CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE
INSTALLATION AND
OPERATING INSTRUCTIONS
CERTIFIED TO CANADIAN AND AMERICAN NATIONAL STANDARDS: CSA 2.22 AND ANSI Z21.50 FOR VENTED GAS FIREPLACES
BGD36CFNTR &
EN
FR
PG
59
FOR INDOOR USE ONLY
SAFETY INFORMATION
!
WARNING
If the information in these instructions
are not followed exactly, a fi re or
explosion may result causing property
damage, personal injury or loss of life.
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fi re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a
certifi ed kit is used.
BGD36CFNTRE
NATURAL GAS MODEL
BGD36CFPTR &
BGD36CFPTRE
PROPANE GAS MODEL
!
DANGER
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this appliance
and shall be installed for the protection of children
and other at-risk individuals.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
1.28G
W415-1345 / C / 02.14.17
2
EN
TABLE OF CONTENTS
NOTE: The camera icon indicates video tutorials are available as additional reference, visit
http://mynapoleon.napoleonproducts.com/download/index/44/1
1.0 INSTALLATION OVERVIEW 3
2.0 INTRODUCTION 4
2.1 DIMENSIONS 5
2.2 GENERAL INSTRUCTIONS 5
2.3 GENERAL INSTRUCTIONS 6
2.4 GENERAL INFORMATION 6
2.5 RATING PLATE INFORMATION 7
3.0 VENTING 8
3.1 VENTING LENGTHS AND COMPONENTS 8
3.2 TYPICAL VENT INSTALLATIONS 9
3.3 SPECIAL VENT INSTALLATIONS 11
3.3.1 PERISCOPE TERMINATION 11
3.3.2 CORNER TERMINATION 11
3.4 VENT TERMINAL CLEARANCES 12
3.5 VENT APPLICATION FLOW CHART 13
3.6 DEFINITIONS 13
3.7 ELBOW VENT LENGTH VALUES 14
3.8 TOP EXIT HORIZONTAL TERMINATION 14
3.9 REAR EXIT HORIZONTAL TERMINATION 16
3.10 TOP OR REAR EXIT VERTICAL TERMINATION 18
4.0 PRE-INSTALLATION PREPARATION 20
4.1 DOOR OPERATION 20
4.2 REAR EXIT 20
4.3 TOP VENT 20
5.0 INSTALLATION 21
5.1 WALL AND CEILING PROTECTION 21
5.2 HORIZONTAL INSTALLATION 22
5.3 VERTICAL INSTALLATION 22
5.4 USING FLEXIBLE VENT COMPONENTS 23
5.4.1 HORIZONTAL AIR TERMINAL INSTALLATION 23
5.4.2 VERTICAL AIR TERMINAL INSTALLATION 24
5.4.3 APPLIANCE VENT CONNECTION 25
5.5 USING RIGID VENT COMPONENTS 25
5.5.1 HORIZONTAL AIR TERMINAL INSTALLATION 25
5.5.2 EXTENDED HORIZONTAL AND CORNER TERMINAL INSTALLATION 25
5.5.3 VERTICAL AIR TERMINAL INSTALLATION 26
5.6 VERTICAL THROUGH EXISTING CHIMNEY 27
5.7 MOBILE HOME INSTALLATION 28
5.8 GAS INSTALLATION 28
5.9 OPTIONAL WALL SWITCH 29
6.0 FRAMING 29
6.1 INSTALLING STAND-OFFS 30
6.2 MINIMUM FRAMING DIMENSIONS 31
6.2.1 STEEL HEADER INSTALLATION 32
6.3 MINIMUM ENCLOSURE CLEARANCES 33
6.3.1 REAR VENT ENCLOSURE 33
6.3.2 TOP VENT ENCLOSURE 34
6.3.3 FINISHED FLOOR INSTALLATION 35
6.3.4 HEARTH INSTALLATION 35
6.4 NON-COMBUSTIBLE FACING MATERIAL 36
6.5 ALCOVE FRAMING 37
6.6 REMOTE RECEIVER PLACEMENT 37
6.7 MINIMUM MANTEL CLEARANCES 38
7.0 FINISHING 38
7.1 SAFETY SCREEN & DOOR INSTALLATION / REMOVAL 38
7.2 CLEAN FACE TRIM KIT INSTALLATION 39
7.3 LOG PLACEMENT 40
7.4 CHARCOAL EMBERS 41
7.5 GLOWING EMBERS 41
7.6 OPTIONAL ROCK KIT 41
8.0 OPTIONAL BLOWER INSTALLATION 41
9.0 OPERATION (ELECTRONIC) 42
10.0 OPERATION (MILLIVOLT) 43
11.0 ADJUSTMENT 44
11.1 PILOT BURNER ADJUSTMENT 44
11.2 VENTURI ADJUSTMENT 44
11.3 FLAME CHARACTERISTICS 45
12.0 MAINTENANCE 45
12.1 ANNUAL MAINTENANCE 46
12.2 DOOR GLASS REPLACEMENT 47
12.3 CARE OF GLASS 47
12.4 CARE OF PLATED PARTS 47
W415-1345 / C / 02.14.17
3
13.0 REPLACEMENTS 48
13.1 OVERVIEW 49
13.2 MILLIVOLT VALVE TRAIN ASSEMBLY 50
13.3 ELECTRONIC VALVE TRAIN ASSEMBLY 51
14.0 ACCESSORIES 52
15.0 TROUBLESHOOTING ELECTRONIC 53
16.0 TROUBLESHOOTING MILLIVOLT 55
17.0 WARRANTY 57
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
1.0 INSTALLATION OVERVIEW
See the sections “MINIMUM
ENCLOSURE CLEARANCES”
for drywall (or other
combustible material)
See the section
“MINIMUM MANTEL
AND ENCLOSURE
CLEARANCES”
EN
See the section
“VENTING” and
“INSTALLATION”
See the section
“INSTALLATION FRAMING”
Side
SAFETY BARRIER
Wall
See the section
“FRAMING”
Batteries must be disposed of according to the local laws and regulations. Some batteries may be
recycled, and may be accepted for disposal at your local recycling center. Check with your
municipality for recycling instructions.
W415-1345 / C / 02.14.17
4
2.0 INTRODUCTION
EN
!
WARNING
• THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
• ANY CHANGES TO THIS APPLIANCE OR ITS CONTROLS CAN BE DANGEROUS AND ARE PROHIBITED.
• Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to
operating instructions could cause fi re or injury.
• Risk of fi re or asphyxiation do not operate appliance with fi xed glass removed.
• Do not connect 110 volts to the control valve.
• Risk of burns. The appliance should be turned off and cooled before servicing.
• Do not install damaged, incomplete or substitute components.
• Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may be sharp.
• Do not burn wood or other materials in this appliance.
• Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns
or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the appliance.
Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is
recommended if there are at risk individuals in the house. To restrict access to an appliance or stove, install an
adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot
surfaces.
• Clothing or other fl ammable material should not be placed on or near the appliance.
• Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
• Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These
screens and guards must be fastened to the fl oor.
• Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to operating the
appliance.
• The appliance is a vented gas-fi red appliance. Do not burn wood or other materials in the appliance.
• The appliance area must be kept clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
• Under no circumstances should this appliance be modifi ed.
• This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning appliance.
• Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance
and to replace any part of the control system and any gas control which has been under water.
• Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done by a
licensed or qualifi ed service person.
• Do not strike or slam shut the appliance glass door.
• When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent exhaust fumes
containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also
cause the surrounding combustible materials to overheat and catch fi re.Only doors / optional fronts certifi ed with the unit are to be
installed on the appliance.
• Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
• Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic bags, these
are not toys and should be kept away from children and infants.
• As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as having a
Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon Monoxide.
• Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated temperatures
on the wall or in the air above the appliance can cause melting, discolouration or damage to decorations, a T.V. or other electronic
components.
• A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be
installed.
• If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this appliance.
• Installation and repair should be done by a qualifi ed service person. The appliance should be inspected before use and
at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from
carpeting, bedding material, etc. It is imperative that control compartments, burners and circulating air passageways of
the appliance be kept clean.
• The millivolt version of this appliance uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple
supplied by Wolf Steel Ltd.
3.1E
W415-1345 / C / 02.14.17
2.1 DIMENSIONS
SAFETY BARRIER
2.2 GENERAL INSTRUCTIONS
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48 INCHES
(121.9cm) FROM THE FRONT FACE OF THE APPLIANCE.
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (35mb).
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THE APPLIANCE MUST NOT BE OPERATED AT TEMPERATURES BELOW FREEZING (32°F / 0°C).
ALLOW THE APPLIANCE TO WARM TO ABOVE FREEZING PRIOR TO OPERATION.
5"
127mm
38 1/2"
978mm
34"
864mm
GAS INLET
3"
76.2mm
!
15"
17"
8"
203mm
381mm
432mm
24 1/4"
616mm
WARNING
PROVIDE ADEQUATE VENTILATION.
WHEN THE APPLIANCE IS OPERATING.
FIRE RISK. EXPLOSION HAZARD.
686mm
27"
1016mm
40"
5
EN
7"
178mm
4"
102mm
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to
conform with local codes. Installation practices vary from region to region and it is important to know the
specifi cs that apply to your area, for example in Massachusetts State:
• This product must be installed by a licensed plumber or gas fi tter when installed within the
commonwealth of Massachusetts.
• The appliance damper must be removed or welded in the open position prior to installation of an
appliance insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The fl exible connector must not be longer than 3 feet (0.9m).
• A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent
sealed combustion product.
W415-1345 / C / 02.14.17
6
A
EN
The installation must conform with local codes or, in
absence of local codes, the National Gas and Propane
Installation Code CSA B149.1 in Canada, or the National
Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United
States. Suitable for mobile home installation if installed
in accordance with the current standard CAN/CSA
Z240MH Series, for gas equipped mobile homes, in
Canada or ANSI Z223.1 and NFPA 54 in the United
States.
s long as the required clearance to combustibles is
maintained, the most desirable and benefi cial location for an appliance is in the center of a building, thereby
allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the
room where the appliance is to be located should be considered. If possible, you should choose a location
where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood
fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must
be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
2.3 GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND
QUALITY!
www.ncertied.org
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certied in the U.S.
by the National Fireplace
®
Institute
(NFI) as NFI Gas
Specialists
4.1C
RATES AND EFFCIENCES
NGP
Altitude (FT)0-4,5000-4500
Max. Input (BTU/HR)17,00017,000
Max. Output Steady State (BTU/HR)10,90010,900
Effi ciency (w/the fan on)64%64%
A.F.U.E. (Annual Fuel Utilization Effi ciency)53%53%
Min. Inlet Gas Supply Pressure4.5" (11mb) w.c.11" (27mb) w.c.
Max. Inlet Gas Supply Pressure7" (17mb) w.c.13" (32mb) w.c.
Manifold Pressure (Under Flow Conditions)3.5" (9mb) w.c.10" (25mb) w.c.
When the appliance is installed at elevations above 4,500 ft (1371m), and in the absence of specifi c
AU CANADA AU CANADA
MANUFACTUREES,MANUFACTUR
PEUT ETRE APPLIQUEE,PEUT ETRE APPLIQUEE
ES SITES ET LES COMMUNAUTES, AS ET LES COMMUNAUTE
TATION 17,000 BTU/hTATION 17,000 BT
P4 59.4%59.4%
D'EAU D'EAU
:NIMUM SUPPL
11"
WATER COLUMNLUMN
WITH GLASSTH GLASS
WILL COME IN CONTACT WITH THE FLAMES, OTHERME IN CONTACT WITH THE FLAMES, OTHE
ALS /ALS /
APPARAPPA
recommendations from the local authority having jurisdiction, the certifi ed high altitude input rating shall be
reduced at the rate of 4% for each additional 1,000 ft (305m).
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is suitable for
mobile home installation.
No external electricity (110 volts or 24 volts) is required for the gas system operation.
Expansion / contraction noises during heating up and cooling down cycles are normal and are to be
expected.
Use only accessories designed for and listed with your specifi c appliance.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the appliance
and must be installed.
2.4 RATING PLATE INFORMATION
For rating plate location, see “INSTALLATION OVERVIEW” section.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
NOTE: The rating plate must remain with the appliance at all times. It must not be removed.
7
EN
DIRECT VENT GAS FIREPLACE. SUITABLE FOR BEDROOM, BATHROOM AND BED-SITTING ROOM
INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE
CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA
OR IN THE UNITED STATES THE MANUFACTURED HOME CONTRUCTION AND SAFETY
STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT APPLICABLE USE
THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATIONS,
SITES AND COMMUNITIES, ANSI / NFPA 501A. WHEN INSTALLED WITH SCREEN KIT GD-565KT,
THE FIREPLACE COMPLIES WITH CGA CERTIFICATION REQUIREMENT CR95-006. FOR USE
ONLY WITH BARRIER W565-0178. FOLLOW THE INSTALLATION INSTRUCTIONS LOCATED IN
THE INSTALLATION MANUAL.
NOT FOR USE WITH SOLID FUEL. FOR USE WITH GLASS
DOORS CERTIFIED WITH THIS UNIT ONLY.
WARNING:
WITH A FAST ACTING THERMOCOUPLE SUPPLIED BY WOLF STEEL LTD.
DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN CONTACT WITH THE FLAMES, OTHER
THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS /
DEGAGEMENTS MINIMAUX DES MATERIAUX COMBUSTIBLES:
TOP/ DESSUS 0 RECESSED DEPTH / PROFONDEUR D'ENCASTRE 17.25"
FLOOR / PLANCHER 0 VENT SIDES / COTES DE L'EVENT 1"
SIDES / COTES 0 VENT TOP / EVENT SUPERIEUR 2"
BACK / ARRIERE 0 VENT BOTTOM / EVENT INFERIEUR 1"
MANTEL / MANTEAU 12" *
* MAXIMUM HORIZONTAL EXTENSION / L'EXTENSION HORIZONTALE MAXIMALE: 2". SEE INSTRUCTION
MANUAL FOR GREATER EXTENSIONS. REFERER AU MANUEL D'INSTRUCTION POUR DES EXTENSIONS PLUS
GRANDES.
SEE OWNER'S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS.
REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR LES LONGUEURS D'EVACUATION
CONFORMS TO / CONFORME AUX: ANSI Z21.50-2014, CERTIFIED TO / CERTIFIE CSA 2.22-2014 VENTED GAS FIREPLACE / FOYER À GAZ VENTILÉ.
BGD36CFNTR BCDV36CFNTR
PRESSION D'ALIMENTATION MINIMALE: 4.5" D'UNE COLONNE D'EAUPRESSION D'ALIMENTATION MINIMALE: 11" D'UNE COLONNE D'EAU
MANIFOLD PRESSURE: 3.5" WATER COLUMN MANIFOLD PRESSURE: 10" WATER COLUMN
PRESSION AU COLLECTEUR: 3.5" D'UNE COLONNE D'EAUPRESSION AU COLLECTEUR: 10"D'UNE COLONNE D'EAU
MINIMUM SUPPLY PRESSURE: 4.5" WATER COLUMNMINIMUM SUPPLY PRESSURE: 11" WATER COLUMN
MAXIMUM SUPPLY PRESSURE: 7.0" WATER COLUMNMAXIMUM SUPPLY PRESSURE: 13" WATER COLUMN
MODEL
FOYER A GAZ VENTILE DIRECT. HOMOLOGUE POUR INSTALLATION DANS UNE CHAMBRE A COUCHER, UNE
SALLE DE BAIN ET UN STUDIO. APPROPRIE POUR INSTALLATION DANS UNE MAISON MOBILE SI SON
INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SERIE DE MAISONS MOBILES
EQUIPEES AU GAZ, EN VIGUEUR AU CANADA OU AUX ETATS-UNIS DE LA NORME DE SECURITE ET DE
CONSTRUCTION DE MAISONS MANUFACTUREES, TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE
NORME D'ETATS-UNIS NE PEUT ETRE APPLIQUEE, SE REFERER A LA NORME RELATIVE AU CRITERE DE
MESURES DE SECURITE CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS
MANUFACTURES, LES SITES ET LES COMMUNAUTES, ANSI/NFPA 501A. LORSQU'IL EST INSTALLE AVEC LA
TROUSSE POUR ECRAN GD-565KT, LE FOYER EST CONFORME A LA NORME DE CERTIFICATION DE L'ACG
CR95-006.POUR UNE UTILISER SEULMENT AVEC BARRIÈRE
ANIFOLD PRESSURE:
RESSION AU COLLECTEUR:
INIMUM SUPPLY PRESSURE
UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILISE AVEC CET
APPAREIL. UTILISER AVEC LES PORTES VITREES
HOMOLOGUEES SEULEMENT AVEC CETTE UNITE.
AVERTISSEMENT:
UNIQUEMENT AVEC UN THERMOCOUPLE À ACTION RAPIDE DE WOLF STEEL LTÉE. N’AJOUTEZ PAS A CET
APPAREIL AUCUN MATERIAU DEVANT ENTRER EN CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI
EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT.
THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE WOLF STEEL VENT KITS. SEE OWNERS
INSTALLATION MANUAL FOR VENTING SPECIFICS. PROPER REINSTALLATION AND RESEALING IS NECESSARY
AFTER SERVICING THE VENT-AIR INTAKE SYSTEM.
L'APPAREIL DOIT EVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'EVACUATION PROPRE A NAPOLEON.
REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR L'EVACUATION PRECISE. IL EST IMPORTANT
DE BIEN REINSTALLER ET RESCELLER L'EVENT APRES AVOIR ASSURE LE MAINTIEN DU SYSTEME DE PRISE
D'AIR.
DECORATIVE PRODUCT: NOT FOR USE AS A HEATING APPLIANCE
PRODUIT DÉCORATIF: NE PAS UTILISER COMME APPPAREIL DE CHAUFFAGE.
ELECTRICAL RATING / CLASSIFICATION: 115V 0.82AMP, 60HZ
OPTIONAL FAN KIT / ENSEMBLE DE VENTILATEUR FACULTATIF: GZ550-KT, GD65
BGD36CFPTRBCDV36CFPTR
BGD36CFPTR
CE FOYER UTILISE ET REQUIERT UN THERMOCOUPLE À ACTION RAPIDE. REMPLACEZ
SERIAL NUMBER/NO. DE SERIE:
W565-0178
D'INSTALLATION SE TROUVENT DANS LE MANUEL D'INSTALLATION.
. SUIVEZ LES INSTRUCTIONS
BGD36CF
W385-1974
W415-1345 / C / 02.14.17
8
3.0 VENTING
EN
!
WARNING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3FT
(0.9m) FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS
REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
THIS APPLIANCE USES A 4” (102mm) EXHAUST / 7” (178mm) AIR INTAKE VENT PIPE SYSTEM.
Refer to the section applicable to your installation.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme
vent confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Although not a
requirement, it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl
spaces) be insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide
a means for visually checking the vent connection to the appliance after the appliance is installed. Use a
fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor
paint suitable for 400°F (204°C). Application and performance of paint is the consumer’s responsibility. Spot
testing is recommended.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions
provided for the initial installation.
NOTE: This appliance must be installed with a continuous connection of exhaust and air intake vent
pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
7.1F
3.1 VENTING LENGTHS AND COMPONENTS
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab
venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations,
clearances from vent pipes to combustibles and air terminal locations as set out in this manual apply to
all vent systems and must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal
Amerivent and Metal-Fab follow the installation procedure provided with the venting components.
A starter adaptor must be used with the following vent systems and may be purchased from the
corresponding supplier:
VENT
MANUFACTURER
DuraventW175-0053Wolf Steelwww.duravent.com
Amerivent4DSC-N2American Metalwww.americanmetalproducts.com
Direct Temp4DT-AANSelkirk www.selkirkcorp.com
SuperSeal4DNAMetal-Fabwww.mtlfab.com
For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the
installation procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed
using a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and
outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection
to the appliance fl ue collar which must be sealed using the black high temperature sealant Mill Pac. High
temperature sealant must be ordered separately.
ST ARTER ADAPTER
PART NUMBER
SUPPLIERWEBSITE
W415-1345 / C / 02.14.17
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with
the following termination kits: wall terminal kit GD-222, GD-222R, or 1/12 to 7/12 pitch roof terminal kit
GD-110, 8/12 to 12/12 roof terminal kit GD-111, fl at roof terminal kit GD-112 or periscope kit GD-201 (for
wall penetration below grade). With fl exible venting, in conjunction with the various terminations, use either
the 5 foot (1.5m) vent kit GD-220 or the 10 foot (3.1m) vent kit GD-330.
For optimum fl ame appearance and appliance performance, keep the vent length and number of
elbows to a minimum. The air terminal must remain unobstructed at all times. Examine the air
terminal at least once a year to verify that it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components
must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable
horizontal run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum
number of vent connections is two horizontally or three vertically (excluding the appliance and the air
terminal connections) when using fl exible venting.
3.2 TYPICAL VENT INSTALLATIONS
9
EN
8.1C
REQUIRED RISE ON HORIZONTAL
VENTING
REAR VENT
TOP VENT
CORNER
VENT
For optimum performance, it is
recommended that all horizontal runs have
a 1" (25mm) rise per foot.
RIGID0" / FT
FLEXIBLE0" / FT
RIGID0" / FT
FLEXIBLE0" / FT
RIGID0"
FLEXIBLE6" (15.2cm)
20" (50.8cm)
MAXIMUM
16" (40.6cm)
MINIMUM
40 FT (12M)
MAXIMUM
3 FT (1M)
MINIMUM
* See "VENTING" section.
24 1/4" (61.6cm)
MINIMUM PLUS
RISE*
24 1/4"
(61.6cm)
REAR VENT
W415-1345 / C / 02.14.17
EN
10
16" (40.6cm)
MINIMUM
24" (61cm)
MAXIMUM
10" (25.4cm)
MINIMUM
34"
(86.4cm)
* See "VENTING" section.
42 3/8"
(1.08m)
MINIMUM
PLUS RISE*
40 FT (12M)
MAXIMUM
3 FT (1M)
MINIMUM
34"
(86.4cm)
TOP VENT
W415-1345 / C / 02.14.17
3.3 SPECIAL VENT INSTALLATIONS
11
3.3.1 PERISCOPE TERMINATION
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that
when fi nal grading is completed, the bottom air slot is located a minimum 12” (30.5cm) above grade.
The maximum allowable vent length is 10’ (3.1m).
30" (76.2cm)
MIN
24 1/4"
(61.6cm)
12" (30.5cm)
MIN TO
GRADE
EN
12" (30.5cm)
MIN TO
GRADE
30"
(76.2cm)
MIN
34"
(86.4cm)
3.3.2 CORNER TERMINATION
The maximum vent length for a corner installation is 20" (50.8cm) of horizontal run, in addition to the 45°
offset. In this case zero rise is acceptable when using rigid venting. It is required to maintain a 6"(15.2cm) rise
when using fl exible venting. See illustrations below.
6” (152.4mm)
RISE MINIMUM
9.4B
20” (50.8cm)
MAXIMUM
FLEXIBLE VENTINGRIGID VENTING
W415-1345 / C / 02.14.17
12
3.4 VENT TERMINAL CLEARANCES
EN
COVERED BALCONY APPLICATIONS ††*
Q
S
R
G
P
Q
MIN
= 3 feet
(0.9m)
R
= 2 x
MAX
Q
ACTUAL
R
MAX
INSTALLATIONS
CANADAU.S.A.
12” (30.5cm)12” (30.5cm)Clearance above grade, veranda porch, deck or balcony.
A
18”
Δ
9” (229mm)Clearance to windows or doors that open.
18”
(45.7cm)**
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’
(0.6m) from the center line of the terminal.
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
Clearance to each side of the center line extended above the meter / regulator assembly to a maximum vertical distance of 15’ (4.6m).
12” (30.5cm)
B
12” (30.5cm)*12” (30.5cm) *Clearance to permanently closed windows.
C
D
(45.7cm)**
12” (30.5cm)**12” (30.5cm)**Clearance to unventilated soffi t.
E
0” (0mm)0” (0mm)Clearance to an outside corner wall.
F
0” (0mm)***0” (0mm)***
G
2” (51mm)***2” (51mm)***Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
3’(0.9m)3’(0.9m)****
H
3’ (0.9m)3’ (0.9m)****Clearance to a service regulator vent outlet.
I
12” (30.5cm)9” (229mm)Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
J
6’ (1.8m)3’ (0.9m) †Clearance to a mechanical air supply inlet.
K
7’ (2.1m) ‡7’ (2.1m) ****Clearance above a paved sidewalk or paved driveway located on public property.
L
12” (30.5cm)†† 12” (30.5cm)**** Clearance under a veranda, porch or deck.
M
IHHW
(4.6m)
16” (40.6cm)16” (40.6cm)Clearance above the roof.
N
O
P
Q
R
12” (30.5cm)12” (30.5cm)Clearance under a covered balcony
S
ΔThe terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
*Recommended to prevent condensation on windows and thermal breakage
**It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
***The periscope requires a minimum 18 inches clearance from an inside corner.
****This is a recommended distance. For additional requirements check local codes.
†3 feet above if within 10 feet horizontally.
‡A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
††Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†*Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
††*Permitted only if the balcony is fully open on a minimum of one side.
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
W415-1345 / C / 02.14.17
2’ (0.6m)†*2’ (0.6m) †*Clearance from an adjacent wall including neighbouring buildings.
8’ (2.4m)8’ (2.4m)
3’ (0.9m)3’ (0.9m)See chart for wider wall dimensions.
6’ (1.8m)6’ (1.8m)
Roof must be non-combustible without openings.
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an
opening between the terminal and the open side of the structure.
12.1E
3.5 VENT APPLICATION FLOW CHART
13
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
TOP EXIT
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of
24.75 feet (7.5m)
4.2 times the
vertical rise equal to
or greater than the
horizontal run
REAR EXIT
Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
EN
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
3 times the vertical
rise equal to or
greater than the
horizontal run
13.1A
Horizontal Termination
Vertical rise is equal
to or greater than
the horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
3.6 DEFINITIONS
For the following symbols used in the venting calculations and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
HT - total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
HR - combined horizontal vent lengths in feet
HO - offset factor: .03 (total degrees of offset - 90°*) in feet
VT - combined vertical vent lengths in feet
Since this formula is not met, this vent configuration is unacceptable.
Formula 2: HT + V
16.1FT (4.9m) < 13.5 (4.1m)
< 40 FT (12.2m)
T
Since only formula 2 is met, this vent configuration is unacceptable and a new fireplace location or vent configuration will
need to be established to satisfy both formulas.
Since both formulas are met, this vent configuration is acceptable.
18.2_3A
W415-1345 / C / 02.14.17
19
EN
2
90°
20
4.0 PRE-INSTALLATION PREPARATION
EN
4.1 DOOR OPERATION
4.2 REAR EXIT
For optimum performance, it is recommended that all horizontal runs have a 1" (25mm) rise per foot.
Release the top and bottom door latches, located at the right side of the door.
!
WARNING
FAILURE TO CREATE A SEAL TO THE FIREBOX WITH THE EXHAUST COLLAR ASSEMBLY WILL CAUSE
THE APPLIANCE TO FUNCTION IMPROPERLY AND CAN CAUSE INJURY OR PROPERTY DAMAGE.
From inside the fi rebox, insert the 4" (10.2cm) fl ue pipe / gasket assembly (provided)
through the rear of the fi rebox. Secure the gasket assembly to the rear and top of the
appliance using 4 #8 x ¾ inch Hex Head Wildrill screws supplied.
Do not overtighten. The gasket needs only to be snug against the fi rebox.
Before attaching elbows to the collars on the back of the appliance, 1½" (38mm) will
need to be trimmed off the 4" (10.2cm) collar.
4.3 TOP VENT
FAILURE TO CREATE A SEAL TO THE FIREBOX WITH THE EXHAUST COLLAR ASSEMBLY WILL CAUSE
THE APPLIANCE TO FUNCTION IMPROPERLY AND CAN CAUSE INJURY OR PROPERTY DAMAGE.
A.Remove the 7" (17.8cm) diameter cap from the top of the appliance and
re-secure it over the 7" (17.8cm) collar located at the rear of the appliance.
Press fi rmly on the cap while securing to ensure an airtight seal. Do not
damage the gasket.
B.Remove the plate covering the 4" (10.2cm) diameter fl ue opening (seen
inside the top of the 7" (17.8cm) diameter collar) and discard. Try not to
disturb the retaining ring or the gasket beneath. Re-secure the ring and
gasket using the screws removed from the plate.
C.From inside the fi rebox, insert the 4" (10.2cm) fl ue pipe / gasket assembly
through the heat shield and out through the retaining ring. Secure the assembly to the rear and top
of the appliance using 4 #8 x ¾" Hex Head Wildrill screws supplied. Do not overtighten. The gasket
needs only to be snug against the fi rebox.
!
WARNING
W415-1345 / C / 02.14.17
5.0 INSTALLATION
21
ENSURE TO UNPACK ALL LOOSE MATERIALS FROM INSIDE THE FIREBOX PRIOR TO HOOKING UP
THE GAS AND ELECTRICAL SUPPLY.
IF YOUR APPLIANCE IS SUPPLIED WITH A REMOTE, ENSURE THE REMOTE RECEIVER IS IN THE
“OFF” POSITION PRIOR TO HOOKING UP THE GAS AND ELECTRICAL SUPPLY TO THE APPLIANCE.
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
ALL EXHAUST AND INTAKE VENT PIPE JOINTS MUST BE SEALED USING RED RTV HIGH TEMP
SILICONE SEALANT (W573-0002) (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC (W573-0007)
(NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR WHICH MUST
BE SEALED USING MILL PAC.
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, A MINIMUM OF 3 SCREWS MUST ALSO
BE USED TO ENSURE THE CONNECTION CANNOT SLIP OFF.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
5.1 WALL AND CEILING PROTECTION
!
WARNING
EXACTLY.
EN
68.2D
!
WARNING
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
70.1
For clearances to combustible materials from the vent pipe, see “FRAMING” section.
For optimum performance it is recommended that all horizontal runs have a minimum 1" (25mm) rise per foot
using fl exible venting. For safe and proper operation of the appliance, follow the venting instructions exactly.
W415-1345 / C / 02.14.17
22
5.2 HORIZONTAL INSTALLATION
EN
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
This application occurs when venting through an exterior wall.
Having determined the correct height for the air terminal
location, cut and frame a hole in the exterior wall as
illustrated to accommodate the fi restop assembly.
Dry fi t the fi restop assembly before proceeding to
ensure the brackets on the rear surface fi t to the
inside surface of the horizontal framing.
The length of the vent shield may be cut shorter
for combustible walls that are less than 8 1/2”
(215.9mm) thick but the vent shield must extend
the full depth of the combustible wall.
NOTE : Do not fi ll the air space between the fi restop spacer and the
exterior wall with any type of insulating material (i.e., spray foam).
!
WARNING
RETURN FLANGE OF THE MOUNTING PLATE.
VENT
CAULKING
FIRESTOP
SPACER
SHIELD
FINISHING
MATERIAL
DETERMINE
THE
CORRECT
HEIGHT
A. Apply a bead of caulking (not supplied) around the corner edge of
the inside surface of the fi restop assembly, fi t the fi restop assembly to the hole and secure using the 4 screws (supplied in your manual baggie).
B. Once the vent pipe is installed in its fi nal position, apply red RTV silicone (W573-0002) (not supplied)
between the pipe and the fi restop.
5.3 VERTICAL INSTALLATION
This application occurs when venting through a roof. Installation kits for
various roof pitches are available from your authorized dealer / distributor.
See accessories to order specifi c kits required.
A. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1" (25mm)
clearance between the vent pipe and any combustible material. Try to
center the vent pipe location midway between two joists to prevent
having to cut them. Use a plumb bob to line up the center of the
openings. A vent pipe shield will prevent any materials such as
insulation, from fi lling up the 1" (25mm) air space around the pipe.
Nail headers between the joist for extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the
Wolf Steel vent pipe shield plate or equivalent (in the case of a fi nished
ceiling), and secure over the opening in the ceiling. A fi restop must be placed
on the bottom of each framed opening in a roof or ceiling that the venting
system passes through. Apply a bead of caulking all around and place a
fi restop spacer over the vent shield to restrict cold air from being drawn into the
room or around the fi replace. Ensure that both spacer and shield maintain the required
clearance to combustibles. Once the vent pipe is installed in its fi nal position, apply
Mill Pac sealant (W573-0007) (not supplied) or red RTV silicone (W573-0002) (not
supplied) between the pipe and the fi restop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and
tighten. This will prevent any materials, such as insulation, from fi lling up the 1" (25mm)
air space around the pipe.
20.2C
9 1/2"
FIRESTOP
UNDERSIDE OF
JOIST
VENT PIPE
SHIELD
SHIELD
21.1B
9 1/2"
CAULKING
VENT
PIPE
COLLAR
VENT
PIPE
W415-1345 / C / 02.14.17
5.4 USING FLEXIBLE VENT COMPONENTS
A
23
!
WARNING
DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND ELBOWS.
KEEP IT PULLED TIGHT.
SPACERS ARE ATTACHED TO THE INNER FLEX PIPE AT PREDETERMINED INTERVALS TO MAINTAIN AN EVEN
AIR GAP TO THE OUTER FLEX PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED
AT THE START, MIDDLE AND END OF EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS
MUST NOT BE REMOVED.
For safe and proper operation of the appliance, follow the venting instructions
exactly.
All inner fl ex pipe and outer fl ex pipe joints may be sealed using high temperature
Elbow
Spacers
“Wolf Steel Approved Venting” or “E2” as identifi ed by the stamp on the fl ex pipes.
red RTV silicone W573-0002 (not supplied) or the high temperature sealant W5730007 Mill Pac (not supplied). However, the high temperature sealant W573-0007
Mill Pac (not supplied) must be used on the joint connecting the inner fl ex pipe
and the exhaust fl ue collar.
Use only approved fl exible vent pipe kits marked:
22.1C
EN
5.4.1 HORIZONTAL AIR TERMINAL INSTALLATION
. Stretch the inner fl ex pipe to the required length taking into
account the additional length needed for the fi nished wall
surface. Apply a heavy bead of the Mill Pac sealant
B. Using the outer fl ex pipe, slide over the outer
C. Insert the vent pipes through the fi restop maintaining the
D. If more vent pipe needs to be used to reach the fi replace,
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth
of its return fl ange.
(W573-0007) (not supplied) to the inner sleeve of
the air terminal. Slip the vent pipe a minimum of 2”
(50.8mm) over the inner sleeve of the air terminal and
secure with a minimum of 3 #8 screws.
combustion air sleeve of the air terminal and secure with
a minimum of 3 #8 screws. Seal using red RTV silicone
(W573-0002) (not supplied).
required clearance to combustibles. Holding the air terminal
(lettering in an upright, readable position), secure to the
exterior wall and make weather tight by sealing with
caulking (not supplied).
couple them together as illustrated. The vent system must
be supported approximately every 3 feet (0.9m) for both
vertical and horizontal runs. Use noncombustible strapping
to maintain the minimum clearance to combustibles.
SCREWS
(SUPPLIED)
HI-TEMP
SEALANT
OUTER
FLEX PIPE
CAULKING
INNER FLEX
PIPE
2" (50.8mm) OVERLAP
HIGH TEMPERATURE
INNER
FLEX PIPE
23.1C
OUTER FLEX PIPE
SEALANT
SCREWS
INNER COUPLER
OUTER COUPLER
OUTER
FLEX PIPE
W415-1345 / C / 02.14.17
24
A
5.4.2 VERTICAL AIR TERMINAL INSTALLATION
EN
MAINTAIN A MINIMUM 2” (51mm) SPACE BETWEEN THE AIR INLET BASE AND THE STORM COLLAR.
NOTE : Fastening hardware provided with appropriate roof terminal and liner kits.
. Fasten the roof support to the roof using 6 screws. The roof support is optional. In this case the
venting is to be adequately supported using either an alternate
method suitable to the authority having jurisdiction or the optional
roof support.
B.Stretch the inner fl ex pipe to the required length. Slip the inner
fl ex pipe a minimum of 2” (51mm) over the inner pipe of the
air terminal connector and secure with a minimum of
3 screws. Seal using a heavy bead of Mill Pac sealant
(W573-0007) (not supplied).
C.Repeat using the outer fl ex pipe, using a heavy bead of red
RTV silicone (W573-0002) (not supplied) and a minimum of
D. Thread the air terminal connector / vent pipe assembly
E. Remove nails from the shingles, above and to the sides of the air
F. Aligning the seams of the terminal and air terminal connector,
G. Apply a heavy bead of weatherproof caulking 2” (51mm)
H. If more vent pipe needs to be used to reach the appliance see
3 screws.
down through the roof. The air terminal must be positioned vertically
and plumb. Attach the air terminal connector to the roof support,
ensuring that the top of the air terminal is 16” (40.6cm) above the
highest point that it penetrates the roof.
terminal connector. Place the fl ashing over the air terminal connector
leaving a min. 3/4” (19mm) of the air terminal connector showing
above the top of the fl ashing. Slide the fl ashing underneath the
sides and upper edge of the shingles. Ensure that the air terminal
connector is properly centered within the fl ashing, giving a 3/4”
(19mm) margin all around. Fasten to the roof. Do not nail through
the lower portion of the fl ashing. Make weather-tight by sealing with
caulking. Where possible, cover the sides and top edges of the
fl ashing with roofi ng material.
place the terminal over the air terminal connector making sure
the vent pipe goes into the hole in the terminal. Secure with 3
screws.
above the fl ashing. Install the storm collar around the air
terminal and slide down to the caulking. Tighten to ensure that
a weather-tight seal between the air terminal and the collar is
achieved.
“HORIZONTAL AIR TERMINAL INSTALLATION” section.
!
WARNING
ROOF SUPPORT
AIR
TERMINAL
CONNECTOR
2” (51mm)
INNER PIPE
MILL PAC
SEALANT
(W572-0007)
INNER FLEX PIPE
OUTER FLEX PIPE
AIR I NL ET
BASE
CAULKING
STORM COLLAR
24.1D
FLASHING
WEA THER
SEALANT
W415-1345 / C / 02.14.17
A
A
5.4.3 APPLIANCE VENT CONNECTION
A
. Install the inner exhaust fl ue collar to the appliance. Secure
with a minimum of 3 #8 screws. Seal the joint and screw
holes using Mill Pac sealant (W573-0007) (not supplied).
B. Install the outer fl ex pipe to the appliance. Attach and seal
the joints using a red RTV silicone and a minimum of 3 #8
screws.
5.5 USING RIGID VENT COMPONENTS
The vent system must be supported approximately every 3 feet (0.9m) for both vertical and horizontal runs.
Use Wolf Steel Ltd. support ring assembly or equivalent noncombustible strapping to maintain the minimum
clearance to combustibles for both vertical and horizontal runs.
ll inner exhaust and outer intake vent pipe joints may be sealed using either red high temperature
silicone sealant (W573-0002) (not supplied) or black high temperature sealant W573-0007 Mill Pac (not
supplied) with the exception of the appliance exhaust fl ue collar which must be sealed using Mill Pac.
5.5.1 HORIZONTAL AIR TERMINAL INSTALLATION
#8 X 1/2”
SELF
DRILLING
SCREWS
28.1D
25
EN
2” (50.8mm)
OVERLAP
HIGH TEMP
SEALANT
25.1A
. Move the appliance into position. Measure the
vent length required between terminal and
appliance taking into account the additional
#10x2"
SCREWS
length needed for the fi nished wall surface
and any 1¼” (31.8mm) overlaps between
venting components.
B.Apply high temperature sealant W573-0007 Mill Pac
(not supplied) to the outer edge of the inner exhaust
fl ue collar of the appliance. Attach the fi rst inner
rigid pipe component and secure using a minimum of
CAULKING
OUTER
RIGID
PIPE
1" (25.4mm)
OVERLAP
HI-TEMP
INNER
RIGID
PIPE
#8x1/2"
SELF DRILLING
SCREWS
SEALANT
3 self tapping screws. Repeat using the outer rigid pipe.
C.Insert the vent pipes through the fi restop maintaining the required clearance to combustibles. Holding
the air terminal (lettering in an upright, readable position), secure to the exterior wall and make
weather tight by sealing with caulking (not supplied).
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the
depth of the return fl ange.
26.1A
5.5.2 EXTENDED HORIZONTAL AND CORNER TERMINAL INSTALLATION
A 45° corner installation can have 0” (0mm) rise between the appliance
combustion air collar and the air terminal. In this case, vent lengths must be
kept to a maximum of 24” (60.9cm) . For longer vent lengths, a minimum
vertical rise of 24” (60.9cm) is required.
A. Follow the instructions for "HORIZONTAL AIR TERMINAL
INSTALLATION" section.
B. Continue adding components alternating inner and outer vent pipes. Ensure that
all inner vent pipes and elbows have sufficient vent spacers attached and each
component is securely fastened to the one prior. Attach the telescopic sleeve to the
vent run. Secure and seal. To facilitate completion, attach inner and outer couplers to
the air terminal.
AIR TERMINAL
20" (508mm)
COUPLER
TELESCOPIC SLEEVE
VENTING
C. Install the air terminal. See “HORIZONTAL AIR TERMINAL INSTALLATION” section. Extend the outer
telescopic sleeve; connect to the air terminal assembly. Fasten with screws and seal.
48.2A
W415-1345 / C / 02.14.17
26
A
5.5.3 VERTICAL AIR TERMINAL INSTALLATION
EN
NOTE: Before attaching elbows to the collars on the back of the appliance, 1 1/2” (38.1mm) will need to
be trimmed off the 4” (101.6mm) collar.
REAR VENT APPLICATION: Attach 4” (101.6mm) and 7” (177.8mm) elbows to the appliance. Secure with
three screws and seal the joints and screw heads using high temperature
sealant. Proceed to step A below.
TOP VENT APPLICATION:
. Move the appliance into position.
B. Fasten the roof support to the roof using the screws provided. The
roof support is optional. In this case the venting is to be adequately
supported using either an alternate method suitable to the authority
having jurisdiction or the optional roof support.
C.Apply high temperature sealant W573-0007 (not supplied) to the
outer edge of the inner sleeve of the air terminal. Slip the inner
coupler a minimum of 2” (50.8mm) over the sleeve and secure using
three screws.
D.Apply high temperature sealant W573-0002 (not supplied) to the
outer edge of the of the outside sleeve of the air terminal connector.
Slip the outer coupler over the sleeve and secure as before. Trim the
outer coupler even with the inner coupler end.
E.Thread the air terminal connector / vent pipe assembly down
through the roof support and attach, ensuring that a minimum
16” (40.6cm)of air terminal connector will penetrate the roof when
fastened. If the attic space is tight, we recommend threading
the Wolf Steel vent pipe collar or equivalent loosely onto the air terminal
connector / vent pipe assembly as it is passed through the attic. The air
terminal connector must be positioned vertically and plumb.
F. Remove nails from the shingles, above and to the sides of the air terminal
connector. Place the fl ashing over the air terminal connector and slide it
underneath the sides and upper edge of the shingles. Ensure that the air
terminal connector is properly centered within the fl ashing, giving a 3/4”
(19.1mm) margin all around. Fasten to the roof. Do NOT nail through the lower portion of the fl ashing. Make weather-tight by sealing with caulking. Where possible, cover
the sides and top edges of the fl ashing with roofi ng material.
G.Apply a heavy bead of waterproof caulking 2” (50.8mm) above the fl ashing. Install the storm collar
around the air terminal and slide down to the caulking. Tighten to ensure that a weather-tight seal
between the air terminal connector and the collar is achieved.
H.Continue adding rigid venting sections, sealing and securing as above. Attach the inner collapsed
telescopic sleeve to the last section of rigid piping. Secure with screws and seal. Repeat using the
outer telescopic sleeve.
REAR VENT APPLICATION:
I. Run a bead of high temperature sealant W573-0007 (not supplied) around the outside of the inner
elbow. Pull the telescopic sleeve a minimum of 2” (50.8mm) onto the elbow. Secure with three
screws. Repeat with the outer telescopic sleeve.
TOP VENT APPLICATION:
J. Run a bead of high temperature sealant W573-0007 (not supplied) around the outside of the inner
collar on the appliance. Pull the telescopic sleeve a minimum of 2” (50.8mm) onto the collar. Secure
with three screws. Repeat with the outer telescopic sleeve.
K.
In the attic, slide the vent pipe collar down to cover up the open end of the shield and tighten. This will
prevent any materials, such as insulation, from fi lling up the 1” (25.4mm) air space around the pipe
AIR
TERMINAL
CONNECTOR
27.1A
INNER PIPE
HIGH
TEMPERATURE
SEALANT
INNER RIGID
PIPE
OUTER
RIGID PIPE
VENT
PIPE
COLLAR
VENT
PIPE
SHIELD
W415-1345 / C / 02.14.17
AIR
INTAKE
EXHAUST
FLUE
FLEX
LINER
* 40 FT (12.2m)
MAX.
10 FT (3.1m)
MIN
COAXIAL TO
CO-LINEAR
ADAPATOR
APPLIANCE
VENT ADAPTOR
TERMINATION
5.6 VERTICAL THROUGH EXISTING CHIMNEY
27
!
WARNING
RISK OF FIRE!
CO-AXIAL TO CO-LINEAR VENTING CONFIGURATIONS MUST ONLY BE USED IN A
NON-COMBUSTIBLE CHIMNEY OR ENCLOSURE. INSTALLATION IN A COMBUSTIBLE ENCLOSURE
COULD RESULT IN A FIRE.
This appliance is designed to be attached to a 3” (76.2mm) co-linear aluminum fl ex vent system running the
full length of a masonry chimney.
The fl ex liners accommodate any contours of a
masonry chimney, however, it is necessary to keep
the fl exible liners as straight as possible. The inlet air
collar of the termination cap must be connected to
the air intake fl ex liner and the exhaust collar must be
connected to the exhaust fl exible liner.
Both Simpson Duravent and Selkirk co-linear to
co-axial adaptors have been approved on this
appliance (NOTE:A vent adaptor will be required directly off the appliance).
Follow vent manufacturer’s installation instructions.
Different manufacturer’s venting components must
not be combined. Once the preferred manufacturer’s
appliance adaptor has been attached, the
remainder of the system must be that of the
same manufacturer.
EN
The only exception to this rule is to use Wolf
Steel’s approved 3” (76.2mm) fl ex liner and
co-linear termination.
* Measured from appliance fl ue collar to
termination fl ue collar
7.6B
W415-1345 / C / 02.14.17
28
5.7 MOBILE HOME INSTALLATION
EN
This appliance must be installed in accordance with the manufacturer’s instructions and the Manufactured
Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home
Standard, CAN/CSA Z240 MH Series, in Canada. This appliance is only for use with the type(s) of gas
indicated on the rating plate.
This Mobile/Manufactured Home Listed appliance comes factory equipped with a means to secure the appliance.
Built in appliances are equipped with 1/4” (6.4mm) diameter holes located in the front left and right corners of the
base. Use appropriate fasteners, inserted through the holes in the base to secure. For free standing products
contact your local authorized dealer / distributor for the appropriate securing kit. For mobile home installations,
the appliance must be fastened in place. It is recommended that the appliance be secured in all installations.
Always turn off the pilot and the fuel supply at the source, prior to moving the mobile home. After moving the
mobile home and prior to lighting the appliance, ensure that the logs are positioned correctly.
This appliance is certifi ed to be installed in an aftermarket permanently located, manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certifi ed kit is used.
Conversion Kits
This appliance is fi eld convertible between Natural Gas (NG) and Propane (P).
To convert from one gas to another consult your Authorized dealer/distributor.
5.8 GAS INSTALLATION
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH AS
SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT
WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE
PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT
THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND
ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS
29.1C
!
WARNING
SPARKS OR OPEN FLAMES.
ELECTRICAL LOCATIONS, SEE “DIMENSIONS” SECTION.
LINE AT TEST PRESSURES ABOVE 1/2 PSIG.
VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.
Installation and servicing to be done by a qualifi ed installer.
• Move the appliance into position and secure.
• If equipped with a fl ex connector the appliance is designed to accept a 1/2” (13mm) gas supply.
• Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
• When fl exing any gas line, support the gas valve so that the lines are not bent or kinked.
• The gas line fl ex-connector should be installed to provide suffi cient movement for shifting the burner
• Check for gas leaks by brushing on a soap and water solution. Do not use open fl ame.
W415-1345 / C / 02.14.17
Without the connector it is designed to accept a 3/8” (9.5mm) gas supply. The appliance is equipped
with a manual shut off valve to turn off the gas supply to the appliance.
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
Z223.1 / NFPA 54 in the United States.
assembly on its side to aid with servicing components.
30.1A
5.9 OPTIONAL WALL SWITCH
29
!
WARNING
DO NOT CONNECT EITHER THE WALL SWITCH, THERMOSTAT OR GAS VALVE DIRECTLY TO
110 VOLT ELECTRICITY.
For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a convenient
location. Route a 2 strand, solid core millivolt wire from the valve to the wall switch or millivolt thermostat. The
recommended maximum lead length depends on wire size:
Disconnect the existing wires from terminals 1 and 3 (from the
ON/OFF switch) and replace with the leads from the wall switch / millivolt thermostat.
50.1A
6.0 FRAMING
!
WARNING
RISK OF FIRE!
IN ORDER TO AVOID THE POSSIBILITY OF EXPOSED INSULATION OR VAPOUR BARRIER COMING
IN CONTACT WITH THE APPLIANCE BODY, IT IS RECOMMENDED THAT THE WALLS OF THE
APPLIANCE ENCLOSURE BE “FINISHED” (IE: DRYWALL / SHEETROCK), AS YOU WOULD FINISH
ANY OTHER OUTSIDE WALL OF A HOME. THIS WILL ENSURE THAT CLEARANCE TO
COMBUSTIBLES IS MAINTAINED WITHIN THE CAVITY.
DO NOT NOTCH THE FRAMING AROUND THE APPLIANCE STAND-OFFS. FAILURE TO MAINTAIN
AIR SPACE CLEARANCE MAY CAUSE OVER HEATING AND FIRE. PREVENT CONTACT WITH
SAGGING OR LOOSE INSULATION OR FRAMING AND OTHER COMBUSTIBLE MATERIALS. BLOCK
OPENING INTO THE CHASE TO PREVENT ENTRY OF BLOWN-IN INSULATION. MAKE SURE
INSULATION AND OTHER MATERIALS ARE SECURED.
WHEN CONSTRUCTING THE ENCLOSURE ALLOW FOR FINISHING MATERIAL THICKNESS TO
MAINTAIN CLEARANCES. FRAMING OR FINISHING MATERIAL CLOSER THAN THE MINIMUMS
LISTED MUST BE CONSTRUCTED ENTIRELY OF NON-COMBUSTIBLE MATERIALS. MATERIALS
CONSISTING ENTIRELY OF STEEL, IRON, BRICK, TILE, CONCRETE, SLATE, GLASS OR PLASTERS,
OR ANY COMBINATION THEREOF ARE SUITABLE. MATERIALS THAT ARE REPORTED AS PASSING
ASTM E 136, STANDARD TEST METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE
FURNACE AT 750°C/1382°F AND UL763 SHALL BE CONSIDERED NON-COMBUSTIBLE MATERIALS.
MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD
COULD RESULT.
THE APPLIANCE REQUIRES A MINIMUM ENCLOSURE HEIGHT. MEASURE FROM THE APPLIANCE
BASE.
IF STEEL STUD FRAMING KITS WITH CEMENT BOARD ARE PROVIDED, THEY MUST BE
INSTALLED.
EN
71.1
It is best to frame your appliance after it is positioned and the vent system is installed. Frame to local building
codes.
It is not necessary to install a hearth extension with this appliance system.
When roughing in the appliance, raise the appliance to accommodate for the thickness of the fi nished fl oor
materials, i.e. tile, carpeting, hard wood, which if not planned for will interfere with the opening of the lower
access door and the installation of many decorative fl ashing accessories.
Combustible materials may be installed fl ush with the front of the appliance but must not cover any of the
black face-areas of the appliance. Non-combustible material (brick, stone or ceramic tile) may protrude in
these areas.
W415-1345 / C / 02.14.17
EN
30
Minimum clearance to combustible construction from appliance and vent surfaces:
Combustible Framing:
- 3 1/2" (89mm) from top of stand-offs
- 1" (25mm) to bottom and sides of the vent pipe*
- 2" (51mm) to top of the vent pipe*
Combustible Finishing:
- 0" to rear
- 0" to front face and sides, 6 1/2"(165mm) for top
- 17 1/4" (438mm) recessed depth
Rear Exit
- 40 1/2" (991mm) to enclosure top from base of the appliance
- 54" (1372mm) to ceiling from base of the appliance
Top Exit
- 49" (1245mm) to enclosure top from base of the appliance
- 54" (1372mm) to ceiling from base of the appliance
* HORIZONTAL VENT SECTIONS - A minimum clearance of 1" (25mm) at the bottom and sides and 2"
(5.1cm) at the top of the vent pipe on all horizontal runs to combustibles is required. Use fi restop spacer
W010-1777 (supplied).
* VERTICAL VENT SECTIONS - A minimum of 1" (25mm) all around the vent pipe on all vertical runs to
combustibles is required except for clearances in appliance enclosures. See "MINIMUM ENCLOSURE
CLEARANCES" section. Use fi restop spacer W500-0096 (not supplied).
6.1 INSTALLING STAND-OFFS
These appliances are supplied with two standoffs. For
convenience, the standoffs have been shipped fl at and located on
the top at the front. Before framing ensure the standoffs are bent
up and screwed into place ensuring a height of 4 1/2" (114.3mm).
NOTE: The information and dimensions in this section
represent the minimum clearances to combustible material.
It is best to frame your appliance after it is positioned and the
vent system is installed. Use 2x4's and frame to local building
codes.
A steel header is required if using optional clean face surround.
W415-1345 / C / 02.14.17
Loading...
+ 94 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.