for DSS (Direct Station Selection) and
Station Speed Dialing. Each keyset requires 2 pair cabling to the Main Distribution Frame (MDF).
AHR-S KTU (Automatic Hold Release Key Telephone
10.
Unit) serves up to 6 CO/PBX lines. This option provides
for restoration of a held line to idle status when the
outside party abandons the call. A timed disconnect
signal must be sent from the central office or PBX to
activate this feature. One AHR-S KTU can be installed
in the ES-6- 1 KSU for this feature.
When any combination of these features is
required in
the system, one PBS-S KTU must be installed in the
ES-6-l KSU.
r-- --j
I
i-
12.
-----
Note:
7Yhis security feature should not he used a$ a
sOurce of protection.
failure, for example. will not result
cation.
-- --..-.-_-_.
A power otrtoge or component
prirrwry
in ,gn alarm indi_
DPH-S KTU (Door Phone Key Telephone Unit)
contains amplifiers and voice switching circuits to
provide a 2-way communication to keysets in the systern. It can also be used as a monitor phone in areas
where monitoring of audible activity is desired. This
KTU can serve up to 2 door/monitor phones and can
provide a tone to signal assigned keysets programmed
to ring when the door phone is activated.
13.
DP-6-l Door Phone is a speaker unit with a speaker,
microphone, and a control button to provide two-way
communication to any keyset in the system. With the
DPH-S KTU installed in the KSU up to two door
phones can be connected at the Main Distribution
Frame (MDF). One pair cabling is required for each
door phone.
DB -6 - 1 BLF is a modular Electronic Busy Lamp Field
14
withe 21 LEDS. 16 LEDS show station status, 1 LED
each shows paging status (both internal and external),
Night Transfer, and BLF Power On status. 2 LEDs
show the status of the door phones. The EB-6- 1
comes equipped with a local power supply with a 117V
AC plug and requires 1 pair cabling to the Main Distribution Frame (MDF).
. .
11
PBS-S KTU (External Paging/Busy Lamp Field/
Security Key Telephone Unit) provides circuitry for
three optional features. It contains a l-watt amplifier
and a control circuit for single-zone external paging.
For applications where a l-watt amplifier is insufficient, a locally provided high power amplifier may be
used in addition to the PBS-S KTU. The Busy Lamp
Field circuitry to detect a signal from an external
source which activates an audible alarm in idle keysets and a visual alarm in the display of all keysets.
Two security circuits are provided for this purpose.
Page 100-6
160 System Configuration
160.1 To
Determine Required Equipment
1. Determine how many electronic key telephones are required in the system. Refer to Table A if the number
of keysets are 8 or less. Refer to Table B if the number
of keysets are more than 8.
2. Determine how many CO/PBX lines are required. The
result will tell you which line of the selected table to
use. See Table 160-l.
Table 160-l
TABLE A:
COIPBX LINES
I
160.2 To Determine Optional Equipment
Total Number of Keysets is 1 - 8
OCIS/MFIS
/
l-3
I
4-6
Note:
I
Power Failure hansfer is provided in ES-6-I KSU for CO/PBX Lines 1 and 2.
SWMS
/
1
1 1
/
I
2
KSI-S
1
t
I
1
1. Required KTUs for options are:
Required Quantities of KThls
TABLE B: Tota! Number of Keysets is 9 - 16
1 CO/PBX LINES
I
I
l-3
4-6
/
I
DCIWMFIS
2
1 svw-s
i
2
2 2
KSIS
I
.I
2
I
I
OPTION
Automatic Hold Release
Door Phone
External Paging
_-_--_+
t-
BLF Console
Security Alarm
Note:
One PBS-S KTU
2 security alarm circuits.
Table 160-2
AHR-S 1
DPH-S 1 2 Door Phones
PBS-S
PBS-S
PBS-S
provides circuits for external
I
1
!
1
1
paging.
2 BLF consoles, and
2 BLF Consoles
I
6
Page 100-7
/---
CQlP0X \
123
1
2
456
---_------__
-I
I
I
I
1
I
I
I
I
I
I
I
I
I
I
I
I
DOOR PHONE 1
DOOR PHONE 2
EXT. SPEAKER
SECURITY
CONTROL
EQUIPMENT
SWM 2
[ 13 installed in ES&l KSU
Fig.
160-l
System Block Diagram
i
I I
PS-6-!
---I-l
I
I
I
Page 100-8
SECTION
200
HARDWARE INSTALLATION
CONTENTS
Page
210
220
230
f
240
250
installation of the Key Service Unit
210.1
210.2
Wall Mounting the KSU
Floor Mounting the KSU
Connecting and Testing the Power Supply
Installation
230.1
230.2
230.3
230.4
230 5
MDF Installation
240.1
240.2
of KTUs
General Information
Installing Basic KTUs
Installing Common KTUs
Installing Optional KTUs
bracket. The bracket should be mounted on a backboard secured in a manner capable of holding the
weight of the KSU. With the mounting tabs of the
bracket facing upward, install appropriate screws into
the 6 holes of the bracket. Loosen the securing screw
located in the upper right position of the bracket.
Align the mounting slots of the KSU with the mount-
2.
ing tabs of the bracket, and push down to seat the
KSU
securely.
Remove the front cover of the KSU, and locate and
3.
tighten the securing .screw through the hole provided
above the J 1 connector.
SECURING SCREW \
\
0
210.2
Floor Mounting the KSU
The same bracket that is provided for wall mounting
1.
can also be used to anchor a floor mounted KSU. Set
the bracket on a level surface with the 6 screw holes
down and the securing screw facing up and the floor
mounting slot to the right.
Loosen the securing screw located in the rear right
2.
position of the bracket.
Engage the mounting tabs on the bracket into the slots
3.
on the bottom of the KSU and push forward to seat
the KSU securely.
Locate and tighten the securing screw through the hold
4.
provided on the bottom panel of the KSU.
’
0
0
-
FLOOR MOUNTING SLOT
Fig. 210-l Front View of hbunting Bracket
Page
220 Connecting and Testing the Power Supply
Note 1:
Note 2: Before proceeding, ensure that the PS-6-I Power
1.
Remove the 9-pin connectorended cable of the power
supply from the connector of the KSU.
2.
Plug the AC cord of the power supply into an AC
outlet. Set PSU Power switch to on position. The PSU
Power Indicator Lamp should
to the figure below:
Verify that the AC outlet is supplying 11% AC
and provides good conduit ground. If there is a
problem with the AC voltage, have it corrected.
If there is no conduit ground, provide alternate
ground as explained in Section 120, “Grounding
Requirements”, of this manual.
Cord is unplugged. The PS-6-I Power Switch
should be off, and its power indicator lamps should
light.
Use a voltmeter,
+41v
7
+24V
t
1
03
I
I@/
e3
I
I@I
I I
cl3
e3
H
,
Fig. 220-2 View of TBI Terminal Block
When measuring DC voltages, note that each voltage has
its own reference ground.
6. The Power Supply Switch must be set in the Offposition before proceeding with installation.
+12v
+5v
+41G
+24G
+12G
+5G
+12G
+5G
I
Fig. 220-I Front View of g-pin Connector of PS-6-l
Set PSU Power Switch to Off Position
3.
Verify that step 3 has been completed before pro-
Note:
ceeding. Verify that PS-6-I Power Indicator Lamp
I
4.
5. Turn the PSU Power Switch on. DC voltage (under
is off:
Connect the 9-pin connectorended cable of the Power
Supply Unit to the 9-pin connector of the KSU. Ensure
that the looking tabs are engaged.
load) can now be read on the TBl terminal block
located on the left side of KSU.
Note:
Veriyy that Step 6 has been completed before pro-
ceeding. Verify that PS-6-i Power indicator Lamp-
is oft
1
I
@)
Page 200-2
F--
230
230.1
1.
Installation of
Note: The following KTUs cannot be inserted or removed
with power on:
CPU-S
CLK-S
SWM-S
General Information
KTUs
KSI-S DPH-S
DCI-S
MFI-S
-_. _... .._ .._ _._. - .- .__J
PBS-S
AHR-S
The KTUs specified directly above cannot be inserted
or removed -with power on. It is recommended that
power be OFF during installation and during maintenance unless this will seriously inconvenience the user.
This will prevent accidental damage to equipment.
are Smm by 20mm and are rated OSA 125V: one
fuse for each keyset. The fuse provides protection on
the data transmission pairs (DT and DR). When a fuse
must be replaced refer to Section 140, “Fuse Replacement” of this manual.
3. SWM-SKTU
An SWM -S KTU must always be installed in SWM 1.
An SWM-S KTU must be installed in SWM2 when
either stations 9
- 16 and/or CO/PBX lines 4 - 6 are
to be connected.
Table 230-I
SWM -S
SLOT
Installing SWM-S KTUs
WHEN
T
The KTUs used in the Electra-616 system make extensive use of CMOS technology. Care must be taken
to avoid static discharge when handling these KTUs.
KTUs are provided with a guide slot to prevent misinstallation. KTU connectors are provided with a guide
key. These guide keys must not be removed.
230.2
Installing Basic MTUs
1
DC1 -S and MFI -S KTUs
When installing DCI-S and MFI-S KTUs there may
be more KTU circuits installed (since there are 3 per
KTU) then will actually be used. Any non-used circuits
should be programmed as “not installed” when programming for CO/PBX line assignment. See Section
300 “Programming”
of this manual for instructions
on programming CO/PBX line assignment. This will
avoid confusion when attempts to access unconnected
CO/PBX lines are made. The DSI-S or MFI-S in the
first designated KTU position (DCI/MFI 1) serve CO/
PBX lines 1 through 3. A DCI-S or MFI-S in the
second designated KTU position (DCI/MFI 2) serve
CO/PBX lines 4 through 6. Refer to figure 230-2 for
KTU positions in the Key Service Unit. See AHR-S
KTU in Section 230 for information’on wiring change
for providing Automatic Hold Release feature when
AHR-S KTU is installed.
/ SWMl
SWM2
230.3 Installing &mmon KTUs
I.
/
For Stations 1
For Stations 9 -
CPU-S STU
- 8 and CO/PEX lines 1 - 3.
16 and/co CO/PBX lines 4 - 6.
Before programming the Network Plan Memory (NPM),
ensure that the SW1 switch located on the CPU-S
KTU is set to the ON position. This will provide
battery back-up for the NPM, speed dial, and last
number dialed memories when power is lost to the
KSU. If there is a power failure and switch is left in
the OFF position, the system will lose the contents of
memory and return to the Resident System Program.
For a description of the Resident System Program see
Section 300 “Programming”. When the CPU-S KTU
is removed for long-term storage, set the SW1 switch
to the OFF position. This will prevent the battery from
constantly discharging until it is no longer capable of
holding a charge. The battery, when fully charged,
will protect the memory for approximately 60 days.
back-up to the Electra-616 system during a power
failure.
I
KS1 -S KTU
2.
There are two designated KS1 KTU positions within
the Key Service Unit. The KS1 -S in the first position
(KS1 1) serves stations 1 through 8, while a KSI-S in
the second position (KS1 2) serves stations 9 through
16. Located on each KS!-S KTU are 8 fuses which
Fig. 230-l
ON-
CPU-S Switch for Volatile Memory
-- OFF
SW1
Page
290-3
On the CPU-S KTU is a momentary switch for system
reset. Depressing the reset switch causes any program
changes to enter the working program and interrupts
all system operation in progress.
D--M
2. CLK-S KTU
When DCI-S KTU(s) is installed ensure the switches
SW1 and SW2 on the CLK-S KTU are set to appro-
priate positions. Refer to Table 230-2 below. The
switch settings are subject to the dialing specifications
of the CO or PBX. The switches have been set by the
manufacturer at 1Opps dial speed and at 39% make
ratio.
Table 230-2
230.4
Rotary Dial Pulse Signalling Switch Settings
Dial Speed SW1
installing Optional KTUs
; :z; /
1. PBS-S KTU
Install PBS-S KTU in ES-6-1 KSU when External
Paging,Busy Lamp Field and/or Security options are
required. Refer to Section 250.2 “EB-6-1 Installa-
tion” for BLF connection. When installing External
Paging and/or Security options, see Section 260, Installing Options”.
7
__ DPH-S KTU
When a DPH-S KTU is installed in the ES-6-l KSU,
two DP-6-1 can be used as Door Phone or Monitor
Phone separately.
When Door Phone 1 is required as a Door Phone, set
the SW1 to the “D” position on the DPH-S KTU.
(In the case of Door Phone 2, set the SW3 to the
“D” position.)
When Door Phone 1 is required as a Monitor Phone,
set the SW1 to the “M” position on the DPH-S KTU.
(In the case of Door Phone 2, set the SW3 to the “M”
position.) and remove the straps Sl and S2 on the
DPH-S KTU. (In the case of Door Phone 2, remove
the straps S3 and S4). Then the voice from Key Set
will be cut off when Door Phone is accessed, and the
voice from DP-6-l is more amplified compared with
being used as Door Phone.
SW1
Fig. 230-2
Door Phone/Monitor Phone
Select Switches
3. AHR-S KTU
Located on each DCI-S and MFI-S KTUs are three
straps (one for each line circuit) that should be
removed when AHR-S KTU is installed for Automatic Hold Release option. When AHR-S KTU is not
installed, the straps should be left connected to the
solder terminals. Refer to Figure 230-3 for terminal
designations. The AHR-S will release a CO/PBX line
which is on hold when the outside party abandons the
call. A timed disconnect signal of more than 150 milliseconds must be provided from the CO or PBX to
enable this option (the AIIR-S does not recognize a
reversal of polarity). The AHR-S KTU serves up to
6 CO/PBX lines and is installed in ES-6-l KSU.
Remove the straps when AHR-S KTrJ is installed.
I
DCI-S 1
or
MFI-S 1
/
Line Circuit 3
Line Circuit 6
1
Page 200-4
Fig. 230-3
DCI-S and MFI-S AHR Straps
230.5 Volume Controls
1. AlI tones from the built-ii speaker in a keyset are
controlled at the keyset by adjusting the volume dial
located at the front of the keyset.
2.
System wide CO/PBX ring (station id!e) and intercom
all call and zone paging are controlled by adjusting
volume controls on the CLK-S KTU. Tone level is
increased by turning the volume control clockwise.
All volumes are pre-adjusted by the manufacturer.
Refer to Table 230-3.
Table 230-3 CLK Volume Controls
.ii,
L
TBl
---K
u
-
- I
OFF
POWER FUSE
5A
- - -...-c2
-
-
-
n
N
3
z
a
8
4
J
-
-
8
2
;’
5
J
-
2
0
z
2
-
-
N
E
-
11
J2
Pl
:
J
L
I
Fig. 2304 ES-6-l KSU Card Layout
Page 200-5
- - ___-___-_
.%
-.
k&+.
240 MDF
240.1
The FCC approved USOC number for 50 position
1.
CO/PBX
Installation
Connection
miniature ribbon jack for connection of CO lines is
IU21X. The CO lines are to be connected in sequence
consecutively within this jack.
Use of 66BSO or 66M50 quick-connect type blocks is
+
2.
recommended for ease of trouble location and correction. Use of bridging clips allows easy separation of
the system to determine cause of trouble.
PIN
26
1
27
2 2R
FUNCTION
1T
1R
2T
3. The following Table 240-1 gives complete information
on 50 position connector pin number, lead function,
running
DCI/MFI slot:
240.2
Station
1. The following tables give complete information on
KSU, cable, 50 position connection pin number, running cable color, lead designation, station cable color,
intercom number assignment, KSI-S slot assignment,
etc. for all stations. Refer to Table
Table 240-l
CO/PBX Connection Information
Pl Connector & Cable ES-6-l KSU
CABLE COLOR CiRCIJlT SLOT
WH-BL CO/PBX
BL-WH
WH-OR
OR-WH
CO/PBX
cable color, circuit designation, associated
Cabling Connection
240-2 and 240-3.
1
2
DCI/MFI
1
28 3T
3 3R
29
4T
4 4R
5T
,
5R
31 6T
6 6Fi
CO/PBX Connection:
I.
FCC approved connector USOC code is RJ21X.
Connector-ended cable for CO/PBX lines to plug info ES-6-I KSU requires
2.
Jack (Female) 50 position miniature ribbon connector.
WH-GN CO/PBX
GN-WH
WH-BR CO/PBX
BR-WH
WH -SL
SL-WH
The rest of PI Cable is spare and is
3
4
CO/PBX
5
not used.
DCI/.MF12
Page 200-6
Table 240-2 Station Connection Information
Jl - 52 Connectors and Cables ES-6-1 KSU
PIN
26 WH-EL
1
27
2
28
3 GN-WH
29
4
30 WH-SL
5 SL-WH
31
6 BL-RD
32 RD-OR
7
33 RD-GN
8 GN-RD
34 RD-BR
P
9 BR-RD
35 RD-SL
10 SL-RD
36 BK-BL
11
37
12 OR-BK
38 BK-GN
13 GN-BK
39 BK-BR
14
40 BK-SL
15 SL-BK
41
16 BL-YL
RUNNING
CABLE
BL-WH
WH-OR
OR-WH
WH-GN
WH-BR
BR-WH
RD-BL
OR-RD
BL-BK
BK-OR
BR-BK
YL-BL
STATION
CABLE
GN
RD
YL
BK
GN
RD
YL
BK
GN
RD
YL
BK
GN
RD
YL
BK
GN
RD
YL
BK
GN
RD
YL
BK
GN
RD
YL
BK
GN
RD
YL
BK
KEY SET
LEADS
VT
VR
DT
DR
VT
VR
DT
DR
VT
VR
DT
DR
VT
VR
DT
DR
VT
VR
DT
DR
VT
VR
DT
DR
VT
VR
DT
DR
VT
VR
DT
DR
SLOT
KSI
1
CABLE
Jl
(See Note)
STA.
1
(ATT)
STA.
2
STA.
3
STA.
4
STA.
5
STA.
6
STA.
7
STA.
8
SLOT
CABLE
(See
STA.
(ATT)
STA.
92
Note)
9
10
I----
STA.
17
STA.
12
KS!
STA.
15
STA.
16
Note: Two stations in rhe sysrem can be assigned as attendant srarions. Stations 1 and 9 are initialIy assigned
these positions. Sration 1 must be insralled for programming purposes.
The ET-6-l is a fully-modular electronic key telephone set. Each keyset requires 2pair cabling to the Main
Distribution Frame (MDF). The maximum cable length is
700 ft. using standard 24 AWG cable and 1,150 ft. using
standard 22 AWG cable. Refer to Section 140, “Cabling
Requirements”, of this manual. For keyset connection,
EB-6 -1 is a modular electronic busy lamp
field. Each unit is provided with a 9V DC 03A power
supply for LED illumination. The power supply is to be
plugged into a standard 117V AC outlet. Each BLF requires
1 -pair cabling to the main distribution frame (MDF).
The maximum cable length is 700 ft. using standard 24
AWG cable and 1,150 ft. using standard 22 AWG cable.
Refer to Section 140, “Cabling Requirements”, of this
manual. For BLF connection, see Figures 250-3, 2504
and 250-S and Table 240-3.
RUNNING CABLE
BLR (BK)
TO KSU
BLT (Y L)
Fig.
2503
DR DT
EB-6-1 BLF
Simplified Schematic - EB-6-1 BLF Connection
Page 200-il
____..__
_._-
-
. . . . . ..- ._.--. _- .-_ ..I ._._
TO KSU
BLFCABLE
_-__-l-._-~-.C_~“~-~~
‘xL..?Au.-.. . . . . __.~,
I
I
MODULAR
TERMINAL
I
I
_____-------
L
Fig. 2504 View of Modular Terminal for Connection of EB-6-1 BLF
-I
Page 200-12
TO POWER
SUPPLY
/
Fig. 250-5 Power Supply Connection
EB-6-1
BLF
250.3 DP-6-1 Installation
The
DP-6-1 is a Door/Monitor phone unit. Each
door phone requires 1 pair cabling to the Main Distribution
Frame (MDF). The maximum cable length is 700 ft. using
standard 24 AWG cable and 1,150 ft. using standard 22
AWG cable. Refer to Section 140, “Cabling Requirements”
of this manual.
To prepare the door phone for wall mounting losen the set
screw and remove the door phone unit from the mounting
plate. Use the two screws provided or other appropriate
fastners to fiiy connect to wall surface. For door phone
cable connection, see Figure 2506 and Table 240-3. Refer
to Section 340, ‘Programming Sheets” for Door Phone
assignment.
SCREW SLOT
POSITIONS
TO
Fig. 250-6
Rear View of DP-6-l Door Phone
Page 2m-13 ‘-_
260
installing Options
2605 External Paging Amplifier
260.1
Music On
Hold
Provision has been made to allow connection of a
locally provided external music source to provide Music-
On-Hold for held CO/PBX calls. Connection of the Music
Source is made at the Jl Block of the Main Distribution
Frame (MDF). The output signal level should be approxi-
mately 1 milliwatt with 8 ohms impedance. See Figure
260.3 and Table 240.3 for connection information to
260.2
External Paging Speaker
MDF .
When a PBS-S KTU is installed in the ES -6 - 1 KSU,
external paging with meet-me answer can be provided. The
PBS-S KTU contains a 1 -watt Amplifier and Control
Circuit for one-zone paging (when a l-watt amplifier is
insufficient, see Section 260.5.) The External Speaker
should be locally-supplied in correspondence to the output
impedance of 600 ohms. The Volume Control (VRl),
located on the PBS-S, provides a way to increase or decrease the output signal of the amplifier to the speakers.
To adjust output signal, turn VR1 clockwise to increase
signal, and counterclockwise to lower signal. An LED is
provided on PBS-S KTU to indicate when paging is being
used. When an External Page is answered (meet-me-answer),
the PBS-S is released to allow access for another page.
See Figure 2 60-3 and Table 240-3 for connection information to MDF.
The PBS-S
KTU contains a l-watt Amplifier and
control circuit for external paging. For applications where
1 -watt is insufficient, an external amplifier may be used.
Provision has been made to allow connection of a locallyprovided amplifier to the MDF for this purpose. The PBS-S
KTU is required when an external amplifier is used. See
Figure 2604 and Table 240-3 for connection information
to the MDF.
260.6
External Background Music when External
Amplifier is Used
To provide for background music with an external
amplifier installed, set the SW4 switch
io
the “ON” position and the SW3 switch to the “OFF” position on the
PBS-S KTU. When background music is not required set
the SW3 switch to the “ON” position and the SW4 switch
to the “OFF” position. Music will be cut off from the
paging speakers when external paging is accessed. The
output level and impedance of the music source should
match the input level and impedance of the external
amplifier. See Figure 2604 and Table 240-3 for connection information to the MDF.
c-.-..
ON
OFF
ON - - OFF
.
260.3 External Background Music when PBS-S KTU
is
Used
When a PBS-S KTU is installed, an external locallyprovided music source can be used to supply background
music over the External Paging System. The recommended
output of the music source is l-watt with 600 ohms impedance. When external paging is accessed music is cut off
from the paging speaker. Connection is made on the Jl
block of the MDF. See Figure 260-3 and Table 240-3 for
connection information to MDF.
260.4 External Tone
Ringer
Provision has been made to allow connection of
locally provided External Tone Ringer to supply common
audible on all incoming CO/PBX calls. For this purpose a
relay contact is prepared on the CLK-S KTlJ. which
provides an interrupted closure (1 SEC. on/ 1 SEC. off)
during the CO/PBX Ring Cycle. The signal of the tone
ringer can be controlled by a locally provided control
switch. See Figure 260-3 and Table 240-3 for connection
information to MDF.
SW4
260-7
SW3
Fig. 260-I PBS-S Switches for BGM
Power
Failure Telephones
ET-6-l Ke:J Telephone Sets cannot be used to
originate or answer calls during a commercial power
failure. Locally-provided single line telephone sets can be
installed for this purpose. The KSU provides automatic
power failure for CO/PBX lines 1 and 2. No optional KTU
is required. Connection of the Single Line Telephones is
made at the Jl block of the MDF. Single Line Telephones
with appropriate dials (rotary or DTMF) should be installed
if the capability of dialing out during a power outage is
desired. See Figtire 260-3 and Table 240-3 for connection
information to MDF.
Page 200-14
26043 Security Control Equipment
260.9 External Amplifier Control
Provision has been made to allow connection of a
locally-provided security control system. For this purpose
the PBS-S KTU contains 2 individual control circuits that,
when activiated, provide an audible alarm through all idle
keyset speakers and a visual alarm on each keyset display.
Each security circuit can be activiated by means of an
external make (closed) or break (open) contact. The SW1
switch on the PBS-S KTU is used to set the desired break
or make detection for security circuit one and the SW2
switch performs the same function for security circuit two.
For connection information to the MDF see Figure 260-3
and 260.4 and Table 240-3.
1M - - 18
piT=q
SW1
Fig. 260-2 PBS-S Security Control Switches
2M - - 20
p7i-l
SW2
A set of dry contacts is provided on the PBS-S
KTU, which can be used to control an auxiliary relay for
External Paging. Although this option is not required when
an external amplifier is used, it may be desired in some
applications. When an external page is activiated the EAS
and EAM contacts are closed for the duration of the page.
In the idle condition the closure is made between the EAS
and EAB contacts. See Figure 2604 and Table 240-3 for
connection information to the MDF.
Page 200 - 15
_. _. __.
-.- . .
CLK-S
Y L-BR
BR-Y L 1SEG
YLSL MOH
SL-YL MOHG
VI-BL SKR
BL-VI SKRG
VI-OR
OR-VI
1SE
BGM
BGMG
44
-oo-oo-
-o&a-
--Qc2Lo-
-o&o-
-o&o-
-4&o-
-oEoo-
-ocPoo-
-oEoo-
-o&*
-o&c
SECURITY 1
ACTIVATION
CONTACT
---p&&i
EXTERNAL
PAGING
SPEAKERS (600.52)
POWER FAILURE
CONNECTION
FOR CO/PBX 1
VI-SL 2PFT
-o&*
25
-ac--Oo-
:
Jl BLOCK
OF MDF
(668-50 OR 66M-50)
Fig. 260-3 Connection of Optional Features
POWER FAILURE
CONNECTION
FOR COIPBX 2
..-
Page 200-16
Loading...
+ 62 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.