Napco Security Technologies MA3000, Signature 5500, SS-P, GEM User Manual

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS
GEM-EZM4, GEM-EZM8GEM-EZM4, GEM-EZM8
ZONE EXPANSION MODULESZONE EXPANSION MODULES
NAPCO SECURITY SYSTEMS, INC.
333 BAYVIEW AVENUE
AMITYVILLE, NEW YORK 11701
SALES, REPAIRS & TECHNICAL SERVICE
TOLL FREE: (800) 645-9445
TECHNICAL SERVICE DIRECT LINE
TOLL FREE: (800) 645-9440
© Napco 1997 WI583C 2/97
DESCRIPTIONDESCRIPTION
The capacity of the MA3000, GEM-Series and Signature 5500 and SS-P Series control panels may be expanded through the use of GEM-EZM zone expansion modules. GEM-EZM4 modules provide up to four additional zones; GEM-EZM8 modules, up to 8 additional zones. Four-zone and 8-zone modules may be combined as necessary to supply the required number of zones. Refer to the installa­tion instructions for the control panel in use for wiring requirements for UL-listed applications.
WIRINGWIRING
Wire the expansion zones to the module and the module to the control panel in accordance with the wiring diagrams using wire no thinner than #22AWG. Install end-of-line resistors on all zones even if one or more zones are not used.
Note:Note: The addition of Zone Expansion Modules will re­duce the amount of current available at the control panel’s Auxiliary Power Output terminals.
MODULE ASSIGNMENTMODULE ASSIGNMENT
Regardless of how the modules are arranged, the expan­sion zones are divided into consecutively-numbered groups of four. Each 4-zone module comprises one group of zones; each 8-zone module comprises two groups.
Every module must be assigned a unique ‘‘base address’’. In the case of a 4-zone module, the base address number is the same as its group number. For the 8-zone module, the base address number will be the lower of its two group numbers. Note that (a) groups must be numbered con­secutively (that is, missing numbers are not permitted); and (b) no two modules may be numbered alike.
Example. Two GEM-EZM8s and one GEM-EZM4 are used to provide 20 expansion zones:
Groups 1 & 2 Group 3 Groups 4 & 5 GEM-EZM8GEM-EZM8 GEM-EZM4GEM-EZM4 GEM-EZM8GEM-EZM8
Base Addr ‘‘1’’ Base Addr ‘‘3’’ Base Addr ‘‘4’’
The base address is assigned to the module by proper selection of Address Jumpers JP1-JP5 (to the right of the LED) in accordance with Table 1. Also refer to the Zone Wiring Diagram.
for MA3000, GEM-Series,for MA3000, GEM-Series,
Signature S5500 & SS-P SeriesSignature S5500 & SS-P Series
Control PanelsControl Panels
BaseBase
AddressAddress
1 ON ON ON ON OFF 2 ON ON ON OFF ON 3 ON ON ON OFF OFF 4 ON ON OFF ON ON 5 ON ON OFF ON OFF 6 ON ON OFF OFF ON 7 ON ON OFF OFF OFF 8 ON OFF ON ON ON
9 ON OFF ON ON OFF 10 ON OFF ON OFF ON 11 ON OFF ON OFF OFF 12 ON OFF OFF ON ON 13 ON OFF OFF ON OFF 14 ON OFF OFF OFF ON 15 ON OFF OFF OFF OFF 16 OFF ON ON ON ON 17 OFF ON ON ON OFF 18 OFF ON ON OFF ON 19 OFF ON ON OFF OFF 20 OFF ON OFF ON ON 21 OFF ON OFF ON OFF 22 OFF ON OFF OFF ON
Table 1. Jumper emplacement as a function of Base Address.Table 1. Jumper emplacement as a function of Base Address.
Shaded area is not applicable to GEM-P3200 or SS-P3200.Shaded area is not applicable to GEM-P3200 or SS-P3200.
JP5JP5 JP4JP4 JP3JP3 JP2JP2 JP1JP1
PROGRAMMINGPROGRAMMING
The control panel must be programmed with regard to the modules (4-zone or 8-zone) in use. Referring to the respective Programming Workbook, program EZM TYPE to enable the module. Starting in the first location and pro­ceeding in succession, program a ‘‘1’’ for each 4-zone group of expansion zones in the system. For example, if one GEM-EZM8 is used for Zones 9 through 16 (two groups of 4), program a ‘‘1’’ in the first and second locations (right ‘‘nibble’’). Similarly, if an GEM-EZM4 is used for Zones 17 through 20 (1 group), program a ‘‘1’’ in the third location (right ‘‘nibble’’). Thus, each GEM-EZM4 will require a ‘‘1’’ in only one location whereas each GEM-EZM8 will require a
Address JumpersAddress Jumpers
‘‘1’’ in two consecutive locations.
ING for other indications.
TAMPERTAMPER
If the cover is removed, the keypad sounder will pulse and the display will indicate a zone-module tamper condition along with the module number. Press [RESET] to silence the sounder.
LOOP RESPONSELOOP RESPONSE
Loop response times for Zones 1 through 8 are pro­grammed in the control panel. Normal loop response for all expansion zones is 750mS. To reduce the response time of an expansion zone to 50mS, cut the respective resistor at the upper-left corner of the board. Refer to the Wiring Diagram.
STATUS LEDSTATUS LED
The Status LED displays the condition of the zone mod­ule. The LED will blink every few seconds to indicate that each 4-zone group is operating normally. The LED in the 4-zone module will blink once; the LED in the 8-zone module will blink once for the first group, then double-blink shortly thereafter for the second. See TROUBLESHOOT-
WIRING DIAGRAMSWIRING DIAGRAMS
PGM TERMINALPGM TERMINAL
The PGM terminal (Terminal 6) will go low when the area is armed. This terminal may be used to light an LED or trip auxiliary equipment. Note:Note: This terminal is programmed in the control panel; it may be selected to trip when any one area is armed (not necessarily its own). Refer to the instal­lation instructions for the control panel for programmable options.
4Z/8Z ZONE JUMPER4Z/8Z ZONE JUMPER
To convert an 8-zone module for use with only 4-zones, remove the jumper just below the large microprocessor IC on the circuit board.
TROUBLESHOOTINGTROUBLESHOOTING
A steady Status LED is most likely caused by loss of
data reception from the control panel at the module’s Terminal 3.
No illumination is most likely due to a loss of power at
Terminals 1 and/or 2.
Zone Wiring Diagram.Zone Wiring Diagram.
22
Loading...
+ 2 hidden pages