NAPCO Commercial GEMC, COMMERCIAL GEMINI-C User Manual

Page 1
24V Addressable &
Conventional Fire
Addressable /
Conventional 255-Zone
Merchantile Burglary
Combination
Burglary/Access & Fire
32, 128 & 255 Points
Universal NAC
Extender
Auxiliary Power
Introducing the all new
Napco Commercial Platform:
The most powerful, feature-rich platform for 24V commercial
fi re, burglary or combination burglary/fi re, supporting up to 255
zones using all-new fi re and burglary devices in hardwire, wireless,
conventional & addressable technologies
Regulated
Supplies
Firewolf 24V Commercial Intelligent Addressable Fire Panel, NFPA72-compliant,
up to 96 outputs, 4 onboard NACs (6.5A total), expandable to 24, built in Sync/ Strobe/Horn Module (System Sensor & Wheelock) and dual line DACT plus optional TCP/IP reporting. Features remote Smoke Obscuration Reporting. Nearly a mile., max. wire run – any wire type –ideal for retrofi ts. Also supports legacy and conventional (12V) devices, too and more of them per loop! Powerful battery capacity up to 32Ah total.
Gemini-C Commercial Addressable/ Conventional 255-Zone Burglary System;
Supports full line of new GEMC Commercial­rated conventional, addressable or wireless devices simultaneously on from 8 to 255 zones, with partitioning. UL Merchantile.
GEM-C Combination Burglary/Access/ Fire System; UL 864, 9th Edition Isolated
commercial Burg./Access and Fire buses and option for separate burg/access battery backups-- easy calcs., ideal for AHJs. No costly extra Bus Isolator or Loop Isolator modules required! Integrates with GeminiAccess ACM Module. Uses familiar Quickloader Up/downloading and Gemini style keypads in burglary or fi re models.
More zones – 255, 128 or 32 points More power – 7 amps More NAC’s – Up to 4 on board Built in strobe/horn synch More standby power 32 Amp hour battery capacity Regulated 24V output
NAC Extender provides nearly 7A and
4 onboard NACs with up to 2A ea; up to 16Ah total battery capacity. Easily distributes synched bell and strobe outputs with built in module. Monitors AC, battery trouble, tamper and ground fault on Napco bus or provides universal FACP support.
Regulated Auxiliary Power Supplies
Commercial burglary or fi re, 12V regulated 2A models (fi re shown); or 1.75A version with plug-in transformer. Backward compatible with all Gemini Panels. Alarm panel supervised power option. Ideal for simultaneous powering of CCTV cameras.
Firewolf Advanced Analog Addressable Commercial Fire Devices support auto-drift
compensation and maintenance alert function
Gemini-C Addressable Commercial Burglary Devices permit longest loop length,
upto 10,000 feet; no repeaters necessary!
Gemini-C New UL Commercial Wireless Line with supervised tamper & automatic,
continuously supervised signal strength (requires no manual test activation).
Gemini-C Burglary & Firewolf Menu-Driven Custom Alpha Keypads Familiar Napco
ez-programming. Keypads mount anywhere on the bus. Burg model with integral
4-zone EZM.
Compliances - NFPA 72, UL Commercial
Fire, UL864 9th Ed., SIA CP01, UL985. UL household & commercial burg.: UL1610, UL609, UL365, UL1023 (CSFM, FM, MEA
listings pending.)
Page 2
Napco Commercial™ Platform GEMC System Components:
24V Fire, Burglary or Combination Burg./Fire Systems
SYSTEM
Main Control board supports up to (2) Addressable SLCs (Signaling
Line Circuit controllers).
Fire Addressable SLC Loop Controller
Burg Addressable SLC Loop Controller
Fire 4-wire bus for keypads and conventional devices
Burglary Control Module
Provides Isolated Burg 4-wire bus for keypads and conventional
devices
Provides independent Burg battery connection and charger
Provides 12V power
Independent Burg Bell output
Power Supply includes either 4A or 7A @ 24V
Integrates with NAPCO ACM – Access Control Modules
RS-232 Printer Module for optional onsite parallel printer
Supports a maximum of 15 Keypads, mounted anywhere on the bus,
fi r e
GEMC-FK1 or burg. GEMC-BK1. ( 7 fi re keypads, max. Or, as few as 1
fi re keypad required on fi re system or equipment savings.)
Addressable SLC Loop Isolator (optional use - for some fi re
applications requiring increased circuit integrity)
Dual Phone Line built in
2 Onboard Serial Ports - One for internet reporting; One for high-
speed local downloading
TCP/IP Internet reporting module
Regulated Auxiliary Power Supplies - Commercial Burglary or fi re, 12V
regulated 2A or 1.75A version with plug in transfomer
Choice of two panel enclosures - Between the studs enclosure, recess
or surface mount. Larger version, with reversible door, supports up to 32Ah at 24V. Dimensions: 24” x 14.25” x 5.2” (H x W x D) without cover. Removable battery shelves, accomodate pairs of 7Ah, 7.5Ah and 8Ah batts. etc. Smaller Enclosure – supports 16Ah at 24V. Dimensions: 16” x 14.25” x 5.2” (H x W x D) without cover. (16Ah battery backup capacity).
INPUTS
Up to 255 Zones. Points/Zones can come from any of the following initiating devices (in up to 8 partitionable areas):
Addressable SLC Loop (Burg or Fire) – supports up to (2) 126 point
loops
Commercial RF Receiver –
Supports Commercial Wireless Fire devices
Wireless Smoke Detector
Wireless Heat Detector
Supports Commercial Wireless Burglary devices
Wireless PIR Sensor
Wireless Dual Technology Sensor
Wireless Glass break Sensor
Wireless 2-Point Window/Door Transmitter
Conventional 1- to 4-zone EZM Expansion modules on the 4-wire burg
or fi re bus or SLC loops
Conventional 2-wire or 4-wire smoke detector input module
Addressable SLC Fire Devices Supported:
Analog Smoke Detector
Heat Detector
Duct Detector
Pull Station
Conventional Zone Module
Short Circuit Isolator
Addressable SLC Burg Devices Supported:
1 Zone Burg Input Module
4 Zone Burg Input modules
PIR Motion Sensor
Dual Tech Microwave/PIR Sensor
OUTPUTS
Up to 96 outputs
Four on board Class B or 2 Class A NAC circuits, 2 amps each, total 6.5
amps at 24V
Built in Wheelock and System Sensor NAC sync/strobe/horn protocol
allows initial silence of audible appliances while maintaining visual notifi cation, without the use of additional modules.
Napco Commercial Platform Systems Simultaneously support all-new UL commercial Firewolf fi re and Gemini burglary devices in hardwire, wireless and addressable technologies
Addressable SLC Fire Devices: Supervised relay, unsupervised relay
Addressable SLC Burg Devices: unsupervised relay
Burg/Fire 4-wire bus devices: 8 zone form C relay (GEMC-RM3008), 8
open collector output (GEMC-OUT8)
Napco Commercial Platform Advantages
Easy Wire Compatibility -SLC controller supports shielded, unshielded,
twisted and untwisted wire - ideal for retrofi ts
Longer SLC loop lengths, support more device load each, too
(see below for distance at maximum device load in alarm/standby each)
10,000ft. #14AWG 6,200ft #16AWG 4,000 ft. #18AWG
Support for Legacy and Existing Notifi cation Appliances - One NAC
output confi gurable for 12V for easy retrofi t compatibility
UL Regulated NAC outputs
Automatic drift compensation for system’s analog smoke detectors
Separate 7A NAC Extender – (4) NAC’s, may be installed anywhere on
the 4-wire bus. Provides universal FACP support.
Keypads mount anywhere on the bus and have fl ash-able fi rmware –
for updates via Quickloader
Smoke Obsuration Report -Quickloader device sensitivity report
allows the printout of a report for the AHJ listing the current status of all analog smoke detectors in the system including the programmed obscuration level for each device and the actual sensitivity reading for each device. Report is generated in 3 ways- either remotely (uploaded) or locally through notebook PC or use optional onsite printer.
Isolated backup battery circuits for Burglary and Fire for EZ backup
calculation and AHJ compliance; allows dealer to accommodate separate backup times for burg and fi re. This allows burg system to drop out after burg battery depletion, while fi re system is maintained and extremely stable for extended period.
Full line of UL Commercial Devices for more fl exibility & labor-savings
Example, Use Gemini Commercial Wireless 2-input module (GEMC­WL-WD2) to convert any UL listed device into a UL wireless device, ideal for sprinkler supervisories or for use with pull stations (mounts on top of wall/conduit or in deep sngle-gang box (plastic).
Firewolf Fire-Only 24V Intelligent Addressable Fire Confi guration, NFPA72
Main Control board - supports (1) Addressable Fire SLC controller
Fire 4-wire bus for keypads and conventional devices
Power Supply 7A and 4A
RS-232 Printer Module
Fire Keypad with Gemini-style Menu-functionality
Dual Phone Line built in; Synch module built in (System Sensor &
Wheelock protocols)
NAC Extender - Powerful fl exibility
Nearly 7Amps power
4 onboard NACs with up to 2A ea., expandable for up to 24 per
system
Up to 16Ah total battery capacity
Regulated 24V Aux. power
Distributes synched bell and strobe outputs with built-in module
Monitors AC, battery trouble, tamper and ground fault on Napco bus
-or- provides universal FACP support.
Gemini-C Intrusion-Only Confi guration, Commercial Conventional/ Addressable 255-Zone Burglary System
Supports full line of new GEMC Commercial-rated addressable
conventional, or wireless devices simultaneously
8 to 255 fully-confi gurable zones, with up to 8 partitions
Familiar Napco Quickloader up/downloading and keypad operation
32Ah, max. battery capacity
Agencies
NFPA 72, UL Commercial Fire, UL864 9th Ed., SIA CP01, UL985. UL household & commercial burg.: UL1610, UL609, UL365, UL1023 (CSFM, FM, MEA listings pending.)
Page 3
RECEIVER
Y
A
WIRELESS
(4, MAX.)
GEMC-RECV
initiating
Single Fire
N/O device
SINGLE ZONE
WITH TAMPER
GEMC-WL-SMK
SMOKE DETECTOR
HEAT DETECTOR
GEMC-WL-HEAT
TRANSMITTER
GEMC-WL-WD2
SUPPLY
12V AUX POWER
GEMC-12V2APS-CF
(5, MAX.)
GEMC-NAC7
NAC EXTENDER
4 OR 7 AMP MAIN
POWER SUPPLY
FIRE BUS DEVICES
(GEMC-PS24V7A-R or
GEMC-PS24V4A-R)
8 ZONE
GEMC-EZM8
CONVENTIONAL
ZONE EXPANSION
GEMC-F8ZCPIM
8 Fire Zone Expander
OUTPUT
MODULE
MODULE
GEMC-OUT8
REMOTE RELAY
8 ZONE OUTPUT
S
S
2-WIRE
2-WIRE
SMOKE
+
+
+
+
S
S
2-WIRE
2-WIRE
SMOKE
+
+
+
+
S
S
2-WIRE
2-WIRE
SMOKE
+
+
+
+
S
S
2-WIRE
2-WIRE
SMOKE
+
+
+
+
S
S
2-WIRE
2-WIRE
SMOKE
+
+
+
+
S
S
2-WIRE
2-WIRE
SMOKE
+
+
+
+
S
S
2-WIRE
2-WIRE
SMOKE
+
+
+
+
S
S
2-WIRE
2-WIRE
SMOKE
+
+
+
+
ALL
OR ALL
SYSTEM
SENSOR
MUST BE
WHEELOCK
ALL
OR ALL
SYSTEM
SENSOR
MUST BE
WHEELOCK
LOOP
2-WIRE
FIRE SLC
ADDRESSABLE
MODULE
GEMC-RM3008
2.2K
SMOKE
EOLR
2.2K
SMOKE
EOLR
2.2K
SMOKE
EOLR
2.2K
SMOKE
EOLR
2.2K
SMOKE
EOLR
8 ZONES OF
2.2K
SMOKE
EOLR
}
2.2K
SMOKE
EOLR
CONVENTIONAL 2-WIRE SMOKES
2.2K
SMOKE
EOLR
PULL STATIONS AND/OR HEAT DETECTORS
HORN
HORN
STROBE
STROBE
HORN
STROBE
HORN
HORN
STROBE
STROBE
HORN
STROBE
FWC-FSLC-SMK
PRINTER
GEMC-FPRINT
MUST BE ALL
WHEELOCK OR ALL
SYSTEM SENSOR
2.2K
HORN
EOLR
}
2.2K
EOLR
2.2K
EOLR
-- or --
CIRCUITS (CLASS A)
CIRCUITS (CLASS B) (SHOWN)
4 ON-BOARD NAC
2 ON-BOARD NAC
2.2K
EOLR
HORN
HORN
STROBE
STROBE
HORN
HORN
ADDRESSABLE
HORN
STROBE
HORN
STROBE
STROBE
SMOKE
DETECTOR
STROBE
HORN
STROBE
HORN
STROBE
HEAT
DETECTOR
ADDRESSABLE
FWC-FSLC-HEAT
HORN
HORN
HORN
STROBE
HORN
HORN
HORN
HORN
STROBE
2.2K
EOLR
2.2K
EOLR
2.2K
EOLR
}
4 ON-BOARD NAC
2.2K
EOLR
FWC-FSLC-PULL
HORN
STROBE
HORN
STROBE
STROBE
HORN
STROBE
STROBE
HORN
STROBE
STROBE
HORN
STROBE
HORN
STROBE
STROBE
FWC-FSLC-RM2
FWC-FSLC-SOM1
FWC-FSLC-EZM1
-- or --
CIRCUITS (CLASS B)
(NOT SHOWN)
CIRCUITS (CLASS A)
2 ON-BOARD NAC
PULL
PULL STATION
ADDRESSABLE
F
L O W E R I F
FWC-FSLC-DUCT
DUCT DETECTOR
F L O W E R I F
FWC-FSLC-EZM2
DUAL INPUT
MONITOR MODULE
GEMC-FK1
F L O W E R I F
MODULE
DUAL RELAY
FWC-FSLC-SMK6B
F L O W E R I F
SUPERVISED
OUTPUT MODULE
FWC-FSLC-CZM
FAST RESPONSE
MONITOR MODULE
FWC-FSLC-ISO
F L O W E R I F
F L O W E R I F
DEVICES
UP TO 126
FIRE KEYPAD
(6" BASE ONLY)
ZONE MODULE
CONVENTIONAL
ISOLATOR
SHORT CIRCUIT
MODULE
FK1
INTERNET REPORTING
MODULE
MOTHERBOARD
GEMINI C-SERIES
GEMINI C-SERIES COMMERCIAL
COMBINATION CONT ROL PANEL
Mount beneath motherboard
GEMC-FW-SLC Fire SCL Mod
GEMC-BSLC Burg SLC Mod. and
MODULE
GEMC-BM or
GEMC-BM/PS
BURGLARY
CONVERTER
GEMC-RS232
SERIAL OUTPUT
LOOP
2-WIRE
BURG SLC
ADDRESSABLE
GEMC-BSLC-1PT
ZONE
EXPANDER
SINGLE POINT
CONVENTIONAL
DUAL TECH PIR
GEMC-BSLC-DT
PIR
GEMC-BSLC-PIR
MODULE
SINGLE RELAY
GEMC-BSLC-RLY
ZONE
4 POINT
EXPANDER
CONVENTIONAL
GEMC-BSLC-4PT
DEVICES
UP TO 126
Note: The four GEMC-RECV max. is reduced by 1 for each SLC module.
Two Fire or
Two Burglary or
One Fire and one Burglary
2 SLC MODULES, max.
GEMC & FIREWOLF SYSTEM COMPONENTS
8 ZONE
MODULE
(31, MAX.)
GEMC-EZM8
CONVENTIONAL
ZONE EXPANSION
RECEIVER
Platform supports commercial analog, addressable, wireless or conventional fire or burglary devices.
BURGLARY BUS DEVICES
WIRELESS
(4, MAX.)
GEMC-RECV
ACCESS
MODULE
CONTROL
ACCESS
DEVICES
CONTROL
(4, MAX.)
GEM-ACM1D
MODULE
(11, MAX.)
GEMC-OUT8
REMOTE RELAY
8 ZONE OUTPUT
OUTPUT
MODULE
(11, MAX.)
GEMC-RM3008
PIR
DUAL TECH PIR
GEMC-WL-PIR
GEMC-WL-DT
GEM-2D
ACCESSORY
SECOND DOOR
(ONE FOR EACH
ACCESS CONTROL
GEMC-WL-WD2*
GEM-ACM1D)
SUPPLY
12V AUX POWER
GEMC-12V2APS-R
WITH TAMPER
TRANSMITTER
WINDOW / DOOR
GEMC-WL-WD
GEMC-BK1
LOW PROFILE
TRANSMITTER
GEMC-WL-GB
WINDOW / DOOR
KEYPAD
BURGLARY
(15, MAX.)
KEYFOB
GEM-KEYF
GLASS BREAK
Single Commercial Burglary Supervised Loop and Integral Magnetic Contact
Residential Burglary when both loops are used
Page 4
NAPCO COMMERCIAL GEMINI-C & FIREWOLF SERIES SYSTEM ORDERING INFORMATION
Napco Commercial Combo. Burglary/Fire Kits
GEMC-COMBO255KT
GEMC-COMBO128KT
GEMC-COMBO32KT
Napco Commercial Fire Kits
GEMC-FW-255KT
GEMC-FW-128KT
GEMC-FW-32KT
Commercial Fire & Burglary Accessories and Options
GEMC-BM/PS
GEMC-BM
GEMC-FW-SLC
GEMC-BSLC
GEMC-F8ZCPIM
Burglary Peripherals
GEMC-BK1 GEMC-BSLC-4PT GEMC-BSLC-1PT
GEMC-BSLC-DT
GEMC-BSLC-PIR
GEMC-BSLC-RLY
GEMC-WL-PIR
GEMC-WL-GB
GEMC-WL-DT
Fire Peripherals
GEMC-FK1 LCD Fire Red Keypad
GEMC-WL-SMK
GEMC-WL-HEAT
Common Peripherals – For Commercial Fire and/or Burglary Systems
GEMC-WL-WD2
GEMC-REVC
GEMC-EZM8 GEMC- FPRINT GEMC-RM3008
GEMC-NL-MOD
GEMC-RS232
GEMC-OUT8
GEMC-KOTAMPERKT
Firewolf Peripherals
FWC-FSLC-SMK
FWC-FSLC-HEAT FWC-FSLC-DUCT FWC-FSLC-EZM2
FWC-FSLC-EZM1
FWC-FSLC-CZM FWC-FSLC-RM2
FWC-FSLC-ISO
FWC-FSLC-SOM1
FWC-FSLC-PULL FWC-FSLC-PROG2 FWC-FSLC-SMK6B
Options
GEMC-12V2APS-CF
GEMC-12V2APS-R
GEMC-NAC6
GEM-ACM1D
GEM-2D
255 Point GEM-C Commercial Combo. Fire/Burg System Kit
•24V Panel, 255 Points via commercial addressable, wireless or conventional fire or burg. devices, 4 on board NACs, 8 partitions (No Loop Isolator/Extender required)
•7 Amp, 24V Power Supply
•Burg. Module, with power supply with built in bus isolator for complete separation of fire and burg power and battery standby operation
•Built in horn/strobe synch. module on each NAC
•Built in dual line communicator; dual onboard serial ports
•Quickloader up/downloading including remote smoke obscuration reporting
•Locking, Large Red Enclosure, 16 x 25” reversible door, with 14.25” x 25” base. Houses up to 32Ah battery backup.
•Menu-driven LCD Fire Keypad mounts anywhere on bus (Also, full keyswitch support)
128 Point GEM-C Commercial Combo. Fire/Burg System Kit
As above, but with
•24V Panel, 128 Points via commercial addressable, wireless or conventional fire or burg. devices, 4 on board NACs, 8 partitions (No Loop Isolator/Extender required)
32 Point GEM-C Commercial Combo. Fire/Burg System Kit
Similar to above, but with
•24V Panel, 32 Points via commercial addressable, wireless or conventional fire or burg. devices, 2 on board NACs, 8 partitions (No Loop Isolator/Extender required)
•Locking, Medium Red Enclosure, 16 x 17” door, with 14.25” x 16” base. Houses up to 16Ah battery backup.
255 Point GEM-C Firewolf™ 24V Commercial Fire System Kit
•24V Panel, 255 Points via commercial addressable, wireless or conventional fire devices, 4 on board NACs providing up to 6.5A notification power
•7 Amp, 24V Power Supply
•Built in horn/strobe synch. module on each NAC
•Built in dual line communicator; dual onboard serial ports
•Quickloader up/downloading including remote smoke obscuration reporting
•Locking, Large Red Enclosure, 16 x 25” reversible door, with 14.25” x 25” base. Houses up to 32Ah battery backup.
•Menu-driven LCD Fire Keypad mounts anywhere on bus. (Also, full keyswitch support)
128 Point GEM-C Firewolf™ 24V Commercial Fire System Kit
As above, but with
•24V Panel, 128 Points via commercial addressable, wireless or conventional fire devices, 4 on board NACs providing up to 6.5A notification power
32 Point GEM-C Firewolf™ 24V Commercial Fire System Kit
Similar to above, but with
•24V Panel, 32 Points via commercial addressable, wireless or conventional fire devices, 2 on board NACs providing up to 4A notification power
•Locking, Medium Red Enclosure, 16 x 17” door, with 14.25” x 16” base. Houses up to 16Ah battery backup.
Burg Module with 12V power supply provides isolated 4-wire burg bus for burg keypads and devices, plus 12V power output for aux. devices. In­dependent Burg. Bell output. Complete separation of fire and burg power, plus indep. burg. battery connection and charger for indep. burg. standby operation in power failure.
Burg Module, isolated 4-wire burg bus for burg keypads and devices, plus 12V power output for aux devices. Indep. Burg bell output. Addressable SLC Fire Module, supports up to 128 addressable SLC fire devices. Up to 2 connect to GEM-C panel. Addressable SLC Burg Module, supports up to 128 addressable SLC burg devices. Up to 2 connect to GEM-C panel. Conventional 8-zone 2-wire fire input module. Plugs into GEM-C panel, for conventional 2-wire smokes or any conventional fire detection device.
LCD Burglary Keypad for Combo. System, with 4-zone EZM built in (Requires GEMC-BM or BM/PS Module.)
Addressable SLC 4 point input expansion module Addressable SLC 1 point input expansion module Addressable SLC Commercial Dual Tech Microwave/PIR, 40 x 40’ Addressable SLC Commercial PIR, 50 x 50’ Addressable SLC Commercial 1 point output module
Gemini Commercial Wireless PIR, 50 x 50’ Gemini Commercial Wireless Glassbreak, Acoustic 25’ Gemini Commercial Wireless Dual Tech Microwave/PIR, 40 x 40’
Gemini Commercial Wireless Smoke, Photoelectric Gemini Commercial Wireless Heat, 135º F
Gemini Comml Wireless 2-input module converts any UL listed device into a UL wireless device (ex., pull stations or sprinkler supervisories.) Gemini Commercial Wireless 255 point RF Receiver (up to 4 per system, max.) 8-point expansion module Parallel printer module
8 Form C Relay Output Module Internet Reporting Module RS232 Adapter for serial output from GEMC Panel PGM Output Module, 8 open collector PGM outputs Merchantile Tamper Kit, for large panel enclosures, supervised.
Addressable Analog SLC Smoke, photoelectric, head** Addressable Analog SLC Heat, 135ºF, head** Addressable SLC Duct smoke detector, photoelectric Addressable SLC 2-zone conventional expansion module. Uses one address on SLC loop, but yields 2 indepent contact monitoring circuits, for pull
stations, water flow and other dry contact alarm initiating devices. Addressable SLC 1-input conventional module, similar to usage above. Addressable SLC single module, for montoring of dry contacts, ie., pull stations and conv. smokes Addressable SLC 2-output module (requires 1 SLC address) Addressable SLC Short Circuit Module. (Optional use, for certain apps. only; meets Class A, Style 7 loop reqts.) Addressable SLC Fire supervised output module. Application examples: elevator recall, HVAC shutdown, add’l NAC output with power supply Addressable SLC Fire Pull Station Tool for address-programming SLC devices ** Smoke/Heat 6" Base, required for FWC-FSLC- SMK and –HEAT devices
12VDC Power Supply for Fire Bus, remote supervised. Direct 120VAC connection, supports 2ea. 12V, 7Ah standby batteries. 12VDC Power Supply for Burg. Bus, remote supervised. Powered by supplied 16.5V, 50VA plug-in transformer, supports 2ea. 12V, 7AH standby
batteries. Remote 4-output NAC Extender, for 6.5A ttl, or 2A, max. on any 1 output. Red 14 x 16” can, connects to 120VAC, supports 32Ah standby batts.
Supervised, fire bus connection. System Sensor and Wheelock NAC synch. (5 per system, for 20 add’l NAC circuits total.)
Access Control Module (with power supply, provision for back up battery, in enclosure, plug-in transformer), 1 door kit Access Add-on 2 door plug–in PCB for expansion of door capacity in above.
(Not necessary if housing is recess-mounted.)
1-800-645-9445 www.napcosecurity.com/newproducts.html ©Napco August 2010. Specifications subject to change A593A
Napco Commercial, Gemini and Firewolf are trademarks of Napco Security Technologies. Wheelock, System Sensor, UL, etc. are trademarks of theiir respective cos.
Loading...