Napoleon 9700 Installation And Operating Instructions Manual

INSTALLER: PLEASE FAMILIARIZE YOURSELF WITH VENTING/DRAINING SECTIONS OF
THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. LEAVE THIS MANUAL WITH THE APPLIANCE FOR FUTURE REFERENCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
OPERATING INSTRUCTIONS
CERTIFIED TO ANSI Z21.47b / CSA 2.3b-2008
1
9700 SERIES
TWO STAGE HIGH EFFICIENCY (CONDENSING) FORCED AIR GAS FURNACE
SAFETY INFORMATION
!
WARNING
ELECTRICAL SHOCK, FIRE OR
EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death or property damage.
- Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
- Before servicing, disconnect all electrical power to furnace.
- When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
- Verify proper operation after servicing.
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
!
MANUFACTURER RESERVES THE RIGHT TO DISCONTINUE, OR CHANGE AT ANY TIME, SPECIFICATIONS OR DESIGNS WITHOUT NOTICE AND
Annual Fuel Utilization Efficiency (AFUE) Gas- or Propane-fired forced-air furnace with a high efficiency motor
90%
WITHOUT INCURRING OBLIGATIONS.
Patent Pending
97.0
98%
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
Phone (705)721-1212 • Fax (705)722-6031 • www.napoleonheatingandcooling.com • ask@napoleonproducts.com
$10.00
W415-1064 / 11.11.11
2
TABLE OF CONTENTS
1.0 INTRODUCTION 3
2.0 SAFETY SYMBOLS AND WARNINGS 4
2.1 SAFETY RULES 5
2.2 CODES 5
2.3 INSTALLATION REQUIREMENTS SPECIFIC TO THE STATE OF MASSACHUSETTS FOR DIRECT VENT, MECHANICAL VENT, AND DOMESTIC HOT WATER APPLIANCES. 8
3.0 FURNACE SIZING 10
4.0 LOCATION OF UNIT 11
4.1 GENERAL GUIDELINES 11
4.2 OTHER CONSIDERATIONS 11
4.3 INSTALLATION IN UPFLOW POSITION 12
4.4 AIR CONDITIONING 12
5.0 COMBUSTIBLE CLEARANCES 13
6.0 DUCTWORK 14
6.1 DUCTWORK STEPS 15
7.0 VENTING AND COMBUSTION PIPING 16
7.1 ACCEPTABLE MATERIALS IN CANADA 16
7.2 ACCEPTABLE MATERIALS IN UNITED STATES 16
8.0 NON-DIRECT VENT FURNACE INSTALLATIONS USING INDOOR COMBUSTION AIR (ONE PIPE SYSTEM) 17
8.1 DETERMINING COMBUSTION AIR 18
8.1.1 CASE 1: FURNACE LOCATED IN A UNCONFINED SPACE 18
8.1.2 CASE 2: FURNACE LOCATED IN A CONFINED SPACE 18
8.1.3 CASE 3: FURNACE LOCATED IN A CONFINED SPACE, OUTDOOR AIR FROM ATTIC OR CRAWL SPACE 19
8.1.4 CASE 4: FURNACE LOCATED IN A CONFINED SPACE, OUTDOOR AIR DUCTED HORIZONTALLY 20
8.1.5 CONNECTION TO FURNACE NON-DIRECT VENT 20
9.0 VENTING GUIDELINES 21
9.1 VENT TERMINATION 22
9.2 IN CANADA 23
9.3 IN UNITED STATES 23
9.4 FURNACE VENTING INSTALLATIONS 24
9.4.1 NON-DIRECT VENT INSTALLATION USING INDOOR COMBUSTION AIR (ONE PIPE SYSTEM) 24
9.4.2 DIRECT VENT INSTALLATION USING OUTDOOR COMBUSTION AIR (TWO PIPE SYSTEM) 24
9.4.3 COMBUSTION AIR 24
10.0 TERMINATIONS 25
10.1 COMBUSTION AIR 25
10.2 EXHAUST 25
10.3 CONCENTRIC VENTING KIT 25
10.4 CONCENTRIC VENT TERMINATION INSTALLATION INSTRUCTIONS 25
10.5 LOCATION 26
10.6 MULTIPLE VENTING 26
10.7 IN CANADA 27
10.8 IN UNITED STATES 27
10.9 FURNACE CONNECTION 27
10.9.1 ROUTING OPTIONS 30
10.9.2 EXHAUSTER ROTATION INSTRUCTIONS & PRESSURE SWITCH MOUNTING 30
10.9.3 PREPARATIONS FOR VENT AND DRAINING OPTION 31
11.0 CONDENSATE DRAINS 33
11 .1 DRAIN HOSE INSTALLATION 33
11.1.1 DRAIN PIPING 33
11.1.2 ALTERNATE CONDENSATE DRAIN PIPING INSTALLATION USING PVC OR CPVC 34
11.2 CONDENSATE NEUTRALIZERS 35
12.0 GAS SUPPLY AND PIPING 36
12.1 GAS SUPPLY 36
12.2 GAS PIPING 36
12.3 GAS INLET PRESSURE 37
12.4 LEAK TESTING 37
12.5 PURGING GAS LINES 37
13.0 CONVERSIONS 38
13.1 CHECKING THE INLET GAS PRESSURE 38
13.2 SETTING THE MANIFOLD GAS PRESSURE 39
13.3 CHECKING FURNACE INPUT 40
14.0 ELECTRICAL SPECIFICATIONS 41
14.1 ELECTRICAL WIRING AND CONNECTIONS 41
14.2 FURNACE CONNECTION 42
W415-1064 / 11.11.11
3
15.0 LOW VOLTAGE WIRING 43
15.1 SINGLE STAGE THERMOSTAT 43
15.2 TWO STAGE THERMOSTAT 43
15.3 THERMOSTAT LOCATION 43
16.0 OPTIONAL ACCESSORIES (FIELD SUPPLIED/INSTALLED) 44
16.1 ELECTRIC AIR CLEANER 44
16.2 POWER HUMIDIFIER 44
16.3 EMERGENCY HEAT MODE 44
17.0 STARTUP PROCEDURES 45
17.1 TO START THE FURNACE 45
17.2 TO SHUT DOWN THE FURNACE 45
17.3 SEQUENCE OF OPERATION 46
17.4 PROGRAMMABLE THERMOSTAT (OPTION) 46
18.0 AIR FLOW 47
18.1 TEMPERATURE RISE CHECK 47
18.2 CALCULATING AIR FLOW 48
18.3 ADJUSTING BLOWER SPEEDS ON ECM 2.3 BLOWER MOTORS 48
18.4 DEHUMIDIFICATION - ECM 2.3 49
18.5 SETTING BLOWER “ON” AND “OFF” TIMINGS - ECM 2.3 MODELS ONLY 49
18.6 CONTINUOUS FAN OPERATION 49
18.7 UV LAMP REPLACEMENT 49
19.0 MAINTENANCE AND TROUBLESHOOTING 51
19.1 AIR FILTER 51
19.2 LUBRICATION 52
19.3 TERMINATIONS 52
19.4 INTAKE AIR/EXHAUST PIPING 52
19.5 OPERATING TIPS 52
19.6 ANNUAL INSPECTION/SERVICE 53
19.7 TROUBLESHOOTING FLOWCHART 54
19.8 DIAGNOSTIC CODES FOR STATUS LED 55
19.9 FAULT CODE HISTORY 55
19.10 INTERNAL LIGHTING SYSTEM 55
20.0 WIRE DIAGRAM FOR TWO STAGE FURNACE WITH ECM 2.3 56
21.0 WARRANTY 57
22.0 REPLACEMENT PARTS LIST 58
23.0 SERVICE HISTORY 59
24.0 NOTES 60
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
ATTENTION: UPFLOW VENTING RIGHT, MUST DRAIN ON LEFT SIDE.
1.0 INTRODUCTION
This high effi cient gas fi red two stage condensing furnace is an upfl ow warm air furnace suitable for residential and light commercial heating applications with inputs from 60,000 to 120,000 Btu/hr.
This high effi cient furnace series is CSA certifi ed as a Category IV indirect or direct vent central forced air furnace. When installed as a direct vent furnace, all combustion air is supplied to the furnace burners through the
air intake system. (See Section 7, “Ventilation and Combustion Piping.”)
The furnace is shipped completely assembled except for the condensate drain trap assembly. Please inspect for damage when the furnace is unpacked.
IMPORTANT: PLEASE READ THIS MANUAL CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.
W415-1064 / 11.11.11
4
2.0 SAFETY SYMBOLS AND WARNINGS
Understand and pay particular attention to the words DANGER, WARNING, and CAUTION and the following defi ned symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels.
! !
DANGER
INDICATES AN IMMINENTLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, WILL
RESULT IN DEATH OR SERIOUS INJURY.
!
WARNING
INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, COULD
RESULT IN DEATH OR SERIOUS INJURY.
!
CAUTION
INDICATES A POTENTIAL HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, MAY
RESULT IN MINOR OR MODERATE INJURY. IT MAY ALSO BE USED TO ALERT AGAINST
UNSAFE PRACTICES.
IMPORTANT: READ THE FOLLOWING INSTRUCTIONS COMPLETELY BEFORE INSTALLING!
!
WARNING
IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE
OR EXPLOSION MAY RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR
LOSS OF LIFE.
!
!
!
THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER
WHEN INSTALLED WITHIN THE COMMONWEALTH OF MASSACHUSETTS.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS, OR OTHER COMBUSTIBLE MATERIALS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
• DO NOT TRY TO LIGHT ANY APPLIANCE.
• DO NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE IN YOUR BUILDING.
• IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR’S PHONE, OR A CEL­LULAR PHONE FROM A LOCATION WELL AWAY FROM THE BUILDING. FOLLOW THE GAS SUPPLIER’S INSTRUCTIONS.
• IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE DEPARTMENT.
• DO NOT RE-ENTER THE BUILDING UNTIL AUTHORIZED TO DO SO BY THE GAS SUPPLIER OR THE FIRE DEPARTMENT.
W415-1064 / 11.11.11
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
5
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE
CAN CAUSE INJURY, PROPERTY DAMAGE OR LOSS OF LIFE. REFER TO THIS MANUAL.
INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER,
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE
PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF
THIS FURNACE. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING
INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY
RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE,
POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE
POISONING, EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
2.1 SAFETY RULES
1. Use this furnace only with type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in dry indoor locations (protected from weather).
3. Provide adequate combustion and ventilation air to the furnace space as specifi ed in Section 7 of this
manual, “Ventilation and Combustion Piping.”
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system
only, as specifi ed in Section 7 of this manual, “Venting and Combustion Piping.”
5. Never test for gas leaks with an open fl ame. Use a commercially available soap solution made specifi cally for the detection of leaks to check all connections as specifi ed in Section 12 of this manual,
“Gas Supply and Piping.”
6. Always install furnace to operate within the furnace’s intended temperature-rise range with a duct system, which has an external static pressure within the allowable range, listed on the furnace rating
plate, and as specifi ed in Sections 3, 6, and 18 of this manual, “Furnace Sizing,” “Ductwork,” and
“Airfl ow.”
7. When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. (Furnace for heating the home located
in the attached garage, for example).
!
WARNING
!
SERVICE AGENCY OR THE GAS SUPPLIER.
8. A gas-fi red furnace for installation in a residential garage must be installed so that the burners and ignitor are no less than 18” above the fl oor. The furnace must be located, or protected to avoid physical damage
by vehicles. (See safety warning).
9. This furnace must not be used for temporary heating of buildings under construction.
2.2 CODES
1. This furnace must be installed:
a. In accordance with all local codes, by-laws and regulations by those authorities having jurisdiction.
b. In Canada, this furnace must be installed in accordance with the current CAN/CGA -B149.1 and .2
Natural Gas and Propane, and the National Electric Code (NEC) NFPA 70.
c. In the United States, this furnace must be installed in accordance with the current ANSI Z223.1 (NFPA
54) National Fuel Gas Code.
W415-1064 / 11.11.11
6
2. Electrical connections must be made in accordance with:
a. Any applicable local codes, by-laws and regulations.
b. Canada: current edition of CAN/CSA C22.1, Canadian Electrical Code (Part 1).
c. United States: current edition of ANSI/NFPA 70, National Electrical Code.
Codes and additional information may be obtained from:
Canadian Standards Association American Gas Association 5060 Spectrum Way 400 North Capitol Street, NW, Suite 450 Mississauga, Ontario, L4W 5N6 Washington DC, 20001 Phone: (416) 747-4000 Phone: (202) 824-7000 website: www.csa.ca website: www.aga.org
National Fire Protection Association 1 Batterymarch Park Quincy, MA, 02169-7471 Phone: (617) 770-3000 website: www.nfpa.org
!
WARNING
!
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME! THIS FURNACE IS NOT
APPROVED FOR INSTALLATION IN A MOBILE HOME. DOING SO COULD CAUSE FIRE,
PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
THE FURNACE CONTAINS FOIL COVERED FIBERGLASS INSULATION. INHALATION OF
FIBERGLASS PARTICLES IS ASSOCIATED WITH RESPIRATORY DISEASE INCLUDING
CANCER.
NATURAL GAS AND PROPANE ARE NORMALLY ODORIZED BY THE FUEL SUPPLIER. IN
SOME CASES, THE ODORANT MAY NOT BE PERCEIVABLE. INSTALLATION OF UL AND
ULC RECOGNIZED FUEL GAS DETECTORS INSTALLED IN ACCORDANCE WITH THEIR
MANUFACTURER’S INSTRUCTIONS IS RECOMMENDED AS AN ADDITIONAL MARGIN OF
SAFETY.
THE EXHAUST GASES FROM THIS FURNACE CONTAIN CHEMICALS WHICH ON SOME OCCASIONS MAY INCLUDE CARBON MONOXIDE. CARBON MONOXIDE IS AN ODORLESS, TASTELESS, CLEAR COLORLESS GAS WHICH IS HIGHLY TOXIC. EVEN
LOW CONCENTRATIONS ARE SUSPECTED OF CAUSING BIRTH DEFECTS AND OTHER
REPRODUCTIVE HARM.
UL AND ULC RECOGNIZED CO DETECTORS ARE RECOMMENDED FOR ALL BUILDINGS
EQUIPPED WITH FOSSIL FUEL BURNING APPLIANCES. ALL CO DETECTORS SHOULD
BE INSTALLED IN ACCORDANCE WITH THEIR MANUFACTURER’S INSTRUCTIONS AND
APPLICABLE LOCAL BUILDING CODES.
FIRE, EXPLOSION OR CARBON MONOXIDE POISONING HAZARD!
FAILURE TO REPLACE WITH PROPER CONTROL COULD RESULT IN FIRE, EXPLOSION
REPLACE GAS VALVE ONLY WITH THE SAME MODEL NUMBER OR AS SPECIFIED BY THE
W415-1064 / 11.11.11
OR CARBON MONOXIDE POISONING.
MANUFACTURER.
!
WARNING
WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL GARAGE, IT MUST BE
INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE LOCATED NO LESS THAN
18” ABOVE THE FLOOR TO PREVENT THE RISK OF IGNITING FLAMMABLE VAPORS
WHICH MAY BE PRESENT IN THE GARAGE.
THE FURNACE MUST BE LOCATED OR PROTECTED TO AVOID PHYSICAL DAMAGE BY
VEHICLES.
FAILURE TO HEED THESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION, RESULTING
IN PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FIGURE 1 - FURNACE DIMENSIONS AND CLEARANCE TO COMBUSTIBLES
%
!
7
$/7(51$7(
&20%867,21
$,5
+9(17
)
$
TOP
*
$/7(51$7( )/8( /2&$7,21
&

$/7*$6/,1( 6&+
$/7)/8(/2&$7,21
$/7&20%867,21 $,5/2&$7,21
'
$/7(51$7( 5(7851$,5
( 
LEFT SIDE
$/7(51$7(&21'( 16$7( 75$3/2&$7,21
$/7(51$7(&21'( 16$7( 75$3/2&$7,21
$/7(51$7( (/(&75,&$/& 211(&7
TABLE A - FURNACE DIMENSIONS (INCHES)
INPUT
OUTPUT
HIGH
INPUT
LOW
OUTPUT
LOW Width Depth Height Supply Air Return Air
K/Btu/hr K/Btu/hr K/Btu/hr K/Btu/hr A B C (F x G) (D x E)
60 58 27 26 17½ 31 32 7/8 16 x 19½ 14 x 22
80 78 48 47 17½ 31 32 7/8 16 x 19½ 14 x 22 100 97 60 58 22½ 31 32 7/8 21½ x 19½ 14 x 22 120 116 72 70 22½ 31 32 7/8 21½ x 19½ 14 x 22
$/7*$6/,1(6&+
$/7&20%867,21 $,5/2&$7,21
$/7)/8(/2&$7,21
5(7851$,5
'
(
RIGHT SIDE
TABLE B - MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS (INCHES)
TOP 0
PLENUM TOP 1/2
FRONT 0*
BACK 0
SIDES 0
BOTTOM 0***
FLUE PIPE 0
ENCLOSURE CLOSET
*24” REQUIRED FOR SERVICE
*** CERTIFIED FOR CLOSET INSTALATION ON COMBUSTIBLE FLOORING.
UPFLOW
0
Top
NOTES: S - Service clearance 24 inches or more. C - Combustible oor (but not carpet or non-ceramic tile). All models approved for closet installation.
W415-1064 / 11.11.11
8
2.3 INSTALLATION REQUIREMENTS SPECIFIC TO THE STATE OF MASSACHUSETTS FOR DIRECT VENT, MECHANICAL VENT, AND DOMESTIC HOT WATER APPLIANCES.
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the commonwealth and where the side wall exhaust vent termination is less than seven feet above fi nished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfi ed:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS:
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfi tter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the fl oor level where the gas equipment is to be installed. In addition, the installing plumber or gasfi tter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualifi ed licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl
space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent fl oor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of
installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS:
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANS/UL 2034 listed and IAS certifi ed.
3. SIGNAGE:
A metal or plastic identifi cation plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half) 1/2 inch in size,
“GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION:
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.0(2)(a)1. through 4.:
5. EXEMPTIONS:
The following equipment is exempt from 248 CMR 5.08(2)(a)1. through 4.:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure
separate from the dwelling, building or structure used in whole or in part for residential purposes.
6. (A) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
W415-1064 / 11.11.11
7. INSTALLATION INSTRUCTIONS:
A copy of all installation instructions, and any instructions relating to venting shall remain with the furnace at the completion of the installation.
FIGURE 2 - FURNACE COMPONENTS
15
7
9
22
1
5
18
10
9
20
14
8
21
19
6
13
12
2
3
17
*16
4
11
LEGEND
1. Combustion Air Intake Fitting 13. Two Speed Exhauster
2. Flame Roll-Out Switch (2) 14. Pressure Switch Assembly
3. Flame Sensor - located underneath 15. Front Manifold Cover Pressure Tap (3)
4. Two Stage Gas Valve *16. PFC “Choke Coil” (used on ¾ and 1 Hp units only)
5. Air High Temperature Limit - supply air 17. Door Switch and Junction Box
6. Vent and Drain (Assembly) Coupling 18. Blower Motor (not shown, located on right side of
7. Drain for Recovery Coil (3) blower)
8. Condensate Trap 19. Circulating Air Blower
9. Two Stage Integrated Furnace Control (IFC) 20. UV Light Ballast
10. Transformer for 24 VAC / 40 VA 21. UV Light Bulb
11. Burner Assembly 22. LED Trouble Light (2)
12. Hot Surface Igniter (HSI)(located underneath)
W415-1064 / 11.11.11
10
3.0 FURNACE SIZING
The maximum hourly heat loss for each heated space shall be calculated in accordance with the procedures
described in the manuals of the Heating, Refrigeration and Air Conditioning Institute of Canada (HRAI), or
by any other method which is suitable for local conditions, provided the results obtained are in substantial agreement with, and not less than those obtained using the procedure described in their manuals.
In the United States, “Manual J - Load Calculation,” published by the Air Conditioning Contractors of America,
describes a suitable procedure for calculating the maximum hourly heat loss.
If the installation is a retrofi t application, do not rely on the capacity of the existing heating equipment as a method to size the new furnace. Many of the heat transfer multiples listed in earlier versions of load calculation manuals were much higher than those listed in more recent editions. It is possible that energy saving measures have been completed since the installation of the existing furnace. This might include additional insulation in the attic or walls, the application of sprayed foam insulation, the addition of storm windows and doors, weather-stripping, caulking, etc.
Many of the older furnaces were equipped with large belt drive blower systems, operating at low RPM’s. If replacing an existing furnace, be sure that the existing ductwork can handle the amount of airfl ow necessary for a reasonable temperature rise. Most older gas furnaces operated with a system temperature rise of 70 ­100°F. This furnace is designed to be operated with a system temperature rise (T) of High Fire 35 - 65°F, Low Fire 20 - 50°F. If the furnace selected has an identical output capacity as the original furnace, a substantial increase in system air fl ow will be necessary. See Table 1 and the airfl ow
characteristics in Section 18 of this manual, “Air ow”.
Existing ductwork should be assessed for its air handling capabilities.
The “Equal Friction Chart,” as published by ASHRAE and HRAI, is the basis for the various air duct calculators available through heating supply companies. Following the air velocity guide lines, according to the “Equal Friction Chart,” or a slide rule air duct calculator, a typical 6” round duct has a capacity of approximately 100
cfm.
TABLE 1 - RANGE OF TEMPERATURE RISE
Furnace Models Temperature Rise
ALL
High Fire (HF) 35 - 65°F
Low Fire (LF) 20 - 50°F
NOTE:
The return air system is equally as important as the supply air system. An under-sized return air system will prevent suffi cient quantities of air from reaching the supply air system and will consequently reduce the service life of the furnace and its components.
W415-1064 / 11.11.11
4.0 LOCATION OF UNIT
4.1 GENERAL GUIDELINES
1. Select a location where the exhaust and combustion air piping can be routed between the furnace and their terminations with a minimum of lengths and fi ttings. Be sure to check that the proposed termination
location will meet code requirements with respect to location and minimum clearances. (See venting
section for minimum and maximum limits.)
2. Select a location as near as possible to the existing or proposed duct system.
3. The furnace location must have provisions for condensate drainage. If a suitable drain is unavailable near the furnace, a condensate pump must be used. The condensate pump drain tubing must not terminate outdoors; similar to some air conditioning condensate installations. Be sure to select a condensate pump that has been approved for furnace condensate applications.
4. The furnace location must permit access for servicing and be within the clearance to combustibles guidelines as marked on the appliance rating plate.
5. The furnace must be installed on a level surface. It is recommended that the rear of the furnace be elevated 1/4” higher than the front to facilitate proper condensate drainage.
6. If the furnace is being installed so that the return air will enter through the bottom, the perimeter of the furnace must be properly supported.
7. In right venting confi guration, furnace must drain on the left side.
11
4.2 OTHER CONSIDERATIONS
1. If the furnace is to be located in an area where the combustion air is laden with chemical compounds such as bromine, chlorine or fl uorine, as may be found in swimming pool chemicals, laundry detergents, etc., use outdoor air for combustion. These compounds when exposed to fl ame, form acids which attack the heat exchanger and other components.
Exposure to the following substances in the combustion air supply (but not limited to the following) will also require OUTDOOR AIR for combustion:
Aerosols, particularly CFC based or propelled aerosols
• Air fresheners
“Airplane Glue” and similar adhesives and cements
Ammonia, as commonly found in permanent wave solutions used in hair dressing salons
Anti-static fabric softeners used in clothes dryers
• Carbon tetrachloride
Chlorinated cleaners and waxes
Chlorine and bromine based swimming pool chemicals
De-icing salts or chemicals (rock salt, etc.)
• Dry cleaning fl uids such as perchloroethylene
Fumes from curing polyurethane and similar substances
Halogen based refrigerants including R-12 and R-22
Hydrochloric acid, muriatic acid and other acid based masonry washing and curing materials
Printer’s inks, paint removers, varnishes, varsol, toluene, etc.
Water softener salt and chemicals
2. If this furnace is to be installed in an area over a fi nished ceiling or living area, install a fi eld fabricated auxiliary drain pan under the furnace to protect that area from accidental condensate spills. The auxiliary pan should be large enough to collect accidentally spilled condensate from the air conditioning evaporator coil assembly if applicable.
3. If the furnace is installed in an area where freezing may occur, a garage, an attic, a crawl space or any unconditioned space, steps must be taken to protect the condensate trap and drain line from freezing.
One possible measure could be to use a self-regulating 5 or 6 watt per foot heat tape covered with a jacket of insulation. Heat tapes are available in plumbing supply houses.
W415-1064 / 11.11.11
12
4.3 INSTALLATION IN UPFLOW POSITION
UPFLOW INSTALLATION: Vent positioning, pressure switch location and drain locations shall be performed in accordance with instructions in the appropriate sections of this manual.
NON-SUSPENDED INSTALLATION: Maintain clearances to combustibles as outlined in Figure 1, Table B. The furnace must be supported in such a way as to not allow twisting or sagging of the cabinet.
IMPORTANT:
THE FURNACE MUST BE INSTALLED ON A LEVEL SURFACE. IT IS RECOMMENDED THAT THE REAR OF THE FURNACE BE ELEVATED 1/4” HIGHER THAN THE FRONT TO FACILITATE PROPER CONDENSATE DRAINAGE.
IF THE FURNACE AND AIR CONDITIONER IS LOCATED ABOVE A FINISHED SPACE, INSTALL A DRAIN PAN UNDERNEATH THE UNIT.
NOTE THIS FURNACE IS CERTIFIED FOR UPFLOW INSTALLATION ONLY.
This furnace is approved for installation in attics, alcoves, utility rooms, closets and crawl spaces. If this furnace is to be installed in a utility room, be sure that it is located in such a way as to allow access for servicing or the removal of other appliances installed in the room (hot water heater, for example). It is not permissible to use a rear return on this appliance. Use only side and bottom returns.
4.4 AIR CONDITIONING
This furnace may be used as part of an air conditioning system. The furnace wiring and control system is “air conditioning ready.” There are the following factors to consider:
The air conditioning evaporator coil must be downstream of the heat exchanger. The cooled air passing over the warmer heat exchanger tubes can cause condensation inside the tubes, resulting in corrosion and premature failure.
A parallel duct system can be installed to direct the air from the furnace through the evaporator coil only. Use dampers or other means to bypass the heat exchanger. If (summer/winter) dampers are used, they should be interlocked to prevent system operation unless the dampers are in the full open or full closed position.
NOTE
If installing a two stage air conditioning system, clip the JW38 jumper wire between Y and Y2 on the furnace control board.
W415-1064 / 11.11.11
5.0 COMBUSTIBLE CLEARANCES
Figure 1, Table B provides the certifi ed clearances to combustibles and dimensional information. Also see the appliance rating plate affi xed to the furnace for specifi c model number, serial number and clearance to combustibles information.
IMPORTANT: THIS FURNACE REQUIRES A MINIMUM OF 24” OF FRONT CLEARANCE FOR SERVICE PURPOSES. FOR THIS PURPOSE, SERVICE CLEARANCE TAKES PRECEDENCE OVER CLEARANCE TO COMBUSTIBLES.
13
WARNING
THIS FURNACE IS CERTIFIED FOR INSTALLATION ON COMBUSTIBLE FLOORS. THIS
SHALL BE INTERPRETED AS A WOOD FLOOR ONLY.
THE FURNACE MUST NOT BE INSTALLED DIRECTLY ON CARPETING, OR OTHER
COMBUSTIBLE MATERIAL EXCEPT WOOD.
INSTALLATION ON COMBUSTIBLE MATERIAL CAN RESULT IN FIRE, CAUSING PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.
THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL
COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS
AND LIQUIDS.
THE HOMEOWNER SHOULD BE CAUTIONED THAT THE FURNACE AREA MUST NOT BE
USED AS A CLOSET OR FOR ANY OTHER STORAGE PURPOSE.
! !
W415-1064 / 11.11.11
14
6.0 DUCTWORK
Proper airfl ow is required for the correct operation of this furnace. Insuffi cient airfl ow may cause erratic operation, could cause the furnace to cycle on the high temperature limit, and may damage the heat exchanger. Excessive airfl ow may result in an excessively noisy duct system and may result in undesirable consequences such as creating uncomfortable drafts.
If air conditioning is to be used with the furnace, the duct system must be capable of delivering the correct amount of airfl ow for each system.
The ductwork should be sized and constructed in accordance with accepted industry standards. Duct sizing and construction information may be obtained from:
A.C.C.A. (Air Conditioning Contractors of America)
A.S.H.R.A.E. (American Society of Heating, Refrigeration and Air Conditioning Engineers
H.R.A.I. (Heating, Refrigerating and Air Conditioning Institute (Canada)
S.M.A.C.N.A. (Sheet Metal and Air Conditioning Contractors’ National Association (United States)
All of the above professional organizations have duct sizing manuals available.
The total static pressure drop of the air distribution system (including fi lters) should not exceed 1.0” w.c.
!
WARNING
DO NOT ALLOW GAS PIPING TO BE ROUTED THROUGH JOIST SPACES THAT ARE
USED FOR RETURN AIR PURPOSES. DO NOT USE JOIST SPACES FOR RETURN AIR
PURPOSES IF THE JOIST SPACE ALREADY CONTAINS PLUMBING STACKS, CHIMNEY
COMPONENTS, ETC. UNLESS THE PORTION USED FOR RETURN AIR PURPOSES CAN
BE COMPLETELY ISOLATED FROM PORTIONS WITH OTHER USAGES.
NEVER ALLOW THE PRODUCTS OF COMBUSTION FROM THE FLUE TO ENTER THE
RETURN AIR OR SUPPLY AIR DUCTWORK.
ALL RETURN AIR DUCTWORK MUST BE ADEQUATELY SEALED AND SECURED TO
THE FURNACE WITH SHEET METAL SCREWS. TAPE THE SHEET METAL SEAMS IN THE
VICINITY OF THE FURNACE WITH DUCT TAPE OR SIMILAR MATERIAL.
WHEN THE FURNACE IS MOUNTED ON A PLATFORM WITH RETURN AIR THROUGH THE
BOTTOM, IT MUST BE SEALED AIR TIGHT BETWEEN THE FURNACE AND THE RETURN
AIR PLENUM. THE FLOOR OR PLATFORM MUST PROVIDE SOUND PHYSICAL SUPPORT
OF THE FURNACE WITHOUT SAGGING, CRACKS OR GAPS AROUND THE BASE,
PROVIDING A SEAL BETWEEN THE SUPPORT AND THE BASE.
FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM BEING CIRCULATED INTO
THE LIVING SPACE CAN CREATE POTENTIALLY HAZARDOUS CONDITIONS, INCLUDING
CARBON MONOXIDE POISONING THAT COULD RESULT IN PERSONAL INJURY OR
DEATH.
!
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN OR SUPPLY AIR
DUCTWORK TO OR FROM ANY OTHER HEAT PRODUCING DEVICE SUCH AS A
FIREPLACE INSERT, STOVE, ETC. DOING SO MAY RESULT IN FIRE, CARBON MONOXIDE
POISONING, EXPLOSION, PERSONAL INJURY, LOSS OF LIFE, OR PROPERTY DAMAGE.
W415-1064 / 11.11.11
6.1 DUCTWORK STEPS
1. Position the furnace to minimize ductwork length and fi ttings.
2. Cut open a return air inlet. The choices are furnace bottom, either side, or any combination thereof (i.e., two sides or a side and the bottom).In all cases, cut the return air opening the full width of the return air markers on the side panel.
15
!
WARNING
!
DO NOT USE THE REAR PANEL AS A RETURN AIR INLET. THERE IS INSUFFICIENT
ROOM TO PERMIT ADEQUATE AIRFLOW.
3. Connect the return air duct or fi lter fi tting to the furnace. The connection should be sealed air tight to prevent entraining combustion gases from an adjacent fuel burning appliance, or entraining combustion air for this furnace or adjacent fuel burning appliances.
4. Ensure that there is adequate space and accessibility for air fi lter removal.
NOTE: If two return air inlets are used, both must be equipped with fi lters.
5. If an air conditioning evaporator coil is required, position it on the supply air side of the furnace. Ensure that no air can bypass the evaporator coil.
6. Connect the supply air plenum to the supply air outlet.
FLEXIBLE DUCT CONNECTORS are an effective device to prevent the telegraphing of mechanical noise from the furnace to other parts of the home via the ductwork. If using fl exible connectors, ensure that the adjoining duct is independently supported.
W415-1064 / 11.11.11
16
7.0 VENTING AND COMBUSTION PIPING
!
WARNING
READ, UNDERSTAND AND FOLLOW ALL INSTRUCTIONS IN THIS SECTION. FAILURE TO
PROPERLY VENT OR SUPPLY COMBUSTION AIR TO THIS FURNACE CAN CAUSE CAR-
BON MONOXIDE POISONING, OR AN EXPLOSION OR FIRE, RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
7.1 ACCEPTABLE MATERIALS IN CANADA
Effective August 1, 2007, all vent piping materials and fi ttings for fl ue gas venting must be ULC S636 listed and identifi ed as such on the material. The fi rst 3ft. (900mm) of venting must be readily available for visual inspection. Specifi ed primers and glues of the certifi ed vent system must be from a single system manufacture, and not intermixed with other system manufacture’s vent system parts. The components of the certifi ed vent system must not be interchanged with other vent systems, or unlisted pipe, and or fi ttings. Follow the venting manufacturers instructions on installation, cutting, de-burring, cementing, curing and supporting of the venting system.
This furnace must be vented with ULC S636 certifi ed PVC (Poly Vinyl Chloride) or PPE (Polypropolene) material with a minimum rating of 149°F (65º C) or more.
The combustion air piping does not have fl ue gases traveling through it and may be installed with common ABS, PVC or CPVC piping or fi ttings. This piping, fi ttings, primer and cement will need to be installed as per the manufacturers instructions including cementing, cutting, curing and supporting the piping.
!
7.2 ACCEPTABLE MATERIALS IN UNITED STATES
For United States installations, the combustion air and vent piping and fi ttings may be comprised of:
Schedule 40 PVC, ASTM D1785 or CSA B137.3
PVC-DWV, ASTM D2665 or CSA B181.2
Schedule 40 CPVC, ASTM F441 or CSA B137.6
PVC PRIMER AND SOLVENT CEMENT: ASTM D2564
Follow piping manufacturers instructions on proper installation of piping and fi ttings including cutting, deburring, priming, cementing, curing and supporting.
W415-1064 / 11.11.11
8.0 NON-DIRECT VENT FURNACE INSTALLATIONS USING INDOOR COMBUSTION AIR (ONE PIPE SYSTEM)
The furnace, although designed as a direct vent type appliance, may be installed with the intake vent inside the structure.
17
!
WARNING
THIS FURNACE AND ANY OTHER FUEL BURNING APPLIANCE MUST BE PROVIDED WITH ENOUGH FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF THE
FLUE GASES. MOST HOMES WILL REQUIRE THAT OUTSIDE AIR BE BROUGHT TO
THE FURNACE AREA. FAILURE TO DO SO CAN CAUSE PERSONAL INJURY, OR DEATH
FROM CARBON MONOXIDE POISONING.
Adequate provisions for combustion and ventilation air must be in accordance with CAN/CGA-B149 in Canada,
and ANSI Z223.1 - 1992, section 5.3, “Air for Combustion and Ventilation,” in the United States. Check with
local authorities for any additional building codes bylaws or regulations.
!
CAUTION
AIR FOR COMBUSTION AND VENTILATION PURPOSES MUST NOT ORIGINATE FROM A COR-
ROSIVE ATMOSPHERE. ANY FURNACE FAILURE CAUSED BY CORROSIVE ELEMENTS IS
EXCLUDED FROM WARRANTY COVERAGE.
The following types of installation sites (but not limited to the following) will REQUIRE OUTDOOR AIR for combustion because of chemical exposures:
• Commercial buildings
Buildings with indoor swimming pools
Furnaces installed in laundry rooms
Furnaces in hobby or craft rooms
Furnaces installed near chemical storage areas
Exposure to the following substances in the combustion air supply (but not limited to the following) will also require OUTDOOR AIR for combustion:
Aerosols, particularly CFC based or propelled aerosols
• Air fresheners
“Airplane Glue” and similar adhesives and cements
Ammonia, as commonly found in permanent wave solutions used in hair dressing salons
Anti-static fabric softeners used in clothes dryers
Carbon tetrachloride
Chlorinated cleaners and waxes
Chlorine and bromine based swimming pool chemicals
De-icing salts or chemicals (rock salt, etc.)
• Dry cleaning fl uids such as perchloroethylene
Fumes from curing polyurethane and similar substances
Halogen based refrigerants including R-12 and R-22
Hydrochloric acid, muriatic acid and other acid based masonry washing and curing materials
Printer’s inks, paint removers, varnishes, varsol, toluene, etc.
Water softener salt and chemicals
!
!
W415-1064 / 11.11.11
18
Combustion air must be free of acid forming chemicals such as sulphur, fl uorine and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresheners, paint and varnish removers, refrigerants, and many other commercial and household products. When burned in a gas fl ame, vapors from these products form acid compounds. Acid compounds increase the dew point temperature of the ue products and are highly corrosive after they condense.
8.1 DETERMINING COMBUSTION AIR
8.1.1 CASE 1: FURNACE LOCATED IN A UNCONFINED SPACE
Unconfi ned space does not necessarily mean that ventilation will not have to be introduced from the outdoors, particularly in airtight homes. The minimum requirement for unconfi ned space is a volume of 50 cubic feet for each 1000 Btu/hr for all fuel burning appliances located within the unconfi ned area.
If the amount of combustion and ventilation air is insuffi cient to properly operate the furnace and other fuel burning appliances within the unconfi ned area, it will be necessary to supply it from the outdoors based on the criteria used when calculating the air supply for a confi ned space.
NOTE
If planning to use the inside air in an unconfi ned space, remember to test for proper furnace operation (as well as other fuel burning appliances located within the unconfi ned space) with respect to adequate combustion and ventilation air with fi replace dampers open, clothes dryer running, bathroom exhaust fans on, kitchen range hood on, etc.
8.1.2 CASE 2: FURNACE LOCATED IN A CONFINED SPACE
A confi ned space, (any space smaller than the minimums discussed in Case 1), must have two air openings; one within 12” of the ceiling and the other within 12” of the fl oor. The air openings must be sized based on whether the combustion and ventilation air is being taken from indoors or outdoors, the method outdoor air (if used) is introduced, and taking into account any other fuel burning appliances in the confi ned space.
If suffi cient indoor combustion and ventilation air is available for the furnace and all other fuel burning
appliances, size each opening on the basis of one square inch of free area per 1000 Btu/hr. (Figure 4)
NOTE
Be sure to consider all clothes dryers, bathroom fans, range hoods, etc., when making this calculation.
The minimum requirement for these openings is 100 square inches, even for the furnace models under 100,000 Btu/hr.
NOTE
If using grills to cover the two openings, factor in the free area of the grill. Typically, a sidewall grill will have a free area approximately 50% of its nominal size. Consequently, if the required opening is 10 x 10, it will have to be doubled if using a sidewall grill with 50% free area.
FIGURE 4 - COMBUSTION/DILUTION AIR FROM
HEATED INSIDE SOURCES (CASE 2)
W415-1064 / 11.11.11
19
IMPORTANT:
IF AN EXHAUST FAN, FIREPLACE, CLOTHES DRYER OR ANY SIMILAR DEVICE IS PRESENT IN THE INDOOR AREA FROM WHICH THE COMBUSTION AND VENTILATION AIR WILL BE DRAWN, NEGATIVE PRESSURE COULD BE A PROBLEM IF NATURAL INFILTRATION FROM THE OUTDOORS DOES NOT MATCH THE RATE AT WHICH AIR IS EXHAUSTED.
8.1.3 CASE 3: FURNACE LOCATED IN A CONFINED SPACE, OUTDOOR AIR FROM ATTIC OR CRAWL SPACE
In this circumstance, the free area of each of the two combustion and ventilation air openings is based on a minimum of 1 square inch per 4000 Btu/hr. In this confi guration, one opening can originate from the fl oor drawing combustion and ventilation air from the ventilated crawl space.
The other opening may communicate freely with a ventilated the attic. If using the attic air, ensure that the opening is ducted from the ceiling high enough to be above the insulation. The attic must be adequately
vented with soffi t vents or gable vents (Figure 5).
As an alternative to creating an opening in the fl oor to draw air from a crawl space, a duct may be dropped from the attic terminating 12” above the fl oor.
The following table shows minimum free areas and round pipe sizes when drawing combustion air vertically from the attic or crawl space for the furnace only. If other fuel burning appliances are present, their combustion air and ventilation air requirements must be added to those of the furnace.
FIGURE 5 - OUTSIDE AIR FOR COMBUSTION, ATTIC OR
CRAWL SPACE (CASE 3)
TABLE 2 - VERTICAL AIR SUPPLY (CASE 3)
Input Free Area
K/Btu/hr Ea. Opening
60 15 in. ² 5 in.
80 20 in. ² 6 in.
100 25 in. ² 6 in.
120 30 in. ² 7 in.
IMPORTANT:
Round Pipe Size
IF THE ATTIC HAS AN EXHAUST FAN (POWER VENT), IT MAY CREATE A NEGATIVE PRESSURE SUFFICIENTLY LARGE ENOUGH TO PREVENT THE ATTIC FROM BEING AN EFFECTIVE SOURCE OF COMBUSTION AND VENTILATION AIR. POWERED ATTIC FANS DO NOT CUSTOMARILY RUN DURING THE HEATING SEASON; HOWEVER, SOME ARE CONTROLLED BY A HUMIDISTAT AS WELL AS A THERMOSTAT, WHICH MAY ALLOW SOME OPERATION DURING THE HEATING SEASON. THE CHOICES ARE (A) USE THE DIRECT VENT OPTION; (B) OBTAIN OUTDOOR AIR FROM ELSEWHERE; OR (C) INTERLOCK THE ATTIC EXHAUST FAN WITH THE FURNACE SUCH THAT THE TWO CANNOT OPERATE SIMULTANEOUSLY.
W415-1064 / 11.11.11
20
8.1.4 CASE 4: FURNACE LOCATED IN A CONFINED SPACE, OUTDOOR AIR DUCTED HORIZONTALLY
Similar to Case 3, outdoor air for combustion and ventilation may be drawn through horizontal ducting. The free area for each opening is calculated on the basis of a minimum of 1 square inch per 2000 Btu/hr input.
The following table shows minimum free areas and round pipe sizes when drawing combustion air horizontally from the outdoors for the furnace only. If other fuel burning appliances are present, their combustion air and ventilation air requirements must be added to those of the furnace.
FIGURE 6 - OUTDOOR AIR FOR COMBUSTION,
HORIZONTAL (CASE 4)
TABLE 3 - HORIZONTAL AIR SUPPLY (CASE 4)
Input Free Area
K/Btu/hr Ea. Opening
60 30 in. ² 7 in.
80 40 in. ² 8 in.
100 50 in. ² 8 in.
120 60 in. ² 9 in.
IMPORTANT:
Round Pipe Size
THE OUTDOOR GRILLS MUST BE INSTALLED IN A LOCATION WHERE THE
Y WILL NOT BE OBSTRUCTED IN
ANY MANNER.
IMPORTANT:
IF GRILLS ARE USED ON THE OUTSIDE WALL, THEY MUST BE SIZED PROPERLY. MOST SIDEWALL GRILLS HAVE ONLY 50% FREE AREA. IN THE CASE OF A UNIT WITH 100,000 BTU/HR INPUT, WHICH REQUIRES A PAIR OF 8” ROUND PIPES TO OBTAIN SUFFICIENT COMBUSTION AND VENTILATION AIR, THE DUCT COULD BE AN EQUIVALENT RECTANGULAR DUCT; 8” X 7” FOR EXAMPLE. BASED ON 50% FREE AREA FOR THE INLET GRILLS, THE ACTUAL GRILL SIZE WOULD HAVE TO BE 14” X 8” OR ITS EQUIVALENT. A TRANSITION MAY BE USED TO REDUCE TO THE SMALLER DUCT SIZE IF NECESSARY.
8.1.5 CONNECTION TO FURNACE NON-DIRECT VENT
IMPORTANT: WHEN USING INDOOR AIR OR THE NON-DIRECT VENT CONFIGURATION, THE COMBUSTION AIR INLET TO THE FURNACE MUST BE PROTECTED FROM BLOCKAGE. USE A DOUBLE ELBOW ARRANGEMENT IF SUPPLYING COMBUSTION AIR THROUGH THE TOP, OR A DOWNWARD POINTING SINGLE ELBOW IF SUPPLYING COMBUSTION
AIR THROUGH THE SIDE. (FIGURE 7)
W415-1064 / 11.11.11
FIGURE 7 - NON-DIRECT
COMBUSTION AIR INLET
9.0 VENTING GUIDELINES
21
!
CAUTION
FAILURE TO FOLLOW ALL VENTING GUIDELINES MAY RESULT IN ERRATIC FURNACE
OPERATION, FREEZE-UP OF THE EXHAUST AIR PIPING, OR SOOTING OF THE FURNACE.
!
WARNING
READ AND FOLLOW ALL INSTRUCTIONS IN THIS SECTION. FAILURE TO PROPERLY VENT THIS
FURNACE CAN CAUSE CARBON MONOXIDE POISONING OR AN EXPLOSION OR FIRE RESULTING
IN PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
NOTE
• Combustion air intake and exhaust termination should be inspected periodically to ensure they are clear of obstructions. i.e. vegetation, debris, snow, etc.
• Accumulation of snow around the combustion air intake and exhaust termination may have negative effects
on appliance operation and/or performance. Snow accumulation should be considered when locating combustion air intake and exhaust terminations.
• Venting may be vertical or horizontal.
• Minimum vent length - 15 total equivalent feet. (See Venting Table)
• Horizontal piping must slope back towards the furnace at a minimum rate of ¼” to the foot, so that condensate drains towards the furnace.
• Horizontal runs must be supported at least every 3 feet. Horizontal sections must not dip or sag.
• All vent runs through unconditioned space where freezing might occur should be insulated with 1” thick, medium density, foil-faced Fiberglass insulation. An equivalent “arm-a-fl ex” or “rub-a-tex” may also be used as long as there is no heat tape applied to the vent pipe. For horizontal runs where water may collect, wrap the vent pipe with self regulating 3 or 5 watt heat tape. The heat tape must be CSA, UL, or ULC listed and installed per the manufacturer’s instructions.
• DO NOT COMMON VENT WITH ANY OTHER APPLIANCE.
• If venting vertically, do not vent up a chimney serving another appliance or install in a chase with a metal or high temperature plastic pipe from another gas or fuel burning appliance unless the required clearances to combustibles can be maintained between the furnace venting system and other pipes.
All exhaust piping must be installed in accordance with CAN/CGA-B149.in Canada; the latest edition of National Fuel Gas Code, NFPA 54 / ANSI Z223.1 in the United States, as well as in accordance with local codes.
Size the combustion air and exhaust piping in accordance with Table 4. When calculating allowable vent lengths, be sure to count all termination fi ttings in addition to counting the concentric vent as a straight pipe.
Take the building orientation and the presence of other buildings or other nearby structures into consideration when planning the venting system location. Certain external structures could create air turbulence around the vent termination leading to downdrafts and similar venting problems. In windy and hill locations, roof venting may improve operations. Maximum venting length is based on 30 mph winds, areas where higher gusts are dominant it is suggest to shorten the horizontal vent length.
The vent and combustion air intake shall be installed so that both are located in the same wind pressure zone.
!
!
W415-1064 / 11.11.11
22
FIGURE 8 - STANDARD (STRAIGHT) HORIZONTAL
VENT DETAIL
RECOMMENDED
*
*18” MIN. FOR COLD CLIMATES (SUSTAINED 0°F (-17°C) FOR 24 OR MORE CONSECUTIVE HOURS
DO NOT CONNECT FURNACE TO A CHIMNEY OR FLUE SERVING OTHER APPLIANCES OR A
9.1 VENT TERMINATION
Horizontal vents should pass through the exterior wall. Figure 8 shows a standard horizontal vent detail. Terminate the vent approximately 8” or more from the wall.
Exterior vent pipe greater than 24” should be insulated with ½” insulation to prevent moisture from freezing within the pipe and accumulating.
Size the exhaust pipe as specifi ed in
Table 4 - Direct and Non-Direct Vent Lengths. This table lists the maximum
allowable length of pipe with respect to the number of 90° elbows used. For the purposes of this calculation, one 90° elbow is equivalent to two 45° elbows.
Avoid locating the terminal in locations where dripping condensate may cause problems such as sidewalks, patios, above planters, near windows where exhaust gases may cause fogging, etc. Avoid locating the termination too close to shrubs and other vegetation. The condensate may stunt or kill them.
!
WARNING
!
SOLID FUEL BURNING APPLIANCE.
TABLE 4 - DIRECT AND NON-DIRECT VENT LENGTHS
Maximum Allowable Length Of Exhaust Or Intake. Minimum Vent Length 15 ft. or equivalent.
INPUT
K/Btu/hr
100
120 3 100 95 90 85 80 75 70
NOTE
When 1½” or 3” pipe is used, exit the cabinet with 2” pipe. Reduce or increase immediately after exiting the cabinet on both intake and exhaust.
60
80
PIPE SIZE
60 55 50 45 40 35 30
275706560555045
3 100 95 90 85 80 75 70
250454035302520
3 100 95 90 85 80 75 70
250454035302520
3 100 95 90 85 80 75 70
NUMBER OF 90° ELBOWS
0123456
NOTES
1. Count concentric vent tting as straight pipe.
2. Use medium or long sweep elbows where possible.
3. One 90° elbow is equivalent to two 45° elbows.
4. For direct vent, the listed lengths are allowed for each vent (intake and exhaust).
5. For non-direct vent, the listed lengths are al­lowed for exhaust. The intake should have a 1½” or 2” snorkel intake tting. (Figure 7)
W415-1064 / 11.11.11
Loading...
+ 50 hidden pages