Napoleon Fireplaces GE38PT-M, GE38NT-M User Manual

Page 1
INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER.
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS, CSA 2.33, ANSI Z21.88 FOR VENTED GAS FIREPLACE HEATERS AND CSA 22.2 NO. 46 FOR ELECTRIC AIR HEATER.
DIRECT VENT MILLIVOLT SYSTEM
INSTALLATION AND OPERATION INSTRUCTIONS FOR
COMBINATION ELECTRIC AND DIRECT VENT GAS FIREPLACE
1
NATURAL GAS MODEL
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI / CSA METHODS
GE38NT-M
GE38PT-M
WARNING: If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapours and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency
or the gas supplier.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada • (705)721-1212 • fax(705)722-6031
www.napoleonfireplaces.com • ask@napoleon.on.ca
W415-0429 / C / 11.04.05
Page 2
2
PG 2-4 INTRODUCTION
Warranty General Instructions General Information Care of Glass & Plated Parts
5 - 11 VENTING
Venting Lengths Air Terminal Locations Typical Vent Installations Special Vent Installations Venting Application Flow Chart Venting Specifications
12
-
16 INSTALLATION
Wall and Ceiling Protection Using Flexible Vent Components Fireplace Vent Connection Using Rigid Vent Components Gas Installation Mobile Home Installation Framing Nailing Tabs Mantle Clearances & Enclosures
17-18 FINISHING
Door Removal & Installation Louvre Installation
TABLE of CONTENTS
Log Placement Charcoal Embers Glowing Embers Glowing Crystal Embers Logo Placement
19
20 20-21 OPERATION / MAINTENANCE
22 ELECTRICAL CONNECTION 23 ADJUSTMENTS
24-25 REPLACEMENTS
26-28 TROUBLE SHOOTING GUIDE
BLOWER REPLACEMENT FLAME EFFECT BULB REPLACEMENT EMBER BED BULB REPLACEMENT
Fireplace Operation Hand Held Remote Operation Operating Instructions Maintenance
Pilot Burner Adjustment Venturi Adjustment
Ordering Replacement Parts Replacement Parts Vent Kits Terminal Kits Accessories
PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE
WARNING
Do not burn wood or other materials in this fireplace.
• Adults and especially children should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Supervise young children when they are in the same room as the fireplace.
• Due to high temperatures, the fireplace should be located out of traffic and away from furniture and draperies.
• Clothing or other flammable material should not be placed on or near the fireplace.
• Any safety screen or guard removed for servicing must be replaced prior to operating the fire­place.
• It is imperative that the control compartments, burners and circulating blower and its passage­way in the fireplace and venting system are kept clean. The fireplace and its venting system should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The fire­place area must be kept clear and free from combustible materials, gasoline and other flammable vapours and liquids.
• Under no circumstances should this fireplace be modified.
• This fireplace must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance.
• Do not use this fireplace if any part has been under water. Immediately call a qualified service technician to inspect the fireplace and to replace any part of the control system and any gas control which has been under water.
• Do not operate the fireplace with the glass door removed, cracked or broken. Replacement of the glass should be done by a licensed or qualified service person. Use only with a glass door certified with the fireplace.
• Do not strike or slam shut the fireplace glass door.
• This fireplace uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
NOTE: changes, other than editorial, are denoted by a vertical line in the margin.
W415-0429 / C / 11.04.05
Page 3
NAPOLEON products are manufactured under the strict Standard of the world recognized
ISO 9001 : 2000 Quality Assurance Certificate. NAPOLEON products are designed with superior components and materials, assembled by trained craftsmen who take great pride in their work. The burner and valve assembly are leak and test-fired at a quality test station. Once assembled the complete fireplace is thoroughly inspected by a qualified technician before packaging to ensure that you, the customer, receives the quality product that you expect from NAPOLEON.
NAPOLEON GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY
3
The following materials and workmanship in your new The following materials and workmanship in your new
The following materials and workmanship in your new
The following materials and workmanship in your new The following materials and workmanship in your new
ranted against defects for as long as you own the fireplace. This covers: combustion chamber,ranted against defects for as long as you own the fireplace. This covers: combustion chamber,
ranted against defects for as long as you own the fireplace. This covers: combustion chamber,
ranted against defects for as long as you own the fireplace. This covers: combustion chamber,ranted against defects for as long as you own the fireplace. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal break-heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal break-
heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal break-
heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal break-heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal break­age only), gold plated parts against tarnishing, porcelainized enamelled components and alumi-age only), gold plated parts against tarnishing, porcelainized enamelled components and alumi-
age only), gold plated parts against tarnishing, porcelainized enamelled components and alumi-
age only), gold plated parts against tarnishing, porcelainized enamelled components and alumi-age only), gold plated parts against tarnishing, porcelainized enamelled components and alumi­num extrusion trims.num extrusion trims.
num extrusion trims.
num extrusion trims.num extrusion trims.
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,
Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,Electrical (110V and millivolt) components and wearable parts such as blowers, gas valves,
thermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly arethermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are
thermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are
thermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly arethermal switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and covered and
covered and
covered and covered and the limited warranty. Light bulbs are not covered by this warranty.the limited warranty. Light bulbs are not covered by this warranty.
the limited warranty. Light bulbs are not covered by this warranty.
the limited warranty. Light bulbs are not covered by this warranty.the limited warranty. Light bulbs are not covered by this warranty.
Labour related to warranty repair is covered free of charge during the first year. RepairLabour related to warranty repair is covered free of charge during the first year. Repair
Labour related to warranty repair is covered free of charge during the first year. Repair
Labour related to warranty repair is covered free of charge during the first year. RepairLabour related to warranty repair is covered free of charge during the first year. Repair
work, however, requires the prior approval of an authorized company official. Labour costs towork, however, requires the prior approval of an authorized company official. Labour costs to
work, however, requires the prior approval of an authorized company official. Labour costs to
work, however, requires the prior approval of an authorized company official. Labour costs towork, however, requires the prior approval of an authorized company official. Labour costs to the account of the account of
the account of
the account of the account of must be done through an authorized must be done through an authorized
must be done through an authorized
must be done through an authorized must be done through an authorized
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
will provide replacement parts free of charge during the first year ofwill provide replacement parts free of charge during the first year of
will provide replacement parts free of charge during the first year of
will provide replacement parts free of charge during the first year ofwill provide replacement parts free of charge during the first year of
are based on a predetermined rate schedule and any repair work are based on a predetermined rate schedule and any repair work
are based on a predetermined rate schedule and any repair work
are based on a predetermined rate schedule and any repair work are based on a predetermined rate schedule and any repair work
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
dealer. dealer.
dealer.
dealer. dealer.
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
gas fireplace are war- gas fireplace are war-
gas fireplace are war-
gas fireplace are war- gas fireplace are war-
CONDITIONS AND LIMITATIONS
NAPOLEON warrants its products against manufacturing defects to the original purchaser only -- i.e., the individual or legal entity (registered customer) whose name appears on the
warranty registration card filed with NAPOLEON -- provided that the purchase was made through an authorized NAPOLEON dealer and is subject to the following conditions and limitations:
This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives.
The gas fireplace must be installed by a licenced, authorized service technician or contractor. Installation must be done in accordance with the installation instructions included with
the product and all local and national building and fire codes.
This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed from other manufacturers will nullify
this warranty.
This limited warranty further does not cover any scratches, dents, corrosion or discolouring caused by excessive heat, abrasive and chemical cleaners nor chipping on porcelain enamel
parts, mechanical breakage of PHAZER™ logs and embers, nor any venting components used in the installation of the fireplace.
NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life, subject to the following conditions: During the first 10 years NAPOLEON will
replace or repair the defective parts at our option free of charge. From 10 years to life, NAPOLEON will provide replacement burners at 50% of the current retail price.
In the first year only, this warranty extends to the repair or replacement of warranted parts which are defective in material or workmanship provided that the product has been operated
in accordance with the operation instructions and under normal conditions.
After the first year, with respect to this President's Limited Lifetime Warranty, NAPOLEON may, at its discretion, fully discharge all obligations with respect to this warranty by refunding
to the original warranted purchaser the wholesale price of any warranted but defective part(s).
After the first year, NAPOLEON will not be responsible for installation, labour or any other costs or expenses related to the reinstallation of a warranted part, and such expenses are
not covered by this warranty.
Notwithstanding any provisions contained in this President's Limited Lifetime Warranty, NAPOLEON’S responsibility under this warranty is defined as above and it shall not in any event
extend to any incidental, consequential or indirect damages.
This warranty defines the obligations and liability of NAPOLEON with respect to the NAPOLEON gas fireplace and any other warranties expressed or implied with respect to this product,
its components or accessories are excluded.
NAPOLEON neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this product. NAPOLEON will not be responsible for: over-firing, downdrafts, spillage caused by environmental conditions such as rooftops, buildings, nearby trees, hills, mountains, inadequate vents or ventilation, excessive venting configurations, insufficient makeup air, or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.
Any damages to fireplace, combustion chamber, heat exchanger, brass trim or other component due to water, weather damage, long periods of dampness, condensation, damaging chemicals or cleaners will not be the responsibility of NAPOLEON.
The bill of sale or copy will be required together with a serial number and a model number when making any warranty claims from your authorized dealer. The warranty registration card must be returned within fourteen days to register the warranty.
NAPOLEON reserves the right to have its representative inspect any product or part thereof prior to honouring any warranty claim.
ALL SPECIFICATIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE TO ON-GOING PRODUCT IMPROVEMENTS. NAPOLEON® IS A REGISTERED TRADEMARK OF WOLF STEEL LTD. PATENTS U.S. 5.303.693.801 - CAN. 2.073.411, 2.082.915. © WOLF STEEL LTD.
W415-0429 / C / 11.04.05
Page 4
4
GENERAL INSTRUCTIONS
THIS GAS FIREPLACE SHOULD BE INSTALLED AND SERV­ICED BY A QUALIFIED INSTALLER to conform with local codes.
Installation practices vary from region to region and it is important to know the specifics that apply to your area,
for example: in Massachusetts State:
• The fireplace damper must be removed or welded in the open position prior to installation of a fireplace insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The flexible connector must not be longer than 36 inches.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
• WARNING: This product must be installed by a licensed plumber or gas fitter when installed within the commonwealth of
Massachusetts.
In absence of local codes, install the GE38 to the current National Fuel Gas Code, ANSI Z223.1, or the current CAN/ CGA B149, Installation Codes. Mobile home installation must conform with local codes. In the absence of local codes, install to the current standard for gas equipped mobile housing CAN/CSA Z240 MH Series in Canada or the manufactured home construction and safety standard, Title 24 CFR, part 3280, or the Fire Safety Criteria for manu­factured home installations, Sites and Community Stand­ard ANSI/NFPA 501A in the United States.
The fireplace and its individual shutoff valve must be dis­connected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The fireplace must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
When the fireplace is installed directly on carpeting, vinyl tile or other combustible material other than wood flooring, the fireplace shall be installed on a metal or wood panel extending the full width and depth.
The junction box must be electrically connected and grounded in accordance with local codes. In the absence of local codes, use the current CSA C22.1 CANADIAN ELEC­TRICAL CODE in Canada or the ANSI/NFPA 70 NATIONAL ELECTRICAL CODE in the United States.
GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS FIREPLACE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUAL­ITY! Maximum input is 26,000 BTU/hr for natural gas and
propane. When the fireplace is installed at elevations above 4,500ft, and in the absence of specific recommendations from the local authority having jurisdiction, the certified high altitude input rating shall be reduced at the rate of 4% for each additional 1,000ft.
Maximum output for natural gas is 22,360 BTU/hr at an efficiency of 86% with the fan on, and 22,880 BTU/hr for propane at an efficiency of 88% with the fan on. The maxi­mum A.F.U.E. (annual fuel utilization efficiency) rating is 64% for natural gas and 65% for propane.
W415-0429 / C / 11.04.05
Minimum inlet gas supply pressure is 4.5 inches water column for natural gas and 11 inches water column for propane. Maximum inlet gas pressure is 7 inches water column for natural gas and 13 inches water column for propane. Manifold pressure under flow conditions is 3.5 inches water column for natural gas and 10 inches water column for propane.
This fireplace is approved for bathroom, bedroom and bed­sitting room installations and is suitable for mobile home installation. The natural gas model can only be installed in a mobile home that is permanently positioned on its site and fueled with natural gas.
No external electricity (110 volts or 24 volts) is re­quired for the gas system operation.
Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected.
CARE OF GLASS, AND PLATED PARTS
Do not use abrasive cleaners to clean plated parts. Buff lightly with a clean dry cloth. The GE38 is factory equipped with ceramic glass for both the firebox front and back panels. The glass thickness is 3/16". Use only replacement glass available from your Napoleon dealer. DO NOT SUBSTITUTE MATERIALS. Clean the glass after the first 10 hours of opera­tion with a recommended gas fireplace glass cleaner. There­after clean as required. DO NOT CLEAN GLASS WHEN HOT! If the glass is not kept clean permanent discolouration and /
or blemishes may result.
Use only accessories designed for and listed with
your specific fireplace.
Provide adequate ventilation air. Provide adequate accessibility clearance for servicing and operating the fireplace. Never obstruct the front opening of the fireplace.
For safe and proper operation of the fireplace follow the venting instruction exactly.
Deviation from the minimum vertical vent length can create difficulty in burner start-up and/or carboning.
Provide a means for visually checking the vent con­nection to the fireplace after the fireplace is installed.
Vent lengths that pass through unheated spaces (at­tics, garages, crawl spaces) should be insulated with the insulation wrapped in a protective sleeve to minimize condensation.
Objects placed in front of the fireplace must be kept a minimum of 48" away from the front face of the unit.
Page 5
VENTING
5
FIGURE 1
VENTING LENGTHS
Use only Wolf Steel or Simpson Dura-Vent Model DV-GS venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air termi­nal locations for either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, follow the installation procedure provided with the venting com­ponents.
When using Wolf Steel venting components, use only ap­proved Wolf Steel rigid / flexible components with the fol­lowing termination kits: WALL TERMINAL KIT GD222, or 1/12 TO 7/12 PITCH ROOF TERMINAL KIT GD210, 8/12 TO 12/12 ROOF TERMINAL KIT GD211, FLAT ROOF TERMI- NAL KIT GD212 or PERISCOPE KIT GD201 (for wall pen- etration below grade). With flexible venting, in conjunction with the various terminations, use either the 5 foot vent kit GD220 or the 10 foot vent kit GD230.
Wolf Steel rigid and flexible venting systems must not be combined.
Wolf Steel and Simpson Dura-Vent venting systems
must not be combined.
These vent kits allow for either horizontal or vertical venting of the fireplace. FIGURES 3a, & 5a. The maximum allow- able horizontal run is 20 feet. The maximum allowable ver­tical vent length is 40 feet. The maximum number of 4" vent connections is two horizontally or three vertically (exclud­ing the fireplace and the air terminal connections) when using aluminum flexible venting.
For optimum flame appearance and fireplace perform­ance, keep the vent length and number of elbows to a minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged.
Purge all gas lines with the glass door of the fireplace open. Assure that a continuous gas flow is at the burner before closing the door.
Under extreme vent configurations, allow several minutes (5-15) for the flame to stabilize after ignition.
6" inches is the minimum bend radius allowed for the 7" diameter flexible liner.
For optimum performance it is recommended that all horizontal runs have a 1 inch rise per foot when using Napoleon flexible vent components.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two sin­gle family dwellings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼" air gap all around between the inner liner and outer liner is required for safe operation. Use a firestop when pen­etrating interior walls, floor or ceiling.
Minimum clearance to combustible con­struction from fireplace and vent sur­faces:
fireplace framing - 0" to stand-offs (top, rear and sides) fireplace finishing - 0" to sides, 3" to top of unit vent pipe - 1 inch recessed depth - 17½" inches
Horizontal runs may have a 0 inch rise per foot in all cases using SIMPSON DURA-VENT or NAPOLEON RIGID OR FLEXIBLE venting components when vent­ing as illustrated in Figures 3, and 4.
Only a clearance to combustibles of 1" all around the vent pipe is required.
W415-0429 / C / 11.04.05
Page 6
6
i
AIR TERMINAL INSTALLATIONS
FIGURE 2
INSTALLATIONS
CANADIAN U.S.A.
A
12 INCHES
12 INCHES
Clearance above grade, veranda porch, deck or balcony.
B
C
12 INCHES
12 INCHES*
9 INCHES
12 INCHES*
Clearance to windows or doors that open.
Clearance to permanently closed windows.
Vertical clearance to ventilated soffit located above the terminal within
D
18 INCHES**
12 INCHES**
E
F
0 INCHES
0 INCHES***
G
2 INCHES***
H
I
J
K
L
M
N
O
**
* Reco mme nded to preven t condensa tio n on windows and the rma l break age
** ****
** It is recommended t
**** ** *** *
** * The perisco pe G
** *** * ** * *** * *
** * * This is a reco
** * *** * * ††
Three feet above if wi thin 10 fe
†† ‡‡
A vent shall not terminate directl y above a sidewalk or paved driveway that is l
‡‡
† †† †
† † Permitted onl y if the veranda, porch, or deck is fully
† †† † † *† *
† * Recomm enc ed to prev ent recirculatio n of ex
† *† *
W415-0429 / C / 11.04.05
3 FEET
3 FEET
12 INCH
ES
6 FEET
7 FEET‡
12 INCHES††
16 INCHES
2 FEET†*
mmended distanc e. For additi onal require ments check local codes.
dwe llings and serves both dwellings.
18 INCHES**
12 INCHES**
0 INCHES
0 INCHES***
2 INCHES***
3 FEET***
3 FEET****
9 INCHES
3 FEET†
a horizontal distance of 2 feet from the centerline of the terminal.
Clearance to unventilated soffit.
Clearance to an outside corner wall.
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
Clearance to an inside combustible corner wall or protruding com­bustible obstructions ( vent chase, etc.).
Clearance to each side of the centerline extended above the meter
*
/ regulator assembly to a maximum vertical distance of 15ft.
Clearance to a service regulator vent outlet.
Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
Clearance to a mechanical air supply inlet.
Clearance above a paved sidewalk or paved driveway located on
7 FEET****
12 INCHES****
16 INCHES
2 FEET†*
o use a heat shield and to maximize the distance to vinyl clad sof fits.
D-20 1 requ ires a mini mum 18 inches clearan ce from an ins ide cor ner.
et horizonta lly.
public property unless fitted with a heat shield kit GD-301.
Clearance under a veranda, porch, deck or balcony.
Clearance above the roof.
Clearance from an adjacent wall including neighbouring buildings.
open on a minimum of two sides beneath the floor.
haus t prod uct s. For addit ional req uirem ents check local cod es.
ocated between two single fam
Page 7
TYPICAL VENT INSTALLATIONS
7"
For optimum performance, it is recommended that all horizontal runs have a 1 inch rise per foot.
When terminating vertically, the vertical rise is a minimum 36 inches and a maximum 40 feet from the centre of the fireplace flue outlet.
SPECIAL VENT INSTALLATIONS
PERISCOPE TERMINATION
7
FIGURES 3
40 FT MAX
3 FT MIN
Use the GD201 periscope kit to locate the air termination above grade. The periscope must be installed so that when final grading is completed, the bottom air slot is located a minimum of 12 inches above grade. The maximum allow­able vent length depends on the fireplace, as illustrated.
VENTING APPLICATION FLOW CHART
HORIZONTAL TERMINATION VERTICAL TERMINATION
vertical rise is equal to or greater than the horizontal run
vertical rise is less than horizontal run
vertical rise is equal to or greater than the horizontal run
FIGURE 4
vertical rise is less than horizontal run
horizontal run + ver­tical rise to maxi­mum of 40 feet
horizontal run + ver­tical rise to maxi­mum of 24.75 feet
4.2 times the verti­cal rise equal to or greater than the horizontal run
horizontal run + ver­tical rise to maxi­mum of 40 feet
horizontal run + ver­tical rise to maxi­mum of 40 feet
3 times the vertical rise equal to or greater than the horizontal run
W415-0429 / C / 11.04.05
Page 8
8
DEFINITIONS
for the following symbols used in the venting calcula­tions and examples are:
> - greater than > - equal to or greater than < - less than < - equal to or less than HT- total of both horizontal vent lengths (HR) and offsets
) in feet
(H
H HO- offset factor: .03(total degrees of offset - 90°*) in
VT- combined vertical vent lengths in feet
O
- combined horizontal vent lengths in feet
R
feet
TOP EXIT / HORIZONTAL TERMINATION
when (HT) < (VT)
Simple venting configuration (only one 90° elbow)
FIGURE 5
ELBOW VENT LENGTH VALUES
feet inches
0.03 0.5 15° 0.45 6.0 30° 0.9 11.0 45° 1.35 16.0 90°* 2.7 32.0
* the first 90° offset has a zero value and is shown in the formula as -90°
For vent configurations requiring more than one 90° el­bow, the following formulas apply:
Formula 1: HT < V Formula 2: HT + VT < 40 feet
Example 1:
T
90°
H
2
See graph to determine the required vertical rise VT for the required horizontal run HT.
VERTICAL RISE IN FEET
V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
The shaded area within the lines represents acceptable values for HT and V
W415-0429 / C / 11.04.05
.
T
V
FIGURE 6
2
H
90°
V
1
V1=3 ft V2=8 ft VT= H1= 2.5 ft H2=2 ft HR= H1 + H2 = 2.5 + 2 = 4.5 ft HO=. HT= HR + HO = 4.5 + 5.4 = 9.9 ft
T
HT + VT = 9.9 + 11 = 20.9 ft
Formula 1: HT < V
Formula 2: HT + VT < 40 feet
Since both formulas are met, this vent configuration is ac­ceptable.
V1 +
V2 =
3 + 8 = 11 ft
03(three 90° elbows - 90°) = .03(270° - 90°) = 5.4 ft
9.9 < 11
20.9 < 40
T
90°
1
Page 9
TOP EXIT / HORIZONTAL TERMINATION
when (Ht) > (Vt)
Simple venting configuration (only one 90° elbow)
See graph to determine the required ver­tical rise VT for the required horizontal run HT.
FIGURE 7
Example 3:
V
9
90°
V
H
H
4
2
3
H
1
H
90°
1
2
FIGURE 9
REQUIRED VERTICAL RISE IN INCHES
V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
T
The shaded area within the lines represents acceptable values for HT and V
.
T
For vent configurations requiring more than one 90° elbow the following formulas apply:
Formula 1: HT < 4.2 V
T
Formula 2: HT + VT < 24.75 feet
H
Example 2:
V
1
1
90°
FIGURE 8
H
2
V
1
V
2
V
T
H
1
H
2
H
3
H
4
H
R
H
O
H
T
=4 ft = 1.5 ft = V1 + V2 = 4 + 1.5 = 5.5 ft =2 ft =1 ft =1 ft = 1.5 ft = H1 + H2 + H3 + H4 = 2 + 1 + 1 + 1. 5 = 5.5 ft = .03(four 90° elbows - 90°) = .03(360° - 90°) = 8.1 ft = HR + HO = 5.5 + 8.1 = 13.6 ft
HT + VT= 13.6 + 5.5 = 19.1 ft
Formula 1:HT < 4.2 V
T
4.2 VT = 4.2 x 5.5 = 23.1 ft
13.6 < 23.1
Formula 2:HT + VT < 24.75 feet
19.1 < 24.75
Since both formulas are met, this vent configuration is ac­ceptable.
V H H H H H
HT + VT=
Formula 1: HT < 4.2 V
= VT = 6 ft
1
=3 ft
1
=5 ft
2
= H1 + H2 = 3 + 5 = 8 ft
R
= .03(two 90° elbows - 90°) = .03(180° - 90°) = 2.7 ft
O
= HR + HO = 8 + 2.7 = 10.7 ft
T
10.7 + 6 =16.7
T
4.2 VT = 4.2 x 6 = 25.2 ft
10.7 < 25.2
Formula 2: HT + VT < 24.75 feet
16.7 < 24.75
Since both formulas are met, this vent configuration is ac­ceptable.
W415-0429 / C / 11.04.05
Page 10
10
TOP EXIT VERTICAL TERMINATION
when (Ht) < (Vt)
Simple venting configurations
FIGURE 10
See graph to determine the required vertical rise VT for the required horizontal run HT.
REQUIRED VERTICAL RISE IN FEET
V
T
Example 4:
FIGURE 11
H
1
V
1
V
2
V
T
H
1
H
2
H
3
H
R
H
O
H
T
HT + VT= 14.6 + 15 = 29.6 ft
=5 ft = 10 ft
=
V1 +
V2 =
5 + 10 = 15 ft
=1 ft
=3 ft = 2.5 ft = H1 + H2 + H3 = 1 + 3 + 2.5 = 6.5 ft = .03(four 90° elbows - 90°) = .03(90 + 90 + 90 + 90 - 90) = 8.1 ft =HR + HO = 6.5 + 8.1 = 14.6 ft
90°
H
2
V
V
2
90°
H
3
1
90°
90°
HORIZONTAL VENT RUN PLUS OFFSET IN FEET
H
The shaded area within the lines represents acceptable values for HT and V
.
T
For vent configurations requiring elbows, the following for­mulas apply:
Formula 1: HT < V
T
Formula 2: HT + VT < 40 feet
W415-0429 / C / 11.04.05
Formula 1: HT < V
14.6 < 15
T
Formula 2: HT + VT < 40 feet
T
29.6 < 40
Since both formulas are met, this vent configuration is ac­ceptable.
Page 11
TOP EXIT VERTICAL TERMINATION
when (Ht) > (Vt) Simple venting configurations See graph to determine the required vertical rise VT for the
required horizontal run HT.
FIGURE 12
For vent configurations requiring elbows, the following for­mulas apply:
MAXIMUM VERTICAL RISE IN FEET
V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET
The shaded area within the lines represents acceptable values for HT and V
Formula 1: HT < 3V Formula 2: HT + VT < 40 feet
.
T
T
V
T
H
1
H
2
H
R
H
O
=
V1 +
V2 +
V3 =
2 + 1 + 1.5 = 4.5 ft
=6 ft =2 ft = H1 + H2 = 6 + 2 = 8 ft = .03(four 90° elbows - 90°) = .03(90 + 90 + 90 + 90 - 90) = 8.1 ft
H
T
H
T
Formula 1: H
=HR + HO = 8 + 8.1 = 16.1 ft
+ VT = 16.1 + 4.5 = 20.6 ft
< 3V
T
T
3VT=
16.1 > 13.5
3 x
4.5 = 13.5 ft
Since this formula is not met, this vent configuration is unacceptable.
Formula 2: HT + VT < 40 feet
20.6 < 40
Since only formula 2 is met, this vent configuration is unac­ceptable and a new fireplace location or vent configuration will need to be established to satisfy both formulas.
Example 6:
H
V
1
V
2
V
T
T
H
90°
1
= 1.5 ft =5 ft
=
V1 +
90°
H
V
V2 =
1.5 + 5 = 6.5 ft
H
3
2
1
45°
H
4
FIGURE 14
V
11
2
90°
Example 5:
V
1
V
2
V
3
=2 ft =1 ft = 1.5 ft
90°
V
H
1
H
2
H
3
H
90°
V
3
H
1
H
1
V
2
2
90°
90°
4
H
R
H
O
H
T
HT + VT= 23.2 + 6.5 = 29.7 ft
Formula 1: HT < 3V
=1 ft
=1 ft =1 ft = 10.75 ft = H1 + H2 + H3 + H4 = 1 + 1 + 1 + 10.75 = 13.75 ft = .03(four 90° elbows + one 45° elbow - 90°) = .03(90 + 90 + 90 + 90 + 45 - 90) = 9.45 ft =HR + HO = 13.75 + 9.45 = 23.2 ft
T
3VT =
3 x
6.5 = 19.5 ft
19.5 = 19.5
Formula 2: HT + VT < 40 feet
FIGURE 13
Since both formulas are met, this vent configuration is ac-
29.7 < 40
ceptable.
W415-0429 / C / 11.04.05
Page 12
12
INSTALLATION
WALL AND CEILING PROTECTION
FOR SAFE AND PROPER OPERATION OF THE FIREPLACE, FOLLOW THE VENTING INSTRUCTIONS EXACTLY.
NOTE: Only a clearance to combustibles of 1" all around the vent pipe is required.
HORIZONTAL INSTALLATION
This application occurs when vent­ing through an exterior wall. Having determined the air terminal location, cut and frame a hole in an exterior wall with a minimum opening as required. See Note above. (As an alternative to framing, a vent pipe shield may be installed, ensuring a 1" clearance to combustibles. See
Figure 16.)
1. Mark and cut the vent pipe shield to the determined depth of the combustible wall. Apply a bead of caulking (not supplied) to the framework or to the shield plate (in the case of a finished wall) and secure the shield through the opening to the interior wall. The final location
of the vent pipe shield should maintain the required clear­ance to the 7" vent pipe / liner. (See note above). Do not fill this cavity with any type of material. Apply a bead of caulk-
ing all around and place a firestop spacer over the vent shield to restrict cold air from being drawn into the room or around the fireplace. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe / liner is installed in its final position, apply sealant between the pipe / liner and the firestop spacer.
FIGURE 15
OR
VERTICAL INSTALLATION
This application oc­curs when venting through a roof. Installa­tion kits for various roof pitches are available from your Napoleon dealer. See Accesso­ries to order the specific kit required.
1. Determine the air terminal location, cut and frame 10 inch openings in the ceiling and the roof to provide the minimum 1 inch clearance between the fire­place pipe / liner and any combustible material. Try to center the exhaust pipe location midway between two joist to pre­vent having to cut them. Use a plumb bob to line up the center of the openings. DO NOT FILL THIS SPACE WITH ANY TYPE OF MATERIAL. A vent pipe shield will prevent any materials such as insulation, from filling up the 1" air space around the pipe. Nail headers between the joist for extra support.
2. Apply a bead of caulking (not sup­plied) to the frame­work or to the Wolf Steel vent pipe shield plate or equivalent (in the case of a finished ceiling), and secure over the opening in the ceiling. FIGURE 18. A firestop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through. Apply a bead of caulking all around and place a firestop spacer over the vent shield to restrict cold air from being drawn into the room or around the fireplace. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe / liner is installed in its final position, apply sealant be­tween the pipe / liner and the firestop spacer.
FIGURE 18
FIGURE 17
FIGURE 16
W415-0429 / C / 11.04.05
Page 13
USING FLEXIBLE VENT COMPONENTS
13
Use only approved aluminum flexi­ble liner kits marked:
"Wolf Steel Approved Venting" as identified by the stamp only on the 7” outer liner.
HORIZONTAL AIR TERMINAL INSTALLATION
FIGURE 19
1. Cut or frame a hole in an exterior wall with a minimum round or square opening listed on page 5. Secure the firestop spacer over the opening to the interior wall.
2. Stretch the 4" diameter aluminum flexible liner to the required length taking into account the additional length needed for the finished wall surface. Slip the liner a mini­mum of 2" over the inner sleeve of the air terminal and secure with 3 #8 screws. Apply a heavy bead of the high temperature sealant.
3. Using the 7" diameter flexible aluminum liner, slide over the outer combustion air sleeve of the air terminal and secure with 3 #8 screws. Seal as before.
4. Insert the liners through the firestop maintaining the required clearance to combustibles. Holding the air termi­nal (lettering in an upright, readable position), secure to the exterior wall and make weather tight by sealing with caulking (not supplied).
5. Apply a heavy bead of the high temperature sealant, supplied with the unit, to the inside of the 4" liner approxi­mately 1" from the end. Slip the liner a minimum of 2" over the fireplace vent collar and secure with 3 #8 screws.
6. Using the 7" diameter flexible aluminium liner, apply sealant, slide a minimum of 2" over the fireplace combus­tion air collar and secure with 3 #8 screws.
EXTENDED HORIZONTAL
AIR TERMINAL INSTALLATION
Use the GD220 vent kit and couplers for this application. If more than one length of liner needs to be used to reach
the fireplace, couple them together as illustrated in FIGURE 20. Seal the joints using the same procedure as described in points 2 and 3. The vent system must be sup­ported approximately every 3 feet for both vertical and hori­zontal runs. Use Wolf Steel support ring assemblies, or equivalent noncombustible strapping to maintain the mini­mum 1" clearance to combustibles as well as to prevent sagging.
Spacers are attached to the 4" inner flex liner at prede­termined intervals to maintain a 1-1/4" air gap to the 7" outer liner. These spacers must not be removed.
FIGURE 20
VERTICAL AIR TERMINAL INSTALLATION
1. Fasten the roof support to the roof using the screws pro­vided. FIGURE 21. The roof sup­port is optional. In this case the venting is to be adequately sup­ported using either an alternate method suitable to the authority having jurisdiction or the op­tional roof support.
2. Stretch the 4" diameter alu­minium flexible liner to the re­quired length. Slip the liner a minimum of 2" over the inner sleeve of the air terminal and se­cure with 3 #8 screws. Seal us­ing a heavy bead of the high temperature sealant.
3. Repeat using the 7" diam­eter flexible aluminium liner.
4. Thread the air terminal pipe assembly down through the roof. The air terminal must be located vertically and plumb. Attach the air terminal assembly to the roof support, ensuring that a minimum 16" of air terminal will penetrate the roof when fastened.
DO NOT CLAMP THE FLEXIBLE ALUMINIUM LINER.
5. Remove nails from the shingles, above and to the sides of the chimney. Place the flashing over the air termi­nal and slide it underneath the sides and upper edge of the shingles. Ensure that the air terminal is properly centered within the flashing, giving a 3/4" margin all around. Fasten to the roof.
FIGURE 22
FIGURE 21
W415-0429 / C / 11.04.05
Page 14
14
Do not nail through the lower portion of the flashing. Make weather-tight by seal­ing with caulking. Where possible, cover the sides and top edges of the flashing with roofing material.
6. Apply a heavy bead of weatherproof caulking 2 inches above the flashing. Slide the storm collar around the air terminal and down to the caulking. Tighten to ensure that a weather-tight seal between the air terminal and the collar is achieved. Attach the other storm collar centered between the air intake and the air exhaust slots onto the air termi­nal. Tighten securely. FIGURE 23. Attach the vertical rain cap.
Spacers are attached to the 4" inner flex liner at prede­termined intervals to maintain a 1-1/4" air gap to the 8" outer liner. These spacers must not be removed.
FIGURE 23
7. If more liner needs to be used to reach the fireplace, follow the same procedure as found in EXTENDED HORI- ZONTAL AIR TERMINAL INSTALLATION. The vent system must be supported approximately every 3 feet for both ver­tical and horizontal runs. Use Wolf Steel support ring as­sembly or equivalent noncombustible strapping to main­tain a clearance to combustibles.
FIREPLACE VENT CONNECTION
1. Install the 4 inch diameter aluminium flexible liner to the fireplace. Secure with 3 screws and flat washers. Seal the joint and screw holes using the high temperature seal­ant provided. FIGURE 24.
2. Install the 7 inch diameter aluminium flexible liner to the fireplace. Attach and seal the joints.
FIGURE 24
USING RIGID VENT COMPONENTS
The vent system must be supported approximately every 3 feet for both vertical and horizontal runs. Use Wolf Steel vent spacers every 3 feet and either side of each elbow to maintain the minimum 1¼" clearance between the outer and inner vent pipes. Use Wolf Steel support ring assem­bly or equivalent noncombustible strapping to maintain the minimum clearance to combustibles for both vertical and horizontal runs.
HORIZONTAL AIR TERMINAL INSTALLATION
FIGURE 25
1. Move the fireplace into position. Meas­ure the vent length required between terminal and fireplace taking into account the additional length needed for the finished wall surface and any 1¼" overlaps between venting components.
2. Apply high temperature sealant to the outer edge of the 4" inner collar of the fireplace. Attach the first vent component and secure using 3 self tapping screws. Repeat using 7" piping.
W415-0429 / C / 11.04.05
3. Holding the air terminal (with the air deflectors to the top), insert into both vent pipes with a twisting motion to ensure that both the terminal sleeves engage into the vent pipes and sealant. Secure the terminal to the exterior wall and make weather tight by sealing with caulking (not supplied).
The air terminal mounting plate may be recessed into the exterior wall or siding by 1½", the depth of the return flange.
EXTENDED HORIZONTAL AND CORNER
AIR TERMINAL INSTALLATION
1. Follow the instructions for "Horizontal Air Terminal In­stallations", items 1 to 3.
2. Continue adding components alternating inner and outer venting. Ensure that all 4" venting and elbows have sufficient vent spacers attached and each component is securely fastened to the one prior. Attach the 4" telescopic sleeve to the vent run.
Repeat using a 7" tel­escopic sleeve. Secure and seal as before. To facilitate completion, at­tach 5" and 8" couplers to the air terminal.
3. Install the air terminal. See item 3 of the Horizontal Air Terminal Installation.
Extend the 4" telescopic sleeve; connect to the air terminal assembly. Fasten with self tapping screws and seal. Repeat using the 7" telescopic sleeve.
FIGURE 26
Page 15
VERTICAL VENTING INSTALLATION GAS INSTALLATION
1. Move the fireplace into position.
2. Fasten the roof support to the roof using the screws
provided. FIGURE 22. The roof support is optional. In this case the venting is to be adequately supported using ei­ther an alternate method suitable to the authority having jurisdiction or the optional roof support.
3. Apply high temperature sealant to the outer edge of the inner sleeve of the air terminal. Slip a 4" diameter coupler a minimum of 2" over the sleeve and secure using 3 screws.
4. Apply high temperature seal- ant to the outer edge of the of the outside sleeve of the air terminal. Slip a 7" diameter coupler over the sleeve and secure as before. FIG- URE 27. Trim the 7" coupler even with the 4" coupler end.
5. Thread the air terminal pipe assembly down through the roof support and attach, ensuring that a minimum 16" of air terminal will penetrate the roof when fas­tened. FIGURE 22. If the attic
space is tight, we recommend threading the Wolf Steel vent pipe collar or equivalent the air terminal assembly as it is passed through the attic. FIGURE 28. The air terminal must
be located vertically and plumb.
6. Remove nails from the shingles, above and to the sides of the chimney. Place the flashing over the air termi­nal and slide it underneath the sides and upper edge of the shingles. Ensure that the air terminal is properly centered within the flashing, giving a 3/4" margin all around. Fasten to the roof. Do NOT nail through the lower portion of the flashing. Make weather-tight by sealing with caulking. Where possible, cover the sides and top edges of the flash­ing with roofing material. FIGURE 23.
7. Apply a heavy bead of waterproof caulking 2 inches above the flashing. Slide the storm collar around the air terminal and down to the caulking. Tighten to ensure that a weather-tight seal between the air terminal and the collar is achieved. Attach the other storm collar centered between the air intake and air exhaust slots onto the air terminal. Tighten securely. Attach the rain cap.
8. Continue adding rigid venting sections, sealing and securing as above. Attach a 4" collapsed telescopic pipe to the last section of rigid piping. Secure with screws and seal. Repeat using a 7" telescopic pipe.
9. Run a bead of high temperature sealant around the outside of the 4" collar on the fireplace. Pull the adjustable pipe a minimum of 2" onto the collar. Secure with 3 screws. Repeat with the 7" telescopic pipe.
10. In the attic, slide the vent pipe collar down to cover up the open end of the shield and tighten. This will prevent any materials, such as insulation, from filling up the 1" air space around the pipe.
loosely onto
FIGURE 27
FIGURE 28
Proceed once the vent installation is complete.
1. Move the fireplace into position and secure using the
nailing tabs and/or secure to the floor through the ¼"diam­eter holes located at either end of the base.
2. Route a 3/8" N.P.T. black iron gas line, 1/2" type-L cop-
per tubing or equivalent to the fireplace.
3. For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a convenient lo­cation. Route 2-strand (solid core) millivolt wire through the electrical hole located at the bottom left side of the unit. The recommended maximum lead length depends on wire size:
Attach the two leads to terminals 1 and 3 located on the gas valve.
FIGURE 29
4. Install rigid black pipe, 1/2" type-L copper tubing or, if local codes permit, a 3/8" flex connector and shutoff valve to the gas line and the fireplace gas valve.
WIRE SIZE MAX. LENGTH
14 gauge 100 feet 16 gauge 60 feet 18 gauge 40 feet
1
2
3
FIGURE 30
The gas line and the shutoff valve (if so equipped) must not interfere with the opening and closing of the door latch.
Seal and tighten securely. An adapter fitting is required between the gas valve and the copper tubing or flex con­nector.
Do not kink flex connector.
5. Check for gas leaks by brushing on a soap and water
solution.
Do not use open flame.
Do not connect either the wall switch, thermostat or gas valve to electricity (110 volts).
Purge all gas lines with the glass door of the fireplace open. Assure that a continuous gas flow is at the burner before closing the door.
15
W415-0429 / C / 11.04.05
Page 16
16
MOBILE HOME INSTALLATION
In Canada, mobile home installation may be vented hori­zontally or vertically. In the United States, it may only be installed vertically. See "Vertical Venting" or "Horizontal Air Terminal Installation" for installation.
The fireplace is equipped with two 1/4" diameter holes located in the front left and right corners of the base. For mobile home installations, the fireplace must be fastened in place. Use #10 hex head screws, inserted through the holes in the base to secure. It is recommended that the fireplace be secured in all installations.
Always turn off the pilot and the fuel supply at the source, prior to moving the mobile home.
After moving the mobile home and prior to lighting the fireplace, ensure that the logs are positioned correctly.
FRAMING
It is best to frame your fireplace after it is positioned and the vent system is installed. Use 2x4's and frame to local building codes. FIGURES 31-33.
1
39
/
4"
3
"
4
/
17
40 1/8"
37
3
/
"
4
3
56
4
/
4"
7"
37
"
3
"
4
/
FIGURE 31
FIGURE 32
It is not necessary to install a hearth extension with this fireplace system.
Note: In order to avoid the possibility of exposed insulation or vapour barrier coming in contact with the fireplace body, it is recommended that the walls of the fireplace enclosure be “finished” (ie: drywall/sheetrock), as you would finish any other outside wall of a home. This will ensure that clear­ance to combustibles is maintained within the cavity.
When roughing in the fireplace, raise the fireplace to ac­commodate for the thickness of the finished floor materi­als, i.e. tile, carpeting, hard wood, which if not planned for will interfere with the opening of the lower access door and the installation of many decorative flashing accessories.
Objects placed in front of the fireplace should be kept a minimum of 48" away from the front face.
A non-combustible finishing material must be used for a minimum of 3" above the fireplace
Combustible materials may be installed flush with the front sides of the fireplace but must not cover or protrude past any of the black face-side-areas of the fireplace. Non-com­bustible material (brick, stone or ceramic tile) may pro­trude in these areas.
NAILING TABS
To install the fireplace face flush with the finished wall, position the framework to accommodate the thickness of the finished wall. Bend out the four nailing tabs, attached on either side of the fireplace and secure to the 2x4 framing. The tabs will facilitate the installation of either a wall thickness.The nailing tabs must not be removed.
MANTLE CLEARANCES & ENCLOSURES
Combustible mantle clearance can vary according to the mantle depth. Use the graph to help evaluate the clear­ance needed. Curtains, above the fireplace, must not be positioned lower than the 3" distance required for the 3" combustible mantle. These same requirements apply to
any combustibles protruding on either side of the fire­place.
FIGURES 34
3
/
" or a 1" finished
4
OUTSIDE
CHASE
FIGURES 33
W415-0429 / C / 11.04.05
7 3/4"
37 3/4"
37 3/4"
17 3/4"
INSIDE CHASE
6"
Page 17
FINISHING
17
DOOR REMOVAL & INSTALLATION
Lift up and remove the upper louvres. Open the valve control door. Release the top and bot­tom door latches, located at the right side of the door.
To close the door, repeat in re­verse order.
The door latch holes are elongated for door levelling. The door may need to be lifted up at the right side before latching to ensure the door is level.
GVFL LOUVRE INSTALLATION
Remove the protec­tive plastic wrap from the louvres and install as illus­trated.
Clip each upper louvre into a slot on the louvre bracket. Ensure that the louvres are centered within the opening.
FIGURE 36a UPPER LOUVRE INSTALLA TION
LOUVRE BRACKET
L38 LOUVRE INSTALLATION
FIGURE 37 a-c
A
B
C
F
Secure the lower louvre assembly to the lip of the fireplace base as shown.
Position the hinge screen into place and with the control door open, secure to the firebox using three screws.
A
CENTRE
B
C
SLOT
CLIPS
HINGE
CLIP
FLANGE
SLOT
TAB
SLOT
HOOD
Attach the hood by pressing the top flange into the clips along the top of the louvre opening. Secure using a screw through the centre slot.
UPPER LOUVRES
Insert the louvre tabs into the slots located at the top left and right corners of the unit.
LOWER LOUVRES
Insert the hinge clips into the slots located at the bottom left and right corners of the unit.
To remove the louvres, pull the back tabs of the clips forward, while pushing the louvre assem­bly back. Lift the clip.
W415-0429 / C / 11.04.05
Page 18
18
LOG PLACEMENT
PHAZERTM logs and glowing embers exclusive to Napoleon Fire-
places, provide a unique and realistic glowing effect that is different in every installation. Take the time to carefully po­sition the glowing embers for a maximum glowing effect. Log colours may vary. During the initial use of the fireplace, the colours will become more uniform as colour pigments burn in during the heat activated curing process.
FIGURE 38a-d
1
1. Place rear logs #1 & #2 against the back of the firebox with the notch in the bottom of log #2 around the pilot assembly, as shown.
3
2. Place logs #3 and #4 onto the locating pins on the burner.
4
2
6
4. Place the bottom of log #6 against the right side of the firebox. The upper branch rests against log #1. The lower branch rests against the 4th and 5th grate posts.
CHARCOAL EMBERS
Randomly place the charcoal embers along the front and sides of the log support tray in a realistic manner. Fine
dust found in the bottom of the bag should not be used.
GLOWING EMBERS
Tear the embers into pieces and place along the front row of ports covering all of the burner area in front of the small logs (#2 & #3). Care should be taken to shred the embers into thin, small irregular pieces as only the exposed edges of the fibre hairs will glow. The ember material will only
glow when exposed to direct flame; however, care should be taken to not block the burner ports.
Blocked burner ports can cause an incorrect flame pattern, carbon deposits and delayed ignition. PHAZERTM logs glow when exposed to direct flame. Use only certified "glowing embers" and PHAZERTM logs available from your Napo­leon dealer.
GLOWING CRYSTAL EMBERS
Place the glowing crystal embers along the front of the log support on the glass only. Make sure the glowing crystal embers don't block the gap between the burner and the glass.
DO NOT PLACE GLOWING CRYSTAL EMBERS
ON THE BURNER.
5
3. Place the bottom of log #5 against the left side of the firebox. Rest the log back, diagonally into the designated pocket in log #1.
W415-0429 / C / 11.04.05
FIGURE 39
GLOWING CRYST AL EMBERS
LOGO PLACEMENT
Remove the backing of the logo supplied and place on the glass viewing door, as indicated.
½"
LOGO
½"
FIGURE 40
Page 19
BLOWER REPLACEMENT
1. Before proceeding, turn off the power to the unit.
2. Turn the pilot light off.
3. Remove the logs and place in a location where they will
not be damaged.
19
SCREWS
FIGURE 41
4. Remove the 2 side metal brick panels by re-
SCREWS
moving the two securing screws on the front of the panels.
FIGURE 42
REAR DOOR
SCREWS
5. Remove the 4 screws that secure the rear door and remove the door.
FLAME
EFFECT
FIGURE 44
7. Remove the flame effect panel by removing the 6 screws.
FIGURE 45
FLAME GENERATOR
8. Remove the flame generator by sliding to the left and dislodging the neoprene tube from the motor shaft. Next, slide the flame generator to the right to remove the shaft from the nylon bearing.
FIGURE 46
FIGURE 43a
SECURING BRACKET
SECURING BRACKET
FIGURE 43b
6. Remove the top and bottom glass securing brackets on the upper and lower portions of the glass opening and remove the glass.
FLAME EFFECT BULB REPLACEMENT
To replace the flame effect bulbs, follow steps 1-8 of the BLOWER REPLACEMENT section above, then continue with step 9.
9. Slide the defective bulb to either side until opposite end is disengaged. Remove the bulb towards the back of the fireplace.
9. Remove the two wires secured to the blower (they should slide off of the connector).
10. Remove the wing nut.
11. Remove the blower and replace with the new one.
12. Repeat steps 9 through 1 to put unit back together.
10. Replace with 75 watt Halogen light (E-11 Base).
Install the replacement bulb using the protective wrap to avoid touching the lense, then discard protective wrap.
11. Repeat steps 8 through1 to put the unit back together.
W415-0429 / C / 11.04.05
Page 20
20
EMBER BED BULB REPLACEMENT
FIGURE 47
1. Remove the lower control panel by removing the 8 se­curing screws.
OPERATION
FIREPLACE OPERATION
To operate the gas features, the pilot needs to be running and the gas valve turned to the on position.
You can run the fireplace on manual or remote.
When operating the main burner on manual,
the fireplace will operate on low input only.
FIGURE 48
2. Hold the lower portion of the light socket and turn clockwise to remove.
3. Pull the bulb straight out of the socket and replace the bulb being careful not to touch the quartz portion with your fingers.
4. To put back together, reinstall the control panel removed in step 1.
FIGURE 50
LIGHT SOCKET
FIGURE 49
GAS
Turn the respective main power switches to manual to operate either the gas or the electric features of the fire­place without the remote or thermostat.
Turn both the main power switches to remote to operate either the gas or the electric features of the fireplace with the remote or thermostat.
Turn both the main power switches to the off position to disable either the gas or the electric features of the fireplace.
In order to save the battery life on the remote, it is recommended that when operating the electric fireplace for an extended period of time, to operate with the electric power switch in the manual position.
HAND HELD REMOTE OPERATION
1. Turns electric flame on/off.
2. Turns gas flame on/off.
3. Activates gas flame adjustment.
4. Activates fan adjustment.
5. Adjusts options #3 & #4 up.
6. Sets the timer.
7. Adjusts options #3 & #4 down.
8. Sets the time.
W415-0429 / C / 11.04.05
Page 21
21
OPERATING INSTRUCTIONS
When lit for the first time, the fireplace will emit a slight odour for a few hours. This is a normal temporary condi­tion caused by the curing of the logs and the "burn-in" of internal paints and lubricants used in the manufacturing process and will not occur again.
FOR YOUR SAFETY READ BEFORE LIGHTING:
A. This fireplace is equipped with a pilot which must be
lit by hand while following these instructions exactly.
B. Before operating smell all around the fireplace area
for gas and next to the floor because some gas is heavier than air and will settle on the floor
C. Use only your hand to turn the gas control knob. Never
use tools. If the knob will not turn by hand, do not try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this fireplace if any part has been under
water. Immediately call a qualified service technician to inspect the fireplace and replace any part of the control system and any gas control which has been under water.
LIGHTING INSTRUCTIONS
WARNING: The gas valve has an interlock device which will not allow the pilot burner to be lit until the thermocou­ple has cooled. Allow approximately 60 seconds for the thermocouple to cool.
When lighting and re-lighting, the gas knob cannot be turned from pilot to off unless the knob is depressed
slightly.
1. Stop! Read the above safety information on this label.
2. Turn off all electric power to the fireplace.
3. Turn the gas knob clockwise to off.
4. Wait five (5) minutes to clear out any gas. If you smell gas
including near the floor. Stop! Follow "B" in the above safety
After extended periods of non-operation such as following a vacation or a warm weather season, the fireplace may emit a slight odour for a few hours. This is caused by dust particles in the heat exchanger burning off. In both cases, open a window to sufficiently ventilate the room.
Purge the gas line with the glass door open. Assure that a continuous gas flow is at the burner before closing the door.
WHAT TO DO IF YOU SMELL GAS
O
• Turn off all gas to the fireplace.
• Open windows.
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier from a neighbour's
phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire de-
partment.
FIGURE 52
information on this label. If you don't smell gas go the next step.
5. Turn gas knob counter-clockwise to pilot.
6. Depress slightly and hold gas knob while lighting the
pilot with the push button ignitor. Keep knob depressed for one minute, then release. If pilot does not continue to burn, repeat steps 3 through 5.
7. With pilot lit, depress and turn gas knob counter-clock­wise to on.
8. If equipped with remote on-off switch/thermostat, main burner may not come on when you turn valve to on. Remote switch must be in the on position to ignite burner.
9. Turn on all electric power to the fireplace.
FIGURE 51
I
L
T
P
O
N
F
O
F
GAS KNOB
TO TURN OFF GAS
1. Turn off all electric power to the fireplace if service is to be performed.
MAINTENANCE
Turn off the gas and electrical power before servicing the fireplace.
CAUTION: Label all wires prior to disconnection when serv­icing controls. Wiring errors can cause improper and dan­gerous operation. Verify proper operation after servicing. This fireplace and its venting system should be inspected before use and at least annually by a qualified service per­son. The fireplace area must be kept clear and free of com­bustible materials, gasoline or other flammable vapours and liquids. The flow of combustion and ventilation air must not be obstructed.
1. In order to properly clean the burner and pilot assembly, remove the logs to expose both assemblies.
2. Push in gas control knob slightly and turn clockwise to off. Do not force.
2. Keep the control compartment, logs, burner, air shutter opening and the area surrounding the logs clean by vacu­uming or brushing, at least once a year.
3. Check to see that all burner ports are burning. Clean out any of the ports which may not be burning or are not burn­ing properly.
4. Check to see that the pilot flame is large enough to engulf the thermocouple and thermopile and reaches to­ward the burner with the third jet.
5. Replace the cleaned logs.
6. Check to see that the main burner ignites completely on all
openings when the gas knob for the burner is turned on. A 5 to 10 second total light-up period is satisfactory. If ignition takes longer, consult your Continental dealer / distributor.
7. Check that the gasketing on the sides, top and bottom of the door is not broken or missing. Replace if necessary.
W415-0429 / C / 11.04.05
Page 22
22
ELECTRICAL CONNECTION
This fireplace requires 6 amps, 120 volt and a 60 hz grounded circuit.
Do NOT use the fireplace if any part has been under water.
Call a qualified service technician IMMEDIATELY to have the fireplace inspected for damage to the electrical cir­cuit.
HARD WIRING CONNECTION
It is necessary to hard wire this fireplace.
Permanently framing the fireplace with an enclosure, re­quires the fireplace to be hardwired.
This fireplace must be electrically connected and grounded in accordance with local codes. In the absence of local codes, use the current CSA C22.1 CANADIAN ELECTRI­CAL CODE in Canada or the ANSI/NFPA 70-1996 NATIONAL ELECTRICAL CODE in the United States.
The plastic coating of the two electrical inlet lines are marked "H" for hot and "C" for common.
Electric Diagram
FIGURE 53
ELECTRICAL DIAGRAM LEGEND
# Part # Description
1. W660-0029 Controller
2. W707-0003 Transformer
3. W660-0034 Rocker Switch
4. W062-0005 Blower
5. W750-0117 Light Harness
6. W387-0004 5 Watt Quartz Light
7. W435-0004 12 Volt Motor
8. W350-0126 Receptical (Electrical Box)
9. W387-0003 75 Watt Quartz Bulbs
10. W725-0035 Natural Gas Valve W725-0034 Propane Valve
11. W750-0122 1 pcs
12. W750-0123 1 pcs
13. W750-0124 1 pcs
14. W750-0134 1 pcs
15. W175-0010 Wire Nut
16. W750-0133 Line In Wire Harness (common)
17. W750-0133 Line In Wire Harness (hot)
18. W750-0135 1 pcs
19. W750-0136 1 pcs
W415-0429 / C / 11.04.05
Page 23
ADJUSTMENTS
23
PILOT BURNER ADJUSTMENT
Adjust the pilot screw to provide properly sized flame. Turn in a clockwise direction to reduce the gas flow.
PILOT SCREW
FIGURE 54
FIGURE 55
VENTURI ADJUSTMENT
Air shutters have been factory set open according to the chart below:
AIR SHUTTER
NG LP
These settings are for the maximum horizontal vent run. Adjustment may be required depending on fuel type, vent configuration and altitude.
1
3
/
16
/16"
"
Closing the air shutter will cause a more yellow flame, but can lead to carboning.
Opening the air shutter will cause a more blue flame, but can cause flame lifting from the burner ports. The flame may not appear yellow immediately; allow 15 to 30 min­utes for the final flame colour to be established.
FIGURE 56
Air shutter adjustment must only be done by a
qualified installer!
VENTURI
COVER
FIGURE 57
1. Remove the front central panel to access the venturi housing.
2. Remove the 2 screws that secure the cover to the venturi housing, taking care not to damage the gasket.
W415-0429 / B / 05.25.04
Page 24
24
REPLACEMENTS
Contact your dealer for questions concerning prices and availability of replacement parts. Normally all parts can be ordered through your Napoleon dealer or distributor.
When ordering replacement parts always give the follow­ing information:
FOR WARRANTY REPLACEMENT PARTS, A PHOTOCOPY OF THE
ORIGINAL INVOICE WILL BE REQUIRED TO HONOUR THE CLAIM.
REPLACEMENT PARTS
# PART NO. DESCRIPTION
1 W135-0214 LEFT REAR LOG (#1) 2 W135-0216 RIGHT REAR LOG (#2) 3 W135-0184 LEFT MIDDLE LOG (#3) 4 W135-0185 RIGHT MIDDLE LOG (#4) 5 W135-0215 LEFT CROSSOVER LOG (#5) 6 W135-0217 RIGHT CROSSOVER LOG (#6) 7 GL-645 LOG SET 8* W361-0016 GLOWING EMBERS 9* W550-0001 CHARCOAL EMBERS 10* W300-0077 GLASS CRYSTAL EMBERS 11 W357-0001 PIEZO IGNITER 12 W680-0004 THERMOPILE 13 W680-0005 THERMOCOUPLE 14 W010-0800 NATURAL GAS PILOT ASSEMBLY 14 W010-0801 PROPANE GAS PILOT ASSEMBLY 15* W573-0007 HIGH TEMPERATURE SEALANT 16 W455-0070 NATURAL GAS PILOT INJECTOR 16 W455-0068 PROPANE GAS PILOT INJECTOR 17 W725-0044 NATURAL GAS VALVE 17 W725-0045 PROPANE VALVE 18* W385-0245 NAPOLEON LOGO 19* W750-0112 20FT OF WIRE 20 W010-0764 PAN BURNER 21 W455-0040 #41 NATURAL GAS ORIFICE 21 W455-0003 #54 PROPANE GAS ORIFICE 22 W500-0044 FIRESTOP SPACER (FLEX VENTING) 23 W062-0005 BLOWER 24 W660-0030 REMOTE TRANSMITTER 25 W660-0031 REMOTE RECEIVER 26 W010-1168 REAR DOOR ASSEMBLY 27 W300-0074 FLAME EFFECT GLASS 28 W475-0330 DECORATIVE BRICK PANEL - LEFT 29 W475-0331 DECORATIVE BRICK PANEL - RIGHT 30 W010-1090 FLAME EFFECT ASSEMBLY 31 W387-0003 130 VAC T-3 78MM QUARTZ LAMP 32 W435-0006 FLAME EFFECT MOTOR 33 W660-0034 ROCKER SWITCH 34 W300-0072 EMBER BED GLASS 35 W300-0073 BURNER DEFUSER GLASS 36 W707-0003 VARIABLE TRANSFORMER
1. MODEL & SERIAL NUMBER OF FIREPLACE
2. INSTALLATION DATE OF FIREPLACE
3. PART NUMBER
4. DESCRIPTION OF PART
5. FINISH
* IDENTIFIES ITEMS WHICH ARE NOT ILLUSTRATED. FOR
FURTHER INFORMATION, CONTACT YOUR NAPOLEON
DEALER.
FLEXIBLE VENT KITS
GD220 (5 FT)
# PART NO. DESCRIPTION
37* W010-0397 4" FLEXIBLE ALUMINIUM LINER - (5 FT ) C/W SPACERS 37* W410-0017 7" FLEXIBLE ALUMINIUM LINER - (5 FT )
GD330 (10 FT)
# PART NO. DESCRIPTION
37* W410-0018 7" FLEXIBLE ALUMINIUM LINER -(10 FT ) 37* W010-0300 4" FLEXIBLE ALUMINIUM LINER -(10 FT ) C/W SPACERS 38* W010-0370 WALL SUPPORT ASSEMBLY
TERMINAL KITS
39 PERISCOPE - GD201 40 WALL TERMINAL KIT - GD222
ROOF TERMINAL KITS
41 1/12 TO 7/12 PITCH - GD110 42 8/12 TO 12/12 PITCH - GD111 43 FLAT ROOF - GD112
PART NO. DESCRIPTION
44 W010-0569 AIR TERMINAL 45 W120-0036 VERTICAL CAP 46 W170-0063 STORM COLLAR 47 W010-0567 ROOF SUPPORT 48 W263-0054 / W263-0055 / W263-0056 ROOF FLASHING
ACCESSORIES
# PART NO. DESCRIPTION
49* W175-0001 4" COUPLER 49* W175-0013 7" COUPLER 50 GDLVK LOUVRE KIT - UPPER & LOWER - BLACK 50 GDLVPB LOUVRE KIT - UPPER & LOWER - POLISHED BRASS 50 GDLVSS LOUVRE KIT - UPPER & LOWER - BRUSHED STAINLESS STEEL 50 GDLVG LOUVRE KIT - UPPER & LOWER - GOLD 51 L38K LOUVRE KIT - UPPER & LOWER - BLACK 52* W573-0008 HI-TEMPERATURE SEALANT 53* W690-0001 MILLIVOLT THERMOSTAT 54* W500-0163 FIRESTOP SPACER (RIGID VENTING) 55 GD501 HEAT GUARD 56* W585-0096 SOFFIT HEAT SHIELD 57* W010-0810 WALL SUPPORT ASSEMBLY 58* W175-0170 DURA-VENT ZERO CLEARANCE ADAPTOR 59 W170-0086 VENT PIPE COLLAR 60 W585-0092 VENT PIPE SHIELD 65* W175-0223 CONVERSION KIT - NG TO LP 65* W175-0224 CONVERSION KIT - LP TO NG 66 D70K BLACK DOOR 66 D70G GOLD DOOR 66 D70SS ST AINLESS STEEL DOOR
W415-0429 / C / 11.04.05
Page 25
25
13
21
17
28
32
12
*
11
16
39
14
22
29
45
44
59
60
48
46
20
55
36
47
33
25
26
66
50
ATTENTION-CHAUD
C A
U
T
I O
N
­H
O T
40
27
7
31
34
35
30
24
N
A
U
M
A
L
O
n
a
N
F
/
O
e m a
F
l F
F
r e
Tim
C
l o
F
c
k
F
O
/
N
O
O
T
U
A
2
4
23
1
3
51
5
* WARNING: This is a fast acting thermocouple. It is an integral safety component.
Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
6
W415-0429 / C / 11.04.05
Page 26
26
TROUBLE SHOOTING GUIDE
B
EFORE ATTEMPTING TO TROUBLESHOOT, PURGE YOUR UNIT AND INITIALLY LIGHT THE PILOT AND THE MAIN BURNER WITH THE GLASS DOOR OPEN
SYMPTOM PROBLEM TEST SOLUTION
.
Main burner goes out; pilot stays on.
Main burner goes out; pilot goes out.
Pilot goes out when the gas knob is re­leased.
The gas valve has an interlock device which will not allow the pilot burner to be lit until the ther­mocouple has cooled. Allow ap­proximately 60 seconds for the thermocouple to cool.
Pilot burning; no gas to main burner; gas knob is on 'HI'; wall switch / thermostat is on.
Pilot will not light. - check if pilot can be lit by a match
Pilot goes out while standing; Main burner is in 'OFF' position.
Pilot flame is not large enough or not engulfing the thermopile Thermopile shorting - clean thermopile connection to the valve. Reconnect.
Remote wall switch wire is too long; too much resist­ance in the system.
Faulty thermostat or switch. - replace.
Refer to "MAIN BURNER GOES OUT; PILOT STAYS ON" Vent is blocked Vent is re-circulating
4" flexible vent has become disconnected from fireplace.
System is not correctly purged. Out of propane gas. - fill the tank.
Pilot flame is not large enough
Pilot flame is not engulfing the thermocouple. Thermocouple shorting / faulty.
Faulty valve.
Themostat or switch is de-
fective. Wall switch wiring is defec­tive.
Main burner orifice is plugged. - remove stoppage in orifice.
Faulty valve. - replace.
No spark at pilot burner
Spark gap is incorrect - spark gap should be 0.150" to 0.175" (5/32" to 11/64" approx.) from
No gas at the pilot burner
Gas piping is undersized. - turn on all gas appliances and see if pilot flame flutters, dimin-
- turn up pilot flame.
- replace pilot assembly.
- replace thermopile / valve.
- shorten wire to correct length or wire gauge.
- check for vent blockage.
- check joint seals and installation.
- re-attach to fireplace.
- purge the gas line.
- turn up the pilot flame.
- gently twist the pilot head to improve the flame pattern around the thermocouple.
- loosen and tighten thermocouple.
- clean thermocouple and valve connection.
- replace thermocouple.
- replace valve.
- replace.
- connect a jumper wire across the wall switch terminals; if main burner lights, replace switch / thermostat.
- disconnect the switch wires & connect a jumper wire across termi­nals 1 & 3; if the main burner lights, check the wires for defects and / or replace wires.
- check that the wire is connected to the push button ignitor.
- check if the push button ignitor needs tightening.
- replace the wire if the wire insulation is broken or frayed.
- replace the electrode if the ceramic insulator is cracked or broken.
- replace the push button ignitor.
- fill the tank.Out of propane gas
the electrode tip and the pilot burner. To ensure proper electrode location, tighten securing nut (finger tight plus 1/4 turn).
- check that the manual valve is turned on.
- check the pilot orifice for blockage.
- replace the valve.
- call the gas distributor.
ishes or extinguishes, especially when main burner ignites. Monitor appliance supply working pressure.
- check if supply piping size is to code. Correct all undersized piping.
W415-0429 / C / 11.04.05
Page 27
SYMPTOM PROBLEM TEST SOLUTION
Flames are con­sistently too large or too small. Carboning occurs.
Flames are very aggressive.
Main burner flame is a blue, lazy, transparent flame.
Carbon is being deposited on glass, logs or com­bustion chamber surfaces.
White / grey film forms.
Remote wall switch is in "OFF" position; main burner comes on when gas knob is turned to "ON" po­sition.
Unit is over-fired or under­fired.
A
B
Door is ajar
Blockage in vent. - remove blockage. In really cold conditions, ice buildup may occur
Incorrect installation.
Air shutter has become blocked
Flame is impinging on the logs or combustion cham­ber.
Sulphur from fuel is being deposited on glass, logs or combustion chamber sur­faces.
Wall switch is mounted up­side down
grounding.
grounding.
Faulty valve.
- check pressure readings: Inlet pressure can be checked by turning screw (A) counter-clock­wise 2 or 3 turns and then placing pressure gauge tubing over the test point. Gauge should read 7" (minimum 4.5") water column for natural gas or 13" (11" minimum) water column for propane. Check that main burner is operating on "HI". Outlet pressure can be checked the same as above using screw (B). Gauge should read 3.5" water column for natural gas or 10" water column for propane. Check that main burner is operating on "HI". AFTER TAKING PRESSURE READINGS, BE SURE TO TURN SCREWS CLOCKWISE FIRMLY TO RESEAL. DO NOT OVERTORQUE. Leak test with a soap and water solution.
- Close door and secure the 2 latches.
on the terminal and should be removed as required.
- refer to Figure 23 to ensure correct location of storm collars.
- ensure air shutter opening is free of lint or other obstructions.
- check that the logs are correctly positioned.
- open air shutter to increase the primary air.
- check the input rate: check the manifold pressure and orifice size as specified by the rating plate values.
- check that the door gasketing is not broken or missing and that the seal is tight.
- check that both 4" and 7" vent liners are free of holes and well sealed at all joints.
- check that minimum rise per foor has been adhered to for any horizontal venting.
- clean the glass with a recommended gas fireplace glass cleaner. DO NOT CLEAN GLASS WHEN HOT.
If deposits are not cleaned off regularly, the glass may become permanently marked.
- reverse.
- replace.Remote wall switch is
- check for ground (short); repair ground or replace wire.Remote wall switch wire is
- replace.
27
ELECTRIC TROUBLE SHOOTING
All but flame light - Light bulbs are loose or - Remove the access panel and change or tighten light bulbs. works have burned out.
Flame light, but no - Flame generator is - Replace the batteries and check the power source. movement in the defective. - Consult your local dealer. flame - Flame generator has - Remove the access panel and check to make sure the flame
come loose. generator bracket is secured to the motor with the rubber tube.
Remote control - Dead batteries. - Make sure batteries are charged. not working - No power to the unit. - Make sure main power is on.
- Power turned off. - Turn on manual power switch.
- Power button on control - Make sure the power button is on REMOTE setting. panel is in the manual or off position.
Fireplace will not - Breaker or fuse has blown. - Reset breaker switch or replace fuse. turn on. - Main switch is in the off - Consult your local dealer.
position - Make sure main power switch is turned to the on position.
W415-0429 / C / 11.04.05
Page 28
28
SYMPTOM PROBLEM TEST SOLUTION
Excessive noise - Flame generator motor is - Consult your local dealer. coming from the unit. faulty.
Odour - Initial curing process. - Run the main burner until odour ceases.
- Dust has settled in the - Consult your local dealer. fireplace.
No light in front - Lights have burned out. - Replace with 5 watt quartz lights (plug in type). ember bed.
Wolf Steel Fireplace Service History
This fireplace must be serviced annually depending on usage.
Date
Dealer
Name
Service Technician
Name
Service
Performed
Special
Concerns
W415-0429 / C / 11.04.05