NCR 4072 Installation And Operation Manual

Page 1
NCR 4072
500–1400 VA
Uninterruptible Power Systems (UPS)
Site Preparation,
Installation, and Operation Manual
Page 2
Class B EMC Statements
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class B digital device,
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
Consult the dealer or an experienced radio/TV technician for help.
ICES-003
This Class B Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES-003.
Cet appareil numérique de la classe B respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
ECopyright 2001–2005 NCR Corporation, Dayton, Ohio. All rights reserved. No part of this document may be reproduced in any way without the express written approval of NCR Corporation.
Page 3
Requesting a Declaration of Conformity
Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:
Harmonized Standards: IEC 62040-1-1 and IEC 62040-2; IEC 60950 Third Edition
EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact:
Loren Schide NCR 1611 South Main Street Dayton, OH 45479 Phone: 937-445-5305
limits 93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC
Page 4
Special Symbols
The f ollowing are examples of symbols used on the UPS to alert you to important information:
CAUTION
Risk of Electric Shock
Do Not Open Cover
CAUTION To reduce the risk of electric shock,
Do not remove cover (or back)
No user-serviceable parts inside
Refer servicing to the factory
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the
associated warning should be observed.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual
for additional information, such as important operating and maintenance instructions.
SAFETY EARTHING TERMINAL - Indicates the primary safety ground.
LOAD ON/OFF - Press the button with this symbol to energize the output receptacles
(
µ indicator illuminates) or to de-energize the output receptacles (µ indicator is
off).
RJ-45 RECEPTACLE - For 230V units only: this receptacle provides network interface
connections. Do not plug telephone or telecommunications equipment into this receptacle.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. The UPS may contain sealed, lead-acid batteries. Batteries must be recycled.
Page 5
Table of Contents
1 NCR 4072 – One of the Best! 1.................................
2 Safety Warnings 3............................................
3 Installation 17.................................................
Inspecting the Equipment 17.................................................
UPS I nternal Battery Connection 18...........................................
Installing the UPS 20........................................................
UPS Rear Panels 22.........................................................
4Operation 27..................................................
Turning the UPS On 27......................................................
Starting the UPS on Battery 27.............................................
Turning the UPS Off 27.....................................................
Standby Mode 28..........................................................
UPS Front Panel 28.........................................................
Initiating the Self-Test 28....................................................
5 Additional UPS Features 29.....................................
Voltage C onfiguration 29....................................................
Communication Options 30..................................................
USB Port 30.............................................................
DB-9 Communication Port 31..............................................
Network Transient Protector 32..............................................
6 UPS Maintenance 33...........................................
UPS and Battery Care 33....................................................
Storing the UPS and Batteries 33...........................................
Replacing Batteries 34......................................................
Testing New Batteries 37....................................................
Recycling the Used Battery 38................................................
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
i
Page 6
Table of Contents
7 Specifications 39..............................................
8 Troubleshooting 43............................................
Audible Alarms and UPS Conditions 43........................................
Silencing an Audible Alarm 44.............................................
Site Wiring Fault (120V Models Only) 44.....................................
Service and Support 47.....................................................
ii
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 7
Chapter 1 NCR 4072 – One of the Best!
The NCR 4072 uninterruptible power system (UPS) protects your sensitive electronic equipment from basic power problems such as power failures, power sags, power surges, brownouts, and line noise.
Power outages can occur when you least expect it and power quality can be erratic. These power problems have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware — causing hours of lost productivity and expensive repairs.
With the NCR 4072 UPS, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. The NCR 4072 UPS’s flexibility to handle an array of network devices makes it the perfect choice to protect your LANs, servers, workstations, and other electrical equipment.
Figure 1. The NCR 4072 UPS
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
1
Page 8
NCR 4072 – One of the Best!
Providing outstanding performance and reliability, the NCR 4072 UPS’s unique benefits include the following:
Battery Save technology doubles battery service life, optimizes
Buck and Boost voltage regulation en sures consistent voltage to your
Hot-swappable batteries simplify maintenance by allowing you to
Start-on-battery capability allows you to power up the UPS even if
Two standard communication options with a USB port and DB-9 serial
Network Transient Protector guards your network communications
The NCR 4072 UPS is backed by worldwide agency approvals.
recharge time, and provides a warning before the end of useful battery life.
load by correcting voltage fluctuations.
replace batteries safely without powering down the critical load.
utility power is not available.
port.
equipment from surges. Low voltage models can also protect modems, fax machines, or other telecommunications equipment.
2
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 9
Chapter 2 Safety Warnings
Read the following precautions before you install the UPS.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY.ThereareNO USER SERVICEABLE PARTS inside the UPS.
This UPS contains its own energy source (batteries). The output receptacles
may carry live voltage even when the UPS is not connected to an AC supply.
For 220–240V models, t he output receptacles may remain electrically live. If
the input power source in your application is wired line-to-neutral (as in most European applications), the voltage to the output receptacles is 0V. With line-to-line input wiring, the voltage to the output receptacles is 110–120V (measured from line-to-ground or line-to-neutral, depending on the UPS wiring).
Do not remove or unplug the input cord when the UPS is turned on. This
removes the safety ground from the UPS and the equipment connected to the UPS.
To reduce the risk of fire or electric shock, install this UPS in a temperature
and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% max).
To comply with international standards and wiring regulations, the total
equipment connected to the output of this UPS must not have an earth leakage current greater than 1.5 milliamperes.
DANGER
WARNING
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
3
Page 10
Safety Warnings
CAUTION
The wall outlet must be within 2 meters of the equipment and accessible to
the operator.
Batteries can present a risk of electrical shock or burn from high
short-circuit current. The following precautions should be observed:
1) Remove watches, rings, or other metal objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries; 4) Disconnect charging source prior to connecting or disconnecting battery terminals.
Proper disposal of batteries is required. Refer to your local codes for
disposal requirements.
Never dispose of batteries in a fire. Batteries may explode when exposed to
flame.
Never open or mutilate batteries. Released electrolyte is harmful to the skin
and eyes, and may be extremely toxic.
Replace batteries with the same number and type of batteries as originally
installed in the UPS.
4
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 11
Sikkerhedsanvisninger
VIGTIGE SIKKERHEDSANVISNINGER GEM DISSE ANVISNINGER DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE SIKKERHEDSANVISNINGER
Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og vedligeholdelse bør kun udføres af en AUTORISERET SERVICETEKNIKER. Ingen af UPS’ens indvendige dele kan repareres af brugeren.
Denne UPS indeholder egen energiforsyning (batterier). Udgangsnetstikkene
kan lede strøm, selv når UPS’en ikke er tilsat en AC-energikilde.
Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en er
tændt. Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.
Installér denne UPS i et temperatur- og fugtighedskontrolleret
indendørsmiljø, frit for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk stød. Rumtemperaturen må ikke overstige 40°C. UPS’en bør ikke betjenes nær vand eller høj fugtighed (maksimalt 95%).
I overensstemmelse med internationale normer og bestemmelser for
el-installation må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 1,5 milliampere.
Safety Warnings
FARE
ADVARSEL!
ADVARSEL
Stikkontakten skal være højest 2 meter fra udstyret og skal være tilgængeligt
til operatøren.
Batterier kan udgøre en fare for elektrisk stød eller forbrændinger
forårsaget af høj kortslutningsspænding. De korrekte forholdsregler bør overholdes.
Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale
regler for bortskaffelsesprocedurer.
Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan
eksplodere ved åben ild.
Batterierne bør aldrig åbnes eller skilles ad. Udløst elektrolyt er skadeligt for
hud og øjne og kan være yderst giftigt.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
5
Page 12
Safety Warnings
Belangrijke Veiligheidsinstructies
BELANGRIJKE VEILIGHEIDSINSTRUCTIES BEWAAR DEZE INSTRUCTIES DEZE HANDLEIDING BEVAT BELANGRIJKE VEILIGHEIDSINSTRUCTIES
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd. Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden GEREPAREERD.
WAARSCHUWING
Deze UPS bevat zijn eigen energiebron (batterijen). De uitgangsaansluitingen
kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is aangesloten.
Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet
uit terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben.
Teneinde de kans op brand of elektrische schok te verminderen dient deze
UPS in een gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd, waar geen geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40°C niet overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid (max. 95%).
Om aan de internationale normen en bedradingsvoorschriften te voldoen
mag de gehele apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van meer dan 1,5 milliampère hebben.
GEVAAR
OPGELET
De hoofdvoedingcontactdoos moet zich op minder dan 2 meter vande
apparatuur bevinden en makkelijk bereikbaar zijn voor de gebruiker.
Batterijen kunnen gevaar voor elektrische schok of brandwonden
veroorzaken als gevolg van un hoge kortsluitstroom. Volg de desbetreffende aanwijzingen op.
De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg
hiervoor uw plaatselijke voorschriften.
Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.Nooit batterijen openen of verminken. Vrijkomend elektrolyt is schadelijk
voor de huid en ogen, en kan uiterst giftig zijn.
6
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 13
Tarkeita Turvaohjeita
TÄRKEITÄ TURVAOHJEITA - SUOMI SÄILYTÄ NÄMÄ OHJEET TÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA
Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot on jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA.
Tämä UPS sisältää oman energialähteen (akuston). Ulostuloliittimissä voi olla
jännite, kun UPS ei ole liitettynä verkkojännitteeseen.
Älä poista tai irrota sisääntulojohtoa, kun UPS on kytkettynä. Tämä poistaa
turvamaadoituksen UPS-laitteesta ja siihen liitetystä laitteistosta.
Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin,
joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia epäpuhtauksia. Ympäristön lämpötila ei saa ylittää 40 °C. Älä käytä lähellä vettä ja vältä kosteita tiloja (95 % maksimi).
Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän
UPS-laitteen ulostulokytkentöjen yhteinen maavuotovirta ei ylitä 1,5 milliampeeria (mA).
Safety Warnings
VAARA
VAROITUS
VARO
Päävirtapistokkeen täytyy olla 2 m:n säteellä laitteistosta ja käyttäjän
saatavilla. UPS-laitteen virtakytkin ei eristä sisäosia virran saannilta.
Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään
oikosulkuun. Noudata asianmukaisia ohjeita.
Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia
määräyksiä.
Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.Älä avaa tai riko akkua. Paljastunut elektrolyytti on vahingollinen iholle ja
silmille ja voi olla erittäin myrkyllistä.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
7
Page 14
Safety Warnings
Consignes de sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ IMPORTANTES
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ. AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.
Cet onduleur renferme sa propre source d’énergie (batteries). Les prises de
sortie peuvent être sous tension même lorsque l’onduleur n’est pas branché sur le secteur.
Ne pas retirer le cordon d’alimentation lorsque l’onduleur est sous tension
sous peine de supprimer la mise à la terre de l’onduleur et du matériel connecté.
Pour réduire les risques d’incendie et de décharge électrique, installer
l’onduleur uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la température et l’humidité ambiantes sont contrôlées. La température ambiante ne doit pas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphère excessivement humide (95 % max).
Afin d’être conforme aux normes et règlements internationaux de câblage,
le courant de fuite à la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pas dépasser 1,5 mA.
DANGER!
AVERTISSEMENT!
ATTENTION!
La prise principale secteur doit se trouver à moins de 2 mètres du matériel
et être accessible à l’utilisateur.
Les batteries peuvent présenter un risque de décharge électrique ou de
brûlure par des courts-circuits de haute intensité. Prendre les précautions nécessaires.
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les
règlements en vigueur dans votre localité.
Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les
faire exploser.
Ne jamais ouvrir ou mutiler des batteries. L’électrolyte qui s’en échappe est
nuisible à la peau et aux yeux et peut s’avérer extrêmement toxique.
8
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 15
Sicherheitswarnungen
WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAHREN. DIESES HANDBUCH ENTHÄLT WICHTIGE SICHERHEITSANWEISUNGEN.
Die USV führt lebensgefährliche Spannungen. Alle Reparatur- und Wartungsarbeiten sollten nur von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine vom Benutzer zu wartenden Komponente
Diese USV ist mit einer eigenen Energiequelle (Batterie) ausgestattet. An den
Ausgangssteckdosen kann auch dann Spannung anliegen, wenn die USV nicht an einer Wechselspannungsquelle angeschlossen ist.
Das Eingangskabel nicht entfernen oder abziehen, während die USV
eingeschaltet ist, weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Geräten entfernt wird.
Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in
Gebäuden mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C nicht übersteigen. Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %) betreiben.
Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen
die an den Ausgang dieser USV angeschlossenen Geräte zusammen einen Erdschlußstrom von insgesamt 1,5 Milliampere nicht überschreiten.
Safety Warnings
WARNUNG
ACHTUNG
VORSICHT!
Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocks
oder Verbrennungen verursachen. Folgende Vorkehrungen sollten getroffen werden, wenn Sie mit der Battery arbeiten: 1) Entfernen Sie Uhren, Ring und andere metallische Objekte; 2) Verwenden Sie Werkzeug mit isolierten Griffen.
Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die
örtlichen Bestimmungen zu beachten.
Batterien niemals verbrennen, da sie explodieren können.Öffnen oder beschädigen Sie nicht die Batterien, ausfließendes Elektrolyt ist
schädlich für Haut und Augen.
Falls Sie die Batterien austauschen, verwenden Sie bitte ausschließlich die
gleiche Anzahl und die Batterietypen.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
9
Page 16
Safety Warnings
РспейдпрпйЮуейт БуцЬлейбт
УЗМБНФЙКЕУ ПДЗГЙЕУ БУЦБЛЕЙБУ ЦХЛБОФЕ БХФЕУ ФЙУ ПДЗГЙЕУ ФП РБСПН ЕГЧЕЙСЙДЙП РЕСЙЕЧЕЙ УЗМБНФЙКЕУ ПДЗГЙЕУ БУЦБЛЕЙБУ
Бхфь фп UPS ресйЭчей ИБНБФЗЦПСБ ФБУЗ. ¼лет пй ерйукехЭт кбй пй ухнфзсЮуейт рсЭрей нб гЯнпнфбй МПНП БРП ЕОПХУЙПДПФЗМЕНП ГЙБ ФЗ УХНФЗСЗУЗ РСПУЩРЙКП. Фп UPS ДЕН РЕСЙЕЧЕЙ КБНЕНБ ЕОБСФЗМБ РПХ НБ МРПСЕЙ НБ ЕРЙУКЕХБУФЕЙ БРП ФП ЧСЗУФЗ.
РСПЕЙДПРПЙЗУЗК
Фп ухгкексймЭнп UPS ресйЭчей фз дйкЮ фпх рзгЮ енЭсгейбт
(ухуущсехфЭт). Пй сехмбфпдьфет еоьдпх мрпсеЯ нб Эчпхн енесгь фЬуз бкьмз кбй ьфбн фп UPS ден еЯнбй ухндедемЭнп уе рзгЮ енбллбууьменпх сеэмбфпт (AC).
Мзн вгЬжефе брь фзн рсЯжб фп кблюдйп фспцпдпуЯбт ьфбн фп UPS еЯнбй
бнпйчфь. М’ бхфь фпн фсьрп бцбйсеЯфе фз геЯщуз буцблеЯбт брь фп UPS кбй брь фпн еопрлйумь рпх еЯнбй ухндедемЭнпт ме фп UPS.
Гйб нб мейюуефе фпн кЯндхнп рхскбгйЬт Ю злекфспрлзоЯбт,
егкбфбуфЮуфе фп ухгкексймЭнп UPS уе еущфесйкь чюсп ме елегчьменз иесмпксбуЯб кбй хгсбуЯб, п прпЯпт нб мзн ресйЭчей бгюгймб хлйкЬ. З иесмпксбуЯб ресйвЬллпнфпт ден рсЭрей нб оереснЬей фпхт 40 хресвплйкЮ хгсбуЯб (мЭгйуфз фймЮ: 95%).
Гйб нб ухмцщнеЯ ме фб дйеинЮ рсьфхрб кбй фпхт кбнпнйумпэт
кблщдЯщузт, фп сеэмб дйбсспЮт рспт фз гз пльклзспх фпх еопрлйумпэ, рпх еЯнбй ухндедемЭнпт ме фзн Эопдп фпх ухгкексймЭнпх UPS, ден рсЭрей нб еЯнбй мегблэфесп брь 1,5 mA.
КЙНДХНПУ
° C. Мз чсзуймпрпйеЯфе фп UPS кпнфЬ уе несь Ю
10
РСПУПЧЗ
Пй ухуущсехфЭт мрпсеЯ нб рспкблЭупхн злекфспрлзоЯб Ю Эгкбхмб
брь хшзль сеэмб всбчхкхклюмбфпт. ЛбмвЬнефе фйт кбфЬллзлет рспцхлЬоейт.
БрбйфеЯфбй ущуфЮ дйЬиеуз фщн ухуущсехфюн. ДеЯфе фпхт фпрйкпэт
кбнпнйумпэт рпх бцпспэн фйт брбйфЮуейт дйЬиеуЮт фпхт.
РпфЭ мзн рефЬфе фпхт ухуущсехфЭт уфз цщфйЬ, гйбфЯ мрпсеЯ нб
ексбгпэн.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 17
Avvisi di sicurezza
IMPORTANTI ISTRUZIONI DI SICUREZZA CONSERVARE QUESTE ISTRUZIONI QUESTO MANUALE CONTIENE IMPORTANTI ISTRUZIONI DI SICUREZZA
la TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All’interno del gruppo statico di continuità NON vi sono PARTI RIPARABILI DALL’UTENTE.
Questo gruppo statico di continuità contiene una fonte di energia autonoma
Non rimuovere nè scollegare il cavo di ingresso quando il gruppo statico di
Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo
Per conformità con gli standard internazionali e con le norme in merito al
Safety Warnings
PERICOLO
AVVERTENZA
(le batterie). Le prese di uscita possono condurre tensione energizzata quando il gruppo statico di continuità non è collegato con una fonte di alimentazioneacorrentealternata.
continuità è acceso poichè in tal modo si disattiverebbe il collegamento a terra di sicurezza del gruppo statico di continuità e dell’apparecchiatura ad esso collegata.
statico di continuità in un ambiente interno a temperatura ed umidità controllata, privo di agenti contaminanti conduttivi. La temperatura ambiente non deve superare i 40°C. Non utilizzare l’unità in prossimità di acqua o in presenza di umidità eccessiva (95% max).
cablaggio, tut ta l’apparecchiatura collegata con l’uscita del gruppo statico di continuità non deve avere una corrente di dispersione di terra superiore a 1,5 milliampere.
ATTENZIONE
La presa di alimentazione principale non deve trovarsi a oltre 2 metri
dall’apparecchiatura e deve essere accessibile all’operatore.
Le batterie possono presentare rischio di scossa elettrica o di ustioni
provocate da alta corrente dovuta a corto circuito. Osservare le apposite istruzioni.
Le batterie devono essere smaltite in modo corretto. Per i requisiti di
smaltimento fare riferimento alle disposizioni locali.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
11
Page 18
Safety Warnings
Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se
esposte alle fiamme.
Maiaprirenèmutilarelebatteriepoichèl’elettrolitadaesserilasciatoè
nocivo alla cute e agli occhi e può essere altamente tossico.
Viktig Sikkerhetsinformasion
Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må kun utføres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE SERVICE PÅ NOEN AV DELENE i UPS’en.
Denne UPS’en har en egen energikilde (batterier). Stikkontaktene kan være
strømførende selv om UPS’en ikke er tilsluttet en vekselstrømforsyning.
Strømforsyningskabelen må ikke fjernes eller trekkes ut når UPS’en er på,
slik at ikke sikkerhetsjordingen fjernes fra UPS’en og det utstyret som er forbundet med den.
For å redusere fare for brann eller elektriske støt, bør denne UPS’en
installeres i et innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende, forurensende stoffer. Romtemperaturen må ikke overskride 40°C.Denmåikkebrukesinærhetenavvannellervedmeget høy luftfuktighet (95% maks.).
Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en
sterkere total lekkasjestrøm enn 1,5 milliampere for å være i overensstemmelse med internasjonale standarder og forkablingsbestemmelser.
FARLIG
FARLIG
12
FORSIKTIG
Stikkontakten må befinne seg innen 2 m fra utstyret og må være tilgjengelig
for operatøren.
Batterier kan forårsake elektriske støt eller forbrenning på grunn av høy
kortslutningsstrøm. Følg instruksene.
Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav
om fjerning av batterier.
Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for
åpen ild.
Batterier må aldri åpnes eller ødelegges. Frigjorte elektrolytter er skadelige
for hud og øyne og kan være ekstremt giftige.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 19
Regulamentos de Segurança
INSTRUÇÕES DE SEGURANÇA IMPORTANTES GUARDE ESTAS INSTRUÇÕES ESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇA IMPORTANTES
A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência t écnica devem ser executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não há nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.
Esta UPS contém sua própria fonte de energia (baterias). Os receptáculos de
saída podem conter voltagem ativa quando a UPS não se encontra conectada a uma fonte de alimentação de corrente alternada.
Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada.
Isto removerá o aterramento de segurança da UPS e do equipamento conectado.
Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em
ambiente interno com temperatura e umidade controladas e livres de contaminadores condutíveis. A temperatura ambiente não deve exceder 40°C. Não opere próximo a água ou em umidade excessiva (máx: 95%).
Para estar de acordo com os padrões internacionais e os regulamentos de
fiação, o equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à terra maior que 1,5 miliampères.
Safety Warnings
CUIDADO
ADVERTÊNCIA
PERIGO
O soquete de alimentação principal deve estar à no máximo dois metros do
equipamento e acessível ao operador.
As baterias podem apresentar o risco de choque elétrico, ou queimaduras
provenientes de alta corrente de curto-circuito. Observe as instruções adequadas.
Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os
códigos do local para maiores informações sobre os regulamentos de descarte de produtos.
Nunca jogue as baterias no fogo, porque há risco de explosão.Nunca abra ou danifique as baterias. O eletrólito liberado é prejudicial à
pele e aos olhos e pode ser extremamente tóxico.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
13
Page 20
Safety Warnings
Предупреждения по мерам безопасности
ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ СОХРАНИТЕ ЭТИ УКАЗАНИЯ ДАННОЕ РУКОВОДСТВО СОДЕРЖИТ ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ
ОПАСНО
В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ. Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКО УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ. Внутри ИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ.
ПРЕДУПРЕЖДЕНИЕ
Данный ИБП содержит собственные источники энергии
(аккумуляторы). На выходных розетках может иметься напряжение, даже когда ИБП не подключен к сети переменного тока.
Не отсоединяйте сетевой шнур и не извлекайте его вилку из розетки
при включенном ИБП. При этом защитное заземление отключается от ИБП и от оборудования, подключенного к ИПБ.
Для снижения опасности пожара или поражения электрическим
током устанавливайте ИБП в закрытом помещении с контролируемыми температурой и влажностью, в котором отсутствуют проводящие загрязняющие вещества. Температура окружающего воздуха не должна превышать 40 эксплуатируйте устройство около воды или в местах с повышенной влажностью (макс. 95%).
Для обеспечения соблюдения требований международных стандартов
и требований к разводке электрических цепей, суммарная величина тока утечки на землю всего оборудования, подключенного к выходу ИБП, не должна превышать 1,5 миллиампера.
°С. Не
14
ОСТОРОЖНО
Аккумуляторы могут вызвать опасность поражения электрическим
током или ожога от тока короткого замыкания. Соблюдайте соответствующие меры предосторожности.
Необходимо соблюдать правила утилизации аккумуляторов.
Обратитесь к местным нормативным актам за информацией о требованиях к утилизации.
Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут
взорваться под воздействием огня.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 21
Advertencias de Seguridad
INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD IMPORTANTES
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE.
Este SIE contiene su propia fuente de energía (las baterías). Los receptáculos
de salida pueden transmitir corriente eléctrica aun cuando el SIE no esté conectado a un suministro de corriente alterna (c.a.).
No retire o desenchufe el cable de entrada mientras el SIE se encuentre
encendido. Esto suprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE.
Parareducirelriesgodeincendioodechoqueeléctrico,instaleesteSIEen
un lugar cubierto, con temperatura y humedad controladas, libre de contaminantes conductores. La temperatura ambiente no debe exceder los 40°C. No trabaje cerca del agua o con humedad excesiva (95% máximo).
Para cumplir con los estándares internacionales y las normas de instalación,
la totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de pérdida a tierra superior a los 1,5 miliamperios.
Safety Warnings
PELIGRO
ADVERTENCIA
PRECAUCIÓN
El tomacorriente de pared debe encontrarse dentro de los 2 metros de
distancia del equipo y ser accesible para el operador.
Lasbateríaspuedenpresentarunriesgodedescargaseléctricasode
quemaduras debido a la alta corriente de cortocircuito. Preste atención a las instrucciones correspondientes.
Es necesario desechar las baterías de un modo adecuado. Consulte las
normas locales para conocer los requisitos pertinentes.
Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se
las expone a la llama.
Nunca abra o mutile las baterías. El electrolito liberado es peligroso para la
piel y los ojos, y puede ser extremadamente tóxico.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
15
Page 22
Safety Warnings
Säkerhetsföreskrifter
VIKTIGA SÄKERHETSFÖRESKRIFTER SPARA DESSA FÖRESKRIFTER DENNA BRUKSANVISNING INNEHÅLLER VIKTIGA SÄKERHETSFÖRESKRIFTER
Denna UPS-enhet innehåller LIVSFARLIG SPÄNNING. ENDAST AUKTORISERAD SERVICEPERSONAL får utföra reparationer eller service. Det finns inga delar som ANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS-enheten.
Denna UPS-enhet har en egen energikälla (batterier). De utgående
kontakterna kan vara strömförande när UPS-enheten inte är ansluten till en växelströmkälla.
Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort
skyddsjordningen från både UPS-enheten och den anslutna utrustningen.
Minska risken för brand eller elektriska stötar genom att installera denna
UPS-enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40°C. Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %).
För att överensstämma med internationell standard och
installationsföreskrifter får inte den totala utrustning som anslutits till uttagen på denna UPS-enhet ha läcksström som överstiger 1,5 milliampere.
FARA
VARNING
16
VIKTIGT
Huvudkontakten måste vara högst 2 meter från utrustningen och inom
räckhåll för användaren.
Batterierna kan ge elektriska stötar eller brännskador från hög
kortslutningsström. Följ tillämpliga anvisningar.
Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning.Använda batterier får aldrig brännas upp. De kan explodera.Öppna aldrig batterierna eller ta isär dem. Utsläppt elektrolyt är skadlig för
hudochögonochkanvaramycketgiftig.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 23
Chapter 3 Installation
This section explains:
Equipment inspectionUPS installationUPS rear panels
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the car rier within 15 days of receipt of the equipment; 2) Send a copy of the damage claim within 15 days to Customer Service.
NOTE Check the battery recharge date on the shipping carton label. If
the date has expired and the batteries were never recharged, do not use the UPS. Contact Customer Service.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
17
Page 24
Installation
UPS Internal Battery Connection
Use the following procedure to ensure proper battery operation before installing the UPS:
1. Verify that the UPS is off and unplugged.
2. Remove the UPS front panel.
3. Slide up and remove the metal battery cover.
Figure 2. Removing the Front Panel
18
1400 VA500–1000 VA
Figure 3. Removing the Battery Cover
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 25
Installation
4. Remove the protective label from the internal battery
connector.
Figure 4. Removing the Protective Label
5. Connect the red wire to the () battery connector.
NOTE A small amount of arcing may occur when c onnecting the
batteries. This is normal and does not damage the unit or present any safety concern.
Figure 5. Connecting the Red Wire
6. Reinstall the metal battery cover.
Figure 6. Reinstalling the Battery Cover
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
19
Page 26
Installation
Installing the UPS
The following steps explain how to install the UPS. Figure 8 shows a typical installation only. See “UPS Rear Panels” on page 22 for the rear panel of each model.
7. Reinstall the UPS front panel.
Figure 7. Reinstalling the Front Panel
8. If the UPS requires any type of transportation in the future,
disconnect the UPS internal battery connector using the above steps in reverse order.
20
1. If you are installing power management software, connect your
computer to the USB port or UPS communication port using the supplied cable (see page 30).
NOTE If you need to change the factory-set defaults for the output voltage
or input voltage range, see “Voltage Configuration” on page 29 before installing the UPS.
2. On 230V models, plug the detachable power cord into the input
connector on the UPS rear panel.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 27
Installation
NOTE
This is a typical setup; your setup may vary.
3. Plug the UPS power cord into a power outlet.
4. Plug the equipment to be protected into the UPS output
1
Connect communication cable from computer to UPS (optional)
5
Press the ON button (on the front panel)
2&3
Connect UPS to power
4
Connect equipment to UPS
Figure 8. Typical UPS Installation (120V Model Shown)
Verify that the circuit has an upstream overcurrent protection of 15A for 120V models or 10A for 230V models.
receptacles.
NOTE DO NOT protect laser printers with the UPS because of the
exceptionally high power requirements of the heating elements.
5. Press and hold the button until you hear the UPS beep
(approximately two seconds).
The
indicator illuminates indicating that power is available
µ
from the UPS output receptacles. The UPS conducts a self-test and enters Normal mode.
If the alarm beeps or a UPS alarm indicator stays on, see Table 9 on page 44.
NOTE The batteries charge to 90% capacity in approximately 3 hours.
However, it is recommended that the batteries charge for 6 to 24 hours after installation or long-term storage.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
21
Page 28
Installation
UPS Rear Panels
This section shows the rear panels of the NCR 4072 UPS models.
Site Wiring Fault
Indicator
Communication Port
6-ft Power Cord
with 5-15 Plug
Communication Port
Site Wiring Fault
Indicator
DIP Switches
USB Port
Figure 9. 500 VA, 120V Rear Panel
DIP Switches
USB Port
Network Transient Protector
Four 5-15 Receptacles
Input Overcurrent Protector
Network Transient Protector
22
Fan
Four 5-15 Receptacles
Input Overcurrent
Protector
6-ft Power Cord
with 5-15 Plug
Figure 10. 750 VA, 120V Rear Panel
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 29
Installation
Communication Port
Site Wiring Fault
Indicator
Fan
Four 5-15 Receptacles
Input Overcurrent
Protector
6-ft Power Cord
with 5-15 Plug
Communication Port
Site Wiring Fault
Indicator
DIP Switches
USB Port
Figure 11. 1000 VA, 120V Rear Panel
DIP Switches
USB Port
Network Transient Protector
Two 5-15 Receptacles
Network Transient Protector
Fan
Six 5-15 Receptacles
Input Overcurrent Protector
6-ft Power Cord
with 5-15 Plug
Figure 12. 1400 VA, 120V Rear Panel
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
23
Page 30
Installation
Communication Port
DIP Switches
USB Port
DIP Switches
Communication Port
Fan
Network Transient Protector
Four 10A, IEC-320 Receptacles
10A, IEC-320 Input Connector
Figure 13. 500 VA, 230V Rear Panel
USB Port Network Transient
Protector
Four 10A, IEC-320 Receptacles
24
10A, IEC-320
Input Connector
Figure 14. 750 VA, 230V Rear Panel
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 31
Installation
DIP Switches
Communication Port
Fan
Two 10A, IEC-320
Receptacles
10A, IEC-320
Input Connector
DIP Switches
Communication Port
Fan
USB Port Network Transient
Protector
Four 10A, IEC-320 Receptacles
Figure 15. 1000 VA, 230V Rear Panel
USB Port Network Transient
Protector
Six 10A, IEC-320 Receptacles
10A, IEC-320 Input Connector
Figure 16. 1400 VA, 230V Rear Panel
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
25
Page 32
Installation
26
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 33
Chapter 4 Operation
This section describes:
Turning the UPS on and offStarting the UPS on batteryStandby modeThe UPS front panel and indicatorsInitiating the self-test
Turning the UPS On
After the UPS is connected to a power outlet, the UPS enters Standby mode. To turn on the UPS, press and hold the the UPS beep (approximately two seconds). After the UPS is turned on, it conducts a self-test and enters Normal mode. The illuminates indicating that power is available from the UPS output receptacles.
Starting the UPS on Battery
button until you hear
indicator
µ
NOTE The UPS does not auto-detect the input frequency when starting
on battery; the default is t he last frequency used by the UPS.
To turn on the UPS without using utility power, press and hold the
button for two seconds. The UPS supplies power to your equipment and goes into Battery mode. When the UPS starts on battery, it does not conduct a self-test to conserve battery power.
Turning the UPS Off
To turn off the UPS, press and hold the button for two seconds and then unplug the UPS from the power outlet. If you do not unplug the UPS, it remains in Standby mode.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
27
Page 34
Operation
Standby Mode
UPS Front Panel
When the UPS is turned off and remains plugged into a power outlet, the UPS is in Standby mode. All indicators are off and power is not available to your equipment. The battery recharges when necessary.
NOTE For 220–240V models, the output receptacles may remain
electrically live (up to 110–120V). Unplug the UPS to ensure power is not available to the output receptacles.
The UPS front panel indicates the UPS status and also identifies potential power problems. Figure 17 shows the UPS front panel indicators and controls.
On/Off Button
Test/Alarm Reset Button
If the alarm beeps or a UPS alarm indicator stays on, see Table 9 on page 44 to identify and correct the problem.
Initiating the Self-Test
NOTE The batteries must be fully charged and the UPS must not be in
Battery mode to perform the self-test.
Press and hold the button for three seconds to initiate the self-test. If the UPS finds a problem, an LED indicates where the problem is. For more information, see “Troubleshooting” on page 43.
28
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Power On Indicator (Green)
On Battery Indicator (Yellow)
Overload Indicator (Red)
Service Indicator (Red)
Figure 17. UPS Front Panel
Page 35
Chapter 5 Additional UPS Features
This section describes:
Changing the voltage configurationUsing the USB or DB-9 communication portThe Network Transient Protector
Voltage Configuration
TheDIPswitchesontherearpanelofeachunit(seeFigure18)areused to configure the output voltage and input voltage range.
1. The UPS must be completely shutdown.
To turn off the UPS, press and hold the
button for two
seconds and then unplug the UPS from the power outlet.
2. Set the DIP switches according to the configurations in Table 1.
3. Plug the UPS power cord into a power outlet.
4. Press and hold the button until you hear the UPS beep
(approximately two seconds) to turn the UPS on.
UPS Rear Panel
21
OFF
ON
Figure 18. DIP S witches
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
29
Page 36
Additional UPS Features
Table 1. DIP Switch Settings
Output Voltage Input Voltage Range DIP Switch 1 DIP Switch 2
110V 99V-116V ON OFF/ON 120V* 108V–127V* OFF OFF/ON
Output Voltage Input Voltage Range DIP Switch 1 DIP Switch 2
220V 198V–233V ON OFF 230V* 207V–243V* OFF OFF/ON 240V 216V–254V ON ON
*Default position
Communication Options
The UPS is equipped with a USB and a DB-9 communication port. Either the USB port or the DB-9 communication port may be used to monitor the UPS; however, they cannot operate simultaneously.
120V Models
230V Models
30
USB Port
The UPS can communicate with a USB-compliant computer using power management software. To establish communication between the UPS and acomputer:
1. Connect the USB cable to the USB port on the UPS rear panel.
Connect the other end of the USB cable to the USB port on your computer.
USB Port
Figure 19. The USB Port
2. Install the power management software.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 37
Additional UPS Features
DB-9 Communication Port
To establish communication between the UPS and a computer, connect your computer to the UPS communication port using the supplied communication cable.
When the communication cable is installed, power management software canexchangedatawiththeUPS.ThesoftwarepollstheUPSfordetailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment.
The cable pins are identified in Figure 20 and the pin functions are described in Table 2.
UPS Rear Panel
7
6
8
9
1
3
245
Figure 20. Communication Port
Table 2. Communication Port Pin Assignment
Pin Number
1 Low Batt Low Battery relay contact; 20 mA,
2 TxD Transmit to external device Out
3 RxD Receive from external device In
4 DTR PnP (Plug and Play) from external
5 GND Signal common (tied to chassis)
6 DSR To external device (tied to Pin 4) Out
7 No Connection
8 AC Fail AC Fail relay contact; 20 mA, 30 Vdc
9 Power Source +V (8 to 24 volts DC power) Out
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Signal Name Function Direction
from the UPS
Out
30 Vdc contact rating
In
device (tied to Pin 6)
Out
contact rating
31
Page 38
Additional UPS Features
Network Transient Protector
The Network Transient Protector, shown in Figure 21, is located on the rear panel and has jacks labeled IN and OUT. This feature accommodates a single RJ-45 (10BaseT) network connector.
Low voltage models can also accommodate an RJ-11 telephone connector that provides protection for modems, fax machines, or other telecommunications equipment. As with most modem equipment, it is not advisable to use this jack in digital P BX (Private Branch Exchange) environments.
NOTE DO NOT connect any telephone or fax/modem equipment to the
230V models; only network protection is available for 230V models.
1. Connect the input connector of the equipment you are
protecting to the jack labeled IN.
2. Connect the network or telephone cable (low voltage models
only) to the jack labeled OUT.
32
OUT IN
IN
OUT
NETWORK TRANSIENT PROTECTOR
Figure 21. Network Transient Protector
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 39
Chapter 6 UPS Maintenance
This section explains how to:
Care for the UPS and batteriesReplace the batteriesTest new batteriesRecycle used batteries
UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of 25°C (77°F).
NOTE If the UPS requires any type of transportation in the future,
disconnect the UPS internal battery connector using the steps in “UPS Internal Battery Connection” on page 18 in reverse order.
Storing the UPS and Batteries
If you store the UPS for a long period, recharge the battery every 6 months by plugging the UPS into a power outlet. The batteries charge to 90% capacity in approximately 3 hours. However, it is recommended that the batteries charge for 6 to 24 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date has expired and the batteries w ere never recharged, do not use the UPS. Contact Customer Service.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
33
Page 40
UPS Maintenance
Replacing Batteries
NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery
mode.
With the hot-swappable battery feature, UPS batteries can be replaced easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the battery, press and hold the
Consider all warnings, cautions, and notes before replacing batteries.
Batteries can present a risk of electrical shock or burn from high short
ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or
Replace batteries with the same number and type of batteries as originally
button for two seconds and then unplug the UPS.
WARNING
circuit current. The following precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use tools with insulated handles;
3) Do not lay tools or metal parts on top of batteries.
connectors. Attempting to alter wiring can cause injury.
installed in the UPS.
34
CAUTION
Pull the battery out onto a flat, stable surface. The battery is unsupported when you pull it out of the UPS.
Use the following steps to replace the batteries:
1. Remove the UPS front panel.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 41
2. Slide up and remove the metal battery cover.
UPS Maintenance
500–1000 VA
1400 VA
3. 500 VA models. Disconnect the red battery cable and then
disconnect the black battery cable. Pull the battery out onto a flat, stable surface.
500 VA
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
35
Page 42
UPS Maintenance
4. 750/1000 VA models. Disconnect the red battery cable and then
pull the battery out onto a flat, stable surface. Disconnect the black battery cable to the UPS as shown.
750/1000 VA
36
5. 1400 VA models. Disconnect the red battery cable and then pull
the battery out onto a flat, stable surface. Remove the battery tie around the black cable set and disconnect the black battery cable to the UPS as shown.
1400 VA
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 43
6. Replace the battery. See “Recycling the Used Battery” on
7. Connect the black battery cable to the new battery and then
8. Reinstall the battery.
9. Reinstall the metal battery cover and front panel.
Testing New Batteries
NOTE Allow batteries to charge for 6 to 24 hours before testing.
Press and hold the button for three seconds to initiate a self-test. The 15-second test automatically distributes the load to the batteries and tests the battery’s performance. While the test is in progress, the indicators cycle through and the alarm sounds. When complete, the UPS returns to Normal mode as indicated by the
page 38 for proper disposal.
connect the red battery cable.
µ
UPS Maintenance
indicator.
+
If there is a problem with the battery, the alarm beeps, the illuminates and the and be sure the battery is fully charged. Call Customer Service if the problem persists.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
indicator flashes. C heck the battery connections
---
indicator
37
Page 44
UPS Maintenance
Recycling the Used Battery
Contact your local recycling or hazardous waste center for information on proper disposal of the used battery.
Do not dispose of the battery or batteries in a fire. Batteries may explode.
Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to the skin and eyes. It may be toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid batteries and must be disposed of properly. For more information, contact your local recycling or hazardous waste center.
WARNING
CAUTION
38
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 45
Chapter 7 Specifications
This section provides the following specifications for the NCR 4072 UPS models:
Dimensions and weightsElectrical input and outputEnvironmental and safetyBattery
Table 3. Model List and Mechanical
120V Models 230V Models
UPS Models
UPS Dimensions (WxHxD)
UPS Weights
Table 4. Electrical Input
Nominal Voltage
Voltage Range
Nominal Frequency
Efficiency (Normal mode)
Noise Filtering
Overcurrent Protection
Connections
4072-0500-7194 4072-0750-7194 4072-1000-7194 4072-1400-7194
500 VA: 15.0 x 19.3 x 27.0 cm (5.9² x7.6² x 10.6²)
750–1000 VA: 15.0 x 19.3 x 33.5 cm (5.9² x7.6² x 13.2²)
1400 VA: 15.0 x 19.3 x 39.0 cm (5.9² x7.6² x 15.4²)
500 VA: 7.8 kg (17.2 lb)
750 VA: 12.4 kg (27.3 lb) 1000 VA: 12.6 kg (27.8 lb) 1400 VA: 16.8 kg (37.0 lb)
120V Models 230V Models
110V, 120V selectable 220V, 230V, 240V selectable
±20% for nominal voltage at full load
45–65 Hz, 50/60 Hz auto-sensing
95%
Full-time EMI/RFI filtering
Resettable input overcurrent protector N/A
6-ft, 5-15P power cord (90° angle) 10A, IEC-320 input connector
4072-0500-7494 4072-0750-7494 4072-1000-7494 4072-1400-7494
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
39
Page 46
Specifications
Table 5. Electrical Output
120V Models 230V Models
Power Levels (rated at nominal inputs)
Power Factor
Regulation (Normal mode)
Regulation (Battery
Same as selected nominal input
mode), Nominal Voltage ±5%
Voltage Wavefor m
Overcurrent Protection
Output Receptacles
500–750 VA: (4) 5-15
1000–1400 VA: (6) 5-15
Table 6. Environmental and Safety
120V Models 230V Models
Operating Temperature
Transit/Storage Temperature
Relative Humidity
Operating Altitude
Audible Noise
Surge Suppression
Safety Conformance
Safety Markings
EMC (Class B)
Up to 1,500 meters: 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)
UL 1778; UL 497A;
CSA C22.2, No. 107.1
FCC Part 15, ICES-003 EN 50091-2, FCC Part 15, ICES-003
500 VA, 320W
750 VA, 500W 1000 VA, 670W 1400 VA, 950W
500 VA, 0.64
750–1400 VA, 0.67
-10% to +6% of nominal voltage
Same as selected nominal input
voltage
110V, 120V
Sine wave
Inverter saturation current limited
500–750 VA: (4) 10A, IEC-320
1000–1400 VA: (6) 10A, IEC-320
Above 1,500 meters: 0°C to 35°C (32°F to 95°F)
-15°C to 55°C (5°F to 131°F)
5–95% noncondensing
Up to 3,000 meters above sea level
Less than 45 dBA typical
ANSI C62.41 Category A (formerly IEEE 587)
UL 1778, UL 497A (data line only);
CSA C22.2, No. 107.1;
EN 50091-1-1 and IEC 60950
UL, cUL UL, cUL, CE, TÜV, C-Tick
voltage
220V, 230V, 240V
40
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 47
Specifications
Table 7. Battery
Configuration
Voltage
Type
Charging
Monitoring
500 VA: (1) 12V, 9 Ah internal battery 750 VA: (2) 12V, 7 or 7.2 Ah internal batteries 1000 VA: (2) 12V, 9 Ah internal batteries 1400 VA: (3) 12V, 9 Ah internal batteries
500 VA: 12 Vdc 750–1000 VA: 24 Vdc 1400 VA: 36 Vdc
Sealed, maintenance-free, valve-regulated, lead-acid
Advanced charging for faster recovery; approximately 3 hours to 90% usable capacity at nominal line and no supplementary power supply load
Advanced monitoring for earlier failure detection and warning
Table8.BatteryRunTimes(inMinutes)
UPS Models by VA Ratings
Load (VA) Watts 500 750 1000 1400
200 128 17 38 41 58
300 192 11 27 28 41
500 320 5 14 15 28
600 402 9 10 19
750 503 6 8 14
900 603 6 10
1000 670 5 8
1200 804 6
1400 938 5
NOTE Battery times are approximate and may vary depending on the load configuration and battery charge.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
41
Page 48
Specifications
42
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 49
Chapter 8 Troubleshooting
This section explains:
UPS alarms and conditionsHow to silence an alarmSite wiring fault on 120V modelsService and support
Audible Alarms and UPS Conditions
The UPS has an audible alarm feature to alert you of potential power problems. Use Table 9 to determine and resolve the UPS alarms and conditions.
Indicator Legend
Unlit Lit
Flashing
Figure 22. UPS Front Panel
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
On/Off Button
Test/Alarm Reset Button
Power On Indicator (Green)
On Battery Indicator (Yellow)
Overload Indicator (Red)
Service Indicator (Red)
43
Page 50
Troubleshooting
theUPSdoesnotstar
t
Silencing an Audible Alarm
Before silencing an alarm, check the alarm condition and perform the applicable action to resolve the condition (see Table 9). To silence the alarm for an existing fault, press the the alarm beeps, overriding the previous alarm silencing. The alarm does not silence if there is a UPS fault, low battery condition, or if the battery needs to be replaced.
Site Wiring Fault (120V Models Only)
The S ite Wiring Fault indicator on the UPS rear panel illuminates if the ground wire connection does not exist or the line and neutral wires are reversed in the line receptacle. This indicator stays on until the condition is resolved. Have a qualified electrician correct the wiring fault. The UPS operates when the indicator is illuminated, but does not provide rated noise and surge suppression.
Table 9. Troubleshooting
Alarm or Condition Possible Cause Action
button. If UPS status changes,
The indicator is not on;
µ
theUPSdoesnotstart.
The UPS operates in Battery mode only, even though normal utility power is present.
TheUPSdoesnotprovidethe expected backup time.
44
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
.
The power cord is not connected correctly.
The UPS is in Standby mode.
Thewalloutletisfaulty. Have a qualified electrician test and repair the
The input overcurrent protector is open (120V models only).
The batteries need charging or service.
Check the power cord connections.
Press and hold the button until you hear the UPS beep (approximately two seconds) to supply power to the connected equipment.
outlet.
Save your work and turn off your equipment. Turn off the UPS. Reduce the load, then press the input overcurrent protector on the UPS rear panel.
Plug the UPS into a power outlet for 24 hours to charge the battery. Press the button, if the alarm beeps, see “Replacing Batteries” on page 34 to replace thebattery. During extended power outages, turn off the UPS after saving your work and shutting down your computer to conserve battery power.
Page 51
Troubleshooting
ActionPossible CauseAlarm or Condition
Normal operation. None. The UPS is operating in Normal mode
and automatically provides consistent voltage with the Buck and Boost feature.
1 beep every 4 seconds.
1 beep every 2 seconds.
1 beep every 2 seconds.
1 beep per second.
1 beep per second.
The UPS is on battery due to a utility failure.
The battery is running low.
The UPS is running on battery power because the input voltage is too high or too low.
Power requirements exceed UPS capacity (overload is greater than 120%) or the load is defective.
The UPS is on battery, and the power requirements exceed UPS capacity (overload is greater than 120%) or the load is defective.
The UPS is powering your equipment with battery power. Prepare your equipment for shutdown. If this is an extended power outage, save your work and turn off your equipment to conserve battery power.
Two minutes or less of battery power remains (depending on load configuration and battery charge).
Save your work and turn off your equipment. Thealarmcannotbesilenced.
Correct the input voltage, if possible. The UPS continues to operate on battery until the condition is corrected or the battery is completely discharged. If the condition persists, the input voltage in your area may differ from the UPS nominal. Change the UPS input voltage to match your local voltage (see “Voltage Configuration” on page 29).
The UPS will automatically shut down in 3 minutes. Save your work immediately and turn off your equipment. Turn off the UPS.
Remove some of the equipment from the UPS. You may need to obtain a larger capacity UPS.
Shutdown is imminent (30 seconds). Save your work and turn off your equipment. Turn off and unplug the UPS.
Remove some of the equipment from the UPS. Wait at least 5 seconds until all LEDs are off and restart the UPS. You may need to obtain a larger capacity UPS.
Continuous beep.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Battery test failed. Check the battery connections and be sure the
battery is fully charged. If the indicator still flashes, see “Replacing Batteries” on page 34 to replace the battery. Call
Customer Service if the problem persists.
45
Page 52
Troubleshooting
ActionPossible CauseAlarm or Condition
Continuous beep.
Continuous beep.
3 beeps every 10 seconds.
Continuous beep.
UPS internal temperature is too high.
UPS fan fault (750–1400 VA models only).
Failed attempt to start the UPS on battery.
Theoutputwaveis abnormal while the UPS is on battery.
Shutdown is imminent. Save your work and turn off your equipment. Turn off the UPS. Clear vents and remove any heat sources. Ensure the airflow around the UPS is not restricted. Wait at least 5 minutes and restart the UPS. If the condition persists, contact Customer Service.
Save your work and turn off your equipment. Turn off the UPS. Contact Customer Service.
Plug the UPS into a power outlet for 24 hours to charge the battery. After charging the battery, press and hold the button for 3 seconds; then check the indicator. If the indicator still flashes, see “Replacing Batteries” on page 34 to replace the battery.
Shutdown is imminent. Save your work and turn off your equipment. Turn off the UPS. Contact Customer Service.
46
Continuous beep.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Theoutputvoltageis below or above the limit while the UPS is on battery.
Save your work and turn off your equipment. Turn off the UPS. Contact Customer Service.
Page 53
Service and Support
If you have any questions or problems with the UPS, call NCR at 1-800-262-7782 and ask for a UPS technical representative.
Please have the following information ready when you call Customer Service:
Model numberSerial numberVersion number (if available)Date of failure or problemSymptoms of failure or problemCustomer return address and contact information
If repair is required, you will be given a Returned Material Authorization (RMA) Number. This number must appear on the outside of the package and on the Bill Of Lading (if applicable). Use the original packaging or request packaging from the Customer Service or the distributor. Units damaged in shipment as a result of improper packaging are not covered under warranty. A replacement or repair unit will be shipped, freight prepaid by NCR for all warrantied units.
Troubleshooting
NOTE For critical applications, immediate replacement may be
available. Call nearest you.
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Customer Service for the dealer or distributor
47
Page 54
Troubleshooting
NCR Limited Warranty
This warranty applies to uninterruptible power system (UPS) products you purchase from NCR Corporation (“NCR”) and use in the United States, unless you have another applicable written agreement with NCR. You indicate your acceptance of this NCR Limited Warranty by your initial use of your NCR products. Any software warranties are contained in the “break seal” license agreement shipped with the software or any other applicable written agreement you may have with NCR.
What Is Covered
The failure of any NCR UPS to operate in accordance with its specifications during the period of this warranty.
What We Will Do
If your NCR product becomes defective within 3 years of the date of purchase, we will repair it or, at our option, replace it at no charge to you. You may call the number listed below for dispatch of an NCR service representative for on-site repair or replacement. All warranty service will be subject to NCR’s standard policies.
If we repair your NCR product, we may use new or reconditioned parts. If we choose to replace your NCR product, we may replace it with a new or reconditioned one of the same or similar design. The repair or replacement will be warranted for either (a) 90 days or (b) the remainder of the original warranty period, whichever is longer.
Limitations
IF YOU ARE A CONSUMER UNDER APPLICABLE LAW, ALL EXPRESS AND IMPLIED WARRANTIES, INCLUDING THOSE OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY (AN UNWRITTEN WARRANTY THAT THE PRODUCT IS FIT FOR ORIGINAL USE) ARE LIMITED TO ONE YEAR FROM THE DATE YOU PURCHASED YOUR NCR PRODUCT. IF YOU ARE NOT A CONSUMER, THERE ARE NO IMPLIED WARRANTIES, INCLUDING THOSE OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY. WE WILL NOT PAY FOR LOSS OF TIME, INCONVENIENCE, LOSS OF DATA, LOSS OF USE OF YOUR NCR PRODUCT, OR PROPERTY DAMAGE CAUSED B Y YOUR NCR PRODUCT OR ITS FAILURE TO WORK, OR ANY OTHER DIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES.
Some states do not allow limitations on how long an implied warranty lasts, or the exclusion or limitation of incidental or consequential damages, so those aspects of the above limitations or exclusions may not apply to you.
What We Ask You To Do
To get warranty service for your NCR product, you must provide proof of the date of purchase. Call us toll free at the number below to report problems or for the address of an authorized service location. If you ship your NCR product to the authorized service location, you must prepay all shipping costs. We suggest you retain your original packing material in the event you need to ship your NCR product. When sending your NCR product to a service location, include you name, address, phone number, proof of date of purchase, and a description of the operating problem. After repairing or replacing your NCR product, we will ship it to your business or home (if you are a consumer) in the United States at no cost to you.
48
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Page 55
Troubleshooting
What This Warranty Does Not Cover
This warranty does not cover defects resulting from accidents, damage while in transit to our service location, alterations, unauthorized repair, failure to follow instructions, misuse, use outside the United States, fire, floods, acts of God. If your NCR product is not covered by our warranty, call us toll free at the number below for advice as to whether we will repair your NCR product and other repair information, including charges. We, at our option, may replace rather than repair your NCR product with a new or reconditioned one of the same or similar design. The repair or replacement will be warranted for 90 days or the remainder of the original warranty period, whichever is longer.
This limited warranty is the only one we give on your NCR product, and it sets forth all our responsibilities regarding your NCR product. There are no other express warranties. Repair or replacement of your NCR product during the warranty period is your exclusive remedy.
Dispute Resolution
Any controversy or claim between you a nd NCR regarding NCR products or services will be resolved by binding arbitration under the current rules and supervision of the American Arbitration Association. The Arbitrator’s decision and award will be final and binding and may be entered in any court with jurisdiction.
State Law Rights
This warranty gives you specific legal rights, and you may also have other legal rights which vary from state to state.
The number to call is:
1-800-262-7782
NCR 4072 UPS Site P reparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
49
Page 56
Troubleshooting
50