Napoleon Fireplaces GDS60-P, GDS60-N, GS60-N, GS60-P User Manual

INSTALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER.
CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS, CSA 2.33, ANSI Z21.88 FOR VENTED GAS FIREPLACE HEATERS
INSTALLATION AND OPERATION INSTRUCTIONS FOR:
VENTED GAS FIREPLACE HEATER
1
NATURAL GAS MODELS GDS60-N and GS60-N
Model GS60 is made up of Model GDS60 and the Adapter Kit GS-150KT
WARNING: If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapours and liquids in the vicin-
ity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your build ing.
Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada • (705)721-1212 • fax(705)722-6031
www.napoleonfireplaces.com • ask@napoleon.on.ca
W415-0158 / E / 02.19.04
2
r
TABLE of CONTENTS
Pg
2-4 INTRODUCTION
Warranty General Instructions General Information Care of Glass & Plated Parts Shipping Bracket
5 LOCATION & CLEARANCES
6-12 DIRECT VENT SPECIFICS
MODEL GDS60
Vent Lengths/Air Terminal Locations Special Installation Example Offset Installation Example Horizontal Terminations Orifice Replacement Top Vent to Rear Vent Modification Venting Parameters Wall & Ceiling Protection Horizontal Venting Installation Vertical Venting Installation Stove Vent Connection Mobile Home Installation
13-14 B-VENT SPECIFICS
MODEL GS60
Chimney Installation 'B' Vent Installation Combustion Air Adding Vent Sections Flashing and Storm Collar Installation
Pg
14 GAS INSTALLATION
15-16 FINISHING
Logo Placement Front Cast Installation Glass Door Closing & Opening Log Placement
17-18 OPERATION / MAINTENANCE
Spill Switch Venting Action Check Operating Instructions Maintenance
19 BLOWER INSTALLATION
19 ADJUSTMENTS
Pilot Burner Adjustment Venturi Adjustments Restricting Vertical Vents
20-21 REPLACEMENTS
Ordering Replacement Parts Termination Kits Replacement Parts Accessories
22-23 TROUBLE SHOOTING GUIDE
24 SERVICE HISTORY
PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE
WARNING
• The stove is a vented gas-fired heater. Do not burn wood or other materials in this stove.
• Adults and especially children should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Supervise young children when they are in the same room as the stove.
• Due to high temperatures, the stove should be located out of traffic and away from furniture and draperies.
• Clothing or other flammable material should not be placed on or near the stove.
• Any safety screen or guard removed for servicing must be replaced prior to operating the stove.
• It is imperative that the control compartments, burners and circulating blower and its passageway in the stove and venting system are kept clean. The stove and its venting system should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The stove area must be kept clear and free from combustible materials, gasoline and other flammable vapours and liquids.
• Under no circumstances should this stove be modified.
• This stove must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance.
• Do not use this stove if any part has been under water. Immediately call a qualified service technician to inspect the stove and to replace any part of the control system and any gas control which has been unde water.
• Do not operate the stove with the glass door opened, cracked or broken. Replacement of the glass should be done by a licensed or qualified service person.
• Do not strike or slam shut the stove glass door.
• This fireplace uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
NOTE: changes, other than editorial, are denoted by a vertical line in the margin.
W415-0158 / E / 02.19.04
NAPOLEON gas fireplaces are manufactured under the strict Standard of the world recognized
ISO 9001 : 2000 Quality Assurance Certificate. NAPOLEON products are designed with superior components and materials, assembled by trained craftsmen who take great pride in their work. The burner and valve assembly are leak and test-fired at a quality test station. The complete fireplace is test-fired and thoroughly inspected by a qualified technician before packaging to ensure that you, the customer, receives the quality product that you expect from NAPOLEON.
NAPOLEON GAS FIREPLACE PRESIDENT'S LIFETIME LIMITED WARRANTY
3
The following materials and workmanship in your new The following materials and workmanship in your new
The following materials and workmanship in your new
The following materials and workmanship in your new The following materials and workmanship in your new
as long as you own the fireplace. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™as long as you own the fireplace. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™
as long as you own the fireplace. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™
as long as you own the fireplace. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™as long as you own the fireplace. This covers: combustion chamber, heat exchanger, stainless steel burner, phazer™ logs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelledlogs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelled
logs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelled
logs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelledlogs and embers, ceramic glass (thermal breakage only), gold plated parts against tarnishing, porcelainized enamelled components and aluminum extrusion trims.components and aluminum extrusion trims.
components and aluminum extrusion trims.
components and aluminum extrusion trims.components and aluminum extrusion trims.
Electrical (110V and millivolt) components and wearable parts such as catalytic tiles, blowers, gas valves, thermalElectrical (110V and millivolt) components and wearable parts such as catalytic tiles, blowers, gas valves, thermal
Electrical (110V and millivolt) components and wearable parts such as catalytic tiles, blowers, gas valves, thermal
Electrical (110V and millivolt) components and wearable parts such as catalytic tiles, blowers, gas valves, thermalElectrical (110V and millivolt) components and wearable parts such as catalytic tiles, blowers, gas valves, thermal
switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and
switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and
switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and switch, switches, wiring, remote controls, ignitor, gasketing, and pilot assembly are covered and provide replacement parts free of charge during the first year of the limited warranty.provide replacement parts free of charge during the first year of the limited warranty.
provide replacement parts free of charge during the first year of the limited warranty.
provide replacement parts free of charge during the first year of the limited warranty.provide replacement parts free of charge during the first year of the limited warranty.
Labour related to warranty repair is covered free of charge during the first year. Repair work, however, requiresLabour related to warranty repair is covered free of charge during the first year. Repair work, however, requires
Labour related to warranty repair is covered free of charge during the first year. Repair work, however, requires
Labour related to warranty repair is covered free of charge during the first year. Repair work, however, requiresLabour related to warranty repair is covered free of charge during the first year. Repair work, however, requires
the prior approval of an authorized company official. Labour costs to the account of the prior approval of an authorized company official. Labour costs to the account of
the prior approval of an authorized company official. Labour costs to the account of
the prior approval of an authorized company official. Labour costs to the account of the prior approval of an authorized company official. Labour costs to the account of predetermined rate schedule and any repair work must be done through an authorized predetermined rate schedule and any repair work must be done through an authorized
predetermined rate schedule and any repair work must be done through an authorized
predetermined rate schedule and any repair work must be done through an authorized predetermined rate schedule and any repair work must be done through an authorized
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
gas fireplace are warranted against defects for gas fireplace are warranted against defects for
gas fireplace are warranted against defects for
gas fireplace are warranted against defects for gas fireplace are warranted against defects for
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
NAPOLEONNAPOLEON
NAPOLEON
NAPOLEONNAPOLEON
are based on a are based on a
are based on a
are based on a are based on a
dealer. dealer.
dealer.
dealer. dealer.
willwill
will
willwill
CONDITIONS AND LIMITATIONS
NAPOLEON warrants its products against manufacturing defects to the original purchaser only -- i.e., the individual or legal entity (registered customer) whose name appears on the
warranty registration card filed with NAPOLEON -- provided that the purchase was made through an authorized NAPOLEON dealer and is subject to the following conditions and limitations:
This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives. The gas fireplace must be installed by a licenced, authorized service technician or contractor. Installation must be done in accordance with the installation instructions included with the product
and all local and national building and fire codes.
This limited warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed from other manufacturers will nullify this
warranty.
This limited warranty further does not cover any scratches, dents, corrosion or discolouring caused by excessive heat, abrasive and chemical cleaners nor chipping on porcelain enamel
parts, mechanical breakage of PHAZER™ logs and embers, nor any venting components used in the installation of the fireplace.
NAPOLEON warrants its stainless steel burners against defects in workmanship and material for life, subject to the following conditions: During the first 10 years NAPOLEON will replace
or repair the defective parts at our option free of charge. From 10 years to life, NAPOLEON will provide replacement burners at 50% of the current retail price.
In the first year only, this warranty extends to the repair or replacement of warranted part s which are defective in material or workmanship provided that the product has been operated in
accordance with the operation instructions and under normal conditions.
After the first year, with respect to this President's Limited Lifetime Warranty , NAPOLEON may , at its discretion, fully discharge all obligations with respect to this warranty by refunding to
the original warranted purchaser the wholesale price of any warranted but defective part(s).
After the first year, NAPOLEON will not be responsible for installation, labour or any other costs or expenses related to the reinstallation of a warranted part, and such expenses are not covered
by this warranty.
Notwithstanding any provisions contained in this President's Limited Lifetime Warranty , NAPOLEON’S responsibility under this warranty is defined as above and it shall not in any event extend
to any incidental, consequential or indirect damages.
This warranty defines the obligations and liability of NAPOLEON with respect to the NAPOLEON gas fireplace and any other warranties expressed or implied with respect to this product,
its components or accessories are excluded.
NAPOLEON neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this product. NAPOLEON will not be responsible for: over-firing, downdrafts, spillage caused by environmental conditions such as rooftops, buildings, nearby trees, hills, mountains, inadequate vents or ventilation, excessive venting configurations, insufficient makeup air, or negative air pressures which may or may not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.
Any damages to fireplace, combustion chamber, heat exchanger, brass trim or other component due to water, weather damage, long periods of dampness, condensation, damaging chemicals or cleaners will not be the responsibility of NAPOLEON.
The bill of sale or copy will be required together with a serial number and a model number when making any warranty claims from your authorized dealer. The warranty registration card must be returned within fourteen days to register the warranty.
NAPOLEON reserves the right to have its representative inspect any product or part thereof prior to honouring any warranty claim.
ALL SPECIFICA TIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE T O ON-GOING PRODUCT IMPROVEMENTS. NAPOLEON® IS A REGISTERED TRADEMARK OF WOLF STEEL LTD. PA TENTS U.S. 5.303.693.801 - CAN. 2.073.411, 2.082.915. © WOLF STEEL L TD.
W415-0158 / E / 02.19.04
4
GENERAL INSTRUCTIONS
THIS GAS STOVE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local codes.
Installation practices vary from region to region and it is important to know the specifics that apply to your area, for example: in Massachusetts State:
• The fireplace damper must be removed or welded in the open position prior to installation of a fireplace insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The flexible connector must not be longer than 36 inches.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
• WARNING: This product must be installed by a licensed plumber or gas fitter when installed within the commonwealth of Massachusetts.
In absence of local codes, install to the current CAN1-B149 Installation Code in Canada or to the National Fuel Gas Code, ANSI Z223.1, and NFPA 54 in the United St ates. Mobile home installation must conform with local codes. In the absence of local codes, install to the current standard for gas equipped mobile housing CAN/CSA Z240 MH Series in Canada or the manufactured home construction and safety standard, Title 24 CFR, part 3280, or the Fire Safety Criteria for manufactured home installations, Sites and Community Standard ANSI/NFPA 501A in the United States.
Purge all gas lines with the glass door of the stove removed. Assure that a continuous gas flow is at the burner before re­installing the door. Under extreme vent configurations, allow several minutes (5-
15) for the flame to stabilize after ignition.
It is recommended that all horizontal runs have a ¼ inch rise per foot. Objects placed in front of the stove must be kept a minimum of 48" away from the front face of the unit.
The stove and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The stove must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psig (3.5 kPa). The stove, when installed with a blower, must be electrically connected and grounded in accordance with local codes. In the absence of local codes, use the current CSA C22.1 CANADIAN ELECTRICAL CODE in Canada or the ANSI/NFPA 70-1996 NATIONAL ELECTRICAL CODE in the United S tates. The blower power cord must be connected into a properly grounded receptacle. The grounding prong must not be removed from the cord plug.
GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS STOVE HAS BEEN TEST­FIRED TO ASSURE ITS OPERATION AND QUALITY!
Minimum inlet gas supply pressure is 4.5 inches water column for natural gas and 11 inches water column for propane. Maximum inlet gas pressure is 7 inches water column for natural gas and 13 inches water column for propane. When the valve is set to "HI", the manifold pressure under flow conditions is 3.5 inches water column for natural gas and 10 inches water column for propane. When the fireplace is installed at elevations above 4,500ft, and in the absence of specific recommendations from the local authority having juris­diction, the certified high altitude input rating shall be reduced at the rate of 4% for each additional 1,000ft.
W415-0158 / E / 02.19.04
Change in flame appearance from "HI" to "LO" is more evi­dent in natural gas than in propane. Expansion / contraction noises during heating up and cooling down cycles are nor­mal and to be expected.
This appliance is only for use with the type of gas indicated on the rating plate. (See page 14). This appliance is not convertible for use with other gases, unless a certified kit is used.
INSTINST
ALLER:ALLER:
INST
ALLER:
INSTINST
ALLER:ALLER:
appropriate box on the rating plate according to theappropriate box on the rating plate according to the
appropriate box on the rating plate according to the
appropriate box on the rating plate according to theappropriate box on the rating plate according to the model, venting and gas type of the unit.model, venting and gas type of the unit.
model, venting and gas type of the unit.
model, venting and gas type of the unit.model, venting and gas type of the unit.
It is y It is y
It is y
It is y It is y
our rour r
our r
our rour r
esponsibesponsib
esponsib
esponsibesponsib
lity to clity to c
lity to c
lity to clity to c
hechec
hec
hechec
k ofk of
k of
k ofk of
ff
the the
f
the
ff
the the
CARE OF GLASS, AND PLATED PARTS
Do not use abrasive cleaners to clean these parts. Buff lightly with a clean dry cloth. The glass is 3/16" ceramic glass available from your Napo­leon / Wolf Steel Lt d. dealer . DO NOT SUBSTITUTE MATE­RIALS. Clean the glass after the first 10 hours of operation with a recommended gas fireplace glass cleaner. Thereaf­ter clean as required. DO NOT CLEAN GLASS WHEN HOT! If the glass is not kept clean permanent discolouration and / or blemishes may result.
SHIPPING BRACKET
To avoid the stove being damaged during shipping, a ship­ping bracket has been used and must be unbolted before the stove can be installed.
1. Remove the four nuts holding the shipping bracket to the bottom of the stove.
2. Lift the stove up and away from the skid to clear the threaded bolts sticking through the bracket. Set down on a flat surface. The stove top is not secured to the unit.
3. Discard the nuts, bracket and the skid.
FIGURE 1
4 NUTS
SHIPPING BRACKET
GDS60: TOP VENT / REAR VENT VERTICAL TERMINATION: Maximum in-
put is 35,000 BTU/hr for natural gas and 31,500 BTU/hr for propane. Maximum output for natural gas is 27,300 BTU/hr at an efficiency of 78%. Maximum output for pro­pane is 24,570 BTU/hr at an efficiency of 78%. Maxi­mum A.F.U.E. (annual fuel utilization efficiency) rating is 72% for natural gas and 71% for propane.
REAR VENT HORIZONTAL TERMINA­TION: Maximum input is 21,000 BTU/hr for natural
and propane gas. This application requires changing the main burner orifice.
This stove is not approved for closet or recessed instal­lations. It is approved for bathroom, bedroom and bed­sitting room installations. This stove may be installed in an aftermarket perma­nently located, manufactured (mobile) home, where not prohibited by local codes.
GS60: Maximum input is 35,000 BTU/hr for natural
gas and 31,500 BTU/hr for propane. This stove is ap­proved for bedroom and bed-sitting room installations.
LOCATION & CLEARANCES
5
Provide adequate ventilation and combustion air.
Provide adequate accessibility clearance for servicing
and operating the stove.
Never obstruct the front opening of the stove.
GDS60 AND GS60
As long as clearance to combustibles is kept within the required distances, the most desirable and beneficial lo­cation for a Napoleon stove is in the centre of a building, thereby allowing the most efficient use of the heat created. The location of windows, doors and the traffic flow in the room where the stove is to be located should be consid­ered. If possible, you should choose a location where the vent will pass through the house without cutting a floor or roof joist.
MAINTAIN THESE MINIMUM CLEARANCES TO COMBUSTIBLES:
FIGURE 3
A. 6" B. 6" C. 2"*
NO ADDITIONAL FLOOR PROTECTION IS REQUIRED
MINIMUM
20" FROM STOVE TOP TO CEILING 6" TO SINGLE WALL CONNECTOR 1" TO DIRECT VENT AND B-VENT *AT A DISTANCE OF 2" FROM THE WALL, ACCESS TO THE BLOWER
, ON-OFF SWITCH OR THE BLOWER POWER CORD MAY NOT
SWITCH
PRACTICAL.
BE
A terminal shall not terminate directly above aA terminal shall not terminate directly above a
A terminal shall not terminate directly above a
A terminal shall not terminate directly above aA terminal shall not terminate directly above a sidewalk or paved driveway which is locatedsidewalk or paved driveway which is located
sidewalk or paved driveway which is located
sidewalk or paved driveway which is locatedsidewalk or paved driveway which is located between two single family dwellings and servesbetween two single family dwellings and serves
between two single family dwellings and serves
between two single family dwellings and servesbetween two single family dwellings and serves both dwboth dw
both dw
both dwboth dw rr
equirequir
r
equir
rr
equirequir
ellingsellings
ellings
ellingsellings
e dife dif
e dif
e dife dif
. Local codes or r. Local codes or r
. Local codes or r
. Local codes or r. Local codes or r
ff
erer
ent cent c
learlear
f
ff
er
erer
ent c
ent cent c
lear
learlear
ancesances
ances
ancesances
ee
gulagula
tions mations ma
e
gula
tions ma
ee
gulagula
tions mations ma
..
.
..
yy
y
yy
Do not allow the inside liner to bunch up on horizontalDo not allow the inside liner to bunch up on horizontal
Do not allow the inside liner to bunch up on horizontal
Do not allow the inside liner to bunch up on horizontalDo not allow the inside liner to bunch up on horizontal or vor v
erer
tical rtical r
or v
er
or vor v
erer
4" air gap all around between the inner liner and outer4" air gap all around between the inner liner and outer
4" air gap all around between the inner liner and outer
4" air gap all around between the inner liner and outer4" air gap all around between the inner liner and outer stove pipe is required for safe operation. Use a firestopstove pipe is required for safe operation. Use a firestop
stove pipe is required for safe operation. Use a firestop
stove pipe is required for safe operation. Use a firestopstove pipe is required for safe operation. Use a firestop when penetrating interior walls, floor or ceiling.when penetrating interior walls, floor or ceiling.
when penetrating interior walls, floor or ceiling.
when penetrating interior walls, floor or ceiling.when penetrating interior walls, floor or ceiling.
uns and elbowsuns and elbows
tical r
uns and elbows
tical rtical r
uns and elbowsuns and elbows
. K. K
eeee
p it pulled tight. p it pulled tight.
. K
ee
p it pulled tight.
. K. K
eeee
p it pulled tight. p it pulled tight.
AA
A
AA
1-1/ 1-1/
1-1/
1-1/ 1-1/
FIGURE 2 - SHOWN WITH OPTIONAL FRONT INST ALLED
NOTE: The total width of the stove is increased to 39" width with the
optional side shelves attached.
W415-0158 / E / 02.19.04
6
DIRECT VENT SPECIFICS - MODEL GDS60
VENTING LENGTHS &
AIR TERMINAL LOCATIONS
Use only Wolf Steel or Simpson Dura-Vent Model DV-GS venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air termi­nal locations for either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, follow the installation procedure provided with the venting com­ponents. Both Wolf Steel and Simpson Dura-Vent venting components may have a 0" rise per foot on horizontal runs.
When using Wolf Steel venting components, use only the following vent kits: WALL TERMINAL KIT GD175 (7-1/2' of venting included), or 1/12 TO 7/12 PITCH ROOF TERMINAL
KIT GD110, 8/12 TO 12/12 ROOF TERMINAL KIT GD111, FLA T ROOF TERMINAL KIT GD1 12 or S TOVE PERISCOPE KIT GD180 (for wall penetration below grade) in conjunc-
tion with the appropriate venting components.
For optimum perform­ance, it is recom­mended that all hori­zontal runs have a mini­mum ¼ inch rise per foot.
These vent kits allow for either horizontal or vertical venting of the stove. The maximum number of 4" flexible connections is two horizontally or three vertically (excluding the stove and the air terminal connections). When terminating vertically, the minimum vertical rise is 34 inches above the stove and the maximum vertical rise is 40 feet. FIGURE 4.
Deviation from the minimum vertical vent length can cre­ate difficulty in burner start-up and/or carboning.
Use an adjustable pipe as the final length of rigid piping to the stove for ease of installation.
For optimum flame appearance and stove performance, keep the vent length and number of elbows to a minimum. The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged. The maximum horizontal run is 34 inches with a 90o elbow located 29" above the stove. FIGURE 5.
The maximum horizontal run with a 57 inch vertical rise immediately above the stove is 20 feet . FIGURES 6a & b.
IF VERTICAL RISES GREATER THAN 57 INCHES ARE NECES­SARY, THE INCREASED RISE MUST BE DEDUCTED FROM THE MAXIMUM HORIZONTAL RUN.
FIGURE 4
FIGURE 5
FIGS 6a-b
HORIZONTAL RUN NOT TO EXCEED VERTICAL RISE
Use the chart on this page to calculate horizontal runs for vertical rises between 29 and 57 inches. When calculating maximum run lengths, include 5 feet for each 90° or 45° elbow. (DO NOT INCLUDE THE FIRST ELBOW DIRECTLY OFF THE UNIT.)
REQUIRED VERTICAL RISE FROM FIREPLACE TO FIRST EL­BOW IN INCHES
FIGURE 7
W415-0158 / E / 02.19.04
CALCULATED HORIZONTAL VENT RUN IN FEET
AIR TERMINAL INSTALLATIONS
f
FIGURE 8
INSTALLATIONS
CANADIAN U.S.A.
A
12 INCHES
12 INCHES
Clearance above grade, veranda porch, deck or balcony.
7
B
C
12 INCHES
12 INCHES*
9 INCHES
12 INCHES*
Clearance to windows or doors that open.
Clearance to permanently closed windows.
Vertical clearance to ventilated soffit located above the terminal within
D
18 INCHES** 12 INCHES**
E
F
0 INCHES
0 INCHES***
G
2 INCHES***
H
I
J
K
L
M
N
O
*
* Recommended to prevent condensation on windows and thermal breakage
* ****
** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffits.
**** ******
*** The periscope GD-201 requires a minimum 18 inches clearance from an inside corner.
****** ********
**** This is a recommended distance. For additional requirements check local codes.
******** †
Three feet above if within 10 feet horizontally.
† ‡
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single
‡ ††† †
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.
††† † †*†*
†* Recommenced to prevent recirculation of exhaust products. For additional requirements check local code
†*†*
3 FEET 3 FEET
12 INCHES
6 FEET
7 FEET‡
12 INCHES††
16 INCHES
2 FEET†*
dwellings and serves both dwellings.
18 INCHES** 12 INCHES**
0 INCHES
0 INCHES***
2 INCHES***
3 FEET**** 3 FEET****
9 INCHES
3 FEET†
7 FEET****
12 INCHES****
16 INCHES
2 FEET†*
a horizontal distance of 2 feet from the centerline of the terminal.
Clearance to unventilated soffit.
Clearance to an outside corner wall.
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
Clearance to an inside combustible corner wall or protruding com­bustible obstructions ( vent chase, etc.).
Clearance to each side of the centerline extended above the meter / regulator assembly to a maximum vertical distance of 15ft.
Clearance to a service regulator vent outlet.
Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
Clearance to a mechanical air supply inlet.
Clearance above a paved sidewalk or paved driveway located on public property unless fitted with a heat shield kit GD-301.
Clearance under a veranda, porch, deck or balcony.
Clearance above the roof.
Clearance from an adjacent wall including neighbouring buildings.
W415-0158 / E / 02.19.04
8
SPECIAL INSTALLATION EXAMPLE
When a horizontal offset is required in a through-the-roof installation, the following procedure for vent length calcula­tions must be followed:
In an installation as shown in FIGURES 9 & 12, lengths A and C are known based on room height and roof require­ments.
Length C must never be less than 29 inches. Any 90° and 45° elbows must be calculated as 5 feet of venting each.
The allowable horizontal run can be calculated using these parameters. In this example, the total vertical height is 20 feet (length "A" is required to be 11 feet while length "C" needs to be 9 feet). The maximum vertical length is 40 feet and all runs and elbows must be sub­tracted from this maximum vertical length.
The maximum allowable horizontal run that "B" can be is:
40 ft. (maximum vertical run length)
-11 ft. (through the roof vertical rise "A")
-10 ft. (2 - 90° elbow)
- 9 ft. (vertical run "C") 10 ft. (maximum allowable horizontal length for "B")
The length of "B" must never be greater than the length of "A" and "C" combined.
FIGURE 9
OFFSET INSTALLATION EXAMPLE
FIGURE 10
If a first run of 120 inches is re­quired, using the "First Vent Run" on the chart shows that a maxi-
mum second run of 60 inches
is allowable.
IF NECESSARY, THE FIRST RUN AND THE SECOND RUN MAY BE REVERSED.
FIGURE 11
The maximum allowable horizontal run that "A" in Figure 13 can be is:
40 ft. (maximum vertical run length)
- 7 ft. (horizontal run "B")
33 ft. (maximum allowable vertical length for "A")
FIGURE 12
FIGURE 13
W415-0158 / E / 02.19.04
REAR VENT HORIZONTAL TERMINATION
When venting off the rear of the unit and terminating horizontally, a #45 natural gas orifice or a #55 propane orifice must be used.
9
Care should be taken not to damage the gas pipe. When removing the orifice, using a 9/16" socket wrench, a 7/8" back-up wrench must be used on the manifold, located below the housing, to ensure that the aluminum tubing does not twist or kink.
CHANGING A TOP VENT TO A REAR VENT
STOVE TOP
FIGURE 14a
TOP VENT FILLER PLATE
The maximum allowable length is 20 feet. All 90° and 45° elbows (except the first two when venting horizontally) re­duce the length by 5 feet each, both horizontally and verti­cally). In this illustration, the maximum allowable length after taking the two elbows into account is 10 feet.
REQUIRED VERTICAL RISE FROM FIREPLACE TO FIRST EL­BOW IN INCHES
FIGURE 14b
CALCULATED HORIZONTAL VENT RUN IN FEET
Use the chart on this page to calculate horizontal runs for vertical rises between 29 and 57 inches. When calculating maximum run lengths, include 5 feet for each 90° or 45° elbow. (DO NOT INCLUDE THE FIRST TWO ELBOWS DIRECTLY OFF THE UNIT WHEN VENTING HORIZONTALLY.)
ORIFICE REPLACEMENT
FIGURE 17a
Unscrew and discard the top vent filler plate. Lift off the cast stove top. Unscrew the four screws holding both the top heat shield and the 7" flue collar in place and lift off.
FIGURE 17b
Lift the gasket off. Unscrew the 4 screws securing the 4" collar and its gasket in place and remove it and the knock­out from the rear panel. Remove the 7" and 4" covers and gaskets from the back. Position the 4" gasket and cover over the flue opening in the top.
FIGURE 17c
Secure with 4 screws. Place the 7" gasket and cover over the air opening in the top. Replace the top heat shield and re-secure. Secure both gaskets and collars over the rear openings. Using the 2 screws secure the optional trivet to the underside of the top. Replace the stove top.
7" COVER
4" COVER
(FLANGE DOWN)
FIGURE 15
In order to access the orifice, the log support secured by two screws, must be removed.
FIGURE 16
TOP HEAT SHIELD
FIGURE 17d
W415-0158 / E / 02.19.04
10
VENTING PARAMETERS
FIGURES 18a-d
CORNER INSTALLA TION
WALL & CEILING
PROTECTION
FOR SAFE AND PROPER OPERA TION OF THE STOVE, FOLLOW THE VENTING INSTRUCTIONS EXACTL Y .
OR
FIGURE 19
HORIZONTAL INSTALLATION
This application occurs when venting through an exterior wall. Having determined the air terminal location, cut and frame a hole in an exterior wall with a minimum square or round opening of 9". (As an alternative to framing, a vent pipe shield may be installed, ensuring a 1" clearance to combustibles.)
FOR OPTIMUM PERFORMANCE, THE STOVE PIPE SHOULD RISE ¼" PER FOOT OF RUN.
1. Mark and cut the vent pipe shield to the determined depth of the combustible wall. Apply a bead of caulking (not supplied) to the framework or to the shield plate (in the case of a finished wall) and secure the shield through the opening to the interior wall. The final location of the vent
pipe shield should maintain the required clearance to the 7" vent pipe. Do not fill this cavity with any type of material.
Apply a bead of caulking all around and place a firestop spacer over the vent shield to restrict cold air from being drawn into the room or around the stove. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its final position, apply sealant between the pipe and the firestop spacer.
W415-0158 / E / 02.19.04
VERTICAL INSTALLATION HORIZONTAL VENTING INSTALLATION
This application occurs when venting through a roof.
Installation kits for vari­ous roof pitches are available from your Na­poleon dealer. See Ac­cessories to order the specific kit required.
1. Determine the air terminal location and move the stove into position. Cut and frame 9 inch openings in the ceiling and the roof to provide the minimum 1 inch clearance be­tween the stove pipe and any combustible material. Try to
FIGURE 21
DO NOT FILL THIS SP ACE WITH ANY TYPE OF MATERIAL. A vent pipe shield will prevent any materials such as insu-
lation, from filling up the 1" air space around the pipe. Nail headers between the joist for extra support.
2. Apply a bead of caulking (not supplied) to the frame­work or to the Wolf Steel vent pipe shield plate or equiva­lent (in the case of a finished ceiling), and secure over the opening in the ceiling. A firestop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through. Apply a bead of caulking all around and place a firestop spacer over the vent shield to restrict cold air from being drawn into the room or around the stove. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its final position, apply sealant between the pipe and the firestop spacer.
3. In the attic, after the pipe has been installed, slide the vent pipe collar down to cover up the open end of the shield and tighten. This will prevent any materials, such as insulation, from filling up the 1" air space around the pipe.
FIGURE 20
center the exhaust pipe location midway be­tween two joist to pre­vent having to cut them. Use a plumb bob to line up the center of the openings.
11
FOR SAFE AND PROPER OPERAFOR SAFE AND PROPER OPERA
FOR SAFE AND PROPER OPERA
FOR SAFE AND PROPER OPERAFOR SAFE AND PROPER OPERA
STST
OO
VE, FOLLVE, FOLL
ST
O
VE, FOLL
STST
OO
VE, FOLLVE, FOLL
FOR HORIZONTFOR HORIZONT
FOR HORIZONT
FOR HORIZONTFOR HORIZONT
SIMPSON DURA-VENT VENTING COMPONENTS MASIMPSON DURA-VENT VENTING COMPONENTS MA
SIMPSON DURA-VENT VENTING COMPONENTS MA
SIMPSON DURA-VENT VENTING COMPONENTS MASIMPSON DURA-VENT VENTING COMPONENTS MA
FOR OPTIMUM PERFORMANCE IT IS RECOM-FOR OPTIMUM PERFORMANCE IT IS RECOM-
FOR OPTIMUM PERFORMANCE IT IS RECOM-
FOR OPTIMUM PERFORMANCE IT IS RECOM-FOR OPTIMUM PERFORMANCE IT IS RECOM-
MENDED THAMENDED THA
MENDED THA
MENDED THAMENDED THA
MINIMUM MINIMUM
MINIMUM
MINIMUM MINIMUM
1. Stretch the 4" diameter aluminum flexible liner to the required length taking into account the additional length needed for the finished wall surface.
Spacers are attached to the 4" inner flex liner at predeter­mined intervals to maintain a 1-1/4" air gap to the 7" outer stove pipe. These spacers must not be removed. Slip a 4" diameter length of aluminum flexible liner a mini­mum of 2" over the inner sleeve of the air terminal. Secure to the sleeve using 3 screws. Seal the joint and screw heads using the high temperature sealant provided.
2. Slip the first section of 7" diameter stove pipe a mini­mum of 2" over the outer sleeve of the air terminal. Secure to the sleeve using 3 screws. Seal the joint and screw heads using high temperature sealant.
3. Insert the liners through the firestop / vent pipe shield. Holding the air terminal (lettering in an upright, readable position), secure to the exterior wall. Make weather tight by sealing with caulking (not supplied). The air terminal mount­ing plate may be recessed (up to exterior wall or siding.
FIGURE 23
OO
W THE VENTING INSTRW THE VENTING INSTR
O
W THE VENTING INSTR
OO
W THE VENTING INSTRW THE VENTING INSTR
EXAEXA
CTLCTL
EXA
CTL
EXAEXA
CTLCTL
AL RAL R
UNSUNS
UNS
UNSUNS
¼ INCH¼ INCH
¼ INCH
¼ INCH¼ INCH
, BO, BO
, BO
, BO, BO
RISE PER FOO RISE PER FOO
RISE PER FOO
RISE PER FOO RISE PER FOO
AL R
AL RAL R
HAHA
VE A 0" RISE PER FOOVE A 0" RISE PER FOO
HA
VE A 0" RISE PER FOO
HAHA
VE A 0" RISE PER FOOVE A 0" RISE PER FOO
T ALL HORIZONTT ALL HORIZONT
T ALL HORIZONT
T ALL HORIZONTT ALL HORIZONT
TION OF THETION OF THE
TION OF THE
TION OF THETION OF THE
UCTIONSUCTIONS
UCTIONS
UCTIONSUCTIONS
YY
..
Y
.
YY
..
TH WTH W
OLF STEEL ANDOLF STEEL AND
TH W
OLF STEEL AND
TH WTH W
OLF STEEL ANDOLF STEEL AND
TT
..
T
.
TT
..
AL RAL R
UNS HAUNS HA
AL R
UNS HA
AL RAL R
UNS HAUNS HA
TT
..
T
.
TT
..
3
/4" maximum) into the
FIGURE 24
VE AVE A
VE A
VE AVE A
YY
Y
YY
FIGURE 22
4. If more than one length of liner needs to be used to reach the stove, couple them together as illustrated in FIGURE 24. Seal the joints using the same procedure as described above.
The vent system must be supported approximately every 10 feet along a horizontal run. Use supports or equivalent non-combustible strapping to maintain the 1" clearance from combustibles.
W415-0158 / E / 02.19.04
12
VERTICAL VENTING INSTALLATION STOVE VENT CONNECTION
1. Fasten the roof support to the roof us­ing the screws pro­vided. The roof support is optional. In this case the venting is to be ad­equately supported us­ing either an alternate method suitable to the authority having juris­diction or the optional roof support.
2. Slip a 4" diameter length of aluminum flexible liner a minimum of 2" over the inner sleeve of the air terminal.
FIGURE 26
3. Thread the air terminal pipe assembly down through the roof support and attach, ensuring that a minimum 16" of air terminal will penetrate the roof when fastened. The air terminal must be located vertically and plumb.
4. Remove nails from the shingles, above and to the sides of the chimney. Place the flashing over the air termi­nal and slide it underneath the sides and upper edge of the shingles.
FIGURE 27
Where possible, cover the sides and top edges of the flash­ing with roofing material.
5. Apply a heavy bead of waterproof caulking 2 inches above the flashing. Slide the storm collar around the air terminal and down to the caulking. Tighten to ensure that a weather-tight seal between the air terminal and the collar is achieved. Attach the other storm collar centered between the air intake and air exhaust slots onto the air terminal. Tighten securely.
6. Attach the vertical rain cap.
7. In the attic, slide the vent pipe collar down to cover up the open end of the shield and tighten. This will prevent any materials, such as insulation, from filling up the 1" air space around the pipe.
Secure to the sleeve using 3 screws and flat washers.Seal the joint and screw heads using high temperature sealant. Repeat using a 7" diameter length of rigid piping.
If the attic space is tight, we rec­ommend adding sufficient lengths of 7" rigid piping, secured and sealed as necessary.
FIGURE 25
Ensure that the air ter­minal is properly centered within the flashing, giving a 3/4" margin all around. Fasten to the roof. Do NOT nail through the lower portion of the flashing. Make weather-tight by seal­ing with caulking.
1. Attach the adjustable pipe to the last section of rigid
piping. Secure with screws and seal.
2. Install the 4" aluminum flexible liner to the stove. Se­cure with 3 screws and flat washers. Seal the joint and screw holes using the high temperature sealant provided.
3. Run a bead of high temperature sealant around the inside of the air intake collar. Pull the adjustable pipe a minimum 2" into the air intake collar.
ENSURE THAENSURE THA
ENSURE THA
ENSURE THAENSURE THA EXTERIOR PIPES ONCE INSTEXTERIOR PIPES ONCE INST
EXTERIOR PIPES ONCE INST
EXTERIOR PIPES ONCE INSTEXTERIOR PIPES ONCE INST COMPLETEDCOMPLETED
COMPLETED
COMPLETEDCOMPLETED BB
AND IS AAND IS A
B
AND IS A
BB
AND IS AAND IS A
A GD175 KIT). IN THE EVENT THAA GD175 KIT). IN THE EVENT THA
A GD175 KIT). IN THE EVENT THA
A GD175 KIT). IN THE EVENT THAA GD175 KIT). IN THE EVENT THA MUST BE DISASSEMBLEDMUST BE DISASSEMBLED
MUST BE DISASSEMBLED
MUST BE DISASSEMBLEDMUST BE DISASSEMBLED RESEAL THE VENTING.RESEAL THE VENTING.
RESEAL THE VENTING.
RESEAL THE VENTING.RESEAL THE VENTING.
T THE SEALT THE SEAL
T THE SEAL
T THE SEALT THE SEAL
. AN OPTION. AN OPTION
. AN OPTION
. AN OPTION. AN OPTION
VV
AILAIL
ABLE FOR THIS USE. (STABLE FOR THIS USE. (ST
V
AIL
ABLE FOR THIS USE. (ST
VV
AILAIL
ABLE FOR THIS USE. (STABLE FOR THIS USE. (ST
ANT IS NOANT IS NO
ANT IS NO
ANT IS NOANT IS NO
AL DECORAAL DECORA
AL DECORA
AL DECORAAL DECORA
, CARE MUST BE T, CARE MUST BE T
, CARE MUST BE T
, CARE MUST BE T, CARE MUST BE T
T VISIBLE ON THET VISIBLE ON THE
T VISIBLE ON THE
T VISIBLE ON THET VISIBLE ON THE
ALLALL
ALL
ALLALL
T THE VENTINGT THE VENTING
T THE VENTING
T THE VENTINGT THE VENTING
MOBILE HOME INSTALLATION
In Canada, mobile home installation may be vented hori­zontally or vertically. In the United States, it may only be installed vertically. See "Vertical Venting" or "Horizontal Air Terminal Installation" for installation.
For mobile home installations, the fireplace must be fas­tened in place. It is recommended that the fireplace be secured in all installations. Use the leveling/securing kit, GDSLL-KT for this purpose.
CONTINUE WITH "GAS INSTALLA­TION", PAGE 14
FIGURE 28
AA
TION ISTION IS
A
TION IS
AA
TION ISTION IS
TIVE BRASSTIVE BRASS
TIVE BRASS
TIVE BRASSTIVE BRASS
ANDAND
ARD WITHARD WITH
AND
ARD WITH
ANDAND
ARD WITHARD WITH
AKEN TAKEN T
AKEN T
AKEN TAKEN T
OO
O
OO
W415-0158 / E / 02.19.04
B-VENT SPECIFICS - MODEL GS60
CHIMNEY INSTALLATION
THREE TYPES OF CHIMNEY SYSTEMS MAY BE USED WITH THIS STOVE:
FIGURES 29
13
Ensure that 2 female ends remain at the top.
Re-secure the access plate.
3. Remove the spill switch bracket from the rear of the adapter. Unscrew the spill switch and discard the bracket. Attach the spill switch to the bracket supplied with the stove and secure onto the adapter.
4. Bring the wires through the lower hole in the adapter. To pass the wires through the hole more easily, temporarily tape the two terminals together.
5. With the spill switch opening aligned to the back of the stove, take hold of the adapter base and push the crimped edge into the stove flue collar.
6. Connect the upper wire terminals to the spill switch.
FIGURE 31
INSTALLING 'B' VENT:
Follow the instructions of the 'B' vent manufacturer for chim­ney installation.
1. Remove the access plate. Remove and discard the air intake cover plate located directly behind the access plate.
2. Feed the 2 wires, supplied, through the 7" collar at the top of the unit; bring them out the air intake opening but behind the rear panel as shown.
7. Disconnect the wire lead from terminal 3 on the valve and reconnect to the male end of the spill switch wire. Con­nect the female end of the spill switch wire to terminal 3 on the valve. Leave all excess wire in an orderly manner.
For aesthetics, the adapter has been designed to ac­cept a standard matte black 7" stove pipe and the Na­poleon decorative brass band (standard with the GS-150KT). Both are available from your Napoleon dealer.
B-VENT MODEL GS60 ONLY
Attach the B-Vent label, shown below, in the control area of the appliance.
THIS FIREPLACE HAS BEEN CONVERTED TO A ‘B’VENT MODEL.
CE FOYER A ETE CONVERTI A UN MODELE A SYSTEME D’EVACUATION ‘B’.
ATTACH THIS LABEL IN THE CONTROL AREA OF THE FIREPLACE.
ATTACHEZ CET ETIQUETTE DANS LA REGION DE CONTROLE DU FOYER.
ws-385-160
COMBUSTION AIR
A chimney venting this stove shall not vent any solid fuel burning appliance.
Any stove needs air for safe operation and must be in­stalled in such a way that adequate combustion air is available.
FIGURE 30
W415-0158 / E / 02.19.04
14
ADDING VENT SECTIONS
For ease of assembly, a 7" telescop­ing stove pipe may be installed over the 4" vent connection of the adapter. Add vent sections, twist locking (clockwise) securely, to the required height. The vent should extend, at least, 3 feet above its point of con­tact with the roof and, at least, 2 feet higher than any wall, roof or build­ing within 10 feet. (This is a guide-
line only; local venting codes should be followed which may differ in height and clearance requirements.)
FIGURE 32
INSTALLING FLASHING
AND STORM COLLAR
Remove nails from the shin­gles above and to the sides of the chimney. Place the flashing over the vent pipe and slide it underneath the sides and upper edge of the shingles. Ensure that the vent pipe is properly centered within the flashing, giving a 3/4" margin all
around. Fasten to the roof on the top and sides. DO NOT NAIL through the lower portion of the flashing. Make
weather-tight by sealing with caulking. Where possible, cover the sides and top edges of the flashing with roofing material.
Apply waterproof caulking around the vent, 1" above the top of the flashing and push the storm collar down into the caulk­ing. Attach a rain cap to the top of the last vent section.
FIGURE 36
FIGURE 33
GAS INSTALLATION
1. Install rigid black pipe, or 1/2" type L copper tubing with a shut-off valve to the stove.
2. Seal and tighten the gas line securely to the flex connec­tor.
FIGURE 34
DO NOT KINK FLEXIBLE CONNECTOR.
3. Check for gas leaks by brushing on a soap and water solution. DO NOT USE OPEN FLAME.
FIGURE 35
4. Mark the appropriate boxes on the rating plate label to indicate the model type depending on the installation (direct vent or B-vent).
Figure 36.
For ease of accessibility , an optional remote wall switch or millivolt thermostat may be installed in a convenient location. Route 2 strand solid core millivolt wire from the gas stove to the wall switch / millivolt thermostat. The recommended maximum lead length depends on the wire size: WIRE SIZE MAX. LENGTH
14gauge 100 feet 16gauge 60 feet 18gauge 40 feet
DIRECT VENT MODEL GDS60: Disconnect the existing wires from terminals 1 and 3 (from the on/off switch) and re­place with the leads from the wall switch/millivolt thermo­stat.
B-VENT MODEL GS60: Disconnect the spill switch wire from terminal 3 on the valve. Connect one lead from the thermostat to terminal 3 on the valve and the other lead to the wire from the spill switch.
INSTINST
ALLER:ALLER:
INST
ALLER:
INSTINST
ALLER:ALLER:
venting and gas type of the unit.venting and gas type of the unit.
venting and gas type of the unit.
venting and gas type of the unit.venting and gas type of the unit.
W415-0158 / E / 02.19.04
It is y It is y
It is y
It is y It is y
our rour r
our r
our rour r
esponsibesponsib
esponsib
esponsibesponsib
lity to clity to c
lity to c
lity to clity to c
hechec
hec
hechec
k ofk of
k of
k ofk of
ff
the a the a
f
the a
ff
the a the a
pprppr
ppr
pprppr
opriaopria
opria
opriaopria
te bote bo
te bo
te bote bo
x on the rx on the r
x on the r
x on the rx on the r
aa
ting plating pla
a
ting pla
aa
ting plating pla
te accorte accor
te accor
te accorte accor
ding to the model,ding to the model,
ding to the model,
ding to the model,ding to the model,
FINISHING
LOGO PLACEMENT
Remove the backing of the logo supplied and centre over the logo installation holes, as indicated.
FIGURE 37
15
LOGO
FRONT CAST INSTALLATION
1. Lift the top casting off the unit.
2. Fit the securing bolts on the cast front into each of the
respective retainer brackets (located at either side on the top SEE FIGURE 37b). Insert and tighten the securing screw from the bottom up (located at the lower center behind the cast front SEE FIGURE 37a). This will hold the cast front in place. Replace the top casting.
3. To remove the front, repeat in reverse order.
GLASS DOOR INSTALLATION
AND REMOVAL
When installing the glass door, a simple procedure must be followed in order to not damage the door.
1. Lift the top casting off.
2. Undo the securing screw (located at the lower center of
the cast front) holding the cast front in place. Figure 37a.
3. Lift the cast front out of its retainers (located at either side on the top). Figure 37b.
4. Open the valve control cover. Pull the latch handles forward to release. Figure 37c. The door may now be safely removed by swinging the bottom out and lifting it off. To install the door, repeat in reverse order.
The return flange must fit over the top of the ridge so that it rests on top of the firebox. Figure 37d. The 'T' latch portion is threaded and can be loos­ened or tightened to adjust for an effective door seal. Care must be taken when re-installing the door to ensure that the gasket at the top of the door does not bunch.
TOP
RETAINER
FRONT
FIGURE 38b
RIDGE
RETURN FLANGE
FIGURE 38c
HANDLE
'T' LATCH
FIGURE 38d
W415-0158 / E / 02.19.04
16
LOG PLACEMENT
Blocked burner ports can cause an incorrect flame pattern, carbon deposits and delayed ignition. PHAZER when exposed to direct flame and provide a unique and realistic glowing effect. Use only certified PHAZER available from your Napoleon dealer.
FIGURE 39a-d
TM
logs glow
TM
logs
7
4
1
3
2
Place log #1 onto the burner, centering it onto the burner tray and pushing it as close to the rear wall of the firebox as possible. Move logs # 2 and 3 into position, lining up the studs located on the burner with the holes on the bottom of the logs. Sit the notch at the bottom of log #4 against the left outermost grate post and position the top of the log into the pocket provided on the rear log (#1).
5
The notch in log #5 should be pressed down onto the skewering pin located at the end of the grate as shown to prevent it from rocking.
Place the bottom of log #7 against the right outermost grate post and the top into the pocket provided on the center log (#6). Bend up the tab in the log support to cradle log #7. Tear the glowing embers into pieces and place onto the front of the burner. Care should be taken to shred the em­bers into thin, small irregular pieces as only the exposed edges of the fibre hairs will glow when exposed to direct flame; however care should be taken to not block the burner ports. Blocked ports can cause an incorrect flame pattern, carbon deposits and delayed ignition.
Log colours may vary. During the initial use of the fireplace, the colours will become more uniform as colour pigments burn in during the heat activated curing process.
POSITIONING THE LOGS IMPROPERL Y WILL CAUSE
FLAME IMPINGEMENT AND CARBONING .
6
Position the notch located in log #6 against the grate post.
W415-0158 / E / 02.19.04
MODEL GS60 ONL
Y
:
OPERATION / MAINTENANCE
17
PURGE ALL GAS LINES WITH THE GLASS DOOR
OPEN. ASSURE THAT A CONTINUOUS GAS FLOW
IS AT THE BURNER BEFORE CLOSING THE DOOR.
ALLOW SEVERAL MINUTES (5-15) FOR THE
FLAME TO STABILIZE AFTER IGNITION.
MODEL GS60 ONLY:
This is a thermally activated switch, attached to the back of the chimney adapter, which senses the change in temperature and shuts down the gas valve in the event
of a blocked or disconnected vent. It acts as a safety shut-off to prevent a build up of carbon monoxide or an explosion of unburnt gases during start up. If the flue is blocked or has no "draw", the spill switch will auto­matically shut off the supply of gas within about 5-10 minutes.
TAMPERING WITH THE SWITCH CAN RESULT IN CARBON MONOXIDE (CO) POISONING AND POSSI­BLE DEATH.
SPILL SWITCH
OPERATING INSTRUCTIONS
The on-off switch is located on the back of the unit at the top left corner on models GDS60 and GS60.
NOTE: The upper firebox baffle of your new cast stove has intentionally been left unpainted. Its shiny appear­ance will quickly transform to a dull black finish during the curing process.
VENTING ACTION CHECK
A CHECK FOR CORRECT VENTING ACTION MUST BE MADE BEFORE THE INSTALLED STOVE IS LEFT WITH THE CUSTOMER. Test in the following manner:
1. Close all doors and windows in the room / start exhaust fans in the home / turn fireplace blower off (if equipped).
2. Set controls to "high" and light the
unit.
3. Wait 5 minutes. Light a match and extend it 1" into the hole located above the spill switch bracket on the adapter.
4. Venting action is satisfactory if the flame stays lit. Venting action is unsat­isfactory if the flame extinguishes.
5. If venting action is unsatisfactory, turn the unit off, wait 10 minutes and try again. If the match does not stay lit, turn the unit off and check for vent blockage or restric­tion. If necessary, consult with a qualified inspector.
When lit for the first time, the fireplace will emit a slight odour for a few hours. This is a normal temporary condi­tion caused by the curing of the logs and the "burn-in" of internal paints and lubricants used in the manufacturing process and will not occur again. Simply open a window to sufficiently ventilate the room. After extended periods of non-operation such as following a vacation or a warm weather season, the fireplace may emit a slight odour for a few hours. This is caused by dust particles in the heat exchanger burning off. Open a window to sufficiently ven­tilate the room.
FIGURE 40
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION
MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
A. This fireplace is equipped with a pilot which must be lit by hand while following these instructions exactly. B. Before operating smell all around the fireplace area for gas and next to the floor because some gas is heavier than
air and will settle on the floor.
WHA T TO DO IF YOU SMELL GAS:
• Turn off all gas to the fireplace.
• Open windows.
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not turn by hand, do not
try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this fireplace if any part has been under water. Immediately call a qualified service technician to inspect
the fireplace and replace any part of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE OPERATING
W415-0158 / E / 02.19.04
18
LIGHTING INSTRUCTIONS
WARNING: The gas valve has an interlock device which will not allow the pilot burner to be lit until the thermo-
couple has cooled. Allow approximately 60 seconds for the thermocouple to cool before attempting to re-light. When lighting and re-lighting, the gas knob cannot be turned from PILOT to OFF unless the knob is depressed.
1. STOP! Read the safety information on the operating label.
2. Turn off all electric power to the fireplace.
3. Turn the gas knob clockwise
to off.
4. Wait five (5) minutes to clear out any gas. If you smell gas including near the floor, STOP! Follow "B" on the op­erating label. If you don't smell gas go to the next step.
L
O
F
O
N
H
I
F
O
P
L
T
I
P
I
L
O
T
O
TO TURN OFF GAS
1. Turn off all electric power to the fireplace if service is to be performed.
MAINTENANCE
TURN OFF THE GAS AND UNPLUG ELECTRICAL POWER
BEFORE SERVICING THE STOVE!
CAUTION: Label all wires prior to disconnection when serv­icing controls. Wiring errors can cause improper and dan­gerous operation. Verify proper operation after servicing. This stove and its venting system should be inspected before use and at least annually by a qualified service per­son. The fireplace area must be kept clear and free of com­bustible materials, gasoline or other flammable vapours and liquids. The flow of combustion and ventilation air must not be obstructed.
1. In order to properly clean the burner and pilot assem-
bly, remove the logs exposing both assemblies.
2. Keep the control compartment, logs, burner, air shut­ter opening and the area surrounding the logs clean by vacuuming or brushing, at least once a year.
5. Find pilot located in front of the back log.
6. Turn gas knob counter-clockwise to pilot.
7. Depress and hold the gas knob while lighting the pilot
with the push button ignitor. Keep knob fully depressed for one minute, then release. If the pilot does not con­tinue to burn, repeat steps 3 through 6.
8. With the pilot lit, turn the gas knob counter-clockwise to on.
9. If equipped with a remote ON-OFF switch, main burner
may not come on when you turn the valve to ON. The remote switch must be in the ON position to ignite the burner.
10. Turn on all electric power to the fireplace.
2. Push in gas control knob slightly and turn clock-
wise to off. Do not force.
3. Check to see that all burner ports are burning. Clean out any of the ports which may not be burning or are not burning properly.
4. Check to see that the pilot flames are large enough to engulf the thermocouple and the thermopile on one leg and reaches toward the burner on the other leg.
5. Replace the cleaned logs.
6. Check to see that the main burner ignites completely
on all openings when the gas knob for the burner is turned on. A 5-10 second total light-up period is satisfactory. If ignition takes longer, consult your Napoleon dealer/dis­tributor.
7. Check that the door gasketing is not broken or miss­ing. Replace if necessary.
W415-0158 / E / 02.19.04
BLOWER
INSTALLATION
1. Ensure that the access cover plate has been installed. For location, see Figure 30.
2. Remove the on/off switch bracket and the cover plate below it. The switch spacers and cover plate may now be discarded.
3. Decide which side of the blower housing you prefer the on/off switch to be located on.
19
Drywall dust will penetrate into blower bearings causing irrepairable damage and must be prevented from coming into contact with the blower or its compartment. Any damage resulting from this condition is not covered by the warranty policy.
ADJUSTMENTS
PILOT BURNER ADJUSTMENT
Adjust the pilot screw to provide properly sized flame. Turn in a clockwise direction to reduce the gas flow.
INLET PRESSURE
TAP
MANIFOLD TAP
SLOT
REMOVED SCREWS
FIGURE 41
4. Remove the 2 screws from the top outer edge of the rear stove panel. The housing is mounted using these two holes, as well as two other holes located in the rear panel. using the same screw holes for one side of the housing.
5. Mount and secure the blower housing using 4 screws. Ensure that the on/off switch wires pass through the ap­propriate slot located on either side of the blower housing.
6. Remove the 2 screws from the side of the blower hous­ing that you want the switch to be located on and resecure the on/off switch.
Because the blower is thermally activated, when turned on, it will automatically start approximately 15-30 min­utes after lighting the stove and will run for approximately 30-45 minutes after the stove has been turned off. Use of the fan increases the output of heat.
L
O
F
I
H
P
I
L
O
T
O
F
N
O
P
L
T
I
O
FIGURE 43
PILOT SCREW
FIGURE 44
VENTURI ADJUSTMENT
Remove the 2 screws securing the log support bracket. Natural gas models have air shutters set to 0.375" open (3/8"). Propane models have air shutters set to 0.313" open (5/16"). Closing the air shutter will cause a more yellow flame, but can lead to carboning. The flame may not ap­pear yellow immediately; allow 15 to 30 minutes for the final flame colour to be established. After making adjust­ments replace the log support bracket.
FIGURE 45
FIGURE 42
Air shutter adjustment must only be done by a qualified gas installer!
RESTRICTING VERTICAL VENTS
Vertical installations may display a very active flame. If this appearance is not desirable, the vent exit must be restricted using the restrictor vent kit, GDSRP-KT. This will reduce the velocity of the exhaust gases, slowing down the flame pattern and creating a more traditional gentle appearance. Specific instructions are included with the kit.
W415-0158 / E / 02.19.04
20
REPLACEMENTS
Contact your dealer for questions concerning prices and availability of replacement parts. Normally all parts can be ordered through your Napoleon dealer or distributor. When ordering replacement parts always give the follow­ing information:
FORFOR
WARRANTYWARRANTY
FOR
WARRANTY
FORFOR
WARRANTYWARRANTY
ORIGINALORIGINAL
ORIGINAL
ORIGINALORIGINAL
COMPONENTS COMMON TO BOTH UNITS:
# PART # DESCRIPTION
1 W135-0209 LOG #1 2 W135-0082 CHARCOAL PIECE (LOG #2) 3 W135-0076 LOG #3 4 W135-0210 LOG #4 5 W135-0211 LOG #5 6 W135-0212 LOG #6 7 W135-0213 LOG #7 8 GL-646 LOG SET 9 W725-0035 SIT VALVE - NG 9 W725-0026 SIT VALVE - LP 10 W010-0624 BURNER 11 W455-0058 #35 BURNER ORIFICE - NG 11 W455-0059 #53 BURNER ORIFICE - LP 11 W455-0065 #45 BURNER ORIFICE - NG 11 W455-0050 #55 BURNER ORIFICE - LP 12 W010-0800 PILOT ASSEMBLY - NG 12 W010-0801 PILOT ASSEMBLY - LP 13 W455-0069 PILOT INJECTOR - NG 13 W455-0067 PILOT INJECTOR - LP 14 W680-0005 THERMOCOUPLE 15 W680-0004 THERMOPILE 16* W290-0029 PILOT GASKET 17 W357-0001 PIEZO IGNITOR 18* W361-0016 GLOWING EMBERS 19* W550-0001 CHARCOAL EMBERS 20* W573-0008 HIGH TEMPERATURE SEALANT 21* W385-0245 NAPOLEON LOGO 22 W390-0001 LATCH 23* W660-0009 ON/OFF SWITCH 24 W690-0002 THERMODISC 25* W380-0002 VARIABLE SPEED SWITCH KNOB 26 KB-35 VARIABLE SPEED SWITCH 27 GZ-552 REPLACEMENT BLOWER 28 W135-0069_ SIDE (LEFT OR RIGHT) 29 W135-0073_ TOP 30 W135-0068_ LEG EA. 31 W135-0074 BASE PAINT FINISH ONLY
32 W010-0459 ADAPTOR C/W SPILL SWITCH 33 W660-0006 SPILL SWITCH 34 W080-0405 SPILL SWITCH BRACKET
35 GD175 - WALL TERMINAL KIT
36 BM6790 90° ELBOW - 7" DIAMETER 37 GD222 TERMINAL ASSEMBLY 38 BM67ADJ 30" TO 53" ADJUSTABLE PIPE - 7" DIA 39 W500-0077 FIRESTOP / WALL PLATE 40 W020-0032 HARDWARE 41 BRTC7 BRASS TRIM COLLAR 42 BM6724 24" STOVE PIPE - 7" DIAMETER 43 W010-0300 10' ALUMINUM FLEX LINER C/W SPACERS - 4" DIA 44 W025-0001 DECORATIVE BRASS BAND
46 GD180 - PERISCOPE TERMINAL KIT
36 BM6790 90° ELBOW - 7" DIAMETER 45 GD201 PERISCOPE 38 BM67ADJ 30" TO 53" ADJUSTABLE PIPE - 7" DIA 49 W500-0077 FIRESTOP / WALL PLATE 40 W020-0032 HARDWARE 41 BRTC7 BRASS TRIM COLLAR 42 BM6724 24" STOVE PIPE - 7" DIAMETER 43 W010-0300 10' ALUMINUM FLEX LINER C/W SPACERS - 4" DIA 44 W025-0001 DECORATIVE BRASS BAND
W415-0158 / E / 02.19.04
INVOICEINVOICE
INVOICE
INVOICEINVOICE
REPLREPL
REPL
REPLREPL
WILLWILL
WILL
WILLWILL
AA
CEMENTCEMENT
A
CEMENT
AA
CEMENTCEMENT
BEBE
REQUIREDREQUIRED
BE
REQUIRED
BEBE
REQUIREDREQUIRED
GS60 COMPONENTS
TERMINAL KITS
, ,
ARAR
AR
ARAR
TSTS
TS
TSTS
,
, ,
TOTO
TO
TOTO
AA
A
AA
PHOPHO
PHO
PHOPHO
HONOURHONOUR
HONOUR
HONOURHONOUR
PP
P
PP
TT
OCOPYOCOPY
T
OCOPY
TT
OCOPYOCOPY
THETHE
THE
THETHE
OFOF
OF
OFOF
CLAIMCLAIM
CLAIM
CLAIMCLAIM
THETHE
THE
THETHE
1. MODEL & SERIAL NUMBER OF FIREPLACE
2. INSTALLATION DATE OF FIREPLACE
3. PART NUMBER
4. DESCRIPTION OF PART
5. FINISH
* IDENTIFIES ITEMS WHICH ARE NOT ILLUSTRATED. FOR
..
.
..
FURTHER
INFORMATION, CONTACT YOUR NAPOLEON
DEALER
.
ROOF TERMINAL KITS
GD110 - 1/12 TO 7/12 PITCH
46 W010-0569 AIR TERMINAL 47 W120-0036 VERTICAL CAP 48 W010-0567 ROOF SUPPORT 49 W170-0063 STORM COLLAR 50 W263-0054 ROOF FLASHING
GD111 - 8/12 TO 12/12 PITCH
46 W010-0569 AIR TERMINAL 47 W120-0036 VERTICAL CAP 48 W010-0567 ROOF SUPPORT 49 W170-0063 STORM COLLAR 50 W263-0055 ROOF FLASHING
GD112 - FLAT ROOF
46 W010-0569 AIR TERMINAL 47 W120-0036 VERTICAL CAP 48 W010-0567 ROOF SUPPORT 49 W263-0056 ROOF FLASHING 50 W170-0063 STORM COLLAR
ACCESSORIES:
51* W690-0001 MILLIVOLT THERMOST AT 52* W690-0010 REMOTE CONTROL - ADVANTAGE 52* W690-0011 REMOTE CONTROL - ADVANTAGE PLUS 53* W300-0041 WINDOW GLASS 54* W562-0031 GLASS GASKET 55 GS830-G GOLD TRIVET 55 GS830-K BLACK TRIVET 55 GS830-C CHROME TRIVET 56* GDSLL-KT LEVELING / SECURING KIT 57 GS-64KT BLOWER KIT 58* GDS-786KT DECORATIVE BRICK PANEL 59 F_A** ART DECO FRONT 60 F_E** EARLY AMERICAN FRONT 61 F_P** PANORAMIC FRONT 62* W175-0138 CONVERSION KIT - NG-LP 62* W175-0139 CONVERSION KIT - LP-NG 63* BM6745 45° ELBOW 64 GD-301 HEAT GUARD
GDS60 ACCESSORIES
65* W175-0001 4" COUPLER 45 GD-201 PERISCOPE 66* GDSRP-KT RESTRICTOR KIT
GS60 ACCESSORIES
67 GS-150KT ADAPTOR KIT 44 W025-0001 DECORATIVE BRASS BAND
**FOR AVAILABLE PORCELAIN COLOURS, ADD THESE LETTERS TO THE BASE PART
:
NUMBER
BLUE - B BLACK GREEN
- K
- F
BROWN ALMOND
- N
- S
21
* WARNING: This is a fast acting thermocouple. It is an integral safety component. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
W415-0158 / E / 02.19.04
22
TROUBLE SHOOTING GUIDE
B
EFORE ATTEMPTING TO TROUBLESHOOT, PURGE YOUR UNIT AND INITIALLY LIGHT THE PILOT AND THE MAIN BURNER WITH THE GLASS DOOR REMOVED
SYMPTOM PROBLEM TEST SOLUTION
.
Pilot will not light. - check if pilot can be lit by a match
Pilot goes out when the gas knob is re­leased.
Pilot burning; no gas to main burner; gas knob is on 'HI'; wall switch / thermostat is on.
No spark at pilot burner
Spark gap is incorrect
No gas at the pilot burner
Out of propane gas.
System is not correctly purged.
Out of propane gas Pilot flame is not large enough Pilot flame is not engulfing the
thermocouple. Thermocouple shorting.
Faultly thermocouple. Faulty valve.
Main burner orifice is plugged.
Faulty thermopile. Faulty themostat or switch.
Faulty valve.
- check that the wire is connected to the push button ignitor.
- check if the push button ignitor needs tightening.
- replace the wire if the wire insulation is broken or frayed. replace the electrode if the ceramic insulator is cracked or
-
broken.
- spark gap should be 0.150" to 0.175" (5/32" to 1 1/64" approx.)
from the electrode tip and the pilot burner. To ensure proper electrode location, tighten securing nut (finger tight plus 1/4 turn).
- check that the manual valve is turned on.
- check the pilot orifice for blockage.
- replace the valve.
- call the gas distributor.
- fill the tank.
- purge the gas line with the stove door open.
- fill the tank.
- turn up the pilot flame.
- turn up pilot flame.
- replace pilot assembly.
- loosen and tighten thermocouple.
- clean thermocouple and valve connection.
- replace thermocouple.
- replace valve.
- replace.
- replace.
- remove stoppage in orifice.
- replace.
- connect a jumper wire across the wall switch terminals; if
main burner lights, replace thermostat.
- disconnect switch wires from the valve & connect a jumper wire across terminals 1 & 3; if the main burner lights, check the wires for defects and / or replace wires.
- replace.
Pilot goes out while standing; Main burner is in 'OFF' position.
Main burner goes out; pilot stays on.
W415-0158 / E / 02.19.04
Gas piping is undersized.
Pilot flame is not large enough or not engulfing the thermo­pile.
Thermopile shorting Remote wall switch wire is too
long, too much resistance in the system
Faulty thermostat or switch
MODEL GS60 ONL Y :
Venting is spilling
- turn on all gas appliances and see if pilot flame flutters, diminishes or extinguishes, especially when main burner ig­nites. Monitor supply pressure.
- check if supply piping size is to code. Correct all undersized piping.
- turn up pilot flame.
- replace pilot assembly.
- clean thermopile and thermopile connection to valve.
- shorten wire to correct length or wire gauge.
- replace
- test with spill switch bypassed. Replace if defective.
- check for vent blockage.
SYMPTOM PROBLEM TEST SOLUTION
23
Main burner goes out; pilot goes out.
Exhaust fumes smelled in room, headaches.
Carbon is being de­posited on glass, logs or combustion cham­ber surfaces.
Flames are very aggressive.(GDS60
REAR VENT VERTI­CAL TERMINA TION)
REFER TO "MAIN BURNER GOES OUT ; PILOT ST A YS ON" Vent re-circulating
(MODEL GDS60 ONL Y)
Thermocouple shorting or
Fireplace is spilling.
Air shutter has become blocked
Flame is impinging on the logs or combustion chamber.
Door is ajar
Venting action is too great.
- check joint seals and installation.
- loosen and tighten thermocouple
- clean thermocouple and valve connection.
- replace thermocouple.
- replace valve.
- check all seals.
- ensure air shutter opening is free of lint or other obstruc­tions.
- check that the logs are correctly positioned.
- open air shutter to increase the primary air.
- check the input rate: check the manifold pressure and orifice size as specified by the rating plate values.
- check that the door gasketing is not broken or missing and that the seal is tight.
- check that both vent liners are free of holes and well sealed at all joints.
- check that minimum rise per foot has been adhered to for any horizontal venting.
- tighten door clamps
- restrict vent exit with restrictor vent kit, GDSRP-KT.
MODEL GDS60 ONL Y:
Main burner flame is a blue, lazy, transpar­ent flame.
White / grey film forms.
Blockage in vent. - remove blockage. In really cold conditions, ice buildup may
occur on the terminal and should be removed as required.
Incorrect installation (vertical termination only).
Sulphur from fuel is being de­posited on glass, logs or com­bustion chamber surfaces.
- refer to Figure 27 to ensure correct location of storm collars.
- clean the glass with a recommended gas fireplace glass cleaner . DO NOT CLEAN GLASS WHEN HOT. If deposits are not cleaned off regularly, the glass may be­come permanently marked.
W415-0158 / E / 02.19.04
24
Wolf Steel Fireplace Service History
Service Performed Special ConcernsDealer Name
Name
Service Technician
This fireplace must be serviced annually depending on usage.