If you believe that your vehicle has a defect that could cause a crash or could cause
injury or death, you should immediately inform the National Highway Traffic Safety
Administration (NHTSA) in addition to notifying Multiquip at 1-800-421-1244.
If NHTSA receives similar complaints, it may open an investigation, and if it finds
that a safety defect exists in a group of vehicles, it may order a recall and remedy
campaign. However, NHTSA cannot become involved in individual problems
between you, your dealer, or Multiquip.
To contact NHTSA, you may either call the Vehicle Safety Hotline toll-free at 1-888327-4236 (TTY: 1-800-424-9153), go to http://www.nhtsa.dot.gov; or write to:
Administrator
NHTSA
1200 New Jersey Avenue S.E.
Washington, DC 20590
You can also obtain information about motor vehicle safety from
http://www.safecar.gov.
Order parts on-line using Multiquip’s SmartEquip website!
■ View Parts Diagrams
■ Order Parts
■ Print Specification Information
Goto www.multiquip.com and click on
Order Parts
to log in and save!
Order via Fax (Dealers Only):
All customers are welcome to order parts via Fax.
Domestic (US) Customers dial:
1-800-6-PARTS-7 (800-672-7877)
Order via Phone:
Non-Dealer Customers:
Contact your local Multiquip Dealer for
parts or call 800-427-1244 for help in
locating a dealer near you.
and Password, E-mail us at: parts@multiquip.
com.
To ob tai n an MQ Acc o un t , cont a ct yo u r
District Sales Manager for more information.
Use the internet and qualify for a 5% Discount
on Standard orders for all orders which include
complete part numbers.*
Fax your order in and qualify for a 2% Discount
on Standard orders for all orders which include
complete part numbers.*
Domestic (US) Dealers Call:
1-800-427-1244
International Customers should contact
their local Multiquip Representatives for
Parts Ordering information.
Note: Discounts Are Subject To Change
Note: Discounts Are Subject To Change
When ordering parts, please supply:
❒ Dealer Account Number
❒ Dealer Name and Address
❒ Shipping Address (if different than billing address)
❒ Return Fax Number
❒ Applicable Model Number
❒ Quantity, Part Number and Description of Each Part
NOTICE
All orders are treated as Standard Orders and will
ship the same day if received prior to 3PM PST.
❒ Specify Preferred Method of Shipment:✓ UPS/Fed Ex ✓ DHL
Do not operate or service the equipment before reading the
Potential hazards associated with the operation of this
entire manual. Safety precautions should be followed at all
times when operating this equipment. Failure to read and
understand the safety messages and operating instructions
could result in injury to yourself and others.
SAFETY MESSAGES
The four safety messages shown below will inform you
about potential hazards that could injure you or others. The
safety messages specifi cally address the level of exposure
to the operator and are preceded by one of four words:
DANGER, WARNING, CAUTION or NOTICE.
SAFETY SYMBOLS
DANGER
Indicates a hazardous situation which, if not avoided,
WILL result in DEATH or SERIOUS INJURY.
WARNING
equipment will be referenced with hazard symbols which
may appear throughout this manual in conjunction with
safety messages.
Indicates a hazardous situation which, if not avoided,
COULD result in DEATH or SERIOUS INJURY.
CAUTION
Indicates a hazardous situation which, if not avoided,
COULD result in MINOR or MODERATE INJURY.
NOTICE
Addresses practices not related to personal injury.
NEVER use accessories or attachments that are not
recommended by MQ Power for this equipment. Damage
Also, know the
and
This information will be invaluable in
emergency or safety devices.
Disconnection of these devices can cause severe injury,
bodily harm or even death. Disconnection of any of these
ensure generator is on level ground before use.
keep the machine in proper running condition.
store equipment properly when it is not being
used. Equipment should be stored in a clean, dry location
out of the reach of children and unauthorized personnel
CAUTION
NEVER operate this equipment without proper protective
clothing, shatterproof glasses, respiratory protection,
hearing protection, steel-toed boots and other protective
devices required by the job or city and state regulations.
NEVER operate this equipment when not
feeling well due to fatigue, illness or when
under medication.
NEVER operate this equipment under the infl uence of
drugs or alcohol.
ALWAYS check the equipment for loosened threads or
bolts before starting.
DO NOT use the equipment for any purpose other than
its intended purposes or applications.
to the equipment and/or injury to user may result.
ALWAYS know the location of the nearest
fi re extinguisher.
ALWAYS know the location of the nearest
fi rst aid kit.
ALWAYS know the location of the nearest
phone or keep a phone on the job site.
phone numbers of the nearest ambulance, doctor
fi re department.
the case of an emergency.
GENERATOR SAFETY
DANGER
NEVER operate the equipment in an explosive
atmosphere or near combustible materials. An
explosion or fi re could result causing severe
bodily harm or even death.
WARNING
NOTICE
This equipment should only be operated by trained and
qualifi ed personnel 18 years of age and older.
Whenever necessary, replace nameplate, operation and
safety decals when they become diffi cult read.
Manufacturer does not assume responsibility for any
accident due to equipment modifi cations. Unauthorized
equipment modifi cation will void all warranties.
NEVER disconnect any
These devices are intended for operato r safety.
devices will void all warranties.
CAUTION
NEVER lubricate components or attempt service on a
running machine.
NOTICE
ALWAYS
ALWAYS
Fix damage to machine and replace any broken parts
run engine without an air fi lter or with a dirty air
fi lter. Severe engine damage may occur. Service air fi lter
Wet stacking is a common problem with diesel engines
no load applied. When a diesel engine operates without
suffi cient load (less than 40% of the rated output), it will
not operate at its optimum temperature. This will allow
In order for a diesel engine to operate at peak effi ciency,
it must be able to provide fuel and air in the proper ratio
and at a high enough engine temperature for the engine
applied to relieve the condition. It can reduce the system
Codes specify that in certain locations, spark arresters
must be used on internal combustion engines that use
hydrocarbon fuels. A spark arrester is a device designed
from the engine exhaust. Spark arresters are qualifi ed
SAFETY INFORMATION
DANGER
The engine fuel exhaust gases contain poisonous carbon
monoxide. This gas is colorless and odorless, and can
cause death if inhaled.
The engine of this equipment
requires an adequate free
fl ow of cooling air. NEVER
operate this equipment in
any enclosed or narrow area
where free fl ow of the air is
restricted. If the air fl ow is
restricted it will cause injury to people and property and
serious damage to the equipment or engine.
WARNING
DO NOT pla c e hand s or f i n g e r s in s i d e en g i n e
compartment when engine is running.
NEVER operate the engine with heat shields or
guards removed.
Keep fi ngers, hands hair and clothing away
from all moving parts to prevent injury.
DO NOT remove the radiator cap while the
engine is hot. High pressure boiling water
will gush out of the radiator and severely
scald any persons in the general area of
the generator.
DO NOT remove the coolant drain plug while the engine
is hot. Hot coolant will gush out of the coolant tank and
severely scald any persons in the general area of the
generator.
NEVER
frequently to prevent engine malfunction.
NEVER tamper with the factory settings
of the engine or engine governor. Damage
to the engine or equipment can result
if operating in speed ranges above the
maximum allowable.
which are operated for extended periods with light or
unburned fuel to accumulate in the exhaust system,
which can foul the fuel injectors, engine valves and
exhaust system, including turbochargers, and reduce
the operating performance.
to completely burn all of the fuel.
Wet stacking does not usually cause any permanent
damage and can be alleviated if additional load is
performance and increase maintenance. Applying an
increasing load over a period of time until the excess
fuel is burned off and the system capacity is reached
usually can repair the condition. This can take several
hours to burn off the accumulated unburned fuel.
State Health Safety Codes and Public Resources
DO NOT remove the engine oil drain plug while the
engine is hot. Hot oil will gush out of the oil tank and
severely scald any persons in the general area of the
generator.
CAUTION
NEVER touch the hot exhaust manifold,
muffl er or cylinder. Allow these parts to cool
before servicing equipment.
to prevent accidental discharge of sparks or fl ames
and rated by the United States Forest Service for this
purpose. In order to comply with local laws regarding
spark arresters, consult the engine distributor or the
local Health and Safety Administrator.
FUEL SAFETY
DANGER
Make sure the hitch and coupling of the towing vehicle
NEVER
tow a trailer with defective hitches, couplings, chains, etc.
Trailer tires should be infl ated to 50 psi cold.
safety
attach trailer’s safety chains to towing
make sure the vehicle and trailer directional,
unless
posted otherwise. Recommended off-road towing is not to
Avoid sudden stops and starts. This can cause skidding,
Trailer should be adjusted to a level position at all times
rolling
underneath the trailer’s bumper
Use the trailer’s swivel jack to adjust the trailer height to
SAFETY INFORMATION
are rated equal to, or greater than the trailer “gross
vehicle weight rating.”
DO NOT start the engine near spilled fuel or combustible
fl uids. Diesel fuel is extremely fl ammable and its vapors
can cause an explosion if ignited.
ALWAYS refuel in a well-ventilated area, away from
sparks and open fl ames.
ALWAYS use extreme caution when working with
fl ammable liquids.
DO NOT fi ll the fuel tank while the engine is running
or hot.
DO NOT overfi ll tank, since spilled fuel could ignite if it
comes into contact with hot engine parts or sparks from
the ignition system.
Store fuel in appropriate containers, in well-ventilated
areas and away from sparks and fl ames.
NEVER use fuel as a cleaning agent.
DO NOT sm o ke around or near the
equipment. Fire or explosion could result
from fuel vapors or if fuel is spilled on a
hot engine.
TOWING SAFETY
Check with your local county or state safety
towing regulations, in addition to meeting
Depar tment of Transportation (DOT)
Safety Towing Regulations, before towing
your generator.
Refer to MQ Power trailer manual for additional safety
information.
In order to reduce the possibility of an accident while
transporting the generator on public roads, ALWAYS
make sure the trailer that supports the generator and
the towing vehicle are mechanically sound and in good
operating condition.
ALWAYS shutdown engine before transporting
CAUTION
ALWAYS inspect the hitch and coupling for wear.
Check the tire air pressure on both towing vehicle and
trailer.
Also check the tire tread wear on both vehicles.
ALWAYS make sure the trailer is equipped with a
chain.
ALWAYS properly
vehicle.
ALWAYS
backup, brake and trailer lights are connected and
working properly.
DOT Requirements include the following:
• Connect and test electric brake operation.
• Secure portable power cables in cable tray with tie
wraps.
The maximum speed for highway towing is 55 MPH
exceed 15 MPH or less depending on type of terrain.
or jack-knifi ng. Smooth, gradual starts and stops will
improve towing.
Avoid sharp turns to prevent rolling.
when towing.
Raise and lock trailer wheel stand in up position when
Make sure power cables are securely connected to the
make certain that proper power or extension
cord has been selected for the job. See Cable Selection
make sure that electrical circuits are properly
Severe injury or death by
can result from operating an ungrounded
DO NOT touch output terminals during
operation. Contact with output terminals
during operation can cause electrocution,
electrical shock or burn.
SAFETY INFORMATION
generator’s output receptacles. Incorrect connections
may cause electric al sho ck a nd dam age to the
generator.
NOTICE
ALWAYS
The ele ctrical voltage required to
operate the generator can cause severe
injury or even death through physical contact with live
circuits. Turn generator and all circuit breakers OFF
before performing maintenance on the generator or
making contact with output terminals.
NEVER insert any objects into the output
receptacles dur ing operation. This is
extremely dangerous. The possibility exists
of electrical shock, electrocution or death.
Backfeed to a utility system can cause
electrocution and/or property damage.
NEVER connect the generator to a
building’s electrical system without
a transfer switch or other approved
device. All installations should be
performed by a licensed electrician in accordance with
all applicable laws and electrical codes. Failure to do so
could result in electrical shock or burn, causing serious
injury or even death.
Chart in this manual.
Grounding Safety
DANGER
ALWAYS
grounded to a suitable earth ground (ground rod) per
the National Electrical Code (NEC) and local codes
before operating generator.
electrocution
generator.
NEVER use gas piping as an electrical ground.
Power Cord/Cable Safety
DANGER
NEVER let power cords or cables lay in water.
NEVER stand in water while AC power from the
generator is being transferred to a load.
NEVER use damaged or worn cables or cords when
connecting equipment to generator. Inspect for cuts in
the insulation.
NEVER grab or touch a live power
cord or cable with wet hands. The
possibility exists of electrical shock,
DO NOT drop the battery. There is a possibility that the
battery will explode.
DO NOT expose the battery to open fl ames,
sparks, cigarettes, etc. The battery contains
combustible gases and liquids. If these
gases and liquids come into contact with a
fl ame or spark, an explosion could occur.
WARNING
ALWAYS wear safety glasses when handling
the battery to avoid eye irritation. The battery
contains acids that can cause injury to the
eyes and skin.
Use well-insulated gloves when picking up the battery.
ALWAYS keep the battery charged. If the battery is not
charged, combustible gas will build up.
ALWAYS recharge the battery in a well-ventilated
environment to avoid the risk of a dangerous concentration
of combustible gasses.
NOTICE
Dispose of hazardous waste properly.
Examples of potentially hazardous waste
are used motor oil, fuel and fuel fi lters.
DO NOT use food or plastic containers to
dispose of hazardous waste.
DO NOT
down a drain or into any water source.
If the battery liquid (dilute sulfuric acid) comes into
contact with clothing or skin, rinse skin or clothing
immediately with plenty of water.
If the battery liquid (dilute sulfuric acid) comes into
contact with eyes, rinse eyes immediately with plenty
of water and contact the nearest doctor or hospital to
seek medical attention.
CAUTION
ALWAYS disconnect the NEGATIVE battery terminal
before performing service on the generator.
ALWAYS keep battery cables in good working condition.
Install the generator in a area that is free of debris,
bystanders, and overhead obstructions. Make sure the
generator is on secure level ground so that it cannot slide
or shift around. Also install the generator in a manner so
that the exhaust will not be discharged in the direction of
nearby homes.
The installation site must be relatively free from moisture
and dust. All electrical equipment should be protected from
excessive moisture. Failure to do will result in deterioration
of the insulation and will result in shor t circuits and
grounding.
Foreign materials such as dust, sand, lint and abrasive
materials have a tendency to cause excessive wear to
engine and alternator parts.
CAUTION
Pay close attention to ventilation when operating the
generator inside tunnels and caves. The engine exhaust
contains noxious elements. Engine exhaust must be
routed to a ventilated area.
GENERATOR GROUNDING
To guard against electrical shock and possible damage to
the equipment, it is important to provide a good EARTH
ground.
Article 250 (Grounding) of the National Electrical Code
(NEC) provides guidelines for proper grounding and
specifies that the cable ground shall be connected to the
grounding system of the building as close to the point of
cable entry as practical.
NEC articles 250-64(b) and 250-66 set the following
grounding requirements:
1. Use one of the following wire types to connect the
generator to earth ground.
a. Copper - 10 AWG (5.3 mm2)
b. Aluminum - 8 AWG (8.4 mm2)
2. When grounding the generator (Figure 2) connect the
ground cable between the lock washer and the nut on
the generator and tighten the nut fully. Connect the
other end of the ground cable to earth ground.
INDOOR INSTALLATION
Exhaust gases from diesel engines are extremely
poisonous. Whenever an engine is installed indoors the
exhaust fumes must be vented to the outside. The engine
should be installed at least two feet from any outside wall.
Using an exhaust pipe which is too long or too small can
cause excessive back pressure which will cause the engine
to heat excessively and possibly burn the valves.
3. NEC article 250-52(c) specifies that the earth ground rod
should be buried a minimum of 8 ft. into the ground.
NOTICE
When connecting the generator to any buildings
electrical system ALWAYS consult with a licensed
electrician.
NOTICE
If connection of the ground rod is not feasible, please
check city, local or state electrical requirements on
generator grounding requirements.
The MQ Power Model SG1400C3 is a 200kVA studio
generator that is designed as a high quality power source
for entertainment and studio applications.
In keeping with Multiquip's policy of constantly improving
its products, the specifications quoted herein are subject
to change without prior notice.
Permanent Magnet Generator Excitation System
The SG1400C3 generator is equipped with a PMG
(Permanent Magnet Generator) generator end. The
excitation system provides a minimum short circuit support
current of 300% of the standby rating for 10 seconds at 60
Hz, and approximately 275% at 50 Hz.
Both the PMG and the exciter are mounted outboard of the
bearing for ease of maintenance. The rotating brushless
exciter features hermetically sealed diodes for three-phase
full-wave rectification. The three-phase bridge is protected
against abnormal transient conditions by a multiplate
selenium surge protector.
Engine
shaft continues to rotate, the main rotor (field) induces a
voltage into the generator's main stator (armature). At rated
speed, the main stator's voltage produced by the residual
magnetism of the exciter allows the automatic voltage
regulator to function.
The regulator provides voltage to the exciter resulting in
a build-up of generator terminal voltage. This system of
using residual magnetism eliminates the need for a special
field flashing circuit in the regulator. After the generator
has established the initial residual voltage, the regulator
provides a controlled DC field voltage to the exciter stator
resulting in a controlled generator terminal voltage.
Voltage Regulation
In the standard configuration (shunt excited), the automatic
voltage regulator receives both its input power and voltage
sensing from the generator's output terminals. The regulator
automatically monitors the generator's output voltage
against an internal reference set point and provides the
necessary DC output voltage to the exciter field required
to maintain constant generator terminal voltage. The
generator's terminal voltage is changed by adjusting the
regulator's reference set point.
This generator is powered by a six-cylinder, 4-cycle direct
injection, turbocharged, air-cooled Cummins QSB7-G5
diesel engine. Engine speed is set at the factory at 1800
RPM. This engine is designed to meet every performance
requirement for the generator. Refer to Table 2 for engine
specifications.
Principle Of Operation
This generator is a brushless, self-excited, externally
voltage regulated, synchronous AC generator. The
generator is made up of six major components: main stator
(armature), main rotor (field), exciter stator (field), exciter
rotor (armature), rectifier assembly, and voltage regulator.
The generator's exciter consists of a stationary field and
a rotating armature. The stationary field (exciter stator)
is designed to be the primary source of the generator's
residual magnetism. This residual magnetism allows the
exciter rotor (armature) to produce AC voltage even when
the exciter stator (field) is not powered. This AC voltage
is rectified to DC by the rotating rectifier assembly and
fed directly to the main rotor (field). As the generator
Electronic Governor System
The electronic governor system controls the RPMs of the
engine. When the engine demand increases or decreases,
the governor system regulates the frequency variation to
± 0.25%.
Battery
The battery system is located in the engine compartment
on the sub-base. The battery’s primary purpose is to
provide starting power for the diesel engine starter motor.
The battery system is comprised of two 12 VDC, sealed
lead acid batteries wired in series to provide 24 VDC to
the starting motor. The battery is charged by the charging
alternator while the engine is engaged.
Exhaust System
The exhaust system is located above the diesel engine. The
exhaust system is comprised of rigid and flexible tubing, a
silencer, and a roof-mounted exhaust riser with a rain cap.
This generator can be equipped with a 150 gallon (567
liters) fuel tank located beneath the trailer deck. The tank
is made of steel (baffled). The tank can be filled from an
external fill port located on the side of the trailer. The fill
port has a 2-inch (51 mm) fill neck with vented cap.
When refueling, it is recommended to use ASTM-D975/No.
2 diesel fuel. A drain port is provided on the end of the tank.
Fuel Priming Pump
The generator set is equipped with an electric (24 VDC)
fuel priming pump to assist in priming the system for
maintenance purposes. The priming pump, bypass valves,
and priming switch are located on the side of the diesel
engine in the engine compartment.
Fuel Water Separator
A 30-micron Racor 900 fuel water separator is part of the
fuel system assembly and is located on the side of the
engine in within the enclosure compartment.
The supply line between the engine fuel pump and tank
passes through an in-line fuel/water separator filter. The
filter element is rated to filter elements down to 10 microns.
Intake Ventilation Door
Interior Lighting
The interior lighting system is distributed throughout the
interior. There are three separate lighting fixtures. Two
lights are in the engine compartment, and one light is in
the generator compartment.The lighting system operates
from the 24 VDC battery system.
The light fixtures are sealed incandescent bulbs which are
activated by a 0-15 minute timer switch located on the side
control panel box. The DC lighting system can be used to
perform off-line maintenance or assist in setup prior to AC
power connection.
Trailer (Optional)
If equipped, the generator set can be mounted on a tandem
axle trailer. Standard trailer is available with 8-lug chrome
wheels and electric or hydraulic brakes. Options may
include electric jack stands, adjustable hitch, ground rod
holder and rear stabilizing jacks.
OPTIONS
Battery Charger — 24 VDC/3 AMP, 120 V Input
Battery Disconnect Switch — 400 Amps
Optima Red Top Batteries — Replaces standard
batteries
The intake air ventilation door is located on the roof of the
generator set enclosure near the control panel. The door is
hydraulically actuated. Upon startup of the diesel engine,
pressure fills the cylinder and opens the door. Intake air
passes through the opening, and across the engine’s
radiator to cool the engine.
During rainy conditions the roof ventilation door will close
when the front ventilation door is opened.
Block Heater —120 V, 1500 Watt
CSA Package — Includes 400 Amp and 200 Amp Circuit
The InteliVision 5 Digital Controller provides monitoring
and fault detection capability of all engine and generator
operating parameters. A list of operating parameters is
shown below: