NAPCO NP-AMOD8 User Manual

R
333 Bayview Avenue
Amityville, New York 11701 For Sales and Repairs, (800) 645-9445 For Technical Service, (800) 645-9440
© NAPCO 2005
NP-AMOD8
ACCESS POWER CONTROLLER
WI1329A 12/05
DESCRIPTION
The NP-AMOD8 is an access power controller that dis-
tributes one (1) 12-24 volt AC or DC input over eight (8) independently controlled (and fuse protected) out­puts. In addition, these 8 outputs can be configured as dry form "C" contacts. The outputs are activated by an open collector sink or normally open (NO) dry trigger input from a Card Reader, Access Control System, Push Button, Keypad, PIR, etc. It will direct power to many access control hardware devices including Elec­tric Strikes, Magnetic Locks and Door Holders, etc. Outputs operate in both fail-secure and fail-safe modes. The NP-AMOD8 can be powered by one com­mon power source that provides power for both the locking devices and board operation, or two totally in­dependent power sources, one supplying power for lock / accessory power and the other for board opera­tion. The FACP Interface enables Alarm Monitoring, Emergency Egress, HVAC Shutdown, Elevator Recall or can be used to trigger other auxiliary devices. The fire alarm disconnect can be configured for the follow­ing modes: Eight (8) outputs unaffected (Fail Safe) or Eight (8) outputs affected (Fail Secure). Each output is independent controlled.
FEATURES
12 to 24volt AC or DC Operation (setting not required).
(.5amp @ 12volt, .22amp @ 24volt current consumption with all relays energized).
Power supply input options:
a) One (1) common power input (board and lock power). b) Two (2) isolated power inputs (one (1) for board
power and one (1) for lock power).
Eight (8) Access Control System trigger inputs.
Input options:
a) Eight (8) normally open (NO) inputs. b) Eight (8) open collector sink inputs. c) Any combination of the above.
Eight (8) independently controlled outputs.
Output options:
a) Eight (8) fail-Safe and/or fail-Secure power outputs.
b) Eight (8) dry form "C" 5 amp rated relay outputs. c) Any combination of the above.
Eight (8) auxiliary power outputs (unswitched).
Output fuses are rated 3. amp.
Main fuse is rated at 10 amp. Note: Total output current
is determined by the power supply, not to exceed a maxi­mum of 10 amp total.
Red LEDs indicate outputs are triggered (relays ener­gized).
Fire Alarm disconnect (latching or non-latching).
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry con-
tact input.
b) Polarity reversal from FACP signal circuit.
Fire Alarm disconnect output options:
a) Eight (8) outputs affected. b) Eight (8) outputs unaffected .
FACP output relay (form "C" contact rated @ 1 amp 28VDC not evaluated by UL).
Green LED indicates when FACP disconnect is triggered.
Removable terminal blocks facilitate ease of installation.
Board Dimensions: 203.2mm L x 114.3mm W x 45mm H
INSTALLATION INSTRUCTIONS
1. Mount NP-AMOD8 in desired location/enclosure. Note: Keep power limited wiring separate from non-
power limited wiring (115VAC / 60Hz Input, Battery wires). Minimum .25" spacing must be provided. Carefully review:
Terminal Identification Table
Typical Application Diagram
LED Diagnostics
Hook-up Diagrams
2. Power supply input: The NP-AMOD8 can be powered with one (1) power
supply which will provide power for both board op­eration and the locking devices or two (2) separate power supplies, one (1) to provide power for the board operation and the other to provide power for the locking devices.
Note: The input power can be either 12 to 24 volts
AC or DC (.5amp @ 12volt, .22amp @ 24volt current consumption with all relays energized).
(a) Single power supply input:
If the NP-AMOD8 and the locking devices are to be
powered using a single power supply, connect the output (12 to 24 volts AC or DC) to the terminals marked [- Control+].
(b) Multiple power supply inputs :
When the use of two power supplies is desired,
jumpers J1 and J2 (located to the left of the power/
1
control terminals) must be cut. Connect power for the NP-AMOD8 to the terminals marked [- Control +] and connect power for the locking devices to the ter­minals marked [- Power +].
Note: When using DC power supplies, polarity must
be observed. When using AC power supplies polar­ity need not be observed.
Note: For UL compliance, the power supplies
must be UL Listed for Access Control Systems and accessories.
3. Output hookup options : The NP-AMOD8 will provide either eight (8) powered
(switched and/or auxiliary), eight (8) form "C", or any combination of both powered and form "C" outputs.
(a) Switched Power outputs:
Connect the negative (-) input of the device being
powered to the terminal marked [COM]. For fail-safe operation connect the positive (+) input of the device being powered to the terminal marked [NC]. For fail­secure operation connect the positive (+) input of the device being powered to the terminal marked [NO].
(b) Form "C" outputs:
When form "C" outputs are desired, the correspond-
ing output fuse (1-8) must be removed. Connect negative (-) of the power supply directly to the lock­ing device. Connect the positive (+) of the power supply to the terminal marked [C]. For fail-safe op­eration, connect the positive (+) of the device being powered to the terminal marked [NC]. For fail­secure operation connect the positive (+) of the de­vice being powered to the terminal marked [NO].
(c) Auxiliary Power outputs (unswitched):
Connect positive (+) input of the device being pow-
ered to the terminal marked [C] and the negative (-) of the device being powered to the terminal marked [COM]. This output can be used to provide power for card readers, keypads etc.
4. Input trigger hookup options :
(a) Normally Open [NO] input trigger:
Inputs 1-8 are activated by normally open or open
collector sink inputs. Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND].
(b) Open Collector Sink inputs:
Connect the access control panel open collector sink
positive (+) to the terminal marked [IN] and the nega­tive (--) to the terminal marked [GND].
5. Fire Alarm Interface : A normally closed [NC], normally open [NO] or rever-
sal of polarity input from a fire alarm control panel (FACP) will trigger all outputs, except when the inde­pendent mode option is selected.
Independent output mode: (eight (8) outputs with
FACP disconnect with or outputs without FACP dis­connect).
To program the independent mode set switch to the
Fail Safe or Fail Secure position. In this mode of op­eration, Fail Safe will be affected when the fire alarm interface is triggered and outputs Fail Secure will re­main unaffected.
(a) Normally Open [NO] input:
Connect the normally open FACP trigger input to the
terminals marked [+ INP] and [T].
(b) Normally Closed [NC] input:
Connect the normally closed FACP trigger input to
the terminals marked [+ INP -] and install a jumper across the terminals marked [+ INP] and [T].
(c) Signaling Circuit input trigger:
Connect the positive (+) and negative (-) from the
FACP signaling circuit to the terminals marked [+ INP -].
Connect the FACP EOL or next signaling device to
the terminals marked [+ RET -- ] (polarity is refer­enced in an alarm condition). Jumper J3 must be
cut.
6. FACP dry contact output: Connect desired device to be triggered by the NP-
AMOD8's dry contact output to the terminals marked [NO] and [C] FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output.
LED DIAGNOSTICS
LED ON OFF
LED 1-LED 8 (Red)
Trigger (Green) FACP input triggered
Output relay(s) ener­gized.
(alarm condition).
Output relay(s) de­energized.
FACP normal (non-alarm condition).
TERMINAL IDENTIFICATION
Terminal
Legend
-- Power + 12 to 24 volts AC/DC from UL Listed lock power supply.
-- Control + 12 to 24 volts AC/DC from UL Listed power sup­ply (operates)
TRIGGER
INPUT 1- IN-
PUT 8
IN,GND
OUTPUT 1-
OUTPUT 8 NC, C, NO,
COM
From normally open and/or open collector sink trigger inputs (request to exit buttons, exit PIR’s, etc.).
12 to 24 volts AC/DC switched controlled out­puts:
Fail-safe [NC positive (+) & COM Negative
(-)],
Fail-secure [NO positive (+) & COM Nega-
tive (-)], Auxiliary outputs (unswitched): [C positive (+) & COM Negative (-)]. (When using AC power sup­plies polarity need not be observed), NC, C, NO convert to 5 amp 24 VAC/VDC rated form “C” dry outputs when fuses 1-8 are removed. Con­tacts referred to in a non-triggered state.
FACP INTER-
FACE
T, + INPUT --
FACP INTER-
FACE
NC, C, NO
Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open, normally closed or an FACP Signal Circuit input.
Form “C” relay contact rated @ 1 amp 28VDC for alarm reporting. (This output has not been evaluated by UL)