National Instruments FP-CTR-502, CFP-CTR-502 User Manual

FP-CTR-502 and cFP-CTR-502
Eight-Channel, 16-Bit Counter Module
These operating instructions describe how to install and use the National Instruments FP-CTR-502 and cFP-CTR-502 counter modules (referred to inclusively as the [c]FP-CTR-502). For information about configuring and accessing the [c]FP-CTR-502 over a network, refer to the user manual for the FieldPoint network module you are using.

Features

The [c]FP-CTR-502 is a FieldPoint counter module with the following features:
Eight 16-bit counters with individual count-input terminals
Four gate-input channels configurable as either gates or digital inputs
Four output channels configurable as either generic digital outputs or associated outputs for the count-input channels
5–30 VDC sourcing inputs and sinking outputs, compatible with TTL devices and other 5, 12, and 24 VDC devices
Internal frequency references of 1 kHz and 32 kHz
Internally cascadable counters
Software-enabled 50 kHz or 200 Hz lowpass filter on count-input channels
On/Off LED indicators
2,300 V
Hot swappable
transient overvoltage protection
rms
FieldPoint™, National Instruments™, NI™, and ni.com™ are trademarks of National Instruments Corporation. Product and company names mentioned herein are trademarks or trade names of their respective companies. For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software, the
patents.txt file on your CD, or ni.com/patents.
323324B-01 June 2003
© 2002–2003 National Instruments Corp. All rights reserved.

Installing the FP-CTR-502

The FP-CTR-502 mounts on a FieldPoint terminal base (FP-TB-x), which provides operating power to the module. Installing the FP-CTR-502 onto a powered terminal base does not disrupt the operation of the FieldPoint bank.
To install the FP-CTR-502, refer to Figure 1 and complete the following steps:
1. Slide the terminal base key to either position X, used for any module, or position 8, used for the FP-CTR-502 module.
2. Align the FP-CTR-502 alignment slots with the guide rails on the terminal base.
3. Press firmly to seat the FP-CTR-502 on the terminal base. When the module is firmly seated, the terminal base latch locks it into place.
Key
Latch
Alignment
Slot
Guide Rails
Terminal BaseI/O Module

Figure 1. Installing the FP-CTR-502

Installing the cFP-CTR-502

The cFP-CTR-502 mounts on a Compact FieldPoint backplane (cFP-BP-x), which provides operating power to the module. Installing the cFP-CTR-502 onto a powered backplane does not disrupt the operation of the FieldPoint bank.
To install the cFP-CTR-502, refer to Figure 2 and complete the following steps:
1. Align the captive screws on the cFP-CTR-502 with the holes on the backplane. The alignment keys on the cFP-CTR-502 prevent backward insertion.
FP-CTR-502 and cFP-CTR-502 2 ni.com
2. Press firmly to seat the cFP-CTR-502 on the backplane.
3. Using a number 2 Phillips screwdriver with a shank of at least 64 mm (2.5 in.) length, tighten the captive screws to 1.1 N ⋅ m (10 lb in.) of torque. The nylon coating on the screws prevents them from loosening.
3 5
2
2
1
1 cFP I/O Module 2 Captive Screws 3 cFP Controller

Figure 2. Installing the cFP-CTR-502

4
4
4 Screw Holes 5 cFP Backplane

Wiring the [c]FP-CTR-502

The FP-TB-x terminal base has connections for each FP-CTR-502 channel and for an external power supply to power the input channels and field devices. The cFP-CB-x connector block provides the same connections for the cFP-CTR-502. The V and V
terminals are all internally connected, as are the C and COM
SUP
terminals.
© National Instruments Corp. 3 FP-CTR-502 and cFP-CTR-502
Use a 5–30 VDC external power supply for the input channels. The power supply must provide enough current to power all of the input channels and all of the field devices on the output channels. Connect the external power supply to multiple V and V
SUP
terminals and to multiple C and COM terminals as needed to ensure that the maximum current through any terminal is 2 A or less.
Install a 2 A maximum, fast-acting fuse between the external power supply and the V or V a 1 A maximum, fast-acting fuse suitable for the load at the V
terminal on each channel. Install
SUP
OUT
terminal. The detailed wiring diagrams in this document show fuses where appropriate.
Table 1 lists the terminal assignments for the signals of each channel. Terminal assignments are also listed on the side panel of the cFP-CTR-502 and under the slide-in card on the front of the FP-CTR-502.

Table 1. Terminal Assignments

Ter m i n a l Nu m b e rs
Channel Name
Count Input 0 1 17 18
Count Input 1 2 17 18
Count Input 2 3 19 20
Count Input 3 4 19 20
Count Input 4 5 21 22
Count Input 5 6 21 22
Count Input 6 7 23 24
Count Input 7 8 23 24
Gate 0 9 25 26
Gate 1 10 25 26
Gate 2 11 27 28
Gate 3 12 27 28
VIN or V
1
OUT
Count Inputs
Gate Inputs
2
V
SUP
COM
FP-CTR-502 and cFP-CTR-502 4 ni.com
Table 1. Terminal Assignments (Continued)
Ter m i n a l Nu m b e rs
Channel Name
Output 0 13 29 30
Output 1 14 29 30
Output 2 15 31 32
Output 3 16 31 32
1
Install a 1 A maximum, fast-acting fuse on each V
2
Install a 2 A maximum, fast-acting fuse on each V and V
VIN or V
1
OUT
Outputs
2
V
SUP
OUT
COM
terminal.
terminal.
SUP

Inputs

Each input channel has one input terminal, VIN. Each channel also has V devices or provide additional connections to the external power supply. You can connect the eight count-input channels and four gate-input channels to devices with sinking outputs. The [c]FP-CTR-502 has sourcing inputs, which means that the V terminal provides a path to a voltage supply.
The [c]FP-CTR-502 input channels are optically isolated from the rest of the FieldPoint bank and have current-limiting circuitry. All the input channels are referenced to the V and V In the ON state, an optoisolator is turned on between the positive external supply voltage (V and V
When choosing your external devices and power supply, keep in mind that the input-logic thresholds are defined by the power supply as detailed in the Specifications section.
where V
When V the channel is ON. Therefore, if you connect a 24 V power supply to the [c]FP-CTR-502, an input channel registers an ON state when
and COM terminals that can supply power to field
SUP
) and the input (VIN).
SUP
V
is the threshold voltage for the channel
threshold
is the supply voltage, measured across V
V
SUP
and COM
has a value of 2–3 V
V
K
, the voltage across VIN and COM, is lower than V
IN
threshold
= V
SUP
– V
K
terminals.
SUP
SUP
IN
threshold
,
© National Instruments Corp. 5 FP-CTR-502 and cFP-CTR-502
VIN is 21 V or lower, and an OFF state when VIN is 22 V or higher.
The channel state is indeterminate when V and22V.
is between 21 V
IN
Ensure that the sinking-output devices have OFF state leakage currents of less than 0.3 mA so they do not send false ON state readings to the [c]FP-CTR-502.
Note Yo u must use the same ground for all of the input
and output channels on the [c]FP-CTR-502.
+
5–30 VDC
External
2 A max
Power Supply
VC
To next channel
Sinking-
Output
Device
V
SUP
V
COM
IN
Sourcing-
Input
Circuitry
[c]FP-CTR-502
Figure 3. Wiring a Count-Input or Gate-Input Channel to a
Sinking-Output Device

Outputs

Each output channel has one output terminal, V also has V
and COM terminals that can supply power to field
SUP
devices.
The [c]FP-CTR-502 has sinking outputs, which means that V provides a path to ground. You can connect the [c]FP-CTR-502 outputs to sourcing-input devices.
In the ON state, a transistor is turned on between the output (V and common (C and COM). In the OFF state, this transistor is turned off, allowing only a small leakage current to flow. Ensure that the load on any output channel does not draw more than 1 A.
. Each channel
OUT
OUT
OUT
)
FP-CTR-502 and cFP-CTR-502 6 ni.com
2 A max
+–
5–30 VDC
External
Power Supply
VC
Sinking-
Output
Circuitry
To next channel
[c]FP-CTR-502
V
SUP
V
OUT
COM
1 A max
Load

Figure 4. Wiring an Output Channel to a Sourcing-Input Device

If you connect a [c]FP-CTR-502 output to an externally powered sourcing-input device, be aware that the voltage applied to the V
terminal by the external device must not exceed the voltage
OUT
level of the power supply connected to the [c]FP-CTR-502.
V
SUP
+
V
To next channel
[c]FP-CTR-502
5–30 VDC
Power Supply
C
Sinking-
Output
Circuitry
External
V
SUP
V
OUT
COM
1 A max
Load
V
SUP
External
Power Supply
+

Figure 5. Wiring an Output to an Externally Powered Sourcing-Input Device

© National Instruments Corp. 7 FP-CTR-502 and cFP-CTR-502