For Sales and Repairs, call toll free: (800) 645-9445
For direct line to Technical Service, call toll free: (800) 645-9440
Internet: http://www.napcosecurity.com
L NAPCO Security Systems
Page 3
1. INTRODUCTION
Page 3
GENERAL DESCRIPTION
The MAGNUM ALERT-1008e and MA1008eM are microcomputer-based eight-zone control panels with provisions for
Ambush, three Keypad Panics (Fire, Police and Auxiliary), a
supervised Fire Zone and a variety of reporting features. An
event log, accessible only through Napco PCD2000 Quickloader software, monitors up to 82 prior events. The
MA1008eM "Mercantile" version is supplied with a heavyduty enclosure for increased tamper resistance and a tamper
switch for tamper protection. (Note: Do not use Fire Zones in
a Mercantile Installation).
The system is contained within a wall-mounted enclosure
and Includes an integral digital communicator and a power
transformer.
The keypad allows the user to:
• arm and disarm the system
• check the status of each zone
• check which zones were violated after an alarm
• selectively bypass one or more zones
• display bypassed zones
• cancel entry delay
• send a Panic or Ambush alarm
• enter or change arm/disarm codes
• test the audible alarm and backup battery
• test each zone for problems (Fault Find)
• test the telephone line while disarmed
• reset AC-Failure indication
• bypass a Priority Zone with Bypass
• turn the Chime feature on/off
• program zone features and communicator information
Four LEDs, a display and a sounder an the keypad provide
visual and audible system and individual zone status Information. Most keys have secondary functions that are accessed
by holding down the key until the sounder beeps, and are
therefore termed "hold-down" functions. The following holddown functions are provided:
Key [1]: Alarm Test
Key [2]: Display Bypassed Zones
Key [3]: Display Status
Key [4]: Instant Alarm (cancels entry delay)
Key [5]: Chime on/off
Key [6]: Communicator Confidence Test or Manual
Download (see text)
Key [7]: Fault Find
Key [8]: Program
Key [9]: Reset (System-trouble indication; Failure-to-
Communicate sounder; Day Zone Indication; Alarm-
Memory display; Fire Zone; Fault-Find mode; Bypass
Priority-with-Bypass; and Power-Up Delay)
Key [B]: Alarm History (indicates last alarmed zone
(s))
The panels may be programmed in a variety of ways: (a)
from the keypad, in its secondary Dealer-Program Mode of
operation; (b) from a PROM (programmable read-only memory), which is itself programmed on an accessory programmer; or (c) from an IBM PC-compatible computer using
Designed for use with the PCI2000 Computer Interface Kit,
the MA1008e includes a modem to permit remote downloading/uploading over telephone lines or local downloading using
a PCL2000 Local Download Cable.
FEATURES
Protection Zones
• Seven end-of-line-resistor supervised zones.
• Two separately-programmable entry delays for Exit/
Entry Zones.
• Burglary Zone options include:
- Priority or Priority with Bypass
- Selective or Group Bypassing
- 24-Hour Protection
- Day Zone Supervision
- Auto Reset
- Exit/Entry Delay 1; Exit/Entry Delay 2
- Preprogrammed Auto Bypass (removable)
- Optional 50mS or 7mS Loop Response (normally
750mS)
- Programmable Abort Delay
- Fire on Burglary Zone
• Separate supervised Fire Zone
• Three keypad panics
Alarm Outputs
• Timed Burglary (sweep siren) and Fire (steady siren)
Output: Programmable by zone and time
• Timed Fire Output: Fixed to dedicated and programmed
Fire Zones, programmable for time
• Pulsing Steady Siren Output: Fixed to dedicated and
programmed Fire Zones, programmable for time
• NTO (No Timed Output) Lug
• Optional voltage on alarm
Keypad Functions
• Keypad permits:
- Arm/Disarm Code Selection of up to 8 user codes, up to
4 digits each
- Digital Code Entry to arm and disarm system
- Selective and Group Bypass Selection
- Panic Zone Activation
- Ambush Activation
- Hold-Down Function Access
- Resetting of various functions and conditions
- Programming zone features and communicator options
• LED display:
- Alarm State (armed/disarmed) (ARMED/ALARM)
- Zone Status (STATUS) - one or more zones in trouble
- Zones Bypassed - one or more zones removed
- Fire Zone Status (FIRE/TROUBLE)
- System troubles
• Display Indicates:
- Zone(s) in alarm and alarm history
- Zone(s) in trouble
- Zone(s) bypassed
- System troubles
- Programmed data entries (Dealer Program Mode)
L NAPCO Security Systems
MA1008e/ 1008eM Installation Instructions
Page 4
Page 4
• Sounder signals:
- Entry Delay in Progress
- Hold-Down Function Accessed
- Entry Door Opened while Disarmed (Chime)
- System Armed with a Zone in Trouble
- Day Zone in Trouble
- Fire Zone Alarm/Trouble
- Central-Station Ringback
- Failure-to-Communicate system trouble
- Exiting Dealer Program Mode
Communicator Features
• Integral digital communicator with true dial tone detec-
tion, double-pole line seizure and anti-jam
• Programmable abort delay time
• Rotary or Touch-Tone
available as backup to unsuccessful Touch-Tone
ing
®
dialing available. Rotary dialing
• Two telephone numbers and receiver/data formats can
be accessed
• Two-digit event codes and 4-digit subscriber codes pro-
grammable for those receivers accepting these formats
• Central-Station Ringback on closing or Auxiliary panic
Reporting Features
• Report on Alarm
• Opening and/or Closing Reporting by Individual User
pad Panics) 12-volt alarm control panel with integral com-
municator and siren driver, RP1054e keypad, 4AH and
TRF12 power transformer.
MA1008eM--As above, but for Mercantile installations. Less
keypad and battery, but with heavy-duty enclosure, Tam-
per Switch and TRF11 40VA power transformer.
Optional Peripherals and Accessories
RP1054e Designer-Style 4-Wire Keypad
RP1000eLCD Designer-Style Keypad with LCD display
RBAT-H1* Dual Battery Harness (not for UL installations)
TRF11 Transformer, 16VAC 40VA, Class 2 (UL Listed)
TRF12 Transformer, 16VAC, 19.2VA, Class 2 (UL Listed)
EOL2.2K End-of-Line Resistor Assembly, 2.2kΩ.
FT2200 End-of-Line Relay/Resistor Supervisory Module
PS3002 Power-Supply Module
MAV-15 Two-Way Voice/Listen In Module
GSM-400 Ground Start Module
LOCK-8 Lock & Key Set
PCI2000 Quickloader Interface and Software
PCL2000 Quickloader Local Download Cable
WL1 Wire with Lug Connector, 20"
*UL Listed Accessory
UL/cUL LISTINGS
Household Fire and Burglary Warning System Control Unit.
Combination Fire and Burglary (see Compatible UL Listed
Devices), Commercial Burglary (MA1008eM)
COMPATIBLE UL-LISTED DEVICES (See Note below)
For Residential control panels:
Smoke Detectors:
4-Wire:
System Sensor 1812, 2812TH, 1851B, 2851B, 2851BTH,
System Sensor 1400*, 2400*, 2400TH*, each with B101B
Base; 1451*, 2451*, 2451TH*, each with B401B Base
Subtract total smoke-detector alarm current from a available
standby current.
Horn:
Wheelock 34T-12R* (Rated at 85dB for indoor household
applications)
*Note: Devices not identified with an asterisk (*) require
optional power supply PS3002 for UL installations. Compatibility of detectors without "*" has not been evaluated by UL.
For Mercantile control panels (MA1008eM)
Bells:
Ademco AD8-12, AD10-12
Amseco MBL-8/12V, -10/12V
Mercantile Bell:
Ademco AB-12, Bell in Box
Speakers:
Ademco 713
Atlas Sound VT-158U
SUMMARY OF UL REQUIREMENTS
Note: The MA1008e may not be used for fire protection
where prohibited by local codes. The MA1008eM may not
be used for fire protection in any installation.
Residential
The following summarizes UL programming and wiring
requirements for Residential Household Fire and Burglary
installations.
• Recognized Limited-Energy Cable for initiating, indicat-
ing and supplementary circuits;
• Initiating loops supervised if longer than 3 feet;
• FT2200 End-of-Line Relay for Fire (if using 4-wire smoke
detectors);
• Minimum alarm timeout of 4 minutes;
• Maximum exit time: 60 seconds; maximum entry time:
45 seconds;
• Do not program Don't Wait for Handshake, Telco 1 & 2;
Swinger Shutdown; Force Arming; Group Bypass; 7mS
or 50mS Loop Response. Abort Delay may not exceed
45 seconds.
• Program Disable Callback Download; Disable Function
6 Download;
• Key Input on Zone 7 feature may not be enabled;
• Automatic dialer may not dial a police-station number
that has not been dedicated for such service;
• System must be tested at least weekly under AC battery
and battery-only conditions;
• Replace the rechargeable battery at least every 5 years;
• If the battery is heavily discharged, replace it or have it
tested by a qualified technician;
• Remote panic switches must be located in the same
room as the control unit and keypad. Wiring may not
pass through any barrier;
• For silent panic, connect only to UL-Listed holdup de-
vices.
In California: CFM-Ilsted for residential use (Listing No.
7165-992:111).
Mercantile
The following summarizes UL programming and wiring
requirements for Mercantile installations.
• TRF11 (40VA) and RBAT6 (7AH) are required;
• Heavy-duty enclosure with door tamper (MA1008eM) is
required;
• Digital communicator must be utilized for Low Battery
reporting, but not Low Battery restore;
• Program Audible Test on Arming; Force-Arm Code; a
maximum exit delay of 10 seconds; Disable Display By-
pass; Auto-Reset;
• Do not use Fire Zones;
• Ademco AB12 Bell & Box is required.
L NAPCO Security Systems
MA1008e/ 1008eM Installation Instructions
Page 6
Page 6
2. INSTALLATION
CONTROL-PANEL MOUNTING
Choose a mounting location accessible to (a) a continuously-powered AC source, (b) a cold-water-pipe ground ideally no further away than 10 feet, and (c) telephone lines
(keep telephone wiring away from speaker wires). Remove
appropriate knockouts for cables. Place the control panel at
a convenient viewing height and mark the mounting holes.
A keypad should be located near the exit/entry door. Up to
5 keypads may be connected if the longest cable run from
the panel to the farthest keypad, whether daisy chained or
home-run wired, is less than 1800 feet. See Combined
Standby Current specifications. Each keypad typically draws
35mA, however do not use more than 5 keypads.
The control panel door is secured shut by 3 screws
(supplied). A lock and keyset are available as an option (see
ORDERING INFORMATION).
Grounding
Connect the mounting screw at the lower-left corner of the
circuit board (EARTH GROUND) to a metal cold water pipe.
Do not use a gas pipe, plastic pipe or AC ground connections. Use at least 16-gauge wire. Make the run as short and
direct as possible. Avoid sharp bends in the wire.
Tamper Switches
Tamper switches may be installed to prevent opening of
the enclosure door or removal of the cabinet from the wall.
Ideally, tamper switches should be connected to a zone that
is active at all times, thus it may be necessary to program that
zone for 24-Hour Protection. When used on a normally-open
zone, normally-closed tamper switches (open when set)
should be wired in parallel. On a normally-closed zone, install Napco normally-open tamper switches (closed when set)
in series. There are two tamper switch provisions in the cabinet:
1. To prevent cabinet removal from the wall, there are three
mounting holes on the left side of the cabinet; another
hole on the back that allows the switch button to contact
the wall.
2. To prevent opening the cabinet door, there are three
mounting holes on the right side of the cabinet. When
mounted, the tamper-switch button should contact the
inside of the door. Be sure to alert the user that opening
the enclosure door will cause a tamper alarm.
KEYPAD MOUNTING (Keypad model RP1054e)
Opening the keypad. There are two slats along the bot-
tom edge of the keypad about 1 inch from each side. To
open, insert a medium screwdriver into either slot and push
up with a slight twisting motion to release the retainer tab.
Repeat for the other slot. Pull out at the bottom and lift off the
two hooks at the top.
This keypad features a handy pull-up reference label. Before mounting the keypad onto the wall, push the Sliding Label Plate (with label and felt backing affixed and handle facing
forward) down the guides at the rear of the keypad until it
snaps into place. Once installed, the Sliding Label Plate cannot be removed without first removing the keypad from the
wall.
When installing the rear case, be sure that the words
"TOP" and "UP" (molded into the case) are properly oriented.
The rear case is provided with a variety of holes to accommodate virtually any mounting situation. The four angled elongated holes are for mounting directly into a wall using appropriate screws; these holes will allow leveling adjustment. If
installing into a double-gang box, insert mounting screws
through the two vertical elongated holes on the left side of the
case and into the box. If the box is visible when viewed from
the front, adjust the keypad vertically, then tighten the screws.
Then, using hardware suitable far the mounting surface, add
one or two screws at the right side of the keypad case directly
into the wall to ensure a secure installation.
Keypad Wiring (Also see Wiring Diagram)
Connections to the keypad are summarized in the following
table. Avoid routing keypad wiring close to zone wiring.
Note: If using a soldering iron, avoid splashing solder onto
keypad circuit board or components.
Keypad Wire Color Control Panel Terminal
Yellow 9 (Clock)
Green 10 (I/O)
Red 7 (+)
Black 8 (-)
White*
White*
Table 1. Keypad Wiring.
to N/O momentary contact
pushbutton switch(es)
*Wire additional Panic Switches in parallel. Insulate both
white wires if not used (a short will cause a panic alarm).
Remote Panic. To connect a remote (Police) panic but-
ton, splice the two white keypad wires to a normally-open
momentary-contact pushbutton switch. Similarly, additional
panic buttons may be wired in parallel with the first, as
needed. If remote panic will not be used, insulate both white
wires, as a short across them will cause a panic alarm. Note
that in UL installations, remote panic buttons must be located
in the same room as the keypad, with no intervening barriers.
Backlighting. Keypad backlighting requires no additional
wiring. In normal use, the keypad is always dimly backlit. To
reduce or disable backlighting, see Keypad Jumper Options,
which follows.
Keypad Jumper Options
Several white jumpers provide a variety of options. Viewing the keypad from the front, these jumpers are conveniently
located at the top edge (Jumper D) and along the right side
edge (top to bottom: Jumpers C, B, A and E) for easy access.
Disable Keypad Panic. Cut Jumper A to disable all three
keypad panic features. (Cutting Jumper A does not disable
the two white remote-panic wires).
Disable Keypad Sounder. Cut Jumper B to completely
disable the sounder.
Disable Touchpad Backlight. Cut Jumper C to disable
touchpad backlighting.
Reduce Touchpad Backlight. Cut Jumper D to reduce
backlight intensity.
MA1008e/1008eM Installation Instructions
L NAPCO Security Systems
Page 7
Page 7
Activate Fire & Aux. Panics. Cut Jumper E to enable F/
P/A keypad panics. Note: This jumper must be cut to utilize
the three-keypad-panic feature of the MA1088e. Conversely,
if the jumper is cut, Enable Keypad Fire Panic or Enable Key-pad Auxiliary Panic must be programmed or adverse operation will result.
Assembling the Keypad. To reassemble the keypad af-
ter installation, hang the top of the front panel onto the hooks
in the rear case and push in firmly at the bottom until the retainer tabs snap into place. (If difficulty is encountered, push
the retainer tabs up lightly using a screwdriver, as when removing).
WIRING TO A MERCANTILE BELL
Refer to Fig. 1. Use an zone for a Tamper Zone and program it for 24-Hour Protection. The Tamper Zone will supervise the cold-water pipe ground, door tamper and bell box.
UL installations require a tamper switch on the control panel
door. For this purpose, use the normally closed (when set)
tamper switch supplied with the MA1008eM in series with the
Tamper Zone.
GROUND
SUPERVISION
WIRE
COLD-WATER-GROUND PIPE
WITH GROU ND CLAMPS MORE
SPLICE
THAN 1/4" APART.
4700-OHM
END-OF-LINE
RESISTOR
TAMPER
EARTH GRO UND
NAPCO MA1008eM
TAMPER
ZONE
DOOR
― BELL +
REQUIRE RIGID CONDUIT
OR ELECTRICAL METALLIC
UL INSTALLATIONS
TUBING (EM T) FOR
ENTIRE LENGTH.
INTERNAL BELL
4700-OHM
END-OF-LINE
RESISTOR
TAMPER
SWITCHES
― BELL +
ADEMCO AB-12
BELL IN BOX
Fig. 1. Wiring to a Mercantile Bell.
TYPICAL FIRE INSTALLATION (Where permitted by local
codes; not for use in Mercantile Installations).
LIVING
ROOM
BASEMENT
CONTROL CENTER; FIRE ALARM SOUNDING DEVICE;
C
K
KEYPAD; SMOKE DETECTOR; HEAT DETECTOR
T
ATTIC
S
BEDROOM
S
S
K
C
S T
Fig. 2. Typical Fire Installation.
T
F
HALL
RECREATION
ROOM
F
ATTIC
S
BEDROOM
T
KITCHEN
T
ATTIC
T
GARAGE
At least one smoke detector should be installed directly
outside each sleeping area. If there is more than one floor,
additional smoke detectors should be installed on each level,
including the basement. The living-area and basement
smoke detectors should be installed near the stairway of the
next upper level.
For increased protection, additional detectors should be
installed in areas other than those required, such as dining
rooms, individual bedrooms, furnace rooms, utility rooms and
hallways. Heat detectors, rather than smoke detectors, are
recommended in garages, attics, and kitchens due to conditions that may result in false alarms and improper operation.
Large areas and areas with partitions, ceiling beams, doorways, and open joists will require additional detectors. Refer
to NFPA Standard 74 (National Fire Protection Association,
Batterymarch Park, Quincy, MA 02269) for additional information, including proper mounting methods.
L NAPCO Security Systems
MA1008e/ 1008eM Installation Instructions
Page 8
Page 8
3. GETTING UP AND RUNNING
POWER-UP SEQUENCE
1. Referring to the Wiring Diagram, (a) connect the keypad to
the four keypad terminals 7 through 10 and (b) Install endof-line resistors (color code red/red/red) across each zone.
2. Connect an earth ground (cold-water pipe) to the left screw
that secures the circuit board to the cross rail.
3. Connect the power transformer to the AC Terminals 1 and
2 and plug the transformer into AC power.
4. Install the standby battery.
5. Check that the green STATUS LED on the keypad is lit.
6. Install loop wiring to zone terminals and relocate resistors
to end of loops. Recheck green STATUS LED.
7. If reporting to a central station, connect a telephone connecting cord to the TELCO terminals: green to 23; red to
24; and PHONE terminals: brown to 25; gray to 26. Then
see CENTRAL-STATION REPORTING.
DEFAULT PROGRAM
The MA1008e will function as a local alarm control panel
right out of the box! The following default program is entered
at the factory. It is the installer's responsibility to add, change
and/or delete features in accordance with these instructions
to customize the system to the user's requirements and to
conform to local codes.
• Arm/Disarm Code: 1,2,3 (User 1)
• User Program Code: 1,2,3,4,5,6
• Dealer Program Code: 4,5,6,7,8,9
• Exit/Entry (Entry Delay 1): Zone 1
• Entry Delay 1: 30 seconds
• Entry Delay 2: 30 seconds
• Exit Delay: 45 seconds
• Priority: Zones 1-7
• Selective Bypass: Zones 1-7
• 24-Hour Protection: Keypad Panic
• Auto Reset: Zones 1-7; Keypad Panic
• Swinger Shutdown: Zones 1-7; Keypad Panic
• Chime: Zone 1
• Chime Time: 2 seconds
• Burglary Output: Zones 1-7; Keypad Panic
• Burglary Timeout: 15 minutes
• Fire Timeout: 15 minutes
• Download with Answering Machine enabled
• Auto-Reset After Alarm Timeout enabled
• Power-Up In Last State enabled
• Pulsing Fire Output enabled
• Reset Fire enabled
• Keypad Tactile Beep enabled
• Keypad Panic enabled
• Communicator-Confidence Test enabled
• Alarm/Trouble Codes,
- Zones 1-7: 31-37
- Panic: 21
- Fire: 11
- Ambush: 22
- Fire Trouble: F1
- No AC: F9
- Low Battery: F8
• Restore Codes,
- Zones 1-7: E1-E7
- Fire: E1
- Fire Trouble: EF
- No AC: E9
- Low Battery: E8
• Closing Codes, Users 1-4: C1-C4
• Opening Codes, Users 1-4: B1--B4
• Force-Arm Code: F
CENTRAL STATION REPORTING
The following additional programming is required for central
station reporting.
• Report on Alarm
• Subscriber ID (Account) Numbers, Groups 1 & 2*
• Receiver Format*
• Data Format*
• Telephone Number*
*Obtained from central station.
Note: Remember, for optimum security, the following code
must also be reprogrammed:
• User-1 Code (see Programming User Codes, below).
For other programming, see Dealer Keypad Programming (Section 4) and the programming aid shown in Fig.
3.
USER KEYPAD PROGRAMMING
Programming User Codes
Note: The User Program Mode is disabled for the first
three minutes after power-up to allow you to use the Dealer
Program Code. To cancel the delay, hold down Key [9].
Up to eight different Arm/Disarm Codes may be entered
into the control panel using the keypad. User Code 5 may be
programmed as a Service Code, a special user code intended for temporary or occasional use only (see Service Code).
To program a User Code:
1. Hold down Key [8] until the sounder beeps, then enter
the User Program Code. (The default User Program
Code is 1,2,3,4,5,6, but this code must be reprogrammed). When the User Program Code has been
entered, the first three LED's on the keypad will flash
and the sounder will beep rapidly, indicating the User
Program Mode.
2. Now enter up to eight codes using any combination of
up to four digits (digits 1-9 only).
Examples:
Press:
[B], [1], then any 4 digits = User 1's code*
[B], [5], then any 4 digits = User 5's code**
[B], [8], then any 4 digits = User 3's code
*Default User-1 Code 1,2,3 must be changed.
**May be programmed as Service Code or Arm-Only
Code.
3. To exit User Program Mode, press [B] twice.
The numbers selected are the only codes recognized by
the system. Each user should be assigned his own dissimilar
code and cautioned against divulging that code to anyone else
Thus, should it became necessary to remove a user from the
MA1008e/1008eM Installation Instructions
L NAPCO Security Systems
Page 9
Page 9
system, that one code may be voided without affecting other
codes, and that user would then be prevented from entry.
Service Code
The Service Code, if programmed, provides reduced access to the control panel for those with limited authority. Operation is similar to that of a regular Arm/Disarm Code, except
that the Service Code is disabled at times. When active, it
may be used to arm or disarm as many times as necessary.
See User 5 Service Code in the Glossary.
The Service Code is controlled by User 1 . Whenever User
1 arms using his code, the Service Code is deactivated. To
activate, merely arm using the Service Code. The Service
Code can always be used to arm.
Changing or Voiding a Code
To change any User's Code, refer to Programming User
Codes and simply change the 4-digit combination. Thus, to
change User 3's code, for example:
1. Hold down Key [8] until the function beep sounds.
2. Enter the User Program Code.
3. Press [B], [3], then 4 new digits = User 3's new code.
4. Press [B] twice to exit User Program Mode.
Similarly, User 3's code may be voided by not entering a 4digit combination. Thus, to void User 3's code:
1. Hold down Key [8] until the function beep sounds.
2. Enter the User Program Code.
3. Press [B], then [3] = User 3's code erased.
4. Press [B] twice to exit User Program Mode.
KEYPAD OPERATION
Arming & Disarming the System
When a User Code is entered into the keypad, the red
ARMED / ALARM LED will either turn on, indicating that the
panel is armed; or turn off, indicating that the panel is disarmed. A "P" on the display with a steady sounder indicates
an attempt to arm with (a) a system trouble (hold down [9] to
reset keypad and arm), or (b) a Priority Zone in trouble (reenter code, then secure or bypass zone). If a wrong code is
entered, the system will fail to respond. Wait at least 2 seconds before attempting to re-enter a code.
Alarm Reset
Disarm the panel to silence a sounding device.
Ambush Zone
The Ambush Zone is tripped by entering the Ambush Code
just prior to disarming. Thus, should a user be forced to disarm by an assailant, the user can silently signal an emergency
while appearing to be merely disarming the system. The Arm/
Disarm Code must be entered less than 10 seconds after the
Ambush Code for an ambush report to be transmitted.
Keypad Panic
If using an F/P/A-Panic keypad, three keypad panics are
available: Fire, Police and Auxiliary (cut keypad jumper to enable panics). If enabled, each is tripped by simultaneously
pressing the following pairs of panic buttons:
• Fire Panic: press Keys [9/F] and [#]
• Police Panic: press Keys [*/P] and [#]
• Auxiliary Panic: press Keys [B/A] and [#]
Police Panic may be programmed to send a silent alarm to
a central station, activate an audible alarm, or both. Note that
the key pairs must be pressed at the same time to activate
panic. See Panic Zone In the Glossary; also see Section 2:
Keypad Jumper Options.
Bell / Battery Test (Hold-Down Function 1)
The terminal voltage of the battery is constantly monitored
by the control panel. Hold-Down Function 1 provides a manual dynamic test by briefly sounding the bell directly from the
battery.
A weak or defective battery is indicated by the display of a
System Trouble "2". The system trouble display will be
cleared and a restore reported when (a) the battery terminal
voltage has returned to its specified restored level and (b) the
condition has been detected by either the subsequent 24-hour
dynamic test, a manual bell / battery test (Hold Down Function
1) or a manual reset (Hold-Down [9]).
To test the battery with a pre-existing low battery displayed,
hold down Key [9] to temporarily reset the keypad, then hold
down Key [1] to check bell operation from the battery. If the
low-battery display returns the next time the system is disarmed, the battery is still weak and may require replacement.
(Allow at least 4 hours for the battery to recharge). Also see
System Trouble 2: Low Battery.
Communicator-Confidence Test (Hold-Down Function 6)
This feature checks the telephone line for the presence of a
dial tone in those systems that are programmed to communicate with a central station. Note: Do not arm and disarm the
panel just before making this test.
Hold down Key [6] until the sounder starts to pulse. If the
line is okay, the pulsing will stop, otherwise a steady tone will
sound (check phone lines). To silence the sounder, hold
down Reset Key [9].
Note: Hold-Down Function 6 has a secondary feature
(Manual Download) that can only be accessed within 5 seconds after arming and disarming the control panel. See
DOWNLOADING FROM A COMPUTER for use of this feature.
Fault Find (Hold-Down Function 7)
When the Fault-Find mode is accessed, two things occur:
(a) the loop response of all zones is preset to 7mS (fastest
loop response), and (b) securing a zone in trouble will cause
the sounder to beep for about 2 seconds. This set of conditions aids both installer and user. The installer, tapping and
poking at suspect points, can easily locate swingers by listening for the beep. Similarly, the user can confirm the repair of a
zone in trouble by listening for the beep, and thus eliminate the
need of returning to the keypad to visually check after each
attempt.
Hold down Reset Key [9] to restore normal operation. Arming the system successfully will automatically cancel the FaultFind mode.
System Trouble Indications
The following system troubles will display at the keypad,
whether armed or disarmed, accompanied by flashing
ARMED, STATUS and BYPASS LED's. The indication may
be temporarily reset by holding down Reset Key [9] in order to
check zone status and/or arm the system.
L NAPCO Security Systems
MA1008e/ 1008eM Installation Instructions
Page 10
Page 10
1. AC Failure. Indicates loss of AC power. The AC-Failure
indication will clear when AC power is restored.
2. Low Battery. Displays when battery terminal voltage
drops below 11.5 volts, nominally. The system trouble display will be cleared and a restore reported when (a) the
battery terminal voltage has returned to its specified restored level and (b) the keypad is reset using Hold-Down
Function 9. Also see Bell / Battery Test.
3. Failure to Communicate. Indicates an unsuccessful
transmission to the central station. If the panel is armed,
disarm. Hold down Key [9] to reset the keypad, then hold
down Key [5] to test the phone lines. If the test is successful, the display will clear; otherwise the trouble will return,
flashing red ARMED/ALARM LED. Subsequent disarming
will initiate the system trouble indication.
4. Auto-Download Failure. Indicates failure of a Function-6
Auto-Download. Reset the display by holding down Key
[9], then try again to auto-download the program.
TESTING THE SYSTEM
After installation is completed, test the system a follows:
Call the central station to inform them of the test. Initiate an
alarm, preferably on a zone that activates a steady output.
Verify proper signaling, then call the central station to confirm
their receipt of a good transmission.
Important: Be sure to test the operation of all enabled
keypad-panic features.
indicating a need for service. A successful communication
followed by a Hold-Down [9] Reset will also clear the display.
Note: If the system is armed and in alarm, the sounder will
turn on but the violated zones will display, along with a
CHANGES FROM PREVIOUS EDITION
The following changes have been made to this manual (WI587E) since the previous edition (WI587D):
• Cover: UL Listing text descriptions changed to "UL/cUL".
• Page 3: 2nd paragraph, removed text "If complemented by NAPCO wireless transmitters…" (to end of paragraph).
Note: A wireless transmitter mapped to Zone 7 may be used for remote arming." from "Key Input
MA1008e/1008eM Installation Instructions
L NAPCO Security Systems
Page 11
4. PROGRAMMING
Page 11
KEYPAD PROGRAMMING
Keypad Programming may be divided into two sub-groups:
User Program Mode and Dealer Program Mode. USER KEY-PAD PROGRAMMING is limited to user codes. In the Dealer
Program Mode, the keypad provides full programming capabilities.
Dealer Keypad Programming.
Set the keypad to the Dealer Program Mode: Hold down
Key [8] until a beep sounds, then enter the Dealer Program
Code. (The default Dealer Program Code is 4,5,6,7,8,9, but
this code must be reprogrammed to preserve system security.
See Glossary and the programming example, which follows).
The center segment of the numeric display will light to indicate
the Dealer Program Mode.
The Dealer Program Mode cannot be accessed while the
panel is armed or communicating except during the first three
minutes after power-up. (See Power-Up Delay in Glossary).
To shut this 3-minute "window" early, that is, before it times
out, hold down Key [9]. Note: If the Dealer Program Mode has
been accessed during this 3-minute "window", then complete
the required programming, exit the Dealer Program Mode (see
following), power down and power up the system once again.
Set the location to be programmed by pressing Key [B] (the
three horizontal segments of the display and the green LED
will light), followed by the location number. Each location must
be entered as a three digit number, that is, 001, 020, 157, etc.
Notice that as each of the three digits is entered, the three display segments extinguish in succession from bottom to top.
When the last digit is entered, the yellow LED will light and the
display will show the data (if any) programmed in that location.
At this point, several numeric keys take on new function assignments, as shown in Fig. 3.
Keys [1] or [6] (Prior Location) and [2] or [3] (Next Location) - Change the location. Use Key [1] or [6] to move down
to the next lower location, or Key [2] or [3] to move up to the
next higher location. Whenever a new location is entered, a
beep will sound.
Keys [4] (Data Up) and [7] (Data Down) - Select the data
for the chosen location: numbers 1-9, 0, and letters B, C, D, E,
and F, as will be indicated in the display. Key [4] sequences
data values in ascending order; Key [7], in descending order.
Key [5] (Clear) - Clears data from the selected location
(display will go blank).
Key [8] (Exit) - Exits the Dealer Program Mode. Hold down
until the beep sounds, then enter the Dealer Program Code
within 10 seconds to exit.
Key [B] (Set) - Sets the location to be programmed. After
pressing Key [B], enter a three-digit location number.
To exit the Dealer Program Mode, hold down Key [8] until
the beep sounds; all four LED's will light. Within 10 seconds,
enter the Dealer Program Code; the LED's will go out. (If the
LED's go out before your code is entered, repeat this procedure).
Caution: Before exiting the Dealer Program Mode, be sure
that Location 083 contains the data shown in Table 2. lf the
control panel comes up armed on power-up, you have three
minutes to access the Dealer Program Mode. Hold down Key
[8] for two seconds, then enter your Dealer Program Code. By
checking Location 083, you can prevent accidental erasures of
required data from going undetected. (If invalid data resides in
Location 083, a non-existent fire trouble and/or loss of keypad
functions may result). If you encounter this problem and need
assistance, call Napco's Technical Service Department (toll
free) at (800) 645-9445.
Disarmed Armed
5 7, D or F
Table 2. Valid data for Location 083
Example 1. Reprogram the existing (default) Dealer Program Code to 8,1,5,4,8,7.
1. Hold down Key [8] until the beep sounds.
2. Enter the existing (default) Dealer Program Code, 4,5,6,7,8,9. The center segment of the display will light.
3. Set Location 244, the first location of the Dealer Program Code block, as follows: (a) Press Key [B] (the three horizontal display
segments and green LED will light); (b) press [2],[4],[4] (the yellow LED will come on and the display will indicate the first digit of
the existing code, "4").
4. Program the first digit of the new Dealer Program Code as follows: Press Key [4] (Data Up) repeatedly until an "8" is displayed.
5. Press Key [2] (Next Location) once to advance to Location 245, the second digit of the code. A "5" (the second digit of the de-
fault code) will be displayed. To program the second digit of the new code press Key [5] (Clear), then press Key [4] (Data Up)
once - a "1" will be displayed.
6. Press Key [2] (Next Location) once again to advance to the third location (246) of the code. Using Key [7] (Data Down), replace
the "6" with a "5".
7. Repeat this procedure, using Key [2] to advance locations and Keys [4] and [7] to select data, until the entire code has been re-
programmed. To check the code, press Key [1] (Prior Location) five times to return to Location 244, then press Key [2] to step
through each location, noting the data displayed.
8. To exit the Dealer Program Mode, hold down Key [8] until the beep sounds, then enter the new Dealer Program Code within 10
seconds. This will confirm operation of the new code.
L NAPCO Security Systems
MA1008e/ 1008eM Installation Instructions
Page 12
Page 12
ENTER/EXIT PROGRAM MODE
HOLD DOWN KEY [8] UNTIL BEEP SOUNDS.
ENT ER DEALER PROGRAM CODE.
SEGMENTS LIT
2: PRESS "SET" (with no LED's lit)
TO SET 3-DIGIT LOCATION.
3,2,1: ENTER 1ST OF 3 DIGITS.
3,2: ENTER 2
3: ENTER 3
2: ENTER DEALER CO DE (with all LED's
ND
OF 3 DIGITS.
RD
DIGIT; DATA DISPLAYED.
lit) TO EXIT.
MAGNUM ALERT
3
2
1
LOCATION DATA PAGE 1
LED'S LIT
GREEN: .......... ENTER LOCATION DIGITS
YELLOW: ........ VIEW/CHANGE DATA
RED (RIGHT) : . PAGE-1 LOCATION
ALL: ................ READY TO EXIT
LOCATION KEYS [1] (OR [8]) AND [2] (OR [3])
BEEP = SHIFTED 1 LOCATION
NO BEEP = NO SHIFT
COMPUTERIZED SECURITY SYSTEM
LOCATION
PRIOR NEXT NEXT DATA UP
5 6 7 8
CLEAR PRIOR DATA DOWN ENTER/E XIT
9 F
2 1 3 4
*
PROGRAMMING SHEETS
Programming Sheets similar to those that follow are completed when planning system features and communicator information for the particular installation. These sheets should
be retained for future reference. The Glossary contains information and instructions for programming each feature.
General Programming Steps
1. Contact the central station to confirm receiver format, data
format, event codes, subscriber numbers and telephone
number(s). Two receiver descriptions and telephone num-
bers, and up to 4 Subscriber Identification Numbers may be
required.
2. Fill out the Programming Record Sheets by circling the
numbers representing the zone features or system features
to be programmed. Referring to the programming sheets
and the accompanying table, note that each program loca-
tion is assigned data values (1, 2, 4, 8) such that adding
any combination will produce a unique total (entry). Also
note that because the entry can be only one character, the
two-digit totals greater than 9 are replaced by zero and let-
ters B through F, as shown. Check the Glossary for guid-
ance in selecting "data" entries.
B
P
A
#
SET
3. To program the subscriber PROM, follow the instructions
furnished with the programmer. While programming, remember to keep the address page number in mind, and be
sure that the position of the PAGE switch (PRO410/410M)
is set accordingly. Note: If using the Napco PRO410/410M
programmer, before attempting to program either page, be
sure that all data in programmer memory are erased (press
[ERASE], then [EXECUTE]).
4. Program the entries (data totals from Programming Record
Sheets in Step 2) into the respective locations. The display
will show the entry numerically, but will display "0" for the
number 10, and letters "B", "C", "D", "E", and "F" for the
numbers 11 through 15, respectively. To program a 10,
enter [0]. To program 11 through 15, enter [B] through [F]
respectively, if using the Napco PRO410/410M programmer to program a PROM, use the [PLUS] key to enter any
two or more digits that add up to the desired entry. To program 13, for example, enter either [d] or [8] [PLUS] [5], or
[8] [PLUS] [4] [PLUS] [1], etc. Similarly, to add to an existing PROM location, first press the [PLUS] key, then the
complementary digit, otherwise the digit entered will re-place the digit in memory. Refer to the PRO410/410M instructions for further programming information.
Example 2. Program Zones 1-7 to report on alarm. Referring to the Communicator Information section of the Programming
Sheet, Report on Alarm is contained in Locations 166 and 167. Circle data values for Zones 1-7.
Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8/
Report on Alarm
166 166 166 166 167 167 167 167 Location
1 2 4 8 1 2 4 8 Data
Add the data values for Location 166: 1 + 2 + 4 + 8 = 15. From Table 3, 15 is programmed as an "F". Now add the data values
for Location 167: 1 +2 + 4 = 7. From Table 3, enter a "7" In Location 167.
MA1008e/1008eM Installation Instructions
Panic
L NAPCO Security Systems
Page 13
Page 13
LOCATION XXX ENTRY
blank
(1) 1
(2) 2
(1) (2) 3
(4) 4
(1) (4) 5
(2) (4) 6
(1) (2) (4) 7
(8) 8
(1) (8) 9
(2) (8) 0 (10)
(1) (2) (8) B (11)
(4) (8) C (12)
(1) (4) (8) D (13)
(2) (4) (8) E (14)
(1) (2) (4) (8) F (15)
Table 3. Determining data entry for a location. Numbers in pa-
rentheses indicate selected zones or features.
(See Programming Sheet.)
DOWNLOADING FROM A COMPUTER USING NAPCO
SOFTWARE AND INTERFACE
Local Downloading
Data may be locally downloaded with the use of PCL2000
Local Download Cable, which is supplied with the PCI2000
interface. The panel need not be wired nor the keypad connected. Also refer to the instructions included with the
PCI2000.
1. Referring to the PCI2000 Wiring Diagram, connect the
PCL2000 Local Download Cable between the modem
LINE connector and the control panel TELCO terminals.
(Remove the plug shown coming from the PCI2000-J5).
2. With the control panel unpowered, set up the computer for
a Function-6 Method download.
3. When a high-pitched tone is heard at the modem, power
up the panel (connect the battery or transformer). A connection will automatically be established, ignoring the
status of the zones.
4. Make all required selections and download the program.
5. After the computer indicates a successful download, terminate the connection, then remove power to the panel.
Remote Downloading
Data may be remotely downloaded to the panel via telephone lines using an IBM PC-compatible computer with Napco
PCD2000 software and PCI2000 interface. Onscreen prompting and the extensive use of help menus simplify programming, and an error-checking mode locates omissions and incompatible data to reduce the possibility of mistakes. Remote
downloading requires (a) a modem compatible with the
PCI2000 and (b) PCD2000 software Version 2.E or higher.
Note: Remote downloading may be disabled through programming and must be disabled in UL installations.
A program may be downloaded remotely using either of the
following procedures.
Callback Method. This method is used to download to an
unattended panel. The MA1008e will accommodate an an-
swering machine at the site if line seizure is used on the house
phones. Program a "1" in Location 082 (Enable Download with Answering Machine). Refer to the instructions furnished
with the PCD2000 for details. Note: The number of rings programmed into the panel must exceed that of the answering
machine.
Function-6 Method. Call the central station from the site
to request a Manual Download. During this procedure, voice
contact will be lost, therefore both the installer and the computer operator should be familiar with the operation. When a
high-pitched tone is heard at the site phone, arm the panel,
disarm, then access Hold-Down Function 6 (Manual Download) within 5 seconds; the site phone will go dead.
Hang up the phone and wait for a call from the central station
confirming a successful download.
Auto-Download Method. Napco PCD2000 Software Ver-
sion 2.E and later includes PC-Preset, a utility wherein blocks
of up to 99 programs each may be preset for remote uploading
or downloading from the installation site while the computer is
unattended. The Auto-Download ID Number identifies the pro-
gram in the computer that will be selected. (Note that the
Dealer Program Code in the PCD2000 must agree with that of
the control panel for the remote connection to be established.)
At the installation site, the Auto-Download ID Number corresponding to that in the computer is programmed into the
panel, along with the Callback Telephone Number of the com-
puter. To execute an Auto-Download, arm the panel, disarm,
then access Function 6 within 5 seconds.
PROM PROGRAMMING
A blank DD493BNK PROM may be programmed using a
PRO410 or PRO410M Programmer. See General Program-ming Steps and the manual furnished with the programmer for
operating instructions, and also the Programming Record
Sheets that follow. PROM programming may be used to program all features except the Dealer Program Code (Locations
244-249) and User Arm/Disarm Codes.
The following programming is required:
• Page-0, Location 083: "5"
• Page-1, Location 251: "C"
• Page-1, Location 252: "4"
Transferring Memory from PROM
Data programmed in the PROM are saved in memory as
follows:
1. At the panel, with AC and battery power off, insert the
programmed PROM into the MEMORY CHIP socket.
Align the dot on the PROM with the dot on the circuit
board.
2. Apply ac power. Enter the Dealer Program Mode: Hold
down Key [8] until the function beep sounds, then enter
the Dealer Program Code.
3. Exit the Dealer Program Mode: Hold down Key [8] until
the beep sounds, then enter the Dealer Program Code.
4. An "L" or "LOADING PROM" will display at the keypad.
When loading is complete, remove both AC and battery
power, remove the PROM from the socket, then power
up normally.
L NAPCO Security Systems
MA1008e/ 1008eM Installation Instructions
Page 14
Page 14
PROGRAMMING RECORD SHEET FOR THE MA1008e
Communicator Features - Default programming shown in parenthesis.
REPORT ON ALARM 166 167 168 169
CONTROL - PANEL RESTORE 170 171 172 173
(SEE NOTE 1)
ZONE RESTORE 184 185
(SEE NOTE 1)
ALARM /
TROUBLE
CODES
Extended or
Two Digit
RESTORE CODES S ingle Digit
Extended or
Two Digit
Single Digit
OPENING / CLOSING CODES CLOSING FORCE OPENING
SINGLE DIGIT
EXTENDED OR TWO DIGIT
SUBSCRIBER ID NUMBERS AL ARM/RESTO RE ID (SEE NOTE 3) OPENING/CLOSING ID
NOTES: (1) IF PROGRAMMING ZONE RESTORE, ALSO
PROGRAM CONTROL-PANEL RESTORE. (2) TWO DIGIT
FORMAT ONLY. (3) GROUP-2 CODES MUST BE ENTERED, EVEN IF THEY ARE THE SAME AS GROUP 1
CODES. (4) MUST BE PROGRAMMED IF OPENING/
NOTE: PROM LOCATIONS
ARE 030 - 045, PAGE 1
CLOSING CODES ARE PROGRAMMED. (5) THESE FORMATS TYPICALLY USE A 2300HZ HANDSHAKE; ADD AN
"8" TO THIS ENTRY.
L NAPCO Security Systems
Page 15
PROGRAMMING RECORD SHEET FOR THE MA1008e
Zone Features & Keypad Codes - Default programming shown in parentheses.
ZONE FEATURES
SWINGER SHUTDOWN 184 085
NO END-OF-LINE RESISTOR 086 087
CHIME ZONE 088 089
NEVER ARM 090 091
PIR ZONE 092 093
UNTIMED OUTPUT 096 097 098 099
(ONTO LUG 15)
ENABLE KEYPAD SOUNDER 164 165
ON ALARM
DAY ZONE 186 187
PRIORITY ZONE WITH BYPASS 188 189
(SEE NOTE 1)
PRIORITY ZONE 190 191
REMOVE AUTO BYPASS 192 193
(SEE NOTE 1)
SELECTIVE BYPASS 194 195 REFER TO R1000 RECEIVER INSTRUCTIONS
GROUP BYPASS 196 197
24-HOUR PROTECTION 198 199
AUTO-RESET 200 201
EXIT / ENTRY ZONE 202 203
(ENTRY DELAY 1)
EXIT / ENTRY ZONE 204 205
(ENTRY DELAY 2)
EXIT / ENTRY FOLLOWER 206 207
ABORT DELAY 208 209
BURGLARY OUTPUT 210 211
7mS LOOP RESPONSE 214 215
(SEE NOTE 2) 1 2 4 8 1 2 4 8
50mS LOOP RESPONSE 216 217
(SEE NOTE 2) 1 2 4 8 1 2 4 8
FIRE ON BURGLARY ZONE 306 307
(SEE NOTE 3) 1 2 4 8 1 2 4 8
1 2 3 4 5 6 7 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8 1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
1 2 4 8 1 2 4 8
GROUP 1 GROUP 2
ZONE K/P FIR DAY TST NO LOW
FIR AMB TBL TBL TMR AC BAT ARM
<--(ALSO SEE TIMES & TIMEOUTS, LOC. 230-231)
<--(SEE NOTE 7)
<--(ALSO SEE TIMES & TIMEOUTS, LOC. 094-095)
<--(SEE NOTE 7)
<--(ALSO SEE TIMES & TIMEOUTS, LOC. 218-219; 220-221)
<--(SEE NOTE 7)
<--(ALSO SEE TIMES & TIMEOUTS, LOC. 218-219; 222-223)
<--(SEE NOTE 7)
<--(SEE NOTE 7)
<--(ALSO SEE TIMES & TIMEOUTS, LOC. 232-233)
<--(ALSO SEE TIMES & TIMEOUTS, LOC. 224-225; 228-229)
NOTE: For wireless systems, refer to R1000 Receiver
Installation Instructions (WI604) for Transmitter Mapping
Locations 308-315.
<--(SEE NOTE 7)
TRANSMI TTER ZONE M AP
(FOR WIRELESS SYSTEMS ONLY)
TX# LOC ZONE
1 308
2 309
3 310
4 311
WI604 FOR TRANSMITTER MAPPING AND
LEARNING INSTRUCTIONS AND OTHER WIRELESS INSTALLATION INFORMATION.
NOTES: (1) If programming PRIORITY ZONE WITH BYPASS, do not program REMOVE AUTO BYPASS. (2) If neither 7mS nor 50mS LOOP RESPONSE is pro-
grammed, Loop response will be 750mS. (3) FIRE ON BURGLARY ZONE's must also be programmed for 24-HOUR PROTECTION, but for no other zone features
except UNTIMED OUTPUT. (4) The Dealer Program Code must not start with the same numbers as the User Program Code. (5) ● (dot) or blank for no entry. (6) To
conform with Telephone Company convention, program zeros in Telephone Numbers, Alarm Codes and Subscriber ID Numbers as an entry total of 10. (Press DATA
UP button until "0" is displayed; in PRO410, press Key [0].) (7) Zone "8" for wireless operation only. To use as other than keypad Panic, also program DIRECT KEYPAD PANIC TO AMBUSH (see GLOSSARY).
L NAPCO Security Systems
USER 3
USER 7
USER 4
328 329 330 331
USER 8
344 345 346 347
MA1008e/ 1008eM Installation Instructions
Page 16
Page 16
PROGRAMMING RECORD SHEET FOR THE MA1008e
System Features & Timeouts - Default programming shown in parentheses.
SYSTEM FEATURES
INSTRUCTIONS: FOR EACH LOCATION: (1) CIRCLE NUMBERS FOR FEATURES DESIRED. (2) PLACE SUM OF CIRCLED NUMBERS IN
"ENTRY" BOX. WARNING: DO NOT ATTEMPT TO PROGRAM "RESERVED" LOCATIONS AS IMPROPER OPERATION MAY RESULT.
LOCATION 078 ENTRY-->
DISPLAY DAY ZONES AFTER RESET 1
NOTES: (1) This feature requires that all system keypads have F/P/A keypad panics. (2) Program in decimal numbers; do not use leading zeros. (3) ● (dot) or blank
for no entry. (4) To conform with Telephone Company convention, program zeros in Telephone Numbers, Alarm Codes and Subscriber ID Numbers as an entry total of
10. (Press DATA UP button until "0" is displayed; in PRO410, press Key [0].)
1
1
X1 X16 TIMEOUT
224 225
228 229
X1 X10
252 253
254 255
BURG OUT TIMEOUT
(F, ) (MINUTES)
FIRE TIMEOUT
(F, ) (MINUTES)
CHIME TIME
(8, ) (1/4 SECONDS)
AUTO D/L ID NO.
(SEE NOTE 2)
CALLBACK SELECT
(ENTER 1 OR 2)
MA1008e/1008eM Installation Instructions
L NAPCO Security Systems
Page 17
5. GLOSSARY & PROGRAMMING DATA
Page 17
Abort Delay (Locations 208, 209; 232, 233)
A delay period that allows cancellation of the central sta-
tion report. This is done by disarming the panel within the
delay period. Program Locations 208-209 for zone selection;
Locations 232, 233 for delay time (see Time Selection). The
NTO Lug E15 will be subject to the abort delay if Untimed Output and Abort Delay are programmed for the same zone. Note: If Abort Delay is selected for a 24-Hour Zone or a
Zone-Restore Zone, the cause of the alarm must be corrected
before disarming the panel.
AC-Failure Reporting (Locations 169;173)
If AC is removed from the panel, the first three LED's will
flash slowly and a "1" will be displayed (while armed or disarmed). If disarmed, holding down Key [9] will reset the indication for about three minutes to permit arming. However, the
failure indication will return within a few minutes, whether
armed or disarmed, unless AC power is restored. If programmed for Report on Alarm, the report will be delayed for 1
hour. Restores report immediately.
Access Number for Outside Line (Locations 115, 147)
Some subscribers will have a telephone system that requires one digit to access an outside line before the telephone
number can be dialed. Also, the first dial tone encountered
(prior to the access number) may have a frequency that is
different from that of the accessed dial tone (440Hz). One or
more 4-second Pre-Dial Delay "D"s may be entered before
the access number instead of a dial tone with frequency "E".
See Pre-Dial Delay.
If your subscriber's system uses an access number:
1. Contact the telephone-equipment supplier to find out if a
dial tone other than 440Hz is received prior to dialing the
access number. If the communicator must delay before
dialing the access number instead of attempting to recognize the dial tone, find out how many 4-second delays
must be programmed.
2. For Telephone 1, (a) enter the Dial-Tone Detection "E"
or Pre-Dial Delay "D" in Location 114. Enter any extra
"D" that may be required starting in Location 115; (b)
enter the access number digit in Location 115, or the
first available location thereafter; (c) starting in the first
available location after the access number, enter any
Pre-Dial Delay "D"s needed before the second dial tone;
the Dial Tone Detection "E" for the second dial-tone fre-
quency; then the telephone number.
3. If Telephone 2 is used, repeat step 2 starting in location
146. (See Backup Reporting; Double Reporting; and
Split Reporting). Also see Dial-Tone Detection; Pre-Dial
Delay.
Alarm Codes See Report on Alarm
Alarm History
Hold-Down Key [B] will display (on the digital readout) all
alarm conditions that have occurred. While holding down Key
[B], note the number(s) displayed indicating the zone(s) violated. When the system is rearmed, the previous alarm history will stay memorized until automatically erased by a new
alarm condition. Note that Alarm History will not display Fire,
Fire Trouble, Ambush, or zones directed to Ambush, but it will
display Fire on Burg Zone alarms.
The MA1008e has a common Burglary/Fire siren output
at Terminals 3 and 4. Steady bell and pulsing bell outputs for
Burglary and Fire, respectively, are selectable options. Table
4 summarizes wiring and programming for signaling an alarm
in typical installations. Refer to Time Selection for timeout
durations.
A 1- or 2-digit code that is entered by the user prior to
disarming to access the Ambush Zone, causing a silent report
to be sent to a central station. Thus, should a user be forced
to disarm by an assailant, he can silently signal an emergency
while appearing to be merely disarming the system. The
Arm/Disarm Code must be entered less than 10 seconds after the Ambush Code for an ambush report to be transmitted.
The Ambush Zone will automatically report when programmed to report on alarm.
To program the ambush feature, (a) program Ambush to
Report on Alarm (enter a "2" in Location 168); (b) enter 1 or 2
digits as the Ambush Code In Locations 236-237; (c) enter an
Ambush alarm report code in Locations 018-019.
Inform the user what the Ambush Code is, and that his
arm/disarm code must be entered less than 10 seconds after
the Ambush Code for an ambush report to be sent.
Fire (Steady) Siren Speaker on 3 (+) & 4 (–) – 228, 229
Fire (Pulsing) Siren Speaker on 3 (+) & 4 (–) "1" in location 181 228, 229
Steady Bell Bell on 3 (+) & 4 (–) 210, 211 224, 225
Pulsing Bell Bell on 3 (+) & 4 (–) "1" in location 181 228, 229
Temporal Fire Bell on 3(+) & 4 (–) "C" in location 175 –
Untimed Output (NTO) E15 (–) & 5 (+) 096-999 –
Note: (1) For UL Residential Fire installations, use a bell on Terminals 3 (+) and 4 (-); cut Jumpers E and PS and install Jumper J2 (see Wiring
Diagram). See Time Selection for timeouts. (2) Cut Jumper to prevent the fire signal from sounding a steady siren (or bell, if Jumper E is cut). (3)
Cut Jumper D to produce an alternating two-tone siren sound.
L NAPCO Security Systems
Fire Zones only
Fire Zones only
Cut Jumper E
Fire Zones only; cut Jumper E
Provides supervised Bell Output
<300mA for strobes, etc. See NTO.
Table 4. Alarm Outputs
MA1008e/ 1008eM Installation Instructions
Page 18
Page 18
conjunction with either Direct Zone 8 to Ambush or Direct Keypad Panic to Ambush to sound are audible alarm when ambush is tripped. Also see Direct Keypad Panic to Ambush; Direct Zone 8 to Ambush.
Anti-Jam Time
If the communicator does not detect a dial tone within 12
seconds, the Anti-Jam feature will be activated. That is, the
communicator will go off-line for a 15-second anti-jam interval
in order to free the telephone circuit from incoming calls, then
make another 12-second attempt at dial-tone detection. If still
unsuccessful, the communicator will again go off-line for 15
seconds, then proceed to dial anyway.
To test the Anti-jam feature, call the alarm phone line from
a different phone line, then activate an alarm. The incoming
call should be disconnected by the control panel.
Arm Lug (Lug E4)
Lug E4 (ARM) will go to approximately 1Vdc when the system is armed. This lug may be used for auxiliary equipment.
For use, refer to the instructions furnished with the peripheral
device. Also see Sounder Output On Lug E4.
Audible Test on Arming (Location 180)
(Required for UL Mercantile installations). To test the alarm
circuit each time the system is armed, add a "1" to Location
180. The alarm is then activated briefly about 8 seconds after
the panel is armed. If the alarm does not sound, the device
may be defective.
Audio Verification on NTO Lug See Untimed Output
Auto-Bypass Zone See Remove Auto-Bypass
Auto-Download ID Number (Locations 252, 253)
Callback Select (Location 254)
Napco PCD2000 Software Version 2.E and later includes a
PC-Preset utility wherein numerous programs may be preset
for automatic remote uploading or downloading from the installation site while the computer is unattended (in standby mode).
The Auto-Download ID Number identifies the program in the
computer that will be selected. (Note that the Dealer Program
Code in the PCD2000 must agree with that of the control panel
for the remote connection to be established).
At the installation site, program the Auto-Download ID Number in Locations 252 and 253, in decimal numbers, corresponding to that in the computer. Also program the Callback Telephone Number of the computer. If two phone numbers
are programmed, select the phone to be called in Location
254. Then, arm the panel, disarm and, within five seconds,
access Function 5 to execute an Auto-Download.
Auto-Reset (Location 200-201)
Auto-Reset After Alarm Timeout (Location 180)
If a zone signals an alarm and is selected for Auto-Reset, it
will automatically rearm itself soon after the alarm condition is
removed. Auto-Reset may be delayed to occur after the timeout period by programming a "2" in Location 180.
Zones 1--8/Panic that are not programmed for Auto-Reset
will not be capable of signaling another alarm until (a) the
cause of the alarm has been removed and (b) the panel is disarmed.
Also see Swinger Shutdown.
Backup Reporting (Location 178)
When Backup Reporting is selected and the communicator
does not reach the first telephone number after two attempts,
seven attempts will be made to reach the second telephone
number. Enter Subscriber Identification Numbers for Telephone 2 (Locations 132-143) and other information required
for Telephone 2 (Locations 144-163). If Double Reporting is
selected with Backup Reporting, all reports sent to the first telephone number will also be transmitted to the second telephone
number. However, if the first transmission fails, two reports will
be sent to Telephone 2 (Double Reporting). Note: Subscriber
Identification Numbers for both Telephones 1 and 2 must be
entered, even if they are the same.
Battery
12VDC standby power source in the control panel to provide backup protection in the event of a power loss. The 4AH
battery is supplied; the 7AH is available as an option. Note
that the battery is an integral part of the system. It must be
installed, even if AC power is present.
Battery Lug (Lug E14)
This is a fused battery output (3A) designed primarily for
use with the MVA-1000 Talking Siren Driver.
Burg Lug (Lug E14)
Lug E10 (BURG) will go to about 1VDC when a burglary
alarm is tripped. E10 may be used to trip an LW-900 LongRange Wireless interface. Or, a relay (400Ω minimum) may
be connected between E10 and Terminal 5 (+ AUX. POWER)
if a diode is wired in series (cathode to E10; anode to relay
coil).
Burglary Output See Alarm Outputs
Burglary Output on Ambush See Ambush Code
Callback Telephone Number 1 (Locations 270-285;
PROM Page-1 Locations 014-029)
Callback Telephone Number 2 (Locations 286-301,
PROM Page-1 Locations 030-045)
Number of Rings (Location 269; PROM Page-1 Location
013)
The control panel will call back the PCI2000 as a security
check prior to downloading when using the Callback Method.
Provisions for two callback telephone numbers are made for
the Auto-Download Mode. Program at least one callback
number starting in Location 270. (Remember that a "D" or an
"E" must be programmed before the telephone number - see
Telephone Numbers). The panel will initiate the callback after
waiting 15 rings, unless programmed otherwise. To change
the number of rings before callback, enter the desired number
of rings (3 minimum, 15 maximum) in Location 269. Also see
Auto-Download ID Number.
Chime Zone (Location 088-089)
Chime On with Group Bypass See Group Bypass
This annunciator feature may be programmed for any zone
to sound at the keypad while disarmed when the zone goes
into trouble. Hold down Key [5] until the function beep sounds
to enable or disable the Chime. Chime duration is programmable (Locations 230, 231) in units of 1/4 seconds. See Time Selection. The Chime-Zone number will be displayed for the
duration of the programmed chime time, or for as long as the
zone is open (or shorted), whichever is greater. Also see
Never-Arm Zone. Note: A "1" in Location 230 will prevent the
sounder from coming on.
MA1008e/1008eM Installation Instructions
L NAPCO Security Systems
Page 19
Page 19
Closing Report (Select User(s) Closing) (Location 174)
Force Arm Report (Locations 179; 038-039)
Status Report (Locations 179; 000-029; 038-039)
Include Manual Bypass in Force-Arm/Status Report
(Location 183)
On arming, the communicator can transmit a closing
code for each user, a Force-Arm Code, and a Status Report that identifies the problem zone to the central station.
Note that Subscriber Identification Numbers (Locations
108-111; 140-143) and Closing Codes (Locations 030-037)
must be entered for any closing report. Program closing
report (Select User(s) Closing, Location 174) to report each
time the panel is armed. Each of up to four users may
have his own Closing Code (Locations 030-037).
Select Force Arm Report ("2" in Location 179) to report
only when arming with an auto-bypassed zone. This transmission will consist of a Closing Code followed by a ForceArm Code. Select both closing report and Force Arm to
always send a closing report, and a Force Arm report only
if one or more zones were auto-bypassed. Also see Prior-ity Zone with Bypass.
Select Status Report ("4" in Location 179) to send a
Force Arm report followed by a Status Report that identifies
the auto-bypassed zone(s). The second Alarm-Code location is usually used for this purpose. If this location is vacant, the first location will be used.
To include manual bypasses in a Force Arm/Status Report, program a "4" in Location 183. (Either Force Arm or
Status Report must also be programmed).
Following is an example of a typical Force-Arm/Status
Report.
Example. A burglar breaks into a commercial establishment during the night, breaking the window foil. The Alarm
Subscriber Identification Number is '"123"; the Alarm Code
is "1" (Burglary Zone 1); the Opening/Closing Subscriber
Identification Number is "456"; the Force-Arm Code is "F";
the Closing Code for User 1 is "C". The communicator will
send the following report to the central station (single-digit
data format):
1231 - Sent when alarm occurs.
456B - Opening; User returned and inspected damage.
456C - Closing.
CCC1 - User 1 rearmed.
456F - Force Arm.
FFF1 - Zone status at time of closing: Window foil still
Control-Panel Restore See Restore Report
broken. Zone 1 auto-bypasses; repair required.
Data Format (Locations 113,145)
Consult the central station to find out which of the following formats to use.
Extended Format. Extended-format reporting allows
the communicator to transmit an extra digit to the central
station. This extra digit is generally used to report the user
or the zone on which the event occurred.
Example. An installation uses the following programmed transmission information: Subscriber Identification Number is ;"678"; a Closing Report is selected for User
3; Extended Format Closing Code is "C3" (Closing, User
3). If User 3 closes, the communicator will transmit:
678C - Subscriber "678" has closed.
CCC3 - Closing, User 3.
Extended Format may be used with most central-station
receivers. Most receivers capable of recognizing multiple
reporting will also recognize Extended Format. The central
station will indicate the event codes to be programmed.
Extended Format does not require any programming in Locations 113 and 145. To use Extended Format, follow
Steps 2 through 5 of Two-Digit Event Code Format later in
this section.
Single-Digit Event Code Format. If the receiver cannot accept extended reporting,
1. Program a "1" in Location 113 (and 145 for a second
telephone number, if used). See Double Reporting
and Backup Reporting.
2. Enter the first digit for any Alarm/Trouble Code, Restore Code and Opening/Closing Codes.
Note: If it is desired to have a Single-Digit Event Code
for one telephone number and Extended Format for the
other, program both digits for all event codes. Use the first
digit to indicate the alarm type and the second digit to indicate the zone. The telephone number with a "1" in Location 113 (or 145) will transmit only the first digit. The other
telephone number will use both digits. (Single-Digit Format
will ignore the second digit of the event code).
Two-Digit Event Code Format. Some central-station
receivers require that a two-digit code be sent in each report.
Example. In a certain installation, the Alarm Subscriber
Number is "123"; a burglar alarm occurs on Zone 1 (Alarm
Code "31"). The communicator will send "12331".
To use Two-Digit Event Code Format,
1. Program a "2" in Location 113 (145 for a second tele-
phone number, if used). See Double Reporting and Backup Reporting.
2. Enter an Alarm Code (Locations 000-029) for each
zone or condition to report on alarm (see Report on Alarm) or for a Force-Arm/Status Report as follows:
a. Enter the first digit of the Alarm Code. (This digit
may be used to indicate alarm type.)
b. Enter the second digit of the Alarm Code. (This
digit may be used to indicate the zone.)
3. Repeat Step 2 to enter Restore Codes (Locations
040-069) for each zone selected for Control-Panel Restore or Zone Restore (see Restore Report).
4. If Opening Report or Opening Report After Alarm is
selected, enter a two-digit Opening Code for each
user (Locations 070-077). See Opening Report; Opening Report After Alarm.
5. If Closing Report is selected, enter a two-digit Closing
Code (Locations 030-037) for each user. If a Force
Arm or Force-Arm/Status Report is selected, also enter a two-digit Force-Arm Code (Locations 038, 039).
Note:Single-Digit Format will override Two-Digit For-
mat in Locations 113 and 145 if both are pro-
grammed.
Sum-Check Format. Sum Check is a sophisticated
data format used to enhance the speed and check the accuracy of the received transmission. This format should be
preferred if the central station is capable of receiving it.
After transmitting the Subscriber identification Number
and the event code, the communicator sends a verifying
digit that is the sum of both. The receiver compares the
L NAPCO Security Systems
MA1008e/ 1008eM Installation Instructions
Page 20
Page 20
verifying digit with the sum of the other two numbers to check
transmission accuracy. To select Sum Check, program a "4"
in Location 113 (or 145 for a second telephone number, if
used).
Day Zone (Locations 186, 187)
Disable Day-Zone Report See PIR Zone
Display Day Zones After Reset (Location 078)
A Day Zone is a Burglary Zone that will cause visual and
audible indication at the keypad if the loop has an open condition only when disarmed. This feature may be used to warn of
trouble during the day, when the control panel is not armed. If
the Day Zone experiences a problem (a break in a window
foil, for example), the green STATUS LED on the keypad will
flash, the sounder will beep repeatedly, and the display will
indicate the problem zone(s). Hold down Key [9] to silence
the sounder and clear the display. Arm and disarm the panel
to reset the Day Zone.
If a "1" is programmed in Location 078 (Display Day Zones After Reset), the Day-Zone number(s) will continue to display
after the sounder is silenced until the condition is corrected,
and the Day Zone will auto-reset without the need to arm/
disarm.
Note: For high security Day-Zone supervision, also program Disable Fault Find (enabling Fault Find will disable Day-
Zone supervision).
Also see Watch On with Group Bypass.
Dealer Program Code (Locations 244-249)
This code is required to enter the Dealer Program Mode.
The default Dealer Program Code is 4,5,6,7,8,9, however this
code must be changed to preserve system security. Reprogram the 3- to 6-digit Dealer Program Code starting in location
244. Note: (1) The Dealer Program Code must not start with
the same numbers as the User Program Code. (2) The
Dealer Program Code also serves as your Download Security Code.
Dial-Tone Detection (Locations 116,148)
At least one Dial-Tone Detection entry is usually required
for each telephone number used to ensure that a dial tone is
present before the communicator dials.
When an "E" is programmed before the first digit of an outside telephone number, the communicator dial-tone detection
circuit is set to detect the standard 440Hz dial tone. The "E" is
generally entered in Location 116 for Telephone 1 and Location 148 for Telephone 2, if used.
It may be necessary to program at least one 4-second Pre-Dial Delay before a Dial Tone Detection "E". With certain nonstandard exchanges, Pre-Dial Delay "D"s may be used without a Dial-Detection "E". (See Access Number for Outside Line; Pre-Dial Delay).
Direct Keypad Panic to Ambush (Location 080)
Direct Zone 8 to Ambush (Location 080)
Program Direct Keypad Panic to Ambush ("1" in Location
080) to free Zone 8 for wireless use while providing silent
panic. Or, select Direct Zone 8 to Ambush ("2" in Location
080) to have wireless transmitters that are mapped to Zone 8
send a silent report. (These will report using the Ambush
Code).
Disable Bell Test (Location 182)
Program an "8" in Location 182 to prevent unauthorized
persons from sounding the bell.
Disable Callback-Method Download (Location 080)
Data may be remotely downloaded to an MA1008e using
Napco Quickloader™ software and interface if the correct
download security code is known. Program this feature to
prevent downloading to an unattended panel.
Disable Day-Zone Report See PIR Zone
Disable Display Bypass (Location 081)
For added security, this feature disables Hold-Down Function 2 and the BYPASS LED after exit delay expires.
Disable Fault Find (Location 182)
When the Fault-Find mode is accessed (Hold-Dawn Key
[7]), two things occur: (a) the loop response of all zones is preset to 7mS (fastest loop response), and (b) securing a zone in
trouble will cause the sounder to beep for about 2 seconds.
This set of conditions aids bath installer and user. The installer, tapping and poking at suspect points, can easily locate
swingers by listening for the beep. Similarly, the user can
confirm the repair of a zone in trouble by listening for the beep
and thus eliminate the need of returning to the keypad to visually check after each attempt.
Hold dawn Reset Key [9] to restore normal operation.
Arming the system successfully will automatically cancel the
Fault-Find mode. Program a "1" in Location 182 to prevent
unauthorized use of the Fault-Find mode.
Disable Function-6 Download (Location 080)
An "8" in Location 080 will prevent manual remote
downloading at the panel. See Manual Download.
Disable Low-Battery Display See Low Battery
Display Any Bypass (Location 183)
Hold-Down Function 2 (Display Bypass) normally displays
manually-bypassed zones only, when Display Any Bypass is
selected and a zone is auto-bypassed, the yellow BYPASS
LED will light, and Hold-Down Function 2 will display AutoBypassed and Priority bypassed Zones as well.
Display Day Zones After Reset See Day Zone
Display Open Zones (Location 081)
A "4" in Location 081 will cause any non-24-Hour zone that
is open (or shorted) while disarmed to automatically display at
the keypad in addition to the flashing green LED.
Don't Wait for Handshake, Telco 1 (Location 304)
Don't Wait for Handshake, Telco 2 (Location 304)
Select this feature for telephones not reporting to a central
station. (This feature may be useful for demo purposes).
Double Reporting (Location 178)
When Double Reporting is selected, only information that
is successfully sent to Telephone 1 will be sent to Telephone
2 as well. To program, enter an "8" in Location 178. Enter
Subscriber Identification Numbers for Telephone 2 (Locations
132-143) and related information required for Telephone 2
(Locations 144-163).
If Backup Reporting is selected with Double Reporting,
reports sent to the first telephone number will also be sent to
the second. However, if the first transmission fails, two reports will be sent to Telephone 2. Split Reporting will override
Double Reporting if both are programmed.
Note: Subscriber Identification Numbers for Telephones 1
and 2 must be entered, even if they are the same.
"E" Lugs see INDEX
MA1008e/1008eM Installation Instructions
L NAPCO Security Systems
Page 21
Page 21
Enable Communicator-Confidence Test (Location 182)
Program a "4" in Location 182 to enable the Communica-
tor-Confidence Test. This feature checks the telephone line
for the presence of a dial tone only in those systems that are
programmed to communicate with a central station. Note:
Do not arm and disarm the panel just before making this test.
Hold down Key [6] until the sounder starts to pulse. If the
line is okay, the pulsing will stop; if not, a steady tone will
sound (check phone lines). To silence, hold down Key [9].
Enable Download with Answering Machine (Location 082)
Permits downloading to a telephone with an answering
machine (factory programmed). After one ring, the panel will
listen for the modem tone produced by the PCI2000. If recognized, the panel will go into line seizure and, if security
codes match, establish connection with the PCI2000.
Enable Keypad Auxiliary Panic (Location 082)
This feature may be enabled only if all system keypads
are F/P/A-panic compatible. (Cut panic-enabling jumpers in
all keypads). Pressing the [B/A] and [#] keys simultaneously
will activate Keypad Auxiliary Panic. This is a "report only"
feature. Program an Alarm Code in Locations 062-063 and a
Group-2 Subscriber ID Number. A successful report will be
indicated by a ringback at the keypad. In order to prevent
multiple alarms from being transmitted, subsequent AuxiliaryPanic alarms cannot be tripped for five minutes. Also see
Keypad Aux. Alarm on NTO Lug.
Enable Keypad Fire Panic (Location 082)
This feature may be enabled only if all keypads in the system have the F/P/A-panic capability. (Cut panic-enabling
jumpers in all keypads). Pressing the [9/F] and [#] keys simultaneously will activate Keypad Fire Panic.
Enable Keypad (Police) Panic See Panic Zone
Enable Keypad Sounder on Alarm (Locations 164-165)
Programmable for Zones 1-7 and Keypad Panic. When
tripped, a steady tone will sound at the keypad until the panel
is disarmed.
Enable Keypad Tactile Beep (Location 181)
Causes the sounder to beep briefly with each press of a
button. For RP1000LCD and RP1000eLCD keypads: Cut
the keypad tactile-beep jumper to prevent a double beep
from sounding.
Exit/Entry Delay (Locations 218-223)
Permits exit and entry through the Exit/Entry Zone(s) (see
Locations 202-205) after the system is armed without setting
off an immediate alarm. Exit delay allows the user to leave
the premises after the panel has been armed. Entry delay
allows the user time to enter and disarm the panel. Upon
entering, the keypad sounder will emit a steady tone to remind the user to disarm.
Two separately-programmable entry delays are provided
to accommodate different entry zones (only one exit delay is
provided). If two or more Exit/Entry Zones are entered in
succession, the delay programmed for the last Exit/Entry
Zone entered will take precedence over all others.
Exit time (Locations 218-219) and entry time (Locations
220-223) may each be programmed for up to 255 seconds
(4¼ minutes). See Time Selection. If times are not programmed, exit time will be 60 seconds; entry delay will be 30
seconds. (In UL installations, exit time may not exceed 60
seconds; entry time may not exceed 45 seconds).
Entry delay may be cancelled by holding down Key [4]
(Instant Protection) prior to or after arming, however it will be
automatically reinstated upon disarming.
Exit Entry Follower (Locations 206, 207)
A zone programmed as an Exit/Entry Follower will ignore
detection during the exit delay, and only during entry delay if
the Exit/Entry Zone is entered first. Thus, detection devices
(passive infrared detectors, for example) along the path between the keypad and the exit/entry door will not signal an
alarm during exit/entry delay under normal conditions. However, if a device in the Exit/Entry Follower Zone detects a violation when the exit/entry door has not first been entered,
there will be no entry delay and the Exit/Entry Follower Zone
will go into an instant alarm.
If the panel is armed with the entry delays cancelled
(Instant Protection), any violation on the Exit/Entry Zone or
the Exit/Entry Follower Zone will cause an immediate alarm.
Extended Format See Data Format
Failure to Communicate on NTO Lug See Untimed Output
Fault Find See Disable Fault Find
Fire Lug (Lug E9)
Lug E9 (FIRE) will go to about 1VDC when a fire alarm is
tripped. E9 may be used to trip an LW-900 Long-Range
Wireless Interface. Or, a relay (400Ω minimum) may be connected between E9 and Terminal 5 (+ AUX. POWER) if a
diode is wired in series (cathode to E9; anode to relay coil).
Fire Zone (Terminals 11 & 12)
Fire on Burg Zone (Locations 306-307)
(Note: Do not use Fire Zones in Mercantile installations).
The Fire Zone is indicated by the red FIRE/TROUBLE keypad LED. Normally-open devices are connected across Terminals 11 and 12, in parallel with the 2200Ω end-of-line resistor (see Wiring Diagram). A short across the Fire Zone will
cause a fire alarm: the red LED will light and the sounder will
pulse; an open circuit (trouble) will cause a blinking red LED
and a pulsing sounder after a 10-second delay. The sounder
may be silenced using Reset Key [9]. The LED will go off
within 30 seconds after reset if the alarm or trouble is cleared.
Note: Even if the Fire Zone is not used, the end-of-line resistor must be installed.
For the Fire Zone to report on alarm (Location 168) or to
restore (Location 172), program Alarm Codes in Locations
016-017 and Restore Codes in Locations 056-057. Trouble
and Restore Trouble on all Fire Zones (including Fire on Burg
Zones, see below) are reported in Locations 020-021 and
060-061, respectively. To reset Fire, program a "2" in Loca-
tion 181 (see Reset Fire Zone).
Any Zone 1-7 may be converted to a Fire Zone by programming it for Fire on Burg Zone, however that zone must
be programmed for 24-Hour Protection as well. No other
zone feature except Untimed Output may be selected for that
zone, however program reporting features as required; Fire
alarms will activate a steady siren unless Pulsing Fire Output
is programmed. Note: Only 4-wire smokes may be used on
zones programmed as Fire on Burg Zone.
When an alarm condition is detected on any Fire Zone, a
Fire Alarm Verification feature will cause all zones to power
down for 10 seconds. Power is restored and a 4-second
L NAPCO Security Systems
MA1008e/ 1008eM Installation Instructions
Page 22
Page 22
power-up time is started. Thereafter, the zone will be active
again. This represents a total processing time of 14 seconds
from the time the alarm is first detected. If an alarm condition
still exists or reoccurs within 2 minutes, an alarm will be initiated, otherwise the zone will return to its original state. Note:
Alarm restores are sent individually; trouble restores are not
sent until all fire troubles are restored.
Force-Arm Report See Closing Report
Ground-Start Module, GSM-400 (Lug E3)
If the dial tone is not continuously active, Ground-Start
Module Model GSM-400 will be required at Lug E3 to establish the dial tone. For installation, refer to the instructions furnished with the GSM-400.
Group Bypass (Location 196, 197)
Chime On with Group Bypass (Location 081)
Group Bypass removes a programmed group of zones
from the system. It is often used to deactivate some or all interior zones simultaneously so that the user may move freely
throughout the premises but still be protected from intrusion
through armed perimeter zones.
Group Bypass is executed by pressing Key [B] twice; the
yellow BYPASS LED on the keypad will light. When the panel
is subsequently disarmed, all bypassed zones automatically
revert to non-bypassed zones. The zones bypassed may be
checked by holding down Key [2] (Display Bypass) until the
beep sounds and all zones have been displayed.
When a "1" is entered in Location 081 (Watch On with Group Bypass), all Day Zones will be activated simultaneously
(Watch Mode) when Group Bypass is activated. See Watch On with Group Bypass.
When a "2" is entered in Location 081 (Chime On with Group Bypass), the Chime Mode will be enabled for all programmed zones when Group Bypass is activated. Note that
(a) Group Bypass need not be programmed for any zone to
use this feature; (b) if a zone is programmed as a Chime
Zone, it may not be programmed for Group Bypass; and (c) if
this feature is programmed, Hold-Down Function 5 (Chime On/Off) is disabled. Also see Chime Zone.
Include Manual Bypass in Force-Arm/Status See Closing
Report
Key Input on Zone 7 (Location 183)
For a remote arm/disarm keyswitch station, program an "8"
in Location 183 and wire a normally-open momentary keyswitch to Zone 7. Supervise the keyswitch with an end-of-line
resistor in parallel and program Zone 7 for 24-Hour Protection.
This feature reports as User 1.
Keypad Aux. Alarm on NTO Lug See Untimed Output
Keypad Panic See Panic Zone
Line-Reversal Module, M278
The Line-Reversal Module allows the control panel to be
monitored by a central station through leased lines. On alarm,
the module reverses normal line voltage polarity. For details,
see instructions furnished with the module.
Listen-in Lug (Lug E5)
If the installation requires one, connect a Listen-In module
to Lug E5. The 12V at Lug E5 will drop to zero when the communicator goes off-hook. The voltage will return when the
transmission is completed and the module can occupy the
phone line. Note: A Listen-In Module may not be used in UL
installations.
Also see Untimed Output: Audio Verification on NTO.
Loop Response (Locations 214-217)
Loop response is the amount of time that a normally
closed circuit must remain open, or a normally-open circuit
remain closed, to trip an alarm. The slower the loop response, the more immune the system will be to intermit tents
("swingers"). Selectable loop-response times are:
750mS (.75 sec.): The slowest loop-response time, rec-
ommended for use with magnetic contacts, window foil,
etc. Unless programmed otherwise, loop-response
time will be .750mS (milliseconds) for all zones.
50mS (.05 sec.): Used for momentary panic buttons and
area protection devices, such as photoelectric eyes,
passive infrared sensors, floor mats, etc.
7mS (.007 sec.): An extremely fast loop response used
A low-battery alarm will signal a system trouble ("2'" flashing with LED's) when the battery terminal voltage drops below
11.5V (nominal). A low-battery condition may report to a central station by programming a "4" in Location 169. LowBattery restores report upon detection of a specified terminal
voltage during a dynamic battery test. See Bell/Battery Test
(Hold-Down Function 1).
If Disable Low-Battery Display is programmed, there will
be no indication of a low-battery system trouble at the keypad
unless accompanied by another system trouble.
Never Arm (Locations 090-091)
A zone programmed as Never-Arm cannot go into alarm.
When tripped, it will display at the keypad when Hold-Down
Function 3 (Display Status) is selected. A chime will sound at
the keypad while armed or disarmed if Chime is programmed
for that zone and enabled. (The display will also indicate the
zone if Display Chime is programmed). This feature is suggested for use as a garage-door or driveway monitor or similar
application.
No AC See AC-Failure Reporting
No End-of-Line Resistor (Locations 088-087)
Program for any normally-closed zone that is not wired
with an end-of-line resistor.
No Opening Report After Alarm on Zone 6 (Location 183)
If Opening Report After Alarm is selected and a TM900
Test Timer is installed, wire the TM900 to zone 6. Program a
"2" in Location 183. Also see Opening Report After Alarm.
NTO Lug See Untimed Output
Number of Rings See Callback Telephone Number 1, 2
Opening (Closing) Codes See Opening (Closing) Report
Opening and closing reports are generally used in commercial installations. On disarming, the communicator can
send an opening code for each user (Select User(s) Open-ing), or it may transmit only when the panel is disarmed
MA1008e/1008eM Installation Instructions
L NAPCO Security Systems
Page 23
Page 23
after an alarm has occurred (Opening Report After
Alarm). Note that Subscriber Identification Numbers
(Locations 108-111; 140-143) and Opening Codes
(Locations 070-077) must be entered for either opening report;
Program Select User(s) Opening (Location 176) to report
each time the panel is disarmed. Each of up to four users
may have his own Opening Code (Locations 070-077). If
selecting Opening Report, do not select Opening Report After Alarm.
Program Opening Report After Alarm ("1" in Location
179) to report only when disarming after an alarm. This feature may be used by the central station to verify that the
subscriber has responded to the alarm and disarmed the
panel. If Opening Report After Alarm is selected, do not
select Opening Report.
Panic Zone
Enable Keypad Panic (Location 182)
To enable Panic from the keypad (K/P on Programming
Sheet), program a "2" in Location 182. The Panic Zone is
tripped by simultaneously pressing Keys [*] and [#] and may
be programmed to send a silent alarm to a central station,
activate an audible alarm, or both. (For silent panic, see
Direct Keypad Panic to Ambush.) Keypad Panic may be
disabled at individual keypads by cutting a jumper on the
keypad circuit board. Also see Enable Keypad Auxiliary Panic; Enable Keypad Fire Panic.
Remote momentary pushbutton panic switches
(normally open) are connected across the two white wires
on the keypad (only on those keypads that support remotepanic switches). In UL systems, remote panic buttons must
be located in the same room as the keypad.
Program for any zone containing a PIR or dualtechnology sensor, floor mats, door contacts, etc. Upon
powering up the control panel, a 3-4 minute delay on these
zones allows sensors to stabilize. For power-up delay only,
do not program Sensor-Watch Time (Locations 094-095,
see Time Selection). Power-up delay may be cancelled by
holding down Reset Key [9] until the function beep sounds.
If no trip is detected within the programmed SensorWatch time, a Day-Zone trouble will be transmitted to the
central station, if programmed to report ("8" in Location
158). There is no audible indication at the keypad.
Program Sensor Watch in Locations 094-095. Select a
value according to the expected activity within the coverage
area while disarmed. In calculating the Sensor Watch time,
note that only the disarmed hours (the time between armed
periods) are added. In moderate traffic areas, a Sensor
Watch time of perhaps 15 hours may be appropriate,
whereas in remote areas, a time of 60 hours or more may
be in order. Sensor Watch time should be calculated for the
PIR Zone with the least amount of traffic. However, if no
activity is expected on a zone (in an attic, for example) that
zone should not be programmed as a PIR Zone, (if Locations 094-095 are left blank, PIR Zones will still be delayed
on power-up, but they will not be monitored for activity).
If this feature is selected and any other zones are pro-
grammed as Day Zones, a "2" may be programmed in Location 079 (Disable Day-Zone Report) to inhibit Day-Zone
trouble reports. A Day-Zone condition will still display at the
keypad, but a trouble report at the central station will now
indicate a PIR-Zone trouble.
Power Up in Last State (Location 180)
If programmed, the panel will return in its last state
(armed or disarmed) when AC is restored after a lengthy
power failure (and the backup battery is depleted). If the
panel returns armed and closings are programmed to report
for User 1, it will report as USER 1.
Pre-Dial Delay (Locations 114,146)
A Pre-Dial Delay may be used whenever a delay is required before dialing. It is usually required to program Dial-Tone Detection, which causes the communicator to wait for
a dial tone before dialing (see Dial-Tone Detection). Certain
telephone exchanges send a nonstandard dial tone that the
communicator may not be able to detect. With these nonstandard exchanges, it is possible to program Pre-Dial De-lay rather than Dial-Tone Detection. This will cause the
communicator to wait for a predetermined time before dialing rather than look for a nonstandard dial tone.
Contact the telephone-equipment supplier to find out
how long a delay is required before dialing. Select Pre-Dial Delay by programming one "D" for each 4-second delay required. Enter Pre-Dial Delay "D"s starting in Location 114
for Telephone 1, and starting in Location 146 if Telephone 2
is used. See Backup Reporting; Double Reporting; Split Reporting. Also see Access Number for Outside Line.
Priority Zone (Locations 190, 191)
A zone that will prevent arming if in trouble. If an attempt is made to arm, the sounder will emit a steady tone
and a "P" will be displayed. The priority condition may be
silenced by disarming. Any zone may be selected as a Priority Zone. A zone in trouble that is neither a Priority Zone
nor an Auto-Bypass Zone will cause an alarm on arming.
Priority Zone with Bypass (Locations 188, 189)
A Priority Zone that will permit arming if the priority condition is bypassed by pressing Reset Key [9], then entering
a User Code. The zone will auto-bypass and, if status is
reported, the condition can be communicated to a central
station.
Any zone not selected as a Priority Zone may be programmed as a Priority Zone with Bypass. When programming a zone as Priority with Bypass, do not program Re-move Auto-Bypass. Also see Display Any Bypass.
Pulsing Fire Output See Alarm Outputs
Receiver Format (Locations 112, 144)
The communicator can transmit to any standard central
station receiver. A receiver format must be programmed for
each telephone number used, but a different format may be
assigned to each.
Refer to Double Reporting and Backup Reporting to determine if Telephone 2 will be programmed. Call the central
station for each telephone number to check the type of receiver in use. From Table 5, enter the receiver format for
each phone number.
L NAPCO Security Systems
MA1008e/ 1008eM Installation Instructions
Page 24
Page 24
Entry Receiver Format
blank
Ademco, Silent
Knight Slow
Sescoa, Vertex,
1
2 Radionics Fast 1800 13/12 400
3 Silent Knight Fast 1900 40/30 560
4
5 Universal Hi-Speed
6 Reserved
8
DCI, Franklin
Radionics, DCI,
Franklin Slow
Add "8" for 2300Hz Handshake; do not add if 1400Hz Handshake
Table 5. Receiver Formats
Data Freq.
(Hz)
1900 60/40mS 600mS
1800 30/20 800
1800 60/40 600
Duty Cycle
(On/Off)
Interdigit
Time
Program the receiver-format entry in Location 112 for
Telephone 1 and Location 144 for Telephone 2, if used.
Receiver See R1000 Installation Instructions WI604
Remote Status LED on NTO Lug (Location 082)
When a "2" is programmed in Location 082, a remote
Status LED connected to the NTO Lug will go on when the
lug is low, giving the same indication as the keypad
STATUS LED. In this application, do not use the NTC Lug
as an output. Connect the LED cathode to the lug through
a 560Ω resistor, and the anode to +12V AUX. POWER
(Terminal 5).
Remove Auto-Bypass (Locations 192, 193)
All zones are normally Auto-Bypass Zones and will be
bypassed if in trouble when arming. (Note that the exit/
entry door must be closed before arming, otherwise the
Exit/Entry Zone will be auto-bypassed). A momentary
beep will sound at the keypad to warn that the system has
been armed with a zone in trouble. Hint: Remove AutoBypass from Follower Zones containing a keypad and PIR
to permit arming while motion is sensed. The zone will be
secure by the time exit delay has expired.
Note: If auto-bypass is removed from a zone in trouble that is not programmed for Priority arming (Locations
190, 191), that zone will cause an alarm on arming. If selecting Priority Zone with Bypass, do not select Remove Auto Bypass.
For UL installations, non-24-Hour Zones with auto-
bypass (Remove Auto-Bypass not programmed) must be
programmed for Priority Zone with Bypass. If an attempt is
made to arm with these zones in trouble, the sounder will
come on, a "P" will be displayed, and the panel will not arm
(enter a valid arm/disarm code to silence the sounder and
clear the display). To arm, hold down Reset Key [9] for
about 2 seconds, then enter the arm/disarm code.
Report on Alarm (Locations 166-169)
Violation of a zone selected to report on alarm will
cause the communicator to transmit the code selected for
that zone to the central station. Enter Alarm Codes
(Locations 000-029) for each zone to report on alarm, even
if identical codes are used for different zones.
Reset Fire (Location 181)
If detection devices in use require removal of DC voltage to reset, program a "2" in Location 181 and wire the
device power leads to Terminals 11(+) and 12(–) for twowire devices, or Terminals 11(+) and 13(–) for four-wire
devices (see Wiring Diagram). Holding down Reset Key [9]
until the sounder beeps will momentarily remove power
from Terminal 11.
Reset Shock Sensors on Arming (Location 305)
Select for detection devices that require a brief power
interruption to reset; wire the device power leads to Terminals 11 and 6. Arming the system will momentarily remove
power from the Fire Power terminal to reset the device.
Reset Test Timer on Report See Test Timer
Restore Report
Restore, Control-Panel (Locations 170-173)
Restore, Zone (Locations 184,185)
If programming Zone Restore, Control-Panel Restore
must be programmed as well. When selecting a Restore
Report, (a) Subscriber Alarm/Restore Identification Numbers must be programmed for Telephone 1 (Locations 100-
107) and Telephone 2 (Locations 132-139), if used; and (b)
Restore Codes (Locations 040-069) must be entered for
each zone selected to report a restore.
The communicator can transmit a report to the central
station when a zone or the control panel is restored. To
select the time of reporting, refer to Table 5.
Select User(s) Closing See Closing Report
Program: for Control-Panel Restore to be sent: and for Zone Restore to be sent:
Instant Auto-Reset (Locations 200,
Auto-Reset After Alarm Timeout
(Locations 200, 201; "2"
201)
in Location
180)
(See Note 2) Zone Repaired with Panel
No Auto-ResetWhen panel is disarmed (regardless of zone condi-
When (a) zone is repaired; or (b) control panel is
When (a) resets (alarm times out & zone repaired);
Note: (1) 24-Hour Zone restores are sent as shown under Zone Restore. (2) It is recommended that Zone-Restore Zones
or 24-Hour Zones be programmed with Auto Reset or Priority Zone to prevent accidental auto-bypassing of a latched zone.
MA1008e/1008eM Installation Instructions
disarmed
or (b) when panel is disarmed.
tion)
Table 6. Restore Reports
When zone is repaired, whether panel is armed or disarmed
When zone resets (alarm times out & zone is repaired) whether panel is
Armed
When panel is disarmed When panel is armed & disarmed
armed or disarmed.
Disarmed
again
L NAPCO Security Systems
Page 25
Page 25
Select User(s) Opening See Opening Report
Selective Bypass (Locations 194,195)
Removal of one particular zone from the system. Any or
all Zones 1-7 programmed for Selective Bypass may be removed from the system, but each must be removed separately.
Selectively bypass a zone by pressing Bypass Key [B]
followed by the zone number. The next time the panel is
disarmed, all bypassed zones will automatically revert to
non-bypassed zones.
When one or more zones is bypassed, the yellow BYPASS LED on the keypad will light. The zones bypassed
may be confirmed by holding down Key [2] (Display By-pass) until the function beep sounds; with the key depressed, the bypassed zones will be displayed.
Sensor Watch™ See P/R Zone; Time Selection
Service Code See User 5 Service Code
Single-Digit Format See Data Format
Smoke Detectors (Terminals 11 & 12)
Connect smoke detectors as shown on the Wring Diagram. Note that Terminals 11 and 12 may be used for the
Fire Zone only. Up to 10 compatible two-wire smoke detectors may be "daisy-chained" together. Subtract smokedetector alarm current from auxiliary standby current. See
COMPATIBLE UL-LISTED DEVICES.
Note: If they are of the self-resetting type, power 4-wire
smokes from the Constant Auxiliary Voltage Output at Terminal 5 instead of Terminal 11.
Sounder Output on Lug E4 (Location 180)
When an "8" is programmed in Location 180, Lug E4 will
go low whenever the keypad sounder is activated. This feature disables Lug E4 for use as an Arm Lug (see Arm Lug).
Split Reporting (Location 179)
Split Reporting causes all reports except Openings,
Closings, and Test Timer to be sent to Telephone No. 1,
while Openings, Closings, and Test Timer report to Telephone No. 2. (Split Reporting overrides Backup Reporting
or Double Reporting if either combination is programmed).
Enter Subscriber ID's (Locations 132-143) and other information (Locations 144-163) required for Telephone 2. Note
that Subscriber ID Numbers for Telephones 1 and 2 must
be entered, even if they are the same.
Different Subscriber Identification Numbers (account
numbers) may be used by the central station to distinguish
Alarm and Restore Reports (Locations 100-107) from
Opening and Closing Reports (Locations 108-111). Similarly, different numbers may be used to distinguish Alarm/
Restore Reports for Group-1 Zones (Zones 1-7) from Group
Zones (Fire to Low Battery). Both groups must be programmed, even if both use the same number. See Report on Alarm; Restore Report; Opening Report; Closing Report.
Furthermore, if a second telephone is used, different
Subscriber Identification Numbers may be required for
Alarm/Restore Reports (Locations 132-139) and Opening/
Closing Reports (Locations 140-143). As above; both
groups must be programmed, even if both use the same
number. See Double Reporting; Backup Reporting.
Note:
1. If the central station cannot accept two-digit or extended event codes, the Alarm and Restore Codes
may be the same as the Opening and Closing Codes;
or, the Alarm/Restore Codes may be the same for
Groups 1 and 2 if the respective Subscriber Identification Numbers are different.
2. Starting at the left-most location, enter at least 3 digits
for each Subscriber Identification Number, even if the
first two are zeros. A fourth digit is available for those
receivers capable of recognizing 4-digit subscriber
codes.
Sum Check See Data Format
Swinger Shutdown (Locations 084-085)
When programmed, Zones 1 through 7 with Auto-Reset
will only reset twice (3 alarms) until rearmed in order to prevent "swingers" (intermittents) from causing repeated false
alarms. (Do not program for UL installations). See Auto-Reset.
Telephone Numbers (Locations 117-131; 149-163)
To report to a central station, Telephone Number 1
(Locations 117-131) must be programmed. Telephone
Number 2 (Locations 149-163) is programmed if Backup Reporting, Split Reporting or Double Reporting is selected.
Telephone Number 1 will be preceded by at least one
Dial-Tone Detection entry ("E" in Location 116) or Pre-Dial
Delay entry ("D" in Location 114) to ensure that the commu-
nicator detects a dial tone or waits a reasonable time to access a telephone line before dialing. (See Dial Tone Detec-tion; Pre-Dial Delay.) Furthermore, private telephone systems may require a separate Dial Tone Detection or PreDial Delay digit, followed by an Access Number (Location
115) to obtain an outside line. (See Access Number for
Outside Line).
It should be noted here that Telephone Number 1 need
not actually start in Location 117 nor end in Location 131,
as extra locations have been provided to allow for additional
prefix digits, if required. What is important is that Telephone
Number 1, with its associated Pre-Dial Delay, Access Num-ber, and Dial-Tone Detection, be wholly contained within
Locations 114-131, and that they be in their proper sequence. It may, in fact, be advantageous to leave one or
two blank locations before entering the telephone number to
allow for the unexpected (an additional Pre-Dial Delay, for
example). The above applies to Telephone Number 2
(Locations 149-163) and the Callback Telephone Number
(Locations 270-285; PROM Page-1 Locations 014-029) as
well.
Note: An "F" in any location will be ignored by the communicator when dialing.
Test Timer (Locations 024, 025;169)
Reset Test Timer on Report (Location 181)
When a "1 " is programmed into Location 169, a daily
test report will be transmitted to the central station from the
time the panel is powered up. The respective Alarm Code
is programmed into Locations 024, 025.
L NAPCO Security Systems
MA1008e/ 1008eM Installation Instructions
Page 26
Page 26
By entering an "8" in Location 181, the timer will be pro-
grammed to send a daily test only if there has been no
other report. (Note that this, or the above, is required in UL
installations). Thus, if one normally reports an opening
every weekday morning, for example, this feature may be
utilized to maintain reporting continuity on weekends.
Test-Timer Offset (Locations 250, 251)
If Test Timer is programmed, the test timer will report
immediately upon power-up, and every 24 hours thereafter.
To delay the timer reporting time up to 24 hours from
power-up time, program Locations 250 and 251 in hours
(see Time Selection). (If these locations are left blank, the
test timer will report immediately upon power-up).
Timeout (Locations 224-231)
Specifies the length of time that an alarm, alert, or delay
will remain active. Abort-Delay time and Burglary timeout
must be programmed, or the feature will not activate. See
Time Selection.
Note: In installations governed by California Fire Marshal regulations, do not program a timeout for fire alarms.
Time Selection Also see Programming Sheet
The times shown in Table 8 are programmable. The
Time Selector Chart on the Programming Sheet shows example times only, in seconds or minutes. In reality, any
time up to those shown in Table 8 may be programmed.
Note that each time is programmed in two locations. The
first location has a time factor of 1, the second a time factor
of 16.
Time (t) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Entry * 1 2 3 4 5 6 7 8 9 0 B C D E
*Blank. Note: if both programming locations are left blank, re-
1st box 2nd box
tx1 tx16
15
F
fer to Table 8 Notes for feature timeout.
Table 7. Program entries for unit times.
To select a time up to 15 seconds, 15 minutes, or 15
quarter-seconds (3.75 seconds), program the respective
entry into the first box only; do not program the second
box. To select a time greater than 15 seconds, 15 minutes,
or 15 quarter-seconds, program both boxes as follows:
1. For the feature selected, choose an appropriate time
in units shown (all seconds, minutes, or quarterseconds -- not minutes and seconds, etc.).
2. Divide the time chosen by 16. Enter the quotient in
the 2nd Box and the remainder in the 1st Box.
3. Check entries by adding the contents of the 1st Box to
16 times the contents of the 2nd Box. (Remember
that a "zero" entry represents "10").
Example 1. Program Entry Delay 1 for 1½ minutes.
1. Entry Delay 1 (Locations 220, 221) is in units of sec-
onds, thus delay time is 90 seconds.
2. Divide by 16: 90/16 = 5 (quotient) + 10 (remainder).
Enter the quotient in the 2nd Box and the remainder
in the 1st Box:
Abort Delay (see Note 1) 232, 233 sec. 4 min., 15 sec.
Exit Delay (See Note 2) 218, 219 sec. 4 min., 15 sec.
Entry Delay 1 (See Note 2) 220, 221 sec. 4 min., 15 sec.
Entry Delay 2 (See Note 2) 222, 223 sec. 4 min., 15 sec.
Burglary Timeout (See Notes
Time Locations Units Max. Time
Note 1)
1 & 3)
Fire-Zone Timeout 228, 229 min. Untimed (See
Chime Duration 230, 231 1/4
Timer Offset 250, 251 hr. 23 hr. (See Note
Table 8 (Programmable times and timeouts.
094, 095 hr. 255 hr.
(255 sec.)
(255 sec.)
(255 sec.)
(255 sec.)
224, 225 min. 4 hr., 15 min. (255
sec.
min.)
Note 4)
Untimed (See
Note 4)
5)
Notes:
1. If both locations are left blank, this feature will not activate (timeout = 0).
2. If both locations are left blank, Exit Delay = 60 sec.;
Entry Delay = 30 sec.
3. In UL installations, timeout must be at least 4 minutes
for Residential; at least 15 minutes for Mercantile.
4. If both locations are left blank, this feature will remain
active until system is disarmed. (Chime may be reset
using Key [9]; however if a time is programmed,
Chime cannot be reset and must time out). If both
locations are programmed "F", maximum time = 4
hours, 15 minutes (255 minutes); or 63.75 seconds
(255 quarter-seconds) for Chime Duration.
MA1008e/1008eM Installation Instructions
L NAPCO Security Systems
Page 27
5. If left blank and Test Timer is selected, will report immediately on power-up.
6. In installations governed by California Fire Marshal regulations, do not program a timeout for fire alarms.
TouchTone® Dialing (Location 178)
TouchTone
®
with Rotary Backup (Location 178)
Select TouchTone Dialing only when the subscriber has
TouchTone service. TouchTone dialing is faster than rotary
dialing, but not always as reliable.
For the communicator to use TouchTone on all dial attempts, add a "1" to Location 178. To use TouchTone on the
first attempt with subsequent rotary dial attempts, add a "2" to
Location 178. TouchTone Dialing will override TouchTone
with Rotary Backup if both are selected. Note that if Backup
Reporting is also selected, the communicator will use rotary
dial to reach Telephone 2.
Trouble
An abnormal zone condition (a break in a normally closed
loop; a short on a normally-open loop; or either on an end-ofline-resistor supervised loop) while disarmed.
Trouble on a Burglary Zone will be indicated by a sounder
beep upon arming (does not apply to selective- or groupbypassed zones). If auto-bypass has been removed from a
Burglary Zone, that zone will go into alarm on arming. Note
that if the zone is Exit/Entry, it will go into alarm after exit-delay
and entry-delay times have elapsed.
Trouble (open circuit) on a Day Zone (normally closed)
will be indicated by a flashing green STATUS LED and a
beeping sounder; the digital readout will display the troubled
zone(s). Keypad indications are reset by Key [9].
A Fire-Zone trouble is indicated by the red FIRE/
TROUBLE LED and by the sounder. An open circuit or short
to ground on Fire Power (Terminal 11) or Aux. Power
(Terminal 5) will cause a flashing LED and a pulsing sounder
after a 10-second delay. (A short across the EOL resistor will
cause an alarm condition: steady LED and pulsing sounder).
Reset Key [9] will silence the sounder; the LED will go out
within 30 seconds if the cause of the trouble has been removed. Note: Fire trouble restores are sent only after all
zones are restored.
Two-Digit Format See Data Format
Untimed Output (NTO Lug E15; Locations 096-099)
Audio Verification on NTO Lug (Location 305)
Failure to Communicate on NTO Lug (Location 078)
Keypad Aux. Alarm on NTO Lug (Location 079)
Lug E15 is an untamed output, programmable for any
zone (Group 1 or Group 2). When tripped, the NTO Lug will
go low. This output may be used for strobes (do not exceed
300mA), or to trip an LW-900 Long-Range Wireless Interface.
A relay (400Ω minimum) may be connected between E15 and
Terminal 5 (+ AUX. POWER) if a diode is inserted in series
(cathode to E15; anode to relay coil).
Select Audio Verification on NTO Lug for the MAV-15
Two-Way Voice or other listen-in device. The NTO lug will go
low when a programmed zone is tripped but will return high
when the central-station communication is complete.
If Failure to Communicate on NTO Lug is programmed
("2" in Location 078), Lug E15 will go low after 9 unsuccessful
transmissions, and remain low until either a transmission or a
Telco Test is successful.
Page 27
If Keypad Aux. Alarm on NTO Lug is programmed, Lug
E15 will go low when the keypad Auxiliary Panic is tripped,
and will remain low until the panel is disarmed.
Also see Abort Delay; Remote Status LED on NTO Lug.
User Program Code (Locations 238-243)
Allows an authority to access the User Program Mode to
program any User Code (see GETTING UP AND RUNNING - Programming User Codes. The default User Program Code
is 1,2,3,4,5,6, however this code must be changed to preserve
system security. Enter the 3-to 6-digit User Program Code
starting in Location 238.
Note: The Dealer Program Code must not start with the
same numbers as the User Program Code.
User 5 Arm Only (Location 078)
User 5 Report as User 1 (Location 078)
Users 6, 7 & 8 Report as Users 2, 3 & 4 (Location 079) User
5 Service Code (Location 079)
To restrict User Code 5 as an "arm-only" code (for singledigit easy arming), program a "4" in Location 078 (Do not pro-
gram User 5 Service Code). Note that if a single-digit armonly code is programmed, the hold-down function for that digit
is disabled.
The Service Code, if programmed, provides reduced access to the control panel for those with limited authority. Operation is similar to that of a regular Arm/Disarm Code, except
that the Service Code is disabled at times. When active, it
may be used to arm or disarm as needed.
The Service Code is controlled by User 1. Whenever
User 1's code is entered, the Service Code is deactivated. To
activate, merely arm using the Service Code. (The Service
Code can always be used to arm). To enable User Code 5 as
a Service Code, program a "1" in Location 079. For the Ser-
vice Code to report, it must report as User 1 ("8" in Location
078). For Users 6, 7 and 8 to report, they must report as Users 2, 3 and 4 ("4" in Location 079).
Watch On with Group Bypass (Location 081)
The Watch Mode activates all Day Zones simultaneously.
When a "1" is entered in Location 081, the Watch Mode will
be enabled when Group Bypass is selected (by pressing Key
[B] twice). Note that (a) Group Bypass need not be programmed for any zone for this feature to operate; (b) if a zone
is programmed as a Day Zone, it may not be programmed for
Group Bypass; and (c) Chime On with Group Bypass should
not be programmed.
Zone Restore See Restore Report
Normally, Control-Panel Restore is programmed for a
zone to send a restore report to the central station when either
the zone is repaired or the panel is disarmed. If the restore
report is to be sent only when the zone is repaired, Zone Re-
store should be selected (also program Control Panel Restore). It is recommended that Auto Reset and Priority Zone
or Priority Zone with Bypass also be selected for proper operation. See Restore Report.
24-Hour Protection (Locations 198, 199)
A zone that provides protection at all times, whether or
not the system is armed. Neither the green STATUS nor the
red ARMED/ALARM LED will indicate the condition of a zone
programmed for 24-Hour Protection, however an alarm will be
logged into Alarm History (see Alarm History).
NAPCO SECURITY SYSTEMS, INC. (NAPCO)
warrants its products to be free from manufacturing
defects in materials and workmanship for thirty-six months following the date of manufacture. NAPCO will,
within said period, at its option, repair or replace any
product failing to operate correctly without charge to the
original purchaser or user.
This warranty shall not apply to any equipment, or any
part thereof, which has been repaired by others,
improperly installed, improperly used, abused, altered,
damaged, subjected to acts of God, or on which any
serial numbers have been altered, defaced or removed.
Seller will not be responsible for any dismantling or
reinstallation charges.
THERE ARE NO WARRANTIES, EXPRESS OR
IMPLIED, WHICH EXTEND BEYOND THE
DESCRIPTION ON THE FACE HEREOF. THERE IS
NO EXPRESS OR IMPLIED WARRANTY OF
MERCHANTABILITY OR A WARRANTY OF FITNESS
FOR A PARTICULAR PURPOSE. ADDITIONALLY,
THIS WARRANTY IS IN LIEU OF ALL OTHER
OBLIGATIONS OR LIABILITIES ON THE PART OF
NAPCO.
Any action for breach of warranty, including but not
limited to any implied warranty of merchantability, must
be brought within the six months following the end of the
warranty period.
IN NO CASE SHALL NAPCO BE LIABLE TO ANYONE
FOR ANY CONSEQUENTIAL OR INCIDENTAL
DAMAGES FOR BREACH OF THIS OR ANY OTHER
WARRANTY, EXPRESS OR IMPLIED, EVEN IF THE
LOSS OR DAMAGE IS CAUSED BY THE SELLER'S
OWN NEGLIGENCE OR FAULT.
In case of defect, contact the security professional who
installed and maintains your security system. In order to
exercise the warranty, the product must be returned by
the security professional, shipping costs prepaid and
insured to NAPCO. After repair or replacement, NAPCO
assumes the cost of returning products under warranty.
NAPCO shall have no obligation under this warranty, or
otherwise, if the product has been repaired by others,
improperly installed, improperly used, abused, altered,
damaged, subjected to accident, nuisance, flood, fire or
acts of God, or on which any serial numbers have been
altered, defaced or removed. NAPCO will not be
responsible for any dismantling, reassembly or
reinstallation charges.
This warranty contains the entire warranty. It is the sole
warranty and any prior agreements or representations,
whether oral or written, are either merged herein or are
expressly cancelled. NAPCO neither assumes, nor
authorizes any other person purporting to act on its
behalf to modify, to change, or to assume for it, any
other warranty or liability concerning its products.
In no event shall NAPCO be liable for an amount in
excess of NAPCO's original selling price of the product,
for any loss or damage, whether direct, indirect,
incidental, consequential, or otherwise arising out of any
failure of the product. Seller's warranty, as hereinabove
set forth, shall not be enlarged, diminished or affected
by and no obligation or liability shall arise or grow out of
Seller's rendering of technical advice or service in
connection with Buyer's order of the goods furnished
hereunder.
NAPCO RECOMMENDS THAT THE ENTIRE SYSTEM
BE COMPLETELY TESTED WEEKLY.
Warning: Despite frequent testing, and due to, but not
limited to, any or all of the following; criminal tampering,
electrical or communications disruption, it is possible for
the system to fail to perform as expected. NAPCO does
not represent that the product/system may not be
compromised or circumvented; or that the product or
system will prevent any personal injury or property loss
by burglary, robbery, fire or otherwise; nor that the
product or system will in all cases provide adequate
warning or protection. A properly installed and
maintained alarm may only reduce risk of burglary,
robbery, fire or otherwise but it is not insurance or a
guarantee that these events will not occur.
CONSEQUENTLY, SELLER SHALL HAVE NO
LIABILITY FOR ANY PERSONAL INJURY,
PROPERTY DAMAGE, OR OTHER LOSS BASED ON
A CLAIM THE PRODUCT FAILED TO GIVE
WARNING. Therefore, the installer should in turn advise
the consumer to take any and all precautions for his or
her safety including, but not limited to, fleeing the
premises and calling police or fire department, in order
to mitigate the possibilities of harm and/or damage.
NAPCO is not an insurer of either the property or safety
of the user's family or employees, and limits its liability
for any loss or damage including incidental or
consequential damages to NAPCO's original selling
price of the product regardless of the cause of such loss
or damage.
Some states do not allow limitations on how long an
implied warranty lasts or do not allow the exclusion or
limitation of incidental or consequential damages, or
differentiate in their treatment of limitations of liability for
ordinary or gross negligence, so the above limitations or
exclusions may not apply to you. This Warranty gives
you specific legal rights and you may also have other
rights which vary from state to state.
MA1008e/1008eM Installation Instructions
L NAPCO Security Systems
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.