National Instruments cRIO-9002, cRIO-9004 User Manual

Page 1
National Instruments cRIO-9004 Manual
Get Pricing & Availability at
ApexWaves.com
Call Today: 1-800-915-6216
Email: sales@apexwaves.com
https://www.apexwaves.com/modular-systems/national-instruments/compactrio-controllers/cRIO-9004
Page 2
USER MANUAL AND SPECIFICATIONS
NI cRIO-9002/9004
Intelligent Real-Time Embedded Controller for CompactRIO
Figure 1. CompactRIO cRIO-9002/9004
2
6
1
3
45
INPUT 9–35 V 17 W MAX
__
---
1. LEDs
2. Power Connector
3. DIP Switches
4. Reset Button
5. RJ-45 Ethernet Port
6. RS-232 Serial Port
This document describes how to connect the cRIO-9002/9004 to a network and how to use the features of the cRIO-9002/9004. This document also contains specifications for the controllers.
Page 3
Safety Guidelines
Caution Do not operate the cRIO-9002/9004 in a manner not specified in this
document. Product misuse can result in a hazard. You can compromise the safety protection built into the product if the product is damaged in any way. If the product is damaged, return it to NI for repair.
Safety Guidelines for Hazardous Locations
The cRIO-9002/9004 is suitable for use in Class I, Division 2, Groups A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC T4 and Ex nA IIC T4 hazardous locations; and nonhazardous locations only. Follow these guidelines if you are installing the cRIO-9002/9004 in a potentially explosive environment. Not following these guidelines may result in serious injury or death.
Caution Do not disconnect I/O-side wires or connectors unless power has been
switched off or the area is known to be nonhazardous.
Caution Do not remove modules unless power has been switched off or the area is
known to be nonhazardous.
Caution Substitution of components may impair suitability for Class I, Division 2.
Caution For Division 2 and Zone 2 applications, install the system in an enclosure
rated to at least IP54 as defined by IEC/EN 60079-15.
Special Conditions for Hazardous Locations Use in Europe and Internationally
The cRIO-9002/9004 has been evaluated as Ex nA IIC T4 Gc equipment under DEMKO Certificate No. 03 ATEX 0324020X and is IECEx UL 14.0089X certified. Each device is marked II 3G and is suitable for use in Zone 2 hazardous locations, in ambient temperatures of -40 °C ≤ Ta ≤ 70 °C.
Caution You must make sure that transient disturbances do not exceed 140% of
the rated voltage.
Caution The system shall only be used in an area of not more than Pollution
Degree 2, as defined in IEC 60664-1.
Caution The system shall be mounted in an ATEX/IECEx-certified enclosure with
a minimum ingress protection rating of at least IP54 as defined in IEC/EN 60079-15.
Caution The enclosure must have a door or cover accessible only by the use of a
tool.
2 | ni.com | NI cRIO-9002/9004 User Manual and Specifications
Page 4
Electromagnetic Compatibility Guidelines
This product was tested and complies with the regulatory requirements and limits for electromagnetic compatibility (EMC) stated in the product specifications. These requirements and limits provide reasonable protection against harmful interference when the product is operated in the intended operational electromagnetic environment.
This product is intended for use in industrial locations. However, harmful interference may occur in some installations, when the product is connected to a peripheral device or test object, or if the product is used in residential or commercial areas. To minimize interference with radio and television reception and prevent unacceptable performance degradation, install and use this product in strict accordance with the instructions in the product documentation.
Furthermore, any changes or modifications to the product not expressly approved by National Instruments could void your authority to operate it under your local regulatory rules.
Special Conditions for Marine Applications
Some products are Lloyd’s Register (LR) Type Approved for marine (shipboard) applications. To verify Lloyd’s Register certification for a product, visit ni.com/certification and search for the LR certificate, or look for the Lloyd’s Register mark on the product.
Caution In order to meet the EMC requirements for marine applications, install the
product in a shielded enclosure with shielded and/or filtered power and input/output ports. In addition, take precautions when designing, selecting, and installing measurement probes and cables to ensure that the desired EMC performance is attained.
Installing the Controller on the Chassis
The following figure shows the dimensions of the cRIO-9002/9004.
NI cRIO-9002/9004 User Manual and Specifications | © National Instruments | 3
Page 5
Figure 2. cRIO-9002/9004, Front and Bottom View with Dimensions
77.3 mm (3.04 in.)
90.2 mm (3.55 in.)
44.2 mm (1.74 in.)
88.1 mm (3.47 in.)
44.2 mm (1.74 in.)
1
1. M4 Thread
Complete the following steps to install the controller on the chassis.
1. Make sure that no power is connected to the controller or the chassis.
2. Align the controller with the chassis as shown in the following figure.
4 | ni.com | NI cRIO-9002/9004 User Manual and Specifications
Page 6
Figure 3. Installing the cRIO-9002/9004 in the Chassis
1
4
3
2
1. Controller
2. Captive Screws
3. Controller Slot
4. Reconfigurable Embedded Chassis
3. Slide the controller onto the controller slot on the chassis. Press firmly to ensure the chassis connector and the controller connector are mated.
4. Using a number 2 Phillips screwdriver, tighten the two captive screws on the front of the controller to 1.3 N · m (11.5 lb · in.) of torque.
Connecting the Controller to a Network
Connect the controller to an Ethernet network using the RJ-45 Ethernet port on the controller front panel. Use a standard Category 5 (CAT-5) or better shielded, twisted-pair Ethernet cable to connect the chassis to an Ethernet hub, or use an Ethernet crossover cable to connect the chassis directly to a computer.
Caution To prevent data loss and to maintain the integrity of your Ethernet
installation, do not use a cable longer than 100 m. If you are using 100 Mbps Ethernet, National Instruments recommends using a CAT-5 or better shielded twisted-pair Ethernet cable.
If you need to build your own cable, refer to the Cabling section for more information about Ethernet cable wiring connections.
The host computer communicates with the controller over a standard Ethernet connection. If the host computer is on a network, you must configure the controller on the same subnet as the
NI cRIO-9002/9004 User Manual and Specifications | © National Instruments | 5
Page 7
host computer. If neither the host computer nor the CompactRIO controller is connected to a network, you can connect the two directly using a crossover cable.
If you want to use the controller on a subnet other than the one the host computer is on, first connect the controller on the same subnet as the host computer. Use DHCP to assign an IP address or reassign a static IP address for the subnet where you want it to be and physically move it to the other subnet. The first time you configure the controller, you must also install software on it. Refer to the Measurement & Automation Explorer Help for more information about configuring the controller in Measurement & Automation Explorer (MAX). Contact your network administrator if you need assistance configuring the host computer and controller on the same subnet.
Wiring Power to the Controller
Caution You must install the controller on a CompactRIO chassis and tighten the
captive screws before you apply power to the controller. Installing the controller while power is applied to it can cause damage to the chassis.
The cRIO-9002/9004 requires an external power supply that meets the specifications in the
Power Requirements section. The cRIO-9002/9004 filters and regulates the supplied power
and provides power for all of the I/O modules in the chassis. You can connect two power sources to the cRIO-9002/9004. The cRIO-9002/9004 draws power from the power source with the higher voltage. The cRIO-9002/9004 has one layer of reversed-voltage protection. The power source you connect to the cRIO-9002/9004 must provide an additional layer of reversed-current flow protection. Complete the following steps to connect power sources to the cRIO-9002/9004.
1. Install a ferrite across the negative and positive wires for both the V1 and V2 terminals.
6 | ni.com | NI cRIO-9002/9004 User Manual and Specifications
Page 8
Figure 4. Wiring Power to the cRIO-9002/9004
V1
V2
C
C
2. Connect the positive lead of one of the power sources to the V1 terminal and the negative lead to one of the C terminals.
3. Connect the positive lead of the other power source to the V2 terminal and the negative lead to one of the C terminals.
Note The controller draws power from either V1 or V2 depending on which
terminal has a higher voltage. It does not draw power from both terminals.
Caution The C terminals are internally connected to each other. Make sure to
use two power sources that have a common ground.
Powering On the cRIO-9002/9004
Plug in each power supply to the CompactRIO system. The controller runs a power-on self test (POST). During the POST, the Power, Status, and User1 LEDs turn on. The User1 and Status LEDs turn off, indicating that the POST is complete.
Boot Options
You can configure the controller to launch an embedded stand-alone application each time you boot the controller. Refer to the LabVIEW Help for more information.
The following table lists the reset options available on CompactRIO backplanes, such as the cRIO-910x devices. Use these options to determine how the CompactRIO controllers, such as the cRIO-9002/9004 controllers, are reset in various conditions.
NI cRIO-9002/9004 User Manual and Specifications | © National Instruments | 7
Page 9
Table 1. CompactRIO Reset Options
Backplane Reset Option Controller Behavior
Do Not Autoload on Reset Does not load the FPGA bit stream from flash memory
Autoload on Power-On Reset Loads the FPGA bit stream from flash memory to the
FPGA when the controller powers on.
Autoload on Any Device Reset Loads the FPGA bit stream from flash to the FPGA when
you reboot the controller either with or without cycling power.
Connecting Serial Devices to the cRIO-9002/9004
The cRIO-9002/9004 has an RS-232 serial port to which you can connect devices such as displays or input devices. Use the Serial VIs to read from and write to the serial port from a LabVIEW Real-Time application. For more information about the Serial VIs, refer to the LabVIEW Help.
Figure 5. Controller Serial Port
Pin 1
Pin 5
Pin 6
Pin 9
Table 2. DB-9 Pin Descriptions
Pin Signal
1 DCD
2 RXD
3 TXD
4 DTR
5 GND
6 DSR
7 RTS
8 CTS
9 RI
8 | ni.com | NI cRIO-9002/9004 User Manual and Specifications
Page 10
Configuring DIP Switches
Figure 6. DIP Switches
SAFE MODE
CONSOLE OUT
IP RESET
NO APP
USER1
ON OFF
All of the DIP switches are in the OFF position when the chassis is shipped from National Instruments.
SAFE MODE Switch
The position of the SAFE MODE switch determines whether the embedded LabVIEW Real­Time engine launches at startup. If the switch is in the OFF position, the LabVIEW Real-Time engine launches. Keep this switch in the OFF position during normal operation. If the switch is in the ON position at startup, the cRIO-9002/9004 launches only the essential services required for updating its configuration and installing software. The LabVIEW Real-Time engine does not launch.
If the software on the controller is corrupted, you must put the controller into safe mode and reformat the controller drive. You can put the controller into safe mode by powering it up either with the SAFE MODE switch in the ON position or with no software installed on the drive. Refer to the Measurement & Automation Explorer Help for more information about installing software on a controller and reformatting the drive on the controller.
CONSOLE OUT Switch
With a serial-port terminal program, you can use the CONSOLE OUT switch to read the IP address and firmware version of the controller. Use a null-modem cable to connect the serial port on the chassis to a computer. Push the switch to the ON position. Make sure that the serial-port terminal program is configured to the following settings:
9,600 bits per second
Eight data bits
No parity
One stop bit
The serial-port terminal program displays the IP address and firmware version. Keep this switch in the OFF position during normal operation.
IP RESET Switch
Push the IP RESET switch to the ON position and reboot the controller to reset the IP address and other TCP/IP settings of the controller to the factory defaults. Refer to the Troubleshooting Network Communication section for more information about resetting the IP address. You also
NI cRIO-9002/9004 User Manual and Specifications | © National Instruments | 9
Page 11
can push this switch to the ON position to unlock a chassis that was previously locked in MAX.
NO APP Switch
Push the NO APP switch to the ON position to prevent a LabVIEW Real-Time startup application from running at startup. If you want to permanently disable a LabVIEW Real-Time application from running at startup, you must disable it in LabVIEW. To run an application at startup, push the NO APP switch to the OFF position, create an application using the LabVIEW Application Builder, and configure the application in LabVIEW to launch at startup. If you already have an application configured to launch at startup and you push the NO APP switch from ON to OFF, the startup application is automatically enabled. For more information about automatically launching VIs at startup and disabling VIs from launching at startup, refer to the LabVIEW Help.
USER1 Switch
You can define the USER1 switch for your application. To define the purpose of this switch in your embedded application, use the RT Read Switch VI in your LabVIEW Real-Time embedded VI. For more information about the RT Read Switch VI, refer to the LabVIEW Help.
Understanding LED Indications
Figure 7. cRIO-9002/9004 LEDs
1 2 3 4
1. POWER
2. BACKUP
3. STATUS
4. USER1
POWER LED
The POWER LED is lit while the cRIO-9002/9004 is powered on. This LED indicates that the power supply connected to the chassis is adequate.
BACKUP LED
The Backup LED is lit when the controller is drawing power from the V2 terminal.
STATUS LED
The STATUS LED is off during normal operation. The cRIO-9002/9004 indicates specific error conditions by flashing the STATUS LED a certain number of times every few seconds, as shown in the following table
10 | ni.com | NI cRIO-9002/9004 User Manual and Specifications
Page 12
Number of Flashes
Every Few
Seconds Indication
Slow, continuous flashing (one flash every couple seconds)
The controller is unconfigured. Use MAX to configure the controller. Refer to the Measurement & Automation Explorer Help for information about configuring the controller.
2
The controller has detected an error in its software. This usually occurs when an attempt to upgrade the software is interrupted. Reinstall software on the controller. Refer to the Measurement & Automation Explorer Help for information about installing software on the controller.
3
The controller is in safe mode because the SAFE MODE DIP switch is in the ON position or there is no software installed on the controller.
4
The software has crashed twice without rebooting or cycling power between crashes. This usually occurs when the controller runs out of memory. Review your RT VI and check the memory usage. Modify the VI as necessary to solve the memory usage issue.
Continuously blinking
The controller has detected an unrecoverable error. Contact National Instruments.
Solid
The flash memory card on the controller is corrupt. Reformat the hard drive on the controller. Refer to Measurement & Automation Explorer Help for more information about reformatting the hard drive.
USER1 LED
You can define the USER1 LED to meet the needs of your application. To define the LED, use the RT LEDs VI in LabVIEW. For more information about the RT LEDs VI, refer to the LabVIEW Help.
Resetting the Network Configuration of the Controller
If the controller is not able to communicate with the network, you can manually restore the unit to the factory network settings. When you reset the controller, the IP address, subnet mask, DNS address, gateway, and Time Server IP are set to 0.0.0.0. Resetting does not affect power-on defaults, watchdog settings, or VIs.
Complete the following steps to reset the controller.
1. Move the IP Reset DIP switch to the ON position.
2. Push the Reset button to cycle power to the controller. The Status LED flashes once, indicating that the controller IP address is unconfigured.
NI cRIO-9002/9004 User Manual and Specifications | © National Instruments | 11
Page 13
3. Move the IP Reset switch to the OFF position.
The network settings are restored. You can reconfigure the settings in MAX from a computer on the same subnet. Refer to the Measurement & Automation Explorer Help for more information about configuring the controller.
cRIO-9002/9004 Specifications
The following specifications are typical for the range -40 °C to 70 °C unless otherwise noted.
Caution Do not operate the cRIO-9002/9004 in a manner not specified in this
document. Product misuse can result in a hazard. You can compromise the safety protection built into the product if the product is damaged in any way. If the product is damaged, return it to NI for repair.
Network
Network interface 10Base-T and 100Base-TX Ethernet
Compatibility IEEE 802.3
Communication rates 10 Mbps, 100 Mbps, auto-negotiated
Maximum cabling distance 100 m/segment
RS-232 Serial Port
Maximum baud rate 115,200 bps
Data bits 5, 6, 7, 8
Stop bits 1, 2
Parity Odd, Even, Mark, Space
Flow control RTS/CTS, XON/XOFF, DTR/DSR
Memory
cRIO-9002
Nonvolatile 64 MB
DRAM 32 MB
cRIO-9004
Nonvolatile 512 MB
DRAM 64 MB
12 | ni.com | NI cRIO-9002/9004 User Manual and Specifications
Page 14
MTBF
The following MTBF specifications apply to the cRIO-9002/9004.
MTBF 1,253,788 hours at 25 °C; Bellcore Issue 6,
Method 1, Case 3, Parts Count Method
Power Requirements
You must use a National Electric Code (NEC) Class 2 power source with the cRIO-9002/9004.
Recommended power supply 48 W secondary, 18 VDC to 24 VDC
Power consumption
Controller only 7 W maximum
Controller supplying power to eight CompactRIO modules
17 W
Power supply
On powerup 9 V to 35 V
After powerup 6 V to 35 V
Note The cRIO-9002/9004 powers up only at 9 V or higher, but when these
devices are powered on, they can run on as little as 6 V.
Physical Characteristics
If you need to clean the module, wipe it with a dry towel.
Tip For two-dimensional drawings and three-dimensional models of the C Series
module and connectors, visit ni.com/dimensions and search by module number.
Screw-terminal wiring
Gauge 0.5 mm 2 to 2.1 mm2 (20 AWG to 14 AWG)
copper conductor wire
Wire strip length 7 mm (0.28 in.) of insulation stripped from the
end
Temperature rating 85 °C
Torque for screw terminals 0.5 N · m to 0.6 N · m (4.4 lb · in. to
5.3 lb · in.)
Wires per screw terminal One wire per screw terminal
Ferrules 0.25 mm2 to 1.5 mm
2
NI cRIO-9002/9004 User Manual and Specifications | © National Instruments | 13
Page 15
Connector securement
Securement type Screw flanges provided
Torque for screw flanges 0.3 N · m to 0.4 N · m (2.7 lb · in. to
3.5 lb · in.)
Dimensions 90.2 mm × 77.3 mm × 88.1 mm
(3.6 in. × 3.0 in. × 3.5 in.)
Weight 488 g (17.2 oz)
Safety Voltages
Connect only voltages that are within the following limits:
V terminal to C terminal 35 V maximum, Measurement Category I
Measurement Category I is for measurements performed on circuits not directly connected to the electrical distribution system referred to as MAINS voltage. MAINS is a hazardous live electrical supply system that powers equipment. This category is for measurements of voltages from specially protected secondary circuits. Such voltage measurements include signal levels, special equipment, limited-energy parts of equipment, circuits powered by regulated low­voltage sources, and electronics.
Note Measurement Categories CAT I and CAT O are equivalent. These test and
measurement circuits are not intended for direct connection to the MAINS building installations of Measurement Categories CAT II, CAT III, or CAT IV.
Caution Do not connect the cRIO-9002/9004 to signals or use for measurements
within Measurement Categories II, III, or IV.
Safety and Hazardous Locations Standards
This product is designed to meet the requirements of the following electrical equipment safety standards for measurement, control, and laboratory use:
IEC 61010-1, EN 61010-1
UL 61010-1, CSA 61010-1
EN 60079-0:2012, EN 60079-15:2010
IEC 60079-0: Ed 6, IEC 60079-15; Ed 4
UL 60079-0; Ed 5, UL 60079-15; Ed 3
CSA 60079-0:2011, CSA 60079-15:2012
Note For UL and other safety certifications, refer to the product label or the Online
Product Certification section.
14 | ni.com | NI cRIO-9002/9004 User Manual and Specifications
Page 16
Hazardous Locations
U.S. (UL) Class I, Division 2, Groups A, B, C, D, T4;
Class I, Zone 2, AEx nA IIC T4
Canada (C-UL) Class I, Division 2, Groups A, B, C, D, T4;
Class I, Zone 2, Ex nA IIC T4
Europe (ATEX) and International (IECEx) Ex nA IIC T4 Gc
Electromagnetic Compatibility
EN 55011 Class A at 10 m FCC Part 15A above 1 GHz
Industrial levels per EN 61326:1997 + A2:2001, Table A.1
CE, C-Tick, and FCC Part 15 (Class A) Compliant
Caution To ensure the specified EMC performance, operate this product only with
shielded cables and accessories.
CE Compliance
This product meets the essential requirements of applicable European Directives, as follows:
2014/35/EU; Low-Voltage Directive (safety)
2014/30/EU; Electromagnetic Compatibility Directive (EMC)
94/9/EC; Potentially Explosive Atmospheres (ATEX)
Online Product Certification
Refer to the product Declaration of Conformity (DoC) for additional regulatory compliance information. To obtain product certifications and the DoC for this product, visit ni.com/
certification, search by model number or product line, and click the appropriate link in the
Certification column.
Shock and Vibration
To meet these specifications, you must panel mount the system.
Operating vibration
Random (IEC 60068-2-64) 5 g
rms
, 10 Hz to 500 Hz
Sinusoidal (IEC 60068-2-6) 5 g, 10 Hz to 500 Hz
Operating shock (IEC 60068-2-27) 30 g, 11 ms half sine; 50 g, 3 ms half sine;
18 shocks at 6 orientations
NI cRIO-9002/9004 User Manual and Specifications | © National Instruments | 15
Page 17
Environmental
Refer to the manual for the chassis you are using for more information about meeting these specifications.
Operating temperature (IEC 60068-2-1, IEC 60068-2-2)
-40 °C to 70 °C
Storage temperature (IEC 60068-2-1, IEC 60068-2-2)
-40 °C to 85 °C
Ingress protection IP40
Operating humidity (IEC 60068-2-78) 10% RH to 90% RH, noncondensing
Storage humidity (IEC 60068-2-78) 5% RH to 95% RH, noncondensing
Pollution Degree 2
Maximum altitude 2,000 m
Indoor use only.
Environmental Management
NI is committed to designing and manufacturing products in an environmentally responsible manner. NI recognizes that eliminating certain hazardous substances from our products is beneficial to the environment and to NI customers.
For additional environmental information, refer to the Minimize Our Environmental Impact web page at ni.com/environment. This page contains the environmental regulations and directives with which NI complies, as well as other environmental information not included in this document.
Waste Electrical and Electronic Equipment (WEEE)
EU Customers At the end of the product life cycle, all NI products must be
disposed of according to local laws and regulations. For more information about how to recycle NI products in your region, visit ni.com/environment/weee.
电子信息产品污染控制管理办法(中国 RoHS
中国客户 National Instruments 符合中国电子信息产品中限制使用某些有害物
质指令(RoHS)。关于 National Instruments 中国 RoHS 合规性信息,请登录
ni.com/environment/rohs_china。(For information about China RoHS
compliance, go to ni.com/environment/rohs_china.)
Cabling
The following table shows the standard Ethernet cable wiring connections for both normal and crossover cables.
16 | ni.com | NI cRIO-9002/9004 User Manual and Specifications
Page 18
Table 3. Ethernet Cable Wiring Connections
Pin Connector 1 Connector 2 (Normal) Connector 2 (Crossover)
1 white/orange white/orange white/green
2 orange orange green
3 white/green white/green white/orange
4 blue blue blue
5 white/blue white/blue white/blue
6 green green orange
7 white/brown white/brown white/brown
8 brown brown brown
Figure 8. Ethernet Connector Pinout
Connector 1 Connector 2
Pin 1 Pin 1 Pin 8Pin 8
Worldwide Support and Services
The NI website is your complete resource for technical support. At ni.com/support, you have access to everything from troubleshooting and application development self-help resources to email and phone assistance from NI Application Engineers.
Visit ni.com/services for NI Factory Installation Services, repairs, extended warranty, and other services.
Visit ni.com/register to register your NI product. Product registration facilitates technical support and ensures that you receive important information updates from NI.
NI cRIO-9002/9004 User Manual and Specifications | © National Instruments | 17
Page 19
A Declaration of Conformity (DoC) is our claim of compliance with the Council of the European Communities using the manufacturer’s declaration of conformity. This system affords the user protection for electromagnetic compatibility (EMC) and product safety. You can obtain the DoC for your product by visiting ni.com/certification. If your product supports calibration, you can obtain the calibration certificate for your product at ni.com/calibration.
NI corporate headquarters is located at 11500 North Mopac Expressway, Austin, Texas, 78759-3504. NI also has offices located around the world. For telephone support in the United States, create your service request at ni.com/support or dial 1 866 ASK MYNI (275 6964). For telephone support outside the United States, visit the Worldwide Offices section of ni.com/
niglobal to access the branch office websites, which provide up-to-date contact information,
support phone numbers, email addresses, and current events.
Refer to the NI Trademarks and Logo Guidelines at ni.com/trademarks for information on NI trademarks. Other product and company names mentioned herein are trademarks or trade names of their respective companies. For patents covering NI products/technology, refer to the appropriate location: Help»Patents in your software, the patents.txt file on your media, or the National Instruments Patent Notice at ni.com/patents. You can find information about end-user license agreements (EULAs) and third-party legal notices in the readme file for your NI product. Refer to the Export Compliance Information at ni.com/
legal/export-compliance for the NI global trade compliance policy and how to obtain relevant HTS codes, ECCNs, and other
import/export data. NI MAKES NO EXPRESS OR IMPLIED WARRANTIES AS TO THE ACCURACY OF THE INFORMATION CONTAINED HEREIN AND SHALL NOT BE LIABLE FOR ANY ERRORS. U.S. Government Customers: The data contained in this manual was developed at private expense and is subject to the applicable limited rights and restricted data rights as set forth in FAR 52.227-14, DFAR 252.227-7014, and DFAR 252.227-7015.
© 2004—2016 National Instruments. All rights reserved.
373561E-01 Feb16
Loading...