INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER.
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS, CSA 2.33, ANSI Z21.88 FOR VENTED GAS FIREPLACE HEATERS
INSTALLATION AND OPERATION INSTRUCTIONS FOR:
VENTED GAS FIREPLACE HEATER
1
NATURAL GAS MODELS GDS60-N and GS60-N
Model GS60 is made up of Model GDS60 and the Adapter Kit GS-150KT
WARNING: If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapours and liquids in the vicin-
ity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your build ing.
Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada • (705)721-1212 • fax(705)722-6031
www.napoleonfireplaces.com • ask@napoleon.on.ca
W415-0158 / E / 02.19.04
2
r
TABLE of CONTENTS
Pg
2-4 INTRODUCTION
Warranty General Instructions General Information Care of Glass & Plated Parts Shipping Bracket
5 LOCATION & CLEARANCES
6-12 DIRECT VENT SPECIFICS
MODEL GDS60
Vent Lengths/Air Terminal Locations Special Installation Example Offset Installation Example Horizontal Terminations Orifice Replacement Top Vent to Rear Vent Modification Venting Parameters Wall & Ceiling Protection Horizontal Venting Installation Vertical Venting Installation Stove Vent Connection Mobile Home Installation
13-14 B-VENT SPECIFICS
MODEL GS60
Chimney Installation 'B' Vent Installation Combustion Air Adding Vent Sections Flashing and Storm Collar Installation
Pg
14 GAS INSTALLATION
15-16 FINISHING
Logo Placement Front Cast Installation Glass Door Closing & Opening Log Placement
17-18 OPERATION / MAINTENANCE
Spill Switch Venting Action Check Operating Instructions Maintenance
19 BLOWER INSTALLATION
19 ADJUSTMENTS
Pilot Burner Adjustment Venturi Adjustments Restricting Vertical Vents
20-21 REPLACEMENTS
Ordering Replacement Parts Termination Kits Replacement Parts Accessories
22-23 TROUBLE SHOOTING GUIDE
24 SERVICE HISTORY
PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE
WARNING
• The stove is a vented gas-fired heater. Do not burn wood or other materials in this stove.
• Adults and especially children should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Supervise young children when they are in the same room as the stove.
• Due to high temperatures, the stove should be located out of traffic and away from furniture and draperies.
• Clothing or other flammable material should not be placed on or near the stove.
• Any safety screen or guard removed for servicing must be replaced prior to operating the stove.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the stove and venting system are kept clean. The stove and its venting system should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The stove area must be kept clear and free from combustible materials, gasoline and other flammable vapours and liquids.
• Under no circumstances should this stove be modified.
• This stove must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance.
• Do not use this stove if any part has been under water. Immediately call a qualified service technician to inspect the stove and to replace any part of the control system and any gas control which has been unde water.
• Do not operate the stove with the glass door opened, cracked or broken. Replacement of the glass should be done by a licensed or qualified service person.
• Do not strike or slam shut the stove glass door.
• This fireplace uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
NOTE: changes, other than editorial, are denoted by a vertical line in the margin.
W415-0158 / E / 02.19.04
NAPOLEON gas fireplaces are manufactured under the strict Standard of the world recognized
ISO 9001 : 2000 Quality Assurance Certificate. NAPOLEON products are designed with superior components and materials, assembled by trained craftsmen who take great pride in their work. The burner and valve assembly are leak and test-fired at a quality test station. The complete fireplace is test-fired and thoroughly inspected by a qualified technician before packaging to ensure that you, the customer, receives the quality product that you expect from NAPOLEON.
NAPOLEON GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY
3
The following materials and workmanship in your new The following materials and workmanship in your new
The following materials and workmanship in your new
The following materials and workmanship in your new The following materials and workmanship in your new
as long as you own the fireplace. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™as long as you own the fireplace. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™
as long as you own the fireplace. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™
as long as you own the fireplace. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™as long as you own the fireplace. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelledlogs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelled
logs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelled
logs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelledlogs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelled components and aluminum extrusion trims.components and aluminum extrusion trims.
components and aluminum extrusion trims.
components and aluminum extrusion trims.components and aluminum extrusion trims.
Electrical (110V and millivolt) components and wearable parts such as catalytic tiles, blowers, gas valves, thermalElectrical (110V and millivolt) components and wearable parts such as catalytic tiles, blowers, gas valves, thermal
Electrical (110V and millivolt) components and wearable parts such as catalytic tiles, blowers, gas valves, thermal
Electrical (110V and millivolt) components and wearable parts such as catalytic tiles, blowers, gas valves, thermalElectrical (110V and millivolt) components and wearable parts such as catalytic tiles, blowers, gas valves, thermal
switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and
switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and
switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and provide replacement parts free of charge during the first year of the limited warranty.provide replacement parts free of charge during the first year of the limited warranty.
provide replacement parts free of charge during the first year of the limited warranty.
provide replacement parts free of charge during the first year of the limited warranty.provide replacement parts free of charge during the first year of the limited warranty.
Labour related to warranty repair is covered free of charge during the first year. Repair work, however, requiresLabour related to warranty repair is covered free of charge during the first year. Repair work, however, requires
Labour related to warranty repair is covered free of charge during the first year. Repair work, however, requires
Labour related to warranty repair is covered free of charge during the first year. Repair work, however, requiresLabour related to warranty repair is covered free of charge during the first year. Repair work, however, requires
the prior approval of an authorized company official. Labour costs to the account of the prior approval of an authorized company official. Labour costs to the account of
the prior approval of an authorized company official. Labour costs to the account of
the prior approval of an authorized company official. Labour costs to the account of the prior approval of an authorized company official. Labour costs to the account of predetermined rate schedule and any repair work must be done through an authorized predetermined rate schedule and any repair work must be done through an authorized
predetermined rate schedule and any repair work must be done through an authorized
predetermined rate schedule and any repair work must be done through an authorized predetermined rate schedule and any repair work must be done through an authorized
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
gas fireplace are warranted against defects for gas fireplace are warranted against defects for
gas fireplace are warranted against defects for
gas fireplace are warranted against defects for gas fireplace are warranted against defects for
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
are based on a are based on a
are based on a
are based on a are based on a
dealer. dealer.
dealer.
dealer. dealer.
willwill
will
willwill
CONDITIONS AND LIMITATIONS
NAPOLEON warrants its products against manufacturing defects to the original purchaser only -- i.e., the individual or legal entity (registered customer) whose name appears on the
warranty registration card filed with NAPOLEON -- provided that the purchase was made through an authorized NAPOLEON dealer and is subject to the following conditions and limitations:
This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives. The gas fireplace must be installed by a licenced, authorized service technician or contractor. Installation must be done in accordance with the installation instructions included with the product
and all local and national building and fire codes.
This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed from other manufacturers will nullify this
warranty.
This limited warranty further does not cover any scratches, dents, corrosion or discolouring caused by excessive heat, abrasive and chemical cleaners nor chipping on porcelain enamel
parts, mechanical breakage of PHAZER™ logs and embers, nor any venting components used in the installation of the fireplace.
NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life, subject to the following conditions: During the first 10 years NAPOLEON will replace
or repair the defective parts at our option free of charge. From 10 years to life, NAPOLEON will provide replacement burners at 50% of the current retail price.
In the first year only, this warranty extends to the repair or replacement of warranted part s which are defective in material or workmanship provided that the product has been operated in
accordance with the operation instructions and under normal conditions.
After the first year, with respect to this President's Limited Lifetime Warranty , NAPOLEON may , at its discretion, fully discharge all obligations with respect to this warranty by refunding to
the original warranted purchaser the wholesale price of any warranted but defective part(s).
After the first year, NAPOLEON will not be responsible for installation, labour or any other costs or expenses related to the reinstallation of a warranted part, and such expenses are not covered
by this warranty.
Notwithstanding any provisions contained in this President's Limited Lifetime Warranty , NAPOLEON’S responsibility under this warranty is defined as above and it shall not in any event extend
to any incidental, consequential or indirect damages.
This warranty defines the obligations and liability of NAPOLEON with respect to the NAPOLEON gas fireplace and any other warranties expressed or implied with respect to this product,
its components or accessories are excluded.
NAPOLEON neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this product. NAPOLEON will not be responsible for: over-firing, downdrafts, spillage caused by environmental conditions such as rooftops, buildings, nearby trees, hills, mountains, inadequate vents or ventilation, excessive venting configurations, insufficient makeup air, or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.
Any damages to fireplace, combustion chamber, heat exchanger, brass trim or other component due to water, weather damage, long periods of dampness, condensation, damaging chemicals or cleaners will not be the responsibility of NAPOLEON.
The bill of sale or copy will be required together with a serial number and a model number when making any warranty claims from your authorized dealer. The warranty registration card must be returned within fourteen days to register the warranty.
NAPOLEON reserves the right to have its representative inspect any product or part thereof prior to honouring any warranty claim.
ALL SPECIFICA TIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE T O ON-GOING PRODUCT IMPROVEMENTS. NAPOLEON® IS A REGISTERED TRADEMARK OF WOLF STEEL LTD. PA TENTS U.S. 5.303.693.801 - CAN. 2.073.411, 2.082.915. © WOLF STEEL L TD.
W415-0158 / E / 02.19.04
4
GENERAL INSTRUCTIONS
THIS GAS STOVE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local codes.
Installation practices vary from region to region and it is important to know the specifics that apply to your area, for example: in Massachusetts State:
• The fireplace damper must be removed or welded in the open position prior to installation of a fireplace insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The flexible connector must not be longer than 36 inches.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
• WARNING: This product must be installed by a licensed plumber or gas fitter when installed within the commonwealth of Massachusetts.
In absence of local codes, install to the current CAN1-B149 Installation Code in Canada or to the National Fuel Gas Code, ANSI Z223.1, and NFPA 54 in the United St ates. Mobile home installation must conform with local codes. In the absence of local codes, install to the current standard for gas equipped mobile housing CAN/CSA Z240 MH Series in Canada or the manufactured home construction and safety standard, Title 24 CFR, part 3280, or the Fire Safety Criteria for manufactured home installations, Sites and Community Standard ANSI/NFPA 501A in the United States.
Purge all gas lines with the glass door of the stove removed. Assure that a continuous gas flow is at the burner before re­installing the door. Under extreme vent configurations, allow several minutes (5-
15) for the flame to stabilize after ignition.
It is recommended that all horizontal runs have a ¼ inch rise per foot. Objects placed in front of the stove must be kept a minimum of 48" away from the front face of the unit.
The stove and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The stove must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psig (3.5 kPa). The stove, when installed with a blower, must be electrically connected and grounded in accordance with local codes. In the absence of local codes, use the current CSA C22.1 CANADIAN ELECTRICAL CODE in Canada or the ANSI/NFPA 70-1996 NATIONAL ELECTRICAL CODE in the United S tates. The blower power cord must be connected into a properly grounded receptacle. The grounding prong must not be removed from the cord plug.
GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS STOVE HAS BEEN TEST­FIRED TO ASSURE ITS OPERATION AND QUALITY!
Minimum inlet gas supply pressure is 4.5 inches water column for natural gas and 11 inches water column for propane. Maximum inlet gas pressure is 7 inches water column for natural gas and 13 inches water column for propane. When the valve is set to "HI", the manifold pressure under flow conditions is 3.5 inches water column for natural gas and 10 inches water column for propane. When the fireplace is installed at elevations above 4,500ft, and in the absence of specific recommendations from the local authority having juris­diction, the certified high altitude input rating shall be reduced at the rate of 4% for each additional 1,000ft.
W415-0158 / E / 02.19.04
Change in flame appearance from "HI" to "LO" is more evi­dent in natural gas than in propane. Expansion / contraction noises during heating up and cooling down cycles are nor­mal and to be expected.
This appliance is only for use with the type of gas indicated on the rating plate. (See page 14). This appliance is not convertible for use with other gases, unless a certified kit is used.
INSTINST
ALLER:ALLER:
INST
ALLER:
INSTINST
ALLER:ALLER:
appropriate box on the rating plate according to theappropriate box on the rating plate according to the
appropriate box on the rating plate according to the
appropriate box on the rating plate according to theappropriate box on the rating plate according to the model, venting and gas type of the unit.model, venting and gas type of the unit.
model, venting and gas type of the unit.
model, venting and gas type of the unit.model, venting and gas type of the unit.
It is y It is y
It is y
It is y It is y
our rour r
our r
our rour r
esponsibesponsib
esponsib
esponsibesponsib
lity to clity to c
lity to c
lity to clity to c
hechec
hec
hechec
k ofk of
k of
k ofk of
ff
the the
f
the
ff
the the
CARE OF GLASS, AND PLATED PARTS
Do not use abrasive cleaners to clean these parts. Buff lightly with a clean dry cloth. The glass is 3/16" ceramic glass available from your Napo­leon / Wolf Steel Lt d. dealer . DO NOT SUBSTITUTE MATE­RIALS. Clean the glass after the first 10 hours of operation with a recommended gas fireplace glass cleaner. Thereaf­ter clean as required. DO NOT CLEAN GLASS WHEN HOT! If the glass is not kept clean permanent discolouration and / or blemishes may result.
SHIPPING BRACKET
To avoid the stove being damaged during shipping, a ship­ping bracket has been used and must be unbolted before the stove can be installed.
1. Remove the four nuts holding the shipping bracket to the bottom of the stove.
2. Lift the stove up and away from the skid to clear the threaded bolts sticking through the bracket. Set down on a flat surface. The stove top is not secured to the unit.
3. Discard the nuts, bracket and the skid.
FIGURE 1
4 NUTS
SHIPPING BRACKET
GDS60: TOP VENT / REAR VENT VERTICAL TERMINATION: Maximum in-
put is 35,000 BTU/hr for natural gas and 31,500 BTU/hr for propane. Maximum output for natural gas is 27,300 BTU/hr at an efficiency of 78%. Maximum output for pro­pane is 24,570 BTU/hr at an efficiency of 78%. Maxi­mum A.F.U.E. (annual fuel utilization efficiency) rating is 72% for natural gas and 71% for propane.
REAR VENT HORIZONTAL TERMINA­TION: Maximum input is 21,000 BTU/hr for natural
and propane gas. This application requires changing the main burner orifice.
This stove is not approved for closet or recessed instal­lations. It is approved for bathroom, bedroom and bed­sitting room installations. This stove may be installed in an aftermarket perma­nently located, manufactured (mobile) home, where not prohibited by local codes.
GS60: Maximum input is 35,000 BTU/hr for natural
gas and 31,500 BTU/hr for propane. This stove is ap­proved for bedroom and bed-sitting room installations.
LOCATION & CLEARANCES
5
Provide adequate ventilation and combustion air.
Provide adequate accessibility clearance for servicing
and operating the stove.
Never obstruct the front opening of the stove.
GDS60 AND GS60
As long as clearance to combustibles is kept within the required distances, the most desirable and beneficial lo­cation for a Napoleon stove is in the centre of a building, thereby allowing the most efficient use of the heat created. The location of windows, doors and the traffic flow in the room where the stove is to be located should be consid­ered. If possible, you should choose a location where the vent will pass through the house without cutting a floor or roof joist.
MAINTAIN THESE MINIMUM CLEARANCES TO COMBUSTIBLES:
FIGURE 3
A. 6" B. 6" C. 2"*
NO ADDITIONAL FLOOR PROTECTION IS REQUIRED
MINIMUM
20" FROM STOVE TOP TO CEILING 6" TO SINGLE WALL CONNECTOR 1" TO DIRECT VENT AND B-VENT *AT A DISTANCE OF 2" FROM THE WALL, ACCESS TO THE BLOWER
, ON-OFF SWITCH OR THE BLOWER POWER CORD MAY NOT
SWITCH
PRACTICAL.
BE
A terminal shall not terminate directly above aA terminal shall not terminate directly above a
A terminal shall not terminate directly above a
A terminal shall not terminate directly above aA terminal shall not terminate directly above a sidewalk or paved driveway which is locatedsidewalk or paved driveway which is located
sidewalk or paved driveway which is located
sidewalk or paved driveway which is locatedsidewalk or paved driveway which is located between two single family dwellings and servesbetween two single family dwellings and serves
between two single family dwellings and serves
between two single family dwellings and servesbetween two single family dwellings and serves both dwboth dw
both dw
both dwboth dw rr
equirequir
r
equir
rr
equirequir
ellingsellings
ellings
ellingsellings
e dife dif
e dif
e dife dif
. Local codes or r. Local codes or r
. Local codes or r
. Local codes or r. Local codes or r
ff
erer
ent cent c
learlear
f
ff
er
erer
ent c
ent cent c
lear
learlear
ancesances
ances
ancesances
ee
gulagula
tions mations ma
e
gula
tions ma
ee
gulagula
tions mations ma
..
.
..
yy
y
yy
Do not allow the inside liner to bunch up on horizontalDo not allow the inside liner to bunch up on horizontal
Do not allow the inside liner to bunch up on horizontal
Do not allow the inside liner to bunch up on horizontalDo not allow the inside liner to bunch up on horizontal or vor v
erer
tical rtical r
or v
er
or vor v
erer
4" air gap all around between the inner liner and outer4" air gap all around between the inner liner and outer
4" air gap all around between the inner liner and outer
4" air gap all around between the inner liner and outer4" air gap all around between the inner liner and outer stove pipe is required for safe operation. Use a firestopstove pipe is required for safe operation. Use a firestop
stove pipe is required for safe operation. Use a firestop
stove pipe is required for safe operation. Use a firestopstove pipe is required for safe operation. Use a firestop when penetrating interior walls, floor or ceiling.when penetrating interior walls, floor or ceiling.
when penetrating interior walls, floor or ceiling.
when penetrating interior walls, floor or ceiling.when penetrating interior walls, floor or ceiling.
uns and elbowsuns and elbows
tical r
uns and elbows
tical rtical r
uns and elbowsuns and elbows
. K. K
eeee
p it pulled tight. p it pulled tight.
. K
ee
p it pulled tight.
. K. K
eeee
p it pulled tight. p it pulled tight.
AA
A
AA
1-1/ 1-1/
1-1/
1-1/ 1-1/
FIGURE 2 - SHOWN WITH OPTIONAL FRONT INST ALLED
NOTE: The total width of the stove is increased to 39" width with the
optional side shelves attached.
W415-0158 / E / 02.19.04
6
DIRECT VENT SPECIFICS - MODEL GDS60
VENTING LENGTHS &
AIR TERMINAL LOCATIONS
Use only Wolf Steel or Simpson Dura-Vent Model DV-GS venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air termi­nal locations for either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, follow the installation procedure provided with the venting com­ponents. Both Wolf Steel and Simpson Dura-Vent venting components may have a 0" rise per foot on horizontal runs.
When using Wolf Steel venting components, use only the following vent kits: WALL TERMINAL KIT GD175 (7-1/2' of venting included), or 1/12 TO 7/12 PITCH ROOF TERMINAL
KIT GD110, 8/12 TO 12/12 ROOF TERMINAL KIT GD111, FLA T ROOF TERMINAL KIT GD1 12 or S TOVE PERISCOPE KIT GD180 (for wall penetration below grade) in conjunc-
tion with the appropriate venting components.
For optimum perform­ance, it is recom­mended that all hori­zontal runs have a mini­mum ¼ inch rise per foot.
These vent kits allow for either horizontal or vertical venting of the stove. The maximum number of 4" flexible connections is two horizontally or three vertically (excluding the stove and the air terminal connections). When terminating vertically, the minimum vertical rise is 34 inches above the stove and the maximum vertical rise is 40 feet. FIGURE 4.
Deviation from the minimum vertical vent length can cre­ate difficulty in burner start-up and/or carboning.
Use an adjustable pipe as the final length of rigid piping to the stove for ease of installation.
For optimum flame appearance and stove performance, keep the vent length and number of elbows to a minimum. The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged. The maximum horizontal run is 34 inches with a 90o elbow located 29" above the stove. FIGURE 5.
The maximum horizontal run with a 57 inch vertical rise immediately above the stove is 20 feet . FIGURES 6a & b.
IF VERTICAL RISES GREATER THAN 57 INCHES ARE NECES­SARY, THE INCREASED RISE MUST BE DEDUCTED FROM THE MAXIMUM HORIZONTAL RUN.
FIGURE 4
FIGURE 5
FIGS 6a-b
HORIZONTAL RUN NOT TO EXCEED VERTICAL RISE
Use the chart on this page to calculate horizontal runs for vertical rises between 29 and 57 inches. When calculating maximum run lengths, include 5 feet for each 90° or 45° elbow. (DO NOT INCLUDE THE FIRST ELBOW DIRECTLY OFF THE UNIT.)
REQUIRED VERTICAL RISE FROM FIREPLACE TO FIRST EL­BOW IN INCHES
FIGURE 7
W415-0158 / E / 02.19.04
CALCULATED HORIZONTAL VENT RUN IN FEET
AIR TERMINAL INSTALLATIONS
f
FIGURE 8
INSTALLATIONS
CANADIAN U.S.A.
A
12 INCHES
12 INCHES
Clearance above grade, veranda porch, deck or balcony.
7
B
C
12 INCHES
12 INCHES*
9 INCHES
12 INCHES*
Clearance to windows or doors that open.
Clearance to permanently closed windows.
Vertical clearance to ventilated soffit located above the terminal within
D
18 INCHES** 12 INCHES**
E
F
0 INCHES
0 INCHES***
G
2 INCHES***
H
I
J
K
L
M
N
O
*
* Recommended to prevent condensation on windows and thermal breakage
* ****
** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffits.
**** ******
*** The periscope GD-201 requires a minimum 18 inches clearance from an inside corner.
****** ********
**** This is a recommended distance. For additional requirements check local codes.
******** †
Three feet above if within 10 feet horizontally.
† ‡
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single
‡ ††† †
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.
††† † †*†*
†* Recommenced to prevent recirculation of exhaust products. For additional requirements check local code
†*†*
3 FEET 3 FEET
12 INCHES
6 FEET
7 FEET‡
12 INCHES††
16 INCHES
2 FEET†*
dwellings and serves both dwellings.
18 INCHES** 12 INCHES**
0 INCHES
0 INCHES***
2 INCHES***
3 FEET**** 3 FEET****
9 INCHES
3 FEET†
7 FEET****
12 INCHES****
16 INCHES
2 FEET†*
a horizontal distance of 2 feet from the centerline of the terminal.
Clearance to unventilated soffit.
Clearance to an outside corner wall.
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
Clearance to an inside combustible corner wall or protruding com­bustible obstructions ( vent chase, etc.).
Clearance to each side of the centerline extended above the meter / regulator assembly to a maximum vertical distance of 15ft.
Clearance to a service regulator vent outlet.
Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
Clearance to a mechanical air supply inlet.
Clearance above a paved sidewalk or paved driveway located on public property unless fitted with a heat shield kit GD-301.
Clearance under a veranda, porch, deck or balcony.
Clearance above the roof.
Clearance from an adjacent wall including neighbouring buildings.
W415-0158 / E / 02.19.04
8
SPECIAL INSTALLATION EXAMPLE
When a horizontal offset is required in a through-the-roof installation, the following procedure for vent length calcula­tions must be followed:
In an installation as shown in FIGURES 9 & 12, lengths A and C are known based on room height and roof require­ments.
Length C must never be less than 29 inches. Any 90° and 45° elbows must be calculated as 5 feet of venting each.
The allowable horizontal run can be calculated using these parameters. In this example, the total vertical height is 20 feet (length "A" is required to be 11 feet while length "C" needs to be 9 feet). The maximum vertical length is 40 feet and all runs and elbows must be sub­tracted from this maximum vertical length.
The maximum allowable horizontal run that "B" can be is:
40 ft. (maximum vertical run length)
-11 ft. (through the roof vertical rise "A")
-10 ft. (2 - 90° elbow)
- 9 ft. (vertical run "C") 10 ft. (maximum allowable horizontal length for "B")
The length of "B" must never be greater than the length of "A" and "C" combined.
FIGURE 9
OFFSET INSTALLATION EXAMPLE
FIGURE 10
If a first run of 120 inches is re­quired, using the "First Vent Run" on the chart shows that a maxi-
mum second run of 60 inches
is allowable.
IF NECESSARY, THE FIRST RUN AND THE SECOND RUN MAY BE REVERSED.
FIGURE 11
The maximum allowable horizontal run that "A" in Figure 13 can be is:
40 ft. (maximum vertical run length)
- 7 ft. (horizontal run "B")
33 ft. (maximum allowable vertical length for "A")
FIGURE 12
FIGURE 13
W415-0158 / E / 02.19.04