National Instruments FP-DO-403, cFP-DO-403 User Manual

FIELDPOINT™ OPERATING INSTRUCTIONS AND SPECIFICATIONS
FP-DO-403 and cFP-DO-403
16-Channel, 5 to 30 V Sinking Digital Output Module
These operating instructions describe how to install and use the National Instruments FP-DO-403 and cFP-DO-403 digital output modules, referred to inclusively as the [c]FP-DO-403. For information about configuring and accessing the [c]FP-DO-403 over a network, refer to the user manual for the FieldPoint network module you are using.

Features

The [c]FP-DO-403 is a FieldPoint digital output module with the following features:
16 sinking digital output channels
Outputs that sink 2 A per channel, 16 A
Compatible with voltages from 5 to 30 VDC
250 V verified by 2,300 V
–40 to 70 °C operation
ON/OFF LED indicators
Hot swappable
CAT II continuous channel-to-ground isolation,
rms
, 5 s dielectric withstand test
rms
2
per module

Installing the FP-DO-403

The FP-DO-403 mounts on a FieldPoint terminal base (FP-TB-x), which provides operating power to the module. Installing the FP-DO-403 onto a powered terminal base does not disrupt the operation of the bank.
To install the FP-DO-403, refer to Figure 1 and complete the following steps:
1. Slide the terminal base key to either position X, used for any module, or position 6, used for the FP-DO-403 module.
2. Align the FP-DO-403 alignment slots with the guide rails on the terminal base.
3. Press firmly to seat the FP-DO-403 on the terminal base. When the module is firmly seated, the terminal base latch locks it into place.
4
5
3
6
1
1 I/O Module 2 Terminal Base
3 Alignment Slot 4Key

Figure 1. Installing the FP-DO-403

5 Latch 6 Guide Rails
2

Installing the cFP-DO-403

The cFP-DO-403 mounts on a Compact FieldPoint backplane (cFP-BP-x), which provides operating power to the module. Installing the cFP-DO-403 onto a powered backplane does not disrupt the operation of the bank.
To install the cFP-DO-403, refer to Figure 2 and complete the following steps:
1. Align the captive screws on the cFP-DO-403 with the screw holes on the backplane. The alignment keys on the cFP-DO-403 prevent backward insertion.
2. Press firmly to seat the cFP-DO-403 on the backplane.
3. Using a number 2 Phillips screwdriver with a shank of at least 64 mm (2.5 in.) length, tighten the captive screws to 1.1 N ⋅ m (10 lb in.) of torque. The nylon coating on the screws prevents them from loosening.
[c]FP-DO-403 2 ni.com
3 5
2
2
1
4
4
1 cFP I/O Module 2 Captive Screws 3 cFP Controller Module
4 Screw Holes 5 cFP Backplane

Figure 2. Installing the cFP-DO-403

Wiring the [c]FP-DO-403

The FP-TB-x terminal base has connections for each FP-DO-403 output channel and for an external supply to power field devices. The cFP-CB-x connector block provides the same connections for the cFP-DO-403.
Each channel has one output terminal, V share eight V
terminals and eight COM terminals. All of the
SUP
channels are referenced to the COM terminals. The V and V terminals are all internally connected, as are the C and COM terminals.
Use a 5–30 VDC external power supply for the output channels. The power supply must provide enough current to power all of the
© National Instruments Corp. 3 [c]FP-DO-403
. The output channels
OUT
SUP
loads on the output channels, up to 2 A per channel.1 Connect the external power supply to multiple V and V
terminals and
SUP
to multiple C and COM terminals as needed to ensure that the maximum current through any terminal is 2 A or less.
Install a 2 A maximum, fast-acting fuse (F2A 250V) between the external power supply and the V
terminal on each channel.
SUP
Install a 2 A maximum, fast-acting fuse suitable for the load at the V
terminal. Figure 3 shows fuses where appropriate.
OUT
Table 1 lists the terminal assignments for the signals associated with each channel. Terminal assignments and wiring diagrams are also listed on the side panel of the cFP-DO-403 and under the slide-in card on the front of the FP-DO-403 module.

Table 1. Terminal Assignments

Terminal Numbers
Channel
V
OUTVSUP
0 1 17 18 8 9 25 26
1 2 17 18 9 10 25 26
2 3 19 20 10 11 27 28
3 4 19 20 11 12 27 28
4 5 21 22 12 13 29 30
5 6 21 22 13 14 29 30
6 7 23 24 14 15 31 32
7 8 23 24 15 16 31 32
COM V
Channel
Terminal Numbers
OUTVSUP
COM
National Instruments recommends that you wire the external power supply to multiple V
and COM terminals. Figure 3
SUP
shows how to connect two output channels to loads.

Wiring for Low-Current Applications

If your application requires 2 A or less combined current through all channels of the [c]FP-DO-403, you can wire your application as shown in Figure 3. Install a 2 A maximum, fast-acting fuse (F2A 250V) between the external power supply and the V terminal as shown.
1
Refer to the Digital Output Circuit and Specifications sections for the maximum output current level on all channels.
[c]FP-DO-403 4 ni.com
2 A Max
User-Supplied
Fuse
V
V
[c]FP-DO-403
SUP
V
OUT
V
OUT
COM
C
Load
Load
5–30 VDC
External Power
Supply
+

Figure 3. Wiring for Low-Current Applications

Wiring for High-Current Applications

If your application requires more than 2 A combined current through all channels of the [c]FP-DO-403, wire your application as shown in Figure 4. Install a 2 A maximum, fast-acting fuse (F2A 250V) in series with each load as shown.
2 A Max
User-Supplied
Fuse
V
2 A Max
User-Supplied
Fuse
Load
2 A Max
User-Supplied
Fuse
Load
5–30 VDC
External Power
Supply
+
[c]FP-DO-403
V
SUP
V
OUT
V
OUT
COM
C

Figure 4. Wiring for High-Current Applications

© National Instruments Corp. 5 [c]FP-DO-403