NAPCO Commercial Firewolf, GEMC-FW-255KT, GEMC-FW-128KT, GEMC-FW-32KT User Manual

Introducing the all new
Napco Commercial Firewolf Series
Robust, flexible 24V commercial fire systems supporting up to 255 zones/ points using all-new fire devices in hardwire, wireless, conventional & addressable technologies
:
Gem-C Firewolf Series 24V Commercial Intelligent Addressable Fire Panel, NFPA72-compliant, 96 outputs, 4 onboard
NACs (6.5A total), expandable to 24, built in Sync/Strobe/Horn Module (System Sensor & Wheelock) and dual line DACT plus optional TCP/IP reporting. Nearly a mile., max. wire run – any wire type –ideal for retrofits. Also supports legacy and conventional devices, too. Powerful battery capacity up to 32Ah total.
Features remote smoke obscuration reporting
4 More zones/points – up to 255 4 More power – 7 amps 4 More NAC’as – 4 on board 4 Built in strobe/horn sync 4 More standby power 4 32 Amp hour battery capacity 4 Regulated 24V output
24V Addressable &
Conventional Fire
255, 128 or 32 point kits
NAC Extender provides nearly 7A and
4 onboard NACs with up to 2A ea; up to 16Ah total battery capacity. Easily distributes synched bell and strobe outputs with built in module. Monitors AC, battery trouble, tamper and ground fault on Napco bus or provides universal FACP support.
Regulated Auxiliary Power Supplies
Commercial fire, 12V regulated 2A models; or 1.75A version with plug-in transformer
Firewolf Advanced Analog Addressable Commercial Fire Devices support auto-drift
compensation and maintenance alert function
Gemini-C New UL Commercial Wireless Line with supervised tamper & automatic,
continuously supervised signal strength (requires no manual test activation).
Firewolf Menu-Driven Custom Alpha Keypads Same familiar Napco ez-
programming and usage. (Keyswitch support, too.)
Compliances - NFPA 72, UL Commercial
Fire, UL864 9th Ed., UL985. (CSFM, FM, MEA listings pending.)
Napco Commercial™ Firewolf-Series Components
for 32 to 255 Point 24V Commercial Fire Systems:
SYSTEM
Main Control board supports up to two (2) Addressable Fire SLCs
(addressable Signaling Line Circuit controllers). (Note: Only 1 SLC is accomodated within the Medium panel enclosure.*)
Fire 4-wire bus for keypads and non-SLC (conventional) devices,
including 12V devices
Power Supply includes either 4A or 7A @ 24V
RS-232 Printer Module for optional onsite parallel printer
Supports up to 7 fire keypads, GEMC-FK1, mounted anywhere on the
bus. (As few as one keypad required on system for equipment savings.)
Easy-to-use Gemini-style menu-driven operation with backlit custom alphanumeric display and functionality for Reset, Acknowledge, Silence (with disable).
Full Keyswitch Support
Synch module built in on each NAC (System Sensor & Wheelock
protocols)
Dual Phone Line built in
2 On board serial ports - one for internet reporting; one for high-speed local downloading
TCP/IP Internet reporting module
Regulated Auxiliary Power Supplies - Commercial fire, 12V regulated
2A or 1.75A version with plug in transfomer
Addressable SLC Loop Isolator (optional use - for some fire
applications requiring increased circuit integrity, e.g., meets Class A, Style 7 loop requirements.
Choice of two enclosures - Between the studs enclosures, recess or
surface mount –
Larger version supports up to 32 AH at 24V. Dimensions: 24” x
14.25” x 5.2” (H x W x D) without cover. Removable battery shelves, accommodate pairs of 7Ah, 7.5Ah and 8Ah batteries, etc.
Medium Enclosure – supports 16 AH at 24V. Dimensions: 16”x
14.25” x 5.2” (H x W x D) without cover. (*Note: Only 1 SLC is accomodated.) 16Ah battery backup capacity.
INPUTS
Up to 255 Zones. Zones can come from any of the following initiating devices:
Addressable SLC Loop – supports up to (2) 126 point loops
Commercial RF Receiver –
Supports Commercial Wireless Fire devices
Wireless Smoke Detector
Wireless Heat Detector
Conventional 1- to 4-zone EZM Expansion modules on the 4-wire fire
bus or SLC loops
Conventional 2-wire or 4-wire smoke detector input module
SLC Fire Devices Supported:
Analog Smoke Detector
Analog Heat Detector
Duct Detector
Pull Station
Conventional Zone Module
Short Circuit Isolator
Advantages
Easy Wire Compatibility - Addressable SLC
controller supports shielded, unshielded, twisted and untwisted wire - ideal for retrofits
Longer SLC loop lengths, support more
device loads each, too (see below for distance at maximum device load in alarm/ standby each):
10,000 ft. #14AWG 6,200 ft. #16AWG 4,000 ft. #18AWG
Support for Legacy and Existing Notification Appliances -One
NAC output configurable for 12V for compatibility for easy retrofit compatibility
UL Regulated NAC outputs
Automatic drift compensation for smoke detectors
Keypads mount anywhere on the bus and have flash-able firmware –
for updates via Quickloader command (# GEMC-FK1, shown above)
Programmable obscuration level by smoke detector device
Smoke Obscuration Report genererated remotely or locally or in any
of 3 ways - Quickloader device sensitivity report allows the printout of a report for the AHJ listing the current status of all smoke detectors in the system including the programmed obscuration level and the actual sensitivity reading for each device. This report can be generated remotely (uploaded) or locally through notebook PC or use optional onsite printer.
Full line of UL Commercial Devices for more flexibility & labor-savings
Example, Use Gemini Commercial Wireless 2-input module (GEMC­WL-WD2) to convert any UL listed fire device into a UL wireless device, ideal for sprinkler supervisories or for use with pull stations (mounts on top of wall/conduit or in deep sngle-gang box (plastic).
Separate 7Amp 4-NAC Extender (GEM-NAC7) 4 onboard NACs with
up to 2A ea., expandable for up to 24 per system. Up to 16Ah total battery capacity. Regulated 24V Aux. power. Monitors AC, battery trouble, tamper and ground fault on Napco bus - Also Provides
Universal FACP support for easy standardization in upgrades
OUTPUTS
Up to 96 outputs
Four on board Class B or 2 Class A NAC circuits, 2 amps each, total 6.5
amps at 24V
Built in Wheelock and System Sensor NAC sync/strobe/horn protocol
allows initial silence of audible appliances while maintaining visual notification, without the use of additional modules.
Addressable SLC Fire Devices: Supervised relay, unsupervised relay
Fire 4-wire bus devices: 8 zone form C relay (GEMC-RM3008), 8 open
collector output (GEMC-OUT8)
(Shown above) 32-Point GEM-C Firewolf™ 24V Commercial Fire System
Agencies
NFPA 72, UL Commercial Fire, UL864 9th Ed., UL985. (CSFM, FM, MEA listings pending.)