Napco Security Technologies WI1501A User Manual

INSTALLATION
R
INSTRUCTIONS
FREEDOM F-64
CONTROL PANEL/COMMUNICATOR
For use with the Freedom F-64TP Wireless Touchpad, F-64TPG Garage Door Touchpad, the F-64TPBR
Bedroom Touchpad, F-64TP-H Hardwire Touchpad and the F-64PROG Stay/Away Programmer
SYSTEM READY 10/03/06 12:03 AM
Freedom F-64TP Touchpad
F-64PROG Programmer
© NAPCO 2006 WI1501A 9/06
THIS MANUAL INCLUDES FEATURES WHICH ARE ONLY AVAILABLE IN THE FREEDOM F-64
CONTROL PANEL FIRMWARE VERSION 30 OR LATER.
IMPORTANT NOTICE
F-64 panel version 30 requires the use of the following version programmer:
F-64PROG Version 01
Upon entering program mode, the LCD window will flash the control panel firmware version, followed by the pro­grammer firmware version:
F-64PROG : [3001]
If Gemini keypads are installed in the system (in addition to the required Freedom F-64TP or F-64TP-H Touch­pads), the following version keypads must be used:
GEM-K1CA Version 9B
GEM-K2AS, Version 7
GEM-K3DGTL, Version 3
GEM-K4/K4RF, Version 2
Differences between the GEM-P1664 and the Freedom F-64 Control Panels:
The GEM-P1664 control panel and the Freedom F-64 V30 control panel are identical, except for the following:
The "Classic" Gemini RP-Series keypads cannot be used with the Freedom F-64 V30 control panel.
The Perimeter Group Bypass zone feature is exclusive to the Freedom F-64 V30 control panel.
Refer to accompanying F-64 Programming Instructions (WI1502) for programming information.
NAPCO Security Systems, Inc.
333 Bayview Avenue, Amityville, New York 11701
For Sales and Repairs, call toll free: (800) 645-9445
For direct line to Technical Service, call toll free: (800) 645-9440
Internet: http://www.napcosecurity.com
WI1501A 9/06
Page 3
TABLE OF CONTENTS
INTRODUCTION ....................................................................................................................................................................... 4
General Description ................................................................................................................................................................... 4
Features .................................................................................................................................................................................... 4
Specifications ............................................................................................................................................................................5
Ordering Information ..................................................................................................................................................................6
Summary of UL Requirements .................................................................................................................................................. 7
INSTALLATION ........................................................................................................................................................................ 8
Mounting ................................................................................................................................................................................... 8
Wiring ........................................................................................................................................................................................ 9
Wireless Systems ...................................................................................................................................................................... 9
Typical Residential Fire Installation ...........................................................................................................................................9
Typical Partitioned Installation ................................................................................................................................................... 9
TESTING THE SYSTEM ......................................................................................................................................................... 10
WIRING CONNECTIONS ........................................................................................................................................................ 11
Battery ..................................................................................................................................................................................... 11
Transformer ............................................................................................................................................................................. 11
Siren/Bell Output ..................................................................................................................................................................... 11
Auxiliary Power ........................................................................................................................................................................ 11
PGM Outputs .......................................................................................................................................................................... 11
Remote Bus ............................................................................................................................................................................ 12
Earth Ground ........................................................................................................................................................................... 12
Zone Configuration Styles ....................................................................................................................................................... 13
Basic Zone Configuration ...................................................................................................................................................13
EZ Zone Doubling Configuration ........................................................................................................................................13
4-Wire Smoke Detectors ......................................................................................................................................................... 14
2-Wire Smoke Detectors ......................................................................................................................................................... 14
Telephone Lines ...................................................................................................................................................................... 15
KEYPAD / TOUCHPAD MESSAGES ..................................................................................................................................... 16
GLOSSARY .......................................................................................................................................................................17-35
STANDBY-BATTERY CALCULATION WORKSHEET ........................................................................................................... 36
WIRING LEGEND ...................................................................................................................................................................37
CP-01 QUICK REFERENCE CHART ......................................................................................................................................38
FACTORY DEFAULT DESCRIPTION .................................................................................................................................... 40
FCC STATEMENT .................................................................................................................................................................. 42
F-64 WIRING DIAGRAM ......................................................................................................................................................... 43
LIMITED WARRANTY ............................................................................................................................................................ 44
L NAPCO Security Systems
Freedom F-64 Installation Instructions
Page 4
WI1501A 9/06
INTRODUCTION
GENERAL DESCRIPTION
Napco's Freedom F-64 is a state-of-the-art microcomputer-based burglary and residential fire alarm control panel of modular design. Integrally an 8-zone panel, it will support up to 64 zones with the use of zone doubling, optional zone expansion modules, wireless receiver modules and/or Freedom 64 Touchpads. Each panel includes an integral digital communicator. The F-64 panel operates with the NAPCO Freedom 64 Touchpads, providing a complete Deadbolt-Activated Home Protection System that combines intuitive interactive arming with passive disarming. The Touchpads provide a system which is not only effortless to use, but also 100% false alarm resistant during the critical arming and disarming sequences. See WI1499 for more information about the Freedom Touchpads.
The control panel features programmable area partitioning. That is, the system may be divided into up to 4 discrete multiple­zone areas, each allowing access by only those users programmed for their respective area.
Opening Suppression and Closing Suppression, available through Napco Quickloader software, suppress reporting within programmed “windows”. Conversely, Exception Reporting can transmit a “fail to close” if the panel is not armed within programmed intervals and, similarly, a “fail to open” if the panel is not disarmed within programmed intervals. Furthermore, the panel can be programmed to automatically arm either area at any time. A log containing up to 400 events (accessible through Quickloader be displayed at the computer, using Napco’s PCD-Windows Quickloader Software.
Touchpads feature a liquid-crystal display for messages. In normal use, the LCD shows zone identification and status messages, and the log can also be viewed. Conventional LEDs and a sounder are also provided for annunciation.
Data may be quickly and easily downloaded to the control panel using a PC-compatible computer with Napco's PCD-Windows Quickloader software and PCI2000 computer interface. Or, the panel may be programmed using the F-64PROG program­mer. In the programming modes (there are two: Dealer and User), the LCD shows memory address, data values, programming prompts, and the alphanumeric characters required for entering up to 64 user codes and custom zone descriptions. NOTE: Failure to install and program as described in this manual for UL Listed systems voids the Listing Mark of Underwriters Laboratories, Inc.
TM
software) monitors control-panel activity referenced to a precision real-time clock. A detailed event history may
FEATURES
Control Panel Features
Features
Eight end-of-line-resistor burglary zones programmable
for Area (expandable to sixteen end-of-line resistors with zone doubling or series zone doubling with loop supervi­sion), Exit/Entry Delay, Interior (Stay) Bypass, Exit/Entry Follower, Day Zone, Chime, Fire options, Swinger Shutdown, Zone Anding and a variety of other features.
Supports up to 64 zones with optional zone-expansion
modules, wireless receiver modules and 4-zone Touch­pads.
Supports up to 64 individually coded users. Supports three outputs (Bell, PGM1 and PGM2) and up to
16 external outputs (using Relay Module RB3008, RM3008 or the GEM-OUT8. See Relay Control in glos- sary for more information).
Supports three Touchpad panics: Fire, Police & Auxiliary. Supports four independent area partitions. Supports up to seven separate access stations
(Touchpads) by up to 64 users.
Supports up to 16 separately-addressable X-10 devices
with the GEM-X10 KIT and PC04 interfaces.
English-language prompts & system status messages. User Codes and Zone Descriptions outside assigned ar-
eas are able to be blocked from Touchpad display.
User-customized zone descriptions, re-programmable as
required.
Supports 2-wire and 4-wire smoke detectors. Reports alarms, restores and troubles by zone. 400 Event Log. Two programmable entry delay times.
One Interior Zone Group. Dynamic battery test interrupts charging and places
battery under load every four hours.
Two Chimes by zone; programmable duration. Quickloader programmable. 2 PGM outputs. Supports Gemini Wireless Devices.
Communicator Features
Compatible with all major receiver formats, including 4/2,
SIA and Point ID (except Radionics Modem II).
Rotary dial and TouchTone
TM
with Rotary backup.
Three 20-digit telephone numbers. Backup Reporting; Double Reporting; Split Reporting. 64 User Codes with Opening/Closing -Reporting by user. AC Failure Reporting with programmable report delay. Supervised telephone line with a fixed 60 second delay. Pager capability.
F-64PROG Programmer Features
English-language LCD display; LED and sounder
annunciators.
Fault-Find diagnostics simplify troubleshooting.
SIA CP-01 Features.
See page 38 for complete information regarding how the
Factory Program complies with the Security Industry As­sociation False Alarm Reduction Control Panel-01 Stan­dard (SIA FAR CP-01).
Freedom F-64 Installation Instructions
L NAPCO Security Systems
WI1501A 9/06
Page 5
SPECIFICATIONS
Freedom F-64 Control Panel
O
perating Temperature: 0-49°C (32-120°F) Input Power: 16.5-18.0 VAC via CLASS 2 Plug-In 20VA, 40VA or 50VA Transformer Loop Voltage: 10-13Vdc Loop Current: 3mA without Zone Doubling, 2.4mA with Zone Doubling using a 2.2K Ohm end-of-line resistor (Model EOL2.2K);
5mA for 2-wire smoke-detector zones; 1.4 mA using a 3.9K Ohm resistor (Model EOL3.9K) with Zone Doubling; 3mA with Se­ries Zone with Loop Supervision and 3mA with Series Zone Doubling with Loop Supervision
Loop Resistance: 300 Ohm max.; 50 Ohm for 2-wire smoke-detector zones
Alarm Voltage Output: 1 Programmable Negative Outputs: 2 Auxiliary Power Output: 11.7-12.5 VDC Remote Power Output: 12 VDC regulated (for the F-64PROG programmer) Combined Standby Current (Remote Power + Aux. Power + Fire Power): See following charts.
16.5VAC
TRANSFORMER
40VA/50VA 7 AH 550 mA 450 mA
20VA* 7 AH 500 mA 2.0 A 4 Hours
20VA* 7 AH 500 mA 2.0 A 6 Hours
16.5VAC
TRANSFORMER
40VA/50VA 7 AH 120 mA
40VA/50VA * Two 7 AH 360 mA
20VA * 7 AH 120 mA
20VA * Two 7 AH 360 mA
(1)
NOTE:
Alarm current can be increased by reducing standby current by the same amount.
RESIDENTIAL BURGLARY & COMMERCIAL BURGLARY**
BATTERY
(12 VDC)
COMBINATION RESIDENTIAL FIRE & RESIDENTIAL BURGLARY
BATTERY
(12 VDC)
STANDBY CURRENT
STANDBY CURRENT
ALARM
CURRENT
(1)
ALARM
CURRENT
(1)
520 mA
(1)
280 mA
(1)
360 mA
(1)
120 mA
* Not evaluated by UL.
** Commercial Burglary specifications not evaluated by UL.
STANDBY
TIME
4 Hours
STANDBY
TIME
24 Hours
24 Hours
24 Hours
24 Hours
Specifications
FOR ALL UL INSTALLATIONS
The feature "Enable Residential Fire" (address 1422, option 4) must be programmed for ALL UL installations.
"DISABLE SYSTEM TROUBLE AUDIBLE TIMEOUT" (ADDRESS 2051) MUST BE PROGRAMMED
The feature "Disable System Trouble Audible Timeout" (address 2051, option 7) must be programmed for ALL UL installations.
To program, please refer to the F-64 Programming Instructions (WI1502) for further information.
L NAPCO Security Systems
"ENABLE RESIDENTIAL FIRE" (ADDRESS 1422) MUST BE PROGRAMMED
EZM Module: GEM-EZM4/8: Input, 50mA Keypad Current: See keypad Installation Instructions. Maximum Number of Keypads / Touchpads: 7 Maximum Wiring Length for each run (#22AWG): 1000' divided by total number of keypads /
Touchpads and EZMs on run
Keypad Dimensions: 4” x 5” x 1” (HWD); 11.1cm x 14.9cm x 2.7cm (HWD)
Freedom F-64 Installation Instructions
Page 6
WI1501A 9/06
ORDERING INFORMATION
System Components
F-64: Residential UL-Listed Burg and Fire Control Panel F-64PROG: 32-Character LCD Burg & Fire Programmer F-64TP: Wireless Touchpad F-64TPG Garage Door Touchpad* F-64TPBR Bedroom Touchpad F-64TP-H Hardwired Touchpad*
Optional Accessories and Peripherals
GEM-EZM8: 8 Zone Expansion Zone Module GEM-EZM4/8: 4-16 Zone Expansion Zone Module* GEM-RECV8: Wireless Receiver, 8 Zones GEM-RECV16: Wireless Receiver, 32 Zones GEM-RECV96: Wireless Receiver, 64 Zones GEM-TRANS2: Window/Door Transmitter, 2-Point GEM-RTRANS: Recessed Window/Door Transmitter GEM-KEYF: Keyfob Transmitter GEM-SMK: Wireless Smoke Detector GEM-PIR: Wireless PIR GEM-PIRPET: Wireless Pet Immune Transmitter* GEM-RS232: Isolated Computer Interface GEM-DT: Wireless Dual-Technology Sensor GEM-GB: Wireless Glass-Break Detector* GEM-X10KIT: X-10 Interface* GEM-OUT8: 8 output active low output module F-GDMS: Freedom Garage Door Motor Sensor F-LTRANS: Freedom Wireless Transmitter F-IFOB: Alarm-Silencing Credential I-FOB RM3008: Relay Module (in enclosure)
Ordering Information
M278: Line-Reversal Module PS3002: Power-Supply Module, 13.2Vdc, 1.9A* EOL2.2K: End-of-Line Resistor Assy., 2.2k Ohm EOL3.9K: End-of-Line Resistor Assy., 3.9k Ohm for
Zone Doubling*
EOL4.7K: End-of-Line Resistor Assy., 4.7k Ohm* FT2200: End-of-Line Relay/Resistor Supervisory Module RB1000: Relay Board, single output* RBATH1: Dual Battery Harness* RPB-3: Universal Keypad Mounting Box* TRF11: Transformer, 16.5Vac/40VA, Class 2* TRF14: Transformer, 16.5Vac/50VA, Class 2 WL1: Wire Assembly with Lug Connector, 20” * VERI-PHONE: Two-Way Voice/Listen-In Module* PCD-Windows: Downloading Software (for Windows)
for IBM PC-Compatible, V5.0 or greater
PCI2000/3000: Software Interface for IBM PC-
Compatible Computer*
PCI-MINI: Notebook Computer Interface*
W834-1: Keypad Cable, plug-in (20”)* OI318: User Guide, Freedom F-64TP Touchpad OI319: User Guide, F-64TPBR Bedroom Touchpad OI320: User Guide F-64TPG Garage Touchpad WI1501: F-64 Installation Instructions WI1502: F-64 Programming Instructions (using the F-
64PROG programmer).
WI1499: Wireless F-64TP Mounting Instructions WI1508: F-64TPG Garage Touchpad Installation In-
structions
WI1505: F-64TPBR Installation Instructions WI1452: Freedom Garage Door Motor Sensor Installa-
tion Instructions
WI1438: Freedom F-LTRANS Wireless Transmitter In-
stallation Instructions
WIZARD IIe: Telephone Interface Module*
UL Listings
Household Burglar Alarm System Units: UL1023 Household Fire Warning System Units: UL985 Security Industry Association (SIA) False Alarm Reduc-
tion Standard CP-01
Napco Group Europe Ltd.
Libra Wireless Transmitters and Receivers for connec­tion to Napco Intruder Control Panels (Operates on 433MHz, European Approved Frequency)
WI925: LIBRA-RECVXP-433 Wireless 8 Zone Receiver WI924: LIBRA-RECV8-433, LIBRA-REC16433, LIBRA-
REC96433, Wireless 8/16/96 Zone Receiver WI923: LIBRA-TRANS433, Wireless Door Contact WI929: LIBRA-PIR433, Wireless PIR WI931: LIBRA-KEYF433, Wireless Keyfob WI930: LIBRA-SMK433, Wireless Smoke Detector WI928: LIBRA-GB433, Wireless Glass Break Sensor
*Not Investigated by UL ** Pending
Freedom F-64 Installation Instructions
L NAPCO Security Systems
WI1501A 9/06
Page 7
Smoke Detectors, 4-Wire:
1. ESL 445AT, 445C, 445CT, 445CR, 445CRT
2. Hochiki America SLG-12 with YBC-RL4-RA Base
3. System Sensor 2312/24T; 1412; 1412TH; 2412TH
Subtract total smoke-detector alarm current from available standby current.
Note: Any normally-open devices that do not require power from the control panel, such as pull stations and thermostats may be used if acceptable to the Authority having Jurisdiction.
UL Compatible Smoke Detectors (Providing UL Recognition or Listing)
Manufacturer 4-Wire
Smoke Detector
Napco FW-4 FW-2
Sentrol
System Sensor
449AT 449C 449CRT 449CST 449CSRT 449CSRH 449CSST
1112 2112
449CLT 449CSLT 449CTE 741U 742U
2112T 2112TSRB
712U 722U 732U 711U 721U 721UT
2100 2100T
2-Wire
Smoke Detector *
731U
1100
Smoke Detector
Base
701U 702U 702RE 702RU
Smoke Detectors & Summary of UL Requirements
Note: * Voltage Rating: 8.5-13.3 VDC, Maximum Number of Detectors: 10
UL Compatible Sounding Appliance:
Wheelock AH-12WP
SUMMARY OF UL REQUIREMENTS
Residential
Recognized Limited-Energy Cable for initiating, indicating and supplementary circuits. FT2200 End-of-Line Relay for Fire (if using 4-wire smoke detectors) Minimum alarm timeout of 5 minutes Maximum exit time: 60 seconds Maximum entry time: 45 seconds Do not program “Swinger Shutdown”, “Auto-Bypass” or “50 ms Loop Response” “Abort Delay” may not exceed 45 seconds Program “Disable Callback Download” Automatic dialer may not dial a police station number that has not been dedicated for such service System must be tested at least weekly under AC/battery and Battery-Only conditions Replace the rechargeable battery at least every 5 years If the battery is heavily discharged, replace it or have it tested by a qualified technician For silent panic, connect only to UL-listed holdup devices All zones must be programmed for “Priority” Do not program any zones for “Keyswitch Arming” System must be serviced at least once every year Residential Fire and Combination Residential Fire & Burglary must program “Residential Fire” Touchpad / Keypad Expansion (EZM) Zones are not to be used as fire zones Touchpad / Keypad Auxiliary is not to be selected The Freedom F-64 series Touchpads must have labels placed on only the appropriate Touchpad keys (Fire, Police and
Auxiliary) that are operational
 Install in accordance with the NEC/CEC requirements  "Force Arm" and "Selective Bypass" must not be programmed for UL installations
L NAPCO Security Systems
Freedom F-64 Installation Instructions
Page 8
WI1501A 9/06
INSTALLATION
CAUTION: This equipment generates and uses radio-frequency energy. If not installed using conventional installation practices for RF devices, it may cause interference to radio and television reception. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference. However, there is no guarantee that interference will not occur in a particular installation. If it has been found to cause interference to radio or television reception, which can be determined by removing and reapplying AC and battery power to the equipment, the installer should try to correct the interference by one or more of the following measures: reorient the receiving antenna; connect the power transformer to a different outlet so that the control panel and receiver are on different branch circuits; relocate the control panel with respect to the receiver.
MOUNTING
Control Panel
Choose a mounting location accessible to (a) a continuously-powered AC source, (b) system ground, a steel or copper ground rod, ideally no further away than 10 feet, and (c) telephone lines (keep telephone wiring away from keypad / Touchpad wires). Remove appropriate knockouts for cables. Place the control panel at a convenient viewing height and mark the mounting holes. Attach the enclosure using screws suitable for the mounting surface.
Grounding
Connect the control-panel grounding screw to a metal cold-water pipe or a long steel (or copper) ground rod driven deeply into the earth. Do not use a gas pipe, plastic pipe or AC ground connections. Use at least 16-gauge wire. Make the run as short and direct as possible, without any sharp bends in the wire.
F-64PROG Programmer
Mounting
For complete programming, the F-64PROG can be used. To simplify programming, the connector used to wire the F­64TPTouchpad to the system buss can also be used with the F-64PROG. To program, first swap the Touchpad for a F-64PROG programmer, then set the panel jumper from "Normal" to "Configuration". See WI1502 for complete panel programming information.
For normal use, a maximum of 4 Touchpads (of any type) and up to 3 additional Gemini "K Series" keypads may be permanently added to the system. Touchpads should be located near each exit/entry door. Before mounting the Touchpad onto the wall, push the Sliding Label Plate (with label and felt backing affixed and handle facing forward) down the guides at the rear of the Touchpad until it snaps into place. Once installed, the Sliding Label Plate cannot be removed without first removing the Touchpad from the wall. Note: (1) The Touchpad fire and panic keys should not be considered a substitute for a listed manual initiating device, such as a pull box. (2) Each Touchpad includes provisions for four additional zones. See ADDING EXPANSION ZONES.
If installing the onto a double-gang box, insert mounting screws through the two vertical elongated holes on the left side of the case and into the box. If the box is visible when viewed from the front, adjust the Touchpad vertically and tighten the screws. Then, using hardware suitable for the mounting surface, add one or two screws at the right side of the Touchpad case directly into the wall to ensure a secure installation. Note: Do not overtighten the screws! Uneven walls may cause the Touchpad case to distort. See WI1499 for more information about installing an F-64TP Touch­pad.
Freedom F-64 Installation Instructions
L NAPCO Security Systems
WI1501A 9/06
Page 9
Wiring
Wire Touchpad(s), zones, expansion zone modules and output devices as shown on the Wiring Diagram. Note that the Wiring Diagram contains important information not available elsewhere in this manual.
CAUTION: Do not run telephone wiring near speaker wires; do not run keypad / Touchpad wiring with loop wiring.
Adding Expansion Zones
The F-64 control panel can support up to 16 zones as is, however this number may be increased to as many as 64 programmable zones using optional expansion zone modules (EZMs).
Wireless Systems
With the addition of at least one GEM-RECV series receiver, the F-64 will support up to 64 wireless transmitters. The panel can accommodate one or two receivers within the premises, responding to the one with the stronger transmitter signal. If any transmitters are selected for the default program, a GEM-RECV receiver will automatically be programmed. The Touchpad can display the status of any transmitter, indicating the condition of the zone (normal or open) and transmitter troubles (low battery, tamper or supervisory failure), and signal strength of the last transmission. A receiver failure will be indicated by “E06-NN” (“no response”, with NN representing the receiver number).
partitions, ceiling beams, doorways, and open joists will require additional detectors. Refer to NFPA Standard No. 74 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269) for additional information, including proper mounting of detectors.
TYPICAL PARTITIONED INSTALLATION
(4 Partitions Available) The system supports (4) areas but only areas 1 and 2
support Touchpads. In addition, Touchpads can only control the area to which they are assigned.
TYPICAL RESIDENTIAL FIRE INSTALLATION (Where permitted by local codes)
At least one smoke detector should be installed directly outside each sleeping area. If there is more than one floor, additional smoke detectors should be installed on each level, including the basement. The living-area and basement smoke detectors should be installed near the stairway of the next upper level. For increased protection, additional detectors should be installed in areas other than those required, such as the dining room, bedrooms, utility room, furnace room, and hallways. Heat detectors, rather than smoke detectors, are recommended in kitchens, attics, and garages due to conditions that may result in false alarms and improper operation. Large areas and areas with
Described and illustrated here are an example of a partitioned
system with common-area protection of the control-panel room. This system meets UL requirements for a partitioned system.
All areas must be owned and managed by the same person(s). All areas must be part of one building at one street address. The control panel and all wiring protecting each partitioned area
must be confined to the respective area and may not impinge upon the other areas. This requires that the control panel room have redundant
protection; that is (a) multiple sets of door contacts, each wired to a separate zone and (b) one of those zones programmed for each area. In order to gain access to this protected area without causing an alarm, both partitions must be disarmed. In lieu of redundant protection, 24-Hour Zones may be used. Any zone protecting the control panel and transformer may not be programmed for bypass.
The sounding device must be placed such that the bell test can be heard by all partitions. Note: NFPA 74
(Household Fire Warning Equipment) requires that a fire alarm audible device be installed indoors.
Program Code is not to be given to anyone except the authority responsible for all partitions.
The User
Wiring
L NAPCO Security Systems
Freedom F-64 Installation Instructions
Page 10
TESTING THE SYSTEM
After installation is completed, test the system as follows.
1. Call the central station to inform them of the test. 2. Initiate an alarm, preferably on a zone that activates a steady siren, and verify proper signalling.
3. Call the central station to confirm their receipt of a good transmission.
Note: Be sure to test all enabled Touchpad panics.
Signal Strength Testing/Wireless Systems
To test the operation of wireless transmitters, proceed as follows.
1. Enter the Fault-Find mode. (See Touchpad Menu Mode in WI1502. Panel must be disarmed). 2. Fault a point of the transmitter to be tested by opening the loop. If the signal strength of the
transmitter is 3 or greater, the Touchpad will beep, as follows:
Signal Power Beeps
0-2 0
3 1 4-5 2 6-7 3
8-10 4
WI1501A 9/06
3. Restore the wireless point (close the loop).
The transmitter signal strength will be displayed on a scale of 3-10 with 3 considered marginal and 10
considered excellent. Note that if the signal strength is less than 3, the Touchpad will not beep and the strength will not be displayed. Except in the Fault-Find mode, signal strengths less than 3 will be entered into the system log. Upon zone restore, the Touchpad will beep once.
Testing the System
Freedom F-64 Installation Instructions
L NAPCO Security Systems
WI1501A 9/06
WIRING CONNECTIONS
BATTERY
7
TRANSFORMER
(The following applies to installations in the United States of America): Connect a 16.5 VAC Transformer to Terminals 1 and 2, using a wire of #18 AWG. or larger at a distance of 15 ft. or less from the control panel. NOTE: Do not connect to a switched outlet.
Page 11
The RED (+) and BLACK (-) flying leads must be connected to a 12VDC 4-7 AH Rechargeable Battery, to serve as backup power in the event of AC Power Failure. NOTE: To calculate the available standby time refer to the Standby­Battery Calculation Worksheet at the back of this manual.
Wiring Connections: Battery, Transformer, Siren Power, Aux. Power & PGM Outputs
SIREN/BELL POWER
AUXILIARY POWER
Connect the auxiliary devices (motion detectors, glass breaks, etc.) to Terminals 5 and 6. Auxiliary Power provides 11.7-12.5 VDC nominal output which is used for powering auxiliary devices. NOTE: To calculate the available standby time refer to the Standby-Battery Calculation Worksheet at the back of this manual.
PGM OUTPUTS (PGM1 & PGM2)
Connect the alarm sounding devices (self-contained sirens, speakers or a mechanical bell) to Terminals 3 and 4. Any self­contained siren requiring a 12 VDC input can be connected. When connecting a mechanical bell, it must be supervised using a 2.2k Ohm resistor. To connect 8 Ohm Speakers use a Siren Driver with the proper polarity observed. NOTE: Refer to the F-64 Panel Wiring Diagram for alarm current specification. Note: In NFPA Household Fire Installations, only a single si­ren or bell can be used on this bell circuit.
PGM1 and PGM2 are negative switched programmable outputs that can be activated depending on the programming options selected (see F-64 Panel Programming Instructions). Connect the device controlled by the programmable output between terminal 5 (+) and the PGM output (-), either terminal 7 or
8. As an example, the connection to the RB1000 Relay Module is shown.
L NAPCO Security Systems
Freedom F-64 Installation Instructions
Page 12
REMOTE BUS
REMOTE BUS
ADDITIONAL
EZMs
(GEM-RP1CAe2)
2 LINE KEYPAD
Example: F-64TP Touchpad
NOTE: Refer to the EZM Installation Instructions for
specific wiring information.
AVAILABLE DEVICES
1. KEYPADS: GEM-RP2AS & GEM-RP1CAe2
2. X-10 INTERFACE: GEM-X10
3. WIRED ZONE EXPANDER: GEM-EZM816
4. WIRELESS RECEIVERS: GEM-RECV8, GEM-RECV16 & GEM-RECV96
5. RELAY MOD ULE: RM3008
6. VO ICE IN TER FAC E: GEM-E VA
7. TELEPHONE INTERFACE: WIZARD2
1. TOUCHPADS / KEYPADS: (3 maximum) F-64PROG: 32-Character LCD Burg & Fire Programmer*, F-64TP: Wireless Touchpad, F-
64TPG Garage Door Touchpad*, F-64TPBR Bedroom Touchpad, F­64TP-H Hardwired Touchpad*
2. X-10 INTERFACE: GEM-X10 (16 devices maximum)*
3. WIRED ZONE EXPANDER: GEM-EZM4/8EX*, GEM-EZM4/8* (64 zones maximum)
4. WIRELESS RECEIVERS: GEM-RECV8, GEM-RECV16, GEM­RECV96 (64 zones maximum)
5. RELAY MODULE: RM3008 (16 relays maximum)
6. VOICE INTERFACE: GEM-EVA 1*
7. TELEPHONE INTERFACE: WIZARD IIe*
AVAILABLE DEVICES
WI1501A 9/06
Connect the available devices as shown above to the remote bus terminals (9, 10, 11 & 12). Observe the correct color wire connections. When connecting the Touchpads, first configure them accordingly (refer to the Touchpad Configuration Mode in WI1502). Up to four Touchpads may be connected if the longest cable run from the panel, to the farthest Touchpad (daisy chained or home-run) is less than 1000 feet. The maximum distance for seven key­pads/Touchpads is 300 feet using 22 AWG. wire. NOTE: When running keypad/Touchpad wire, avoid wiring parallel to other types of wiring.
EARTH GROUND
Wiring Connections: Remote Bus & Earth Ground
Connect the control panel EARTH GROUND screw to a metal cold-water pipe using at least a #16 AWG. wire. Do not use a gas pipe, plastic pipe or AC ground connections. Also, connect the circuit board to the metal enclosure. Connect a wire with a ground lug crimped or soldered onto one end of the EARTH GROUND screw to the cabinet.
NOTE: Grounding connections should avoid bends in the grounding wire whenever possible.
NOTE: Do not use a gas pipe, plastic pipe or AC ground connections.
Freedom F-64 Installation Instructions
* Not evaluated by UL
L NAPCO Security Systems
WI1501A 9/06
Page 13
BASIC ZONE CONFIGURATION
(–)
include Zone Type (Entry/Exit, Interior, 24 Hour Protection, Trouble and Fire), Instant, Chime, Area Selection and PGM Output selection. Additional expansion zone modules or wireless sensor transmitters/receivers can be used to obtain zones numbered 9 through 32.
The basic zone configuration for the F-64 Panel is 8 zones. Connect as shown above to terminals 13-24. Normally Closed (N.C.) devices may be wired in series or Normally Open (N.O.) devices may be wired in parallel. Use the 2.2K Ohm end-of-line (E.O.L.) resistor in each zone, if selected in programming (refer to the F­64 Programming Instructions WI1502). Zones 1-8 can be selected for a “Fast Loop Response (50 ms)” or a “Normal Loop Response (750 ms)”. Other zone options
EZ ZONE DOUBLINGTM CONFIGURATION
If Normally open zones for fire or panic devices are required, then the lower zone (2.2K EOL resistor) must be used and the higher zone (3.9K EOL resistor) must not be programmed for any area. Additional expansion zone modules or wireless sensor transmitters/receivers can be used to obtain zones numbered 9 through 32
The control panel zone configuration may be expanded from 8 to 16 zones without the use of EZM Modules. To do so simply select “EZ Zone Doubling” in programming (refer to the F-64 Panel Programming Instructions WI1502) and connect zones as shown above. NOTE: If both zones in a zone-pair configuration (ex: zones 1 & 9 in the above diagrams) are to be used, then normally closed devices must be wired to both zones. The 3.9K EOL resistor must be placed at the end of the loop of the higher zone and the
2.2K EOL resistor must be placed at the end of the loop of the lower zone.
Wiring Connections: Basic Zone Configuration & EZ Zone Doubling Configuration
WARNING: Assigning a fire zone or keyswitch zones to a zone doubled will disable the respective complimentary
zone. For example, if zone 8 is assigned as a fire zone, it will disable zone 16. If zone 3 is assigned as a fire zone, it will disable zone 11.
L NAPCO Security Systems
Freedom F-64 Installation Instructions
Page 14
4-WIRE SMOKE DETECTORS
4-WIRE SMOKE DETECTOR WIRING
The F-64 Panel can use conventional 12 VDC 4-wire smoke detectors. To use them, select fire zone programming option and do not select 2-wire smoke detector programming option for the desired fire zone (refer to the F-64 Panel Programming Instructions). Set JP3 to the position as shown, if zones 7 or 8 are to be used.
Four wire smoke detectors may be connected to any programmed fire zone (1-8) as shown, within the panel. If the Zone Doubling is used (see EZ Zone Doubling Configuration), the respective complementary zones (9-16) are disabled when 4­wire smoke detectors are connected to zones 1-8. If external EZMs are used for zones 9-64, then 4-wire smoke detectors may be connected to any programmed fire zones (9-64).
Power must be obtained from terminal 25 and 6. If Fire Alarm Verification is desired to reset the smoke detectors, select this option for the desired fire zone.
WI1501A 9/06
2-WIRE SMOKE DETECTORS
2-WIRE SMOKE DETECTOR WIRING
Two-wire smoke detectors can only be connected to zones 7 and 8. To use them, select fire zone programming option and select 2-wire smoke detector programming option for the desired fire zone 7 or 8 (refer to the F-64 Panel Programming Instructions) and set JP3 to the “2-WF” position as shown. Connect the 2-wire smoke detectors as shown.
If the Zone Doubling is used (see EZ Zone Doubling Configuration), the respective complementary zones (15 & 16) are disabled when 2-wire smoke detectors are connected to zones 7 & 8.
If Fire Alarm Verification is desired to reset the smoke detectors, select this
Wiring Connections: 4-Wire Smoke Detectors & 2-Wire Smoke Detectors
option for the desired fire zone (zone 7 or 8).
Freedom F-64 Installation Instructions
L NAPCO Security Systems
Loading...
+ 30 hidden pages