NAPCO StarLink SLE-LTE Commercial, SLE-LTEV-CB, SLE-LTEV-CFB, SLE-LTEV-CB-TF, SLE-LTEV-CFB-PS Installation Instructions Manual

333 Bayview Avenue
Amityville, New York 11701
For Sales and Repairs, (800) 645-9445
For Technical Service, (800) 645-9440 or visit us at
(Note: Technical Service is for security professionals only)
http://tech.napcosecurity.com/
Publicly traded on NASDAQ Symbol: NSSC
© NAPCO 2018
StarLink™ SLE-LTE Commercial Series
Alarm Communicators
INSTALLATION INSTRUCTIONS
WI2226ALF 8/18
INTRODUCTION
The StarLink™ Commercial / Residential Fire and Burglary
alarm capture radio communicators are fully supervised, wireless digital two-way subscriber units supported by an extensive nationwide wireless network. All models are compatible with most 12VDC alarm control panels (always adhere to the documentation provided by the control panel manufacturer). Model SLE-LTEV-CFB is compatible with most 12 or 24VDC control panels. All can function as a backup to existing telephone lines, or as sole path primary communicators. In backup mode, all units will automatical­ly switch the communication channel from the telephone line to the network when telephone line trouble is detected.
See WI2140 for programming information.
The SLE-LTE Series radios use data-capture technology
that captures the alarm report from the control panel and transmits the alarm signals to the SLE Control Center; the alarm signals are then forwarded to ANY central station via Contact ID or Sur-Gard System II or Sur-Gard System V central station receivers via TCP/IP using standard line security. The SLE Control Center reports a trouble signal in the event that the network does not receive the expected supervision signal from the wireless communicator.
For Commercial Burglary installations, under the
STARLINK RADIO REPORTING PATH
The diagram below shows the transmission path of a
signal from the StarLink radio to the central station.
1. Signal from a Control Panel.
2. StarLink radio receives the signal transmission (from the TIP an RING wires); sends RF signal through the network operator.
3. Network Operator, part of the vendor system, a section of the cellular spectrum.
4. SLE Control Center, receiv es and routes data.
5. Central Station.
( ( ( ( ( ( ( ( ( ( ) ) ) ) ) ) ) ) ) )
StarLink
Radio
armed condition, any loss of communication must be
treated as a Burglary Alarm at the Central Station.
The following models are available:
Burglary Radio in red metal housing with SLE-ULPS-R power supply and 16.5V / 20VA transformer mounted inside housing
SLE-LTEV-CB-TF: Commercial / Residential Burglary
and Residential Fire Radio in white metal housing with SLE-ULPS-R power supply and TRF12/T123 plug-in
16.5V / 20VA transformer
SLE-LTEV-CFB: Commercial / Residential Fire and Bur-
glary in red metal housing. Powered directly from control panel (no power supply, no transformer, rated 12/24VDC input)
SLE-LTEV-CB: Commercial / Residential Burglary and
Residential Fire Radio in white metal housing. Powered directly from control panel (no power supply, no trans­former)
The following features are included with models that include
a SLE-ULPS-R power supply:
 Power limited output to the StarLink radio PC board 12V
input terminals
 Battery connection red and black flying leads  Monitored battery charging and Active battery test circuits  StarLink radio trouble input (from StarLink radio PC board
PGM1 terminal to de tect StarLink radio trouble)
 Requires a sealed lead acid min 4AH / max 7AH battery
for minimum 24-hour standby time (max charge current 200mA).
 Trouble relay output (C, N/O and N/C termi nals) to w i re
to a panel zone dedicated to "LTE Trouble" (dry con­tacts). Remove jumper "J2" to isolate common from ground
 Green AC ON LED visible from the exterior housing  Yellow TROUBLE LED on PC board. Flashes signify:
One flash: AC fail / brownout (2 hour delay) Two flashes: Low battery Three flashes: Charging circuit trouble Four flashes: StarLink radio trouble
The housing-mounted transformer (when provided) is mount-
(2)
Control Panel
CENTRAL
STATION
StarLink
SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions 1
(1)
(5)
UL Classified StarLink Network
Operations Center
(3)
Network
Operator
(4)
AGENCY LISTINGS
 UL 864 Standard For Control Units and Accessories For
Fire Alarm Systems, 10th Editio n
 UL 1610 Standard For Central-Station Burglar-Ala rm Units  UL 985 Standard For Household Fi re Wa rning Sy stem Unit s  UL 1023 Standard For Household Burglar-Alarm System
Units
LTEV models are Verizon® Network Certified
ed inside its own housing compartment with a replaceable UL Listed .5A fast blow primary fuse. 120VAC connections are to be made by a licensed electrician using suitable con­nectors, in accordance with N.E.C. and local code require­ments.
ADDITIONAL COMPONENTS
In addition to the models listed above, the following sub-
assemblies are available: SLE-ULPS-R - Power Supply. Required for installations
where the control panel cannot provide the 71mA of Auxiliary power required to operate the StarLink radio. Uses a standard 4AH / 12V minimum (7AH maximum) rechargeable battery to provide radio standby power. Requires connection to either the model NAPCO TRF12/T123 (16.5V / 20VA) external plug-in transformer or the chassis-mounted 16.5VAC / 20VA transformer affixed inside the housing (see wiring diagrams further in this manual). Note: For models without the SLE-ULPS­R, connect the radio terminals 1 and 2 to the control panel Aux Power terminals (observing polarity).
SLE-DLCBL - Download Cable, 6 feet SLE-ANTEXT30 - Extended antenna with 30 feet of cable SLE-ANTEXT50 - Extended antenna with 50 feet of cable SLE-ANTEXT75 - Extended antenna with 75 feet of cable
(Any suitable external cellular antenna is permitted by
UL). Always follow the manufacturer's installation in­structions. Note: Antennas are not Listed by UL. For LTE radios where an External Antenna needs to be in­stalled outside of the room in which the radio is installed (maximum 30 meters (98 feet) in Residential applica­tions), please use RF Transmitter Board 9SLELTEEXAPSLD available from our Customer Ser­vice Department, if not provided. The 9SLELTEEXAPSLD is identified by "two red dots" locat­ed on the lower right corner of the board. See WI2239 included with the 9SLELTEEXAPSLD for the simple in­stallation procedure.
GEM-Tamperkit - Tamper switches and screws to protect
metal housing (see page 18).
SPECIFICATIONS
The following specifications apply to all StarLink radio mod-
els unless otherwise stated:
Electrical Ratings for 120VAC, 60Hz
For Models with Power Supply
 Input Voltage: 120VAC nominal  Input Current: 150mA maximum  Maximum Charging Current: 200mA
Electrical Ratings for +12V For Models without Power Supply*
 Input Voltage: 10-15VDC (power-limited output from
Listed control panel). Note: Model SLE-LTEV-CFB is rated 10-25VDC input.
 Input Current for SLE-LTEV-CB: 10V = 90mA , 12V =
71mA, 15V = 63mA, with peak RF transmission current of 200mA.
 Input Current for SLE-LTEV-CFB: 10V = 90m A , 12V =
71mA, 25V = 68mA, with peak RF transmission current of 200mA.
Electrical Ratings for the IN 1 Burg/Fire Input:
 Input Voltage: 9-15VDC. Note: Model SLE-LTEV-CFB
is rated 9-25VDC input.
 Maximum Input Current: Up to 2mA from FACP NAC
circuit
Electrical Ratings for IN 2 and IN 3:
 Maximum Loop Voltage: 15VDC. Note: Model SLE-
LTEV-CFB is rated max 25VDC input.
 Maximum Loop Current: 1.2mA  End of Line Resistor (EOLR) Value: 10K (2 req'd)
Electrical Ratings for 3 PGM Outputs:
 Open Collector Outputs: Maximum Voltage 3V when
active; 15V maximum when not active. Note: Model SLE-LTEV-CFB is rated max 25VDC output.
 Maximum PGM Sink Current: 50mA (up to 15VDC),
25mA (15.1VDC - 25VDC)
Physical (W x H x D)
 Metal Housing: 11½ x 9½ x 3½" (29.2 x 24.1 x 8.9cm)  Mounting: Metal housing includes two keyhole slots for
wall mounting (see measurements on page 7)
Environmental
 Operating Temperature: 0°C - 49°C (32°F - 120°F)  Humidity: Maximum 93% Non-Condensing  Indoor / dry location use only
NOTICE TO AUTHORITIES HAVING JURISDICTION, USERS, INSTALLERS,
DEALERS, AND OTHER AFFECTED PARTIES
FIRE PROGRAMMING OPTION
Unattended Remote Downloading No Enable / Disable
IN2 and IN3 Unsupervised Yes Supervised / Unsupervised
7 Day Supervision, Radio to NOC No
*For Commercial Fire installations, a UL Listed Fire Alarm regulated power supply or FACP regulated auxiliary output is required.
2 StarLink
PERMITTED IN
UL864? (Y/N)
AVAILABLE SETTINGS REQUIRED UL 864 SETTINGS
Disabled (Jumper 1 installed). Also required for Commercial / Burgla-
ry installations. Note: See page 7 "Configuration Download / Firm- ware Updates" for jumper instructions.
Unsupervised using conduit within 20 feet of FACP (default). If not using conduit, install Jumpers 4 and 5 and EOL Resistors (see pages 3 and 4).
200 seconds, 5 minutes,
60 minutes, 7 days
SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions
200 seconds, 5 minutes, 60 minutes
TERMINAL DESCRIPTIONS
Configure all inputs and outputs using the Manage­ment Center screen (located at www.napconoc.com).
Located at the bottom of the StarLink radio PC board, the 17 terminals are described as follows:
TB1: PWR (+12V) Note: Model SLE-LTEV-CFB is rat-
ed 12/24VDC input. (Refer to section "STEP 4: APPLY POWER") TB2: PWR GND (–) (Refer to section "STEP 4: APPLY POWER") TB3: PGM1 (–): Open collector output. PGM1 is nor-
mally on (active low). When it is triggered (for ex-
ample, a trouble is detected) it becomes open col-
lector/high. To have a zone dedicated to an Star-
Link radio trouble, insert one side of the end of line
resistor into this PGM1 terminal, and wire the other
side of the resistor to the positive terminal of the
zone. TB4: PGM2 (–): Open collector output. This output is
defaulted as "Fail to Communicate", and is normally
open collector/high. When a report fails to com-
municate anywhere in the communications path, the
output is active low. TB5: PGM3 (–): Open collector output. This output is
defaulted as "Telephone Line Cut". When the tele-
phone line voltage is correct, the output is open col-
lector/high; when the telephone line voltage is too
low, the output is active low. TB6: IN 1: Active high input for wiring to the panel
bell output. When this input detects a pulsing tem-
poral 3 high, it sends a Fire alarm; a pulsing tem-
poral 4 (CO Alarm), a CO alarm is sent. When
used, these conductors must be run in conduit (max
20 feet for Commercial Fire, and 3 feet for Residen-
tial Fire). Do not use for Burglary applications.
TB7: IN 2: See TB9, below. TB8: GND: Common ground terminal. TB9: IN 3: Both terminals IN 2 and IN 3 by default are
supervised end-of-line resistor inputs that can be
triggered with N/O or N/C relay contacts. Wire the common ground terminal GND (terminal TB8) to the relay common. In Burglary applications, when used as arm/disarm status input, a low indicates "armed" and a high indicates "disarmed". For these inputs to report to a central station, the radio must be config­ured with the central station telephone number and correct reporting formats and codes. See table on page 17 for more information.
TB10: TIP: See TB11, below. TB11: RING: Terminals TIP and RING: Wh en used f o r
backup reporting, the house Tip and Ring telephone wires must be routed from the outside to these ter­minals. Under normal back up conditions, these terminals are internally wired to the PANEL TIP and PANEL RING terminals, allowing all transmissions to the central station to be monitored. These wires are monitored for voltage such that if voltage falls below 1.5V, a Telco Line Fault trouble is detected, and the StarLink radio applies telephone line volt­age to the control panel Tip and Ring DACT inter­connect to the radio allowing it to receive and trans­mit any alarms sent by the panel.
TB12: PANEL RING: See wiring diagrams. TB13: PANEL TIP: See wiring diagrams.
Note: TB14-TB17 no connections permitted by UL. TB14: RTS (R): See TB17 below. TB15: PANEL TX (B): See TB17 below. TB16: PANEL RX (G): See TB17 below. TB17: CTS (Y): No connections permitted.
LED DESCRIPTIONS
The PC board contains several LED's, as follows: GREEN RF SIGNAL STRENGTH LED
Labeled "D3", this LED is located at the lower right corner
of the PC board.
Every 30 seconds, the StarLink radio receiver section
turns on and listens to the cell tower. Depending on the
Supervised Fire / Burg Input
8 7 9
Radio GND
(TB8)
(Radio)
(Alarm Panel)
10K
10K
C C N/O
TBL*
The EOLR must be installed and located within the control panel housing.
*Reverse polarity / energized state.
StarLink
SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions 3
Alarm
-or-
To StarLink Terminals IN2 (TB7)
-or-
IN3 (TB9)
N/O
N/C
Supervised Arm / Disarm Input
To StarLink
-or-
8 7 9
Radio GND
(TB8)
(Radio)
(Alarm Panel)
10K
10K
C
Open = Disarmed
Closed = Armed
The EOLR must be installed and located within the control panel housing.
Terminals IN2 (TB7)
-or-
IN3 (TB9)
RED DIAGNOSTIC LED (Labeled "D7")
YELLOW OPERATIONAL STATUS LED (Labeled "D4")
GREEN RF SIGNAL STRENGTH LED (Labeled "D3")
RED TROUBLE LED (Labeled "D5")
D4 D3 D5
LED LOCATIONS
signal strength detected, it will blink the Signal Strength LED from 1 to 8 times, providing a signal strength indica­tor that is updated constantly and is always displayed. Refer to Coverage Table below.
Green LED Operation
Signal strength (as received by the radio) is displayed by
this LED blinking 1 to 8 times at a constant rate (with a short delay between blink cycles). Acceptable power level is greater than or equal to -91dBm (minimum 4 blinks at the mounting location).
LED Blinks 8 7 6 5 4 3 2 1
GREEN RF SIGNAL STRENGTH LED
RADIO RECEIVER COVERAGE TABLE
Power (dBm)
-55 -65 -75 -85 -91 -95 -99 -105
YELLOW OPERATIONAL STATUS LED
Labeled "D4", this LED is located at the bottom right of
the PC board. Operation is as follows:
Normal Standby Condition:
 Blinks on momentarily every 10 seconds: Unit is in
standby waiting for an alarm to report.
Processing Alarm Conditions:
 When processing an alarm, this LED will blink variably
during each part of the process (dialing, handshaking, data transmission, etc.).
RED TROUBLE LED
Labeled "D5", this LED is located at the bottom right of
the PC board. Operation is as follows:
 1 Blink: Low Aux Power input voltage  2 Blinks: Battery trouble  3 Blinks: Alarm report Failed to Communicate  4 Blinks: RF trouble (antenna connection or cellu-
lar registration)
 5 Blinks: Network trouble (signal unable to reach
the SLE Control Center)
 6 Blinks: Unit disabled (r eporting or control panel
downloading not allowed)
 7 Blinks: Unit was shutdown and has no function-
ality; requires a restart (full power down and full power up sequence) to restore operation
 8 Blinks: Telco Line Cut (this is not the DACT inter-
connect to the radio)
RED DIAGNOSTIC LED
Labeled "D7", this LED is located in the middle of the PC
board. One blink indicates a weak or non-existent signal from the network (green LED is off). If this red LED is blinking in any other manner, please contact technical support.
SUPPLYING POWER
Control panels can provide power through their Auxiliary
Power terminals if the available standby current is reduced by 71mA. When there is insufficient standby current due to the application (such as when 24-hour standby time is required for Fire or CO), the SLE-ULPS-R Charger Module accessory must be used to charge an additional battery and to supply the power for the StarLink radio. See WI2131.
JUMPER DESCRIPTIONS
Jumper block labeled "X5"; from top to bottom, as detailed in
the following table. Note: Contact ID is always available in response to a Contact ID handshake.
Tech on site must temporarily
remove to download
4/2 with Checksum Pulse Format 2 4/2 Pulse Format
Supervised inputs. EOLR(s) re-
quired, see page 3
The StarLink SLE-LTE Series radios are compatible with
any Listed alarm control unit DACT communicating contact ID or any 4+2 pulse format (4/2 Pulse Dialing formats such as Ademco Slow, Radionics Slow, Silent Knight Fast, Radi­onics Fast and Universal High Speed, with 10pps, 20pps, and 40pps with and without checksum, either 1400Hz or 2300Hz handshake / kissoff).
The StarLink SLE-LTE Series radios and NOC are compati-
ble with the Listed Ademco model 685 with model 685-8 line card DACR or any Listed compatible DACR with any 4+2 pulse or contact ID format which is specified in the Installa­tion Instructions for the interconnected DACT / Alarm Con­trol Unit.
Refer to WI2140 (available on the NOC) for selecting the
required handshake / kissoff frequency in the NOC (www.NapcoNOC.com) setup screens (as required by the control panel).
Jumper Block "X5" Options
Jumper block labeled "X5" contains 5 jumper terminals; from top
(labeled "1") to bottom (labeled "5") as follows:
Jumper ON
Backup Mode 3 Primary Mode
Jumper Number
1
4 and 5
Jumper OFF
Not permitted by UL 864 and
UL 1610
Not permitted by UL 864 and
UL 1610 (UL 864 permits use of
conduit within 20 feet of FACP in
lieu of Supervision)
PRIMARY AND BACK-UP REPORTING
The StarLink radio can function as a primary wireless com-
municator, in cases where there are no telephone lines pre­sent, when connected directly to the control panel Telco
4 StarLink
SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions
terminals. For primary reporting, do NOT install jumper 3 in terminal block "X5". The StarLink radio can also func­tion as a backup to the existing telephone lines (install jumper 3 in terminal block "X5"). When used as a back up communicator and when it senses telephone line trouble, the StarLink radio automatically switches the communica­tion channel from the telephone line to the network.
NETWORK COVERAGE
The StarLink radio constantly supervises the network cov-
erage. When the StarLink radio is configured for primary reporting, and the StarLink radio detects a loss in network coverage, the StarLink radio must be configured to prompt the control panel to announce a Telco Line Cut failure trou­ble using the Management Center screen (located at www.NapcoNoc.com). Note: This Telco Line Cut failure trouble will NOT activate when the StarLink radio is config­ured for backup reporting.
INSTALLATION STEPS
STEP 1: ACCOUNT REGISTRATION
Create a new account and register specific StarLink radio
modules at www.NapcoComNet.com. Accounts and mod­ules registered via the Internet are enabled for activation within 24 hours.
STEP 2: SELECT A MOUNTING LOCATION
The mounting location should be indoors within the protect­ed area and selected based on RF performance. It is HIGHLY recommended that the installer carefully adhere to the following recommendations BEFORE any wires are in­stalled.
 Generally, high locations are best. DO NOT mount radio
in basements or below grade as unpredictable perfor­mance may result.
 DO NOT mount the radio in non-climate controlled envi-
ronments (i.e. attics may become extremely hot in sum­mer, garages may become extremely cold in winter).
 Avoid mounting locations within 3 feet of AC power lines,
fluorescent light fixtures, or large metal objects (air con­ditioners, metal garage doors, etc.) as these locations have been shown to have a detrimental effect on signal strength.
 A fair amount of care may be required to mount the Star-
Link radio so as to achieve an optimal RF path. The
installer should spend as much time as needed to obtain the highest signal level possible.
 For Commercial Burglary installations, install in accord-
ance with UL 681, Standard for Installation and Classifi­cation of Burglary and Holdup Alarm Systems. Installa­tion shall also be in accordance with UL 827, Standard for Central-Station Alarm Services, and UL 1641, Stand­ard for Installation and Classification of Residential Bur­glar Alarm Systems
a. Before applying power, be sure to connect the
antennas. Temporarily connect power to the Star­Link radio from a fully charged 12V (4AH minimum) battery. DO NOT mount the radio at this time. Press Tamper switch to send a signal.
b. Position the unit in the desired mounting location, with
antenna oriented vertically. The signal strength is displayed by the Green "Signal Strength LED" labeled
StarLink
SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions 5
"D3" (located at the lower right corner of the PC board). The radio tower signal strength may fluctuate from day to day, therefore it is best to try to find a mounting location where the LED provides a mini- mum of 4 blinks.
c. Once a location has been selected based on signal
coverage, permanently secure the unit using #8 screws (not supplied) in the two mounting holes.
WARNING: To ensure user safety and to satisfy FCC
RF exposure requirements, this unit must be installed so that a minimum separation distance of 60cm (24") is al­ways maintained between the antenna of the transmitting device and nearby persons.
STEP 3: WIRING (PRIMARY AND BACKUP MODES)
22-gauge wire may be used if mounted up to 50 feet from the control panel, and 18-gauge wire should be used for up to 100 feet. Reference the wiring diagrams further in this manual. See the section CONTROL PANEL PROGRAM-
MING further in this manual.
For Primary Mode:
Remove jumper #3 in jumper block labeled "X5". The wir­ing between the control panel and the StarLink radio is over five (5) wires, as follows:
 TB1: PWR (+12V) Note: Model SLE-LTEV-CFB is
rated 12/24VDC input.
 TB2: PWR GND (–)  TB13: PANEL TIP  TB12: PANEL RING  TB3: PGM1 (–). Normally low output wired to the
(+) of a zone dedicated to monitoring the radio status. See page 12 for GEMC-F8ZCPIM wiring. Should be programmed on Napco control panels as Day Zone, but be programmed to sound locally and NOT activate the bell. Note : See steps "a" and "b", below.
For Backup Mode:
Install jumper #3 in jumper block labeled "X5". The wiring between the control panel and the StarLink radio is over seven (7) wires, as follows:
 TB1: PWR (+12 or 12/24V)  TB2: PWR GND (–)  TB10: TIP  TB11: RING  TB13: PANEL TIP  TB12: PANEL RING  TB3: PGM1 (–). Normally low output wired to the
(+) of a zone dedicated to monitoring the radio status (see page 12 for GEMC-F8ZCPIM wiring). Should be programmed on Napco panels as Day Zone, but be programmed to sound locally and NOT activate the bell.
a. Without applying power (voltage), connect to screw
terminals TB1 (+12 or 12/24V) and TB2 (–). If t h e control panel Aux. Output cannot supply the neces­sary current, then you must use the SLE-ULPS-R Power Supply accessory with additional battery (see WI2131). For wir i ng con n ec ti ons , se e t he wi r ing d ia­grams further in this manual.
b. Referencing the correct wiring diagram for the ap-
propriate control panel (wiring diagrams are located further in this manual), connect the "TELCO" control
panel terminals TIP and RING (DACT interconnect
wiring to the radio). Do NOT connect the StarLink
radio terminals TB10-13 to house telephone lines
(RJ31X modular plug wires, etc.).
Wiring Methods
 Strip wire carefully to avoid exposed conductors after
installation, etc.
 Use UL Listed wire, ensuring that all conductors are to be
insulated for the maximum voltage of any conductor in the enclosure
 All wiring methods must be performed in accordance with
NFPA 70, Articles 725, and 800
STEP 4: APPLY POWER
 Attach primary (top left) antenna before applying
power !
 The StarLink radio requires +12 or 12/24VDC. It draws
less than 71mA during standby, and almost 200mA dur- ing transmissions (for less than 1 second).
STEP 5: SIGNAL VERIFICATION
 Verify Online: To veri fy t hat the signals have been
received by the StarLink radio LTE Network online, go to www.napconoc.com, log in with your Username and Password, enter your Company ID number and the Star- Link LTE Radio Number, then click Signal Log.
IMPORTANT: Verify that the signals transmitted by the
StarLink radio have been properly received by your central station before leaving the premises.
NAPCO CONTROL PANEL PROGRAMMING
To program the central station receiver reporting format,
use PCD-Windows Quickloader download software. Open the Digital Communications screen, Central Station Receiv- ers tab, as shown in the following image. A "Point ID" (also called "Contact ID") receiver format programming example is shown:
The radio can transmit to any central station capable of re-
ceiving SIA Contact ID via DACR technology or the DSC Sur-Gard System II or Sur-Gard System V central station receivers via TCP/IP.
STARLINK RADIO RELATED EVENT
REPORT CODES
EVENT AREA
IN 1 Fire
IN 2 Panic
IN 3 Trouble
Low Battery/Voltage
Tamper Trouble
Line Cut
Reboot
IN 1 CO (Carbon Monoxide)
Panic Alarm*
Holdup Alarm*
Medical Alarm*
24 hour Aux. Alarm*
24 hour Aux. Restore*
Burg Perimeter Alarm*
Burg Interior Alarm*
Keypad Holdup Alarm (ambush)*
Keypad Panic Alarm*
Keypad Emergency Alarm*
Opening*
Closing*
A.C. Trouble*
Tel 1 Fail*
*Not generated by the StarLink radio.
Note: A receiver reporting format must be entered for
each telephone number used, but each telephone number may be assigned a different format.
CAUTION: The installer should always be certain an area code is programmed into the control panel. Optional: If you wish the StarLink radio to report a code and zone number (Contact ID by default) to the central sta­tion in response to a triggered input event, see the table on
(Contact ID by default)
CONTACT ID
CODE ZONE #
0 E110 990 1A 0 E120 992 22 0 E300 993 F3 0 E302 994 F4 0 E341 995 F5 0 E352 996 F6 0 E625 997 F7 0 E162 998 18
E123 E122 E100 E150 R150 E131 E132 E121 E123 E140 E401 R401 E301 E351
PULSE
4/2
SIGNALS ORIGINATED AT THE NOC
NOC Originated
Alarms
Supervisory Fail E356 A00 Zn000
Press to Send
Test Signal
Press to Send
Radio Test
6 StarLink
Contact ID
Event Data
Sent
E601 A00 Zn000
Not Applicable
Nothing sent to
CS receiver
Automatically by NOC if fail to receive any signal from StarLink radio within Supervisory Timeout duration.
Manually by dealer from the Management Center Signal Log screen (located at
www.napconoc.com). Sends test into CS receiv-
er. Manually by dealer from the Management Center
Checkins screen (located at
www.napconoc.com). Sends a command to the
StarLink radio to force a check-in to the NOC.
Initiated By Comments
For Auto Enroll, uses captured telephone number, Sub ID and format. For Dealer Programmed, uses entered telephone number, Sub ID and format.
Same comment as above.
----
SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions
Loading...
+ 14 hidden pages