Multiquip MQP240 User Manual

MQP240
Diesel Generator
Prime Rating — 240 kW (300 kVA)
Standby Rating — 260 kW (330 kVA)
3-Phase, 60 Hertz, 0.8 PF
STANDARD FEATURES
 Heavy duty, turbocharged, direct injection diesel engine
Brushless alternator reduces service and maintenance
requirements and meets temperature rise standards for Class F insulation systems.
Open delta alternator design provides virtually unlimited
excitation for maximum motor starting capability.
Automatic voltage regulator (AVR) provides precise
regulation.
Electronic governor system with idle switch maintains
frequency to ±0.25%.
Full load acceptance of standby nameplate rating in one
step (NFPA 110, para 5-13.2.6).
Sound attenuated, weather resistant, steel housing
provides operation at 73 dB(A) at 23 feet. Fully lockable enclosure allows safe unattended operation.
Fuel/water separator removes condensation from fuel for
extended engine life.
Complete engine analog instrumentation includes DC
ammeter, oil pressure gauge, fuel gauge, water temp. gauge, tachometer/hour meter, preheat indicator, manual engine speed control, emergency shutdown monitors, and emergency stop button.
Complete generator analog instrumentation includes
voltage regulator control, ammeter phase selector switch, voltmeter phase selector switch, AC voltmeter, AC ammeter, frequency meter, panel light, and circuit breaker.
Automatic safety shutdown system monitors the water
temperature, engine oil pressure, overspeed, and overcrank. Warning lights indicate abnormal conditions.
Auto start/stop control allows generator to start automatically
in the event of a commercial power failure.
Complete power panel. Fully covered; three-phase terminals
and single phase receptacles allow fast and convenient hookup for most applications including temporary power boxes, tools and lighting equipment. All are NEMA standard.
 Two stage air filter
 E-Coat primer with polyurethane enamel finish coat.
 Low coolant level shutdown system provides protection
from critically low coolant levels. Includes control panel warning light.
MQP240 — DIESEL GENERATOR — REV. #0 (10/05/12)
 Simultaneous single and three phase power
 Emergency stop switch
 Battery switch
 Documentation box
 EPA emissions certified - Tier 3 emissions compliant.
MQP240
Diesel Generator
SPECIFICATIONS
Generator Specifications
Design
No. of Poles 4
Excitation Brushless with AVR
Phase 3
Standby Output 260 KW (330 KVA)
Prime Output 240 KW (300 KVA)
Generator RPM 1800
Voltage - 3Ø
Voltage - 1Ø
Armature Connection Star with Neutral
Voltage Regulation (No load to full load) ±0.5%
Power Factor 0.8
Frequency 60 Hz
Frequency Regulation:
No Load to Full Load
Frequency Regulation: Steady State
Insulation Class F
Sound Level dB(A) Full load at 23 feet 73
Revolving field, self-ventilated
Drip-proof, single bearing
208, 220, 240, 416, 440, 480V
Reconnectable
120, 127, 139, 240, 254, 277V
Adjustable
Isochronous under varying loads from
no load to 100% rated load
±0.25% of mean value for constant
loads from no load to full load.
Engine Specifications
Make / Model Cummins / QSL9-G3
Emissions EPA Tier 3 Certified
Starting System Electric
Design
Displacement 543 in
No. cylinders 6
Bore x Stroke 4.49 x 5.71 in. (114 x 145 mm)
Gross Engine Power Output 399 hp (297 kW)
BMEP 287 psi (1979 kPa)
Piston Speed 1707 ft/min (8.7 m/s)
Compression Ratio 17.8:1
Engine Speed 1800 rpm
Overspeed Limit 2040 rpm
Oil Capacity 7.0 gallons (26.5 liters)
Battery 150Ah x 2 (24 V Systems)
Fuel System
Maximum Fuel Flow (per hour) 22 gallons (83 liters)
Maximum Inlet Restriction (Hg) 6.0 in (152 mm)
- External fuel tank. No fuel tank installed on generator.
*
- Use ultra-low sulfur diesel fuel.
**
*
Recommended Fuel
Fuel Consumption gph lph
At full load 19.0 72.0
At 3/4 load 15.5 58.6
At 1/2 load 11.1 41.9
At 1/4 load 5.9 22.4
4-cycle, water cooled,
direct injection, turbocharged. Charged
Air Cooled.
3
(8900 cc)
ASTM-D975-No.1 & No.2-D
Cooling System
Fan Load 12 hp (9 kW)
Coolant Capacity (with radiator) 11.3 gallons (43 liters)
Coolant Flow Rate (per minute) 60.5 gallons (229 liters)
Heat Rejection to Coolant (per minute) 6310 Btu (6.6 MJ)
Maximum Coolant Friction Head 5.0 psi (35 kPa)
Maximum Coolant Static Head 60 feet (18 meters)
Ambient Temperature Rating 104°F (40°C)
Air
Combustion Air 770 cfm (21.8 m3/min)
Maximum Air Cleaner Restriction 25 in. H2O (6.25 kPa)
Alternator Cooling Air 2797 cfm (79.0 m3/min)
Radiator Cooling Air 7946 cfm (225 m3/min)
Exhaust System
Gas Flow (full load) 2040 cfm (57.9 m3/min)
Gas Temperature 1035°F (560°C )
Maximum Back Pressure 40.8 in. H
O (10.2 kPa)
2
Amperage
Rated Voltage Maximum Amps
1Ø 120 Volt 666.7 Amps (4 wire)
1Ø 240 Volt 333.3 Amps (4 wire)
3Ø 240 Volt 722 Amps
3Ø 480 Volt 361 Amps
Main Line Circuit Breaker Rating 800 Amps
Over Current Relay Trip Set Point 361 Amps
WARRANTY*
Cummins Engine
12 months from date of purchase with unlimited hours.
Generator
24 months from date of purchase or 2000 hours (whichever occurs first).
Trailer
12 months excluding normal wear items.
*Refer to the express written, one-year limited warranty sheet for additional information.
**
NOTICE
Generator is not intended for use in enclosed areas or where free flow of air is restricted.
Backfeed to a utility system can cause electrocution and/or proper ty damage. Do not connect to any building’s electrical system except through an approved device.
Specifications are subject to change without notice.
MQP240 — DIESEL GENERATOR — REV. #0 (10/05/12)
MQP240
LUG TERMINALS
Diesel Generator
MQ POWER DECIBEL LEVELS
Our soundproof housing allows substantially lower operating noise levels than competitive designs. WhisperWatts are at home on construction sites, in residential neighborhoods, and at hospitals — just about anywhere.
90
80
70
60
50
GENERATOR OUTPUT PANEL
Subway / truck traffic
Average city traffic
MQP240 at 23 feet
Inside car at 60 mph
Air conditioner at 20 feet
Normal conversation
73.0
DECIBELS
CIRCUIT BREAKERS FOR CS-6369 TWIST
LOCK RECEPTACLES
CIRCUIT BREAKERS
FOR GFCI RECEPTACLES
OPTIONAL GENERATOR FEATURES
Battery charger — provides fully automatic and self-
adjusting charging to the generator's battery system.
Jacket water heater — for easy starting in cold weather
climates.
Special batteries — long life batteries provide extra engine
cranking power.
Spring isolaters — provides extra vibration protection for
standby applications.
Trailer mounted package — highway legal trailer with
electric or surge brakes with triple axle configuration. Extra capacity fuel tanks are also available.
OPTIONAL CONTROL FEATURES
Audible Alarm — alerts operator of abnormal conditions.
OPTIONAL FUEL CELL FEATURES
Trailer fuel tank — fuel cell located in the trailer.
Subbase fuel cell (double wall) — contains a leak
sensor, low fuel level switch, and a secondary containment tank. UL142 listed.
CS-6369 TWIST-LOCK
RECEPTACLES (3)
240Y/139, 50 AMPS
U
120-480 VAC OUTPUT
V
1Ø AND 3Ø
GFCI RECEPTACLES (2)
120V, 20 AMP
W
O
NEUTRAL
TERMINAL
GROUND
TERMINAL
12 hours of minimum run time.
 24 hours of minimum run time.
OPTIONAL OUTPUT CONNECTIONS
Cam-Loks — provides quick disconnect alternative to bolt-
on connectors.
Pin and Sleeve Connectors — provides industry standard
connectors for all voltage requirements.
Output Cable — available in any custom length and size
configuration.
MQP240 — DIESEL GENERATOR — REV. #0 (10/05/12)
MQP240
Diesel Generator
DIMENSIONS
1800 mm/
70.87 in.
1320 mm/
51.97 in.
1400 mm/
55.12 in.
Weight
Dry Weight 8,645 lbs. (3,920 kg)
Wet Weight 8,865 lbs. (4,020 kg)
Max. Lifting
Point Capacity
16,500 lbs. (7,484 kg)
139 mm/
5.50 in.
650 mm/
25.60 in.
900 mm/
35.43 in.
2180 mm/85.82 in.
1010 mm/
39.76 in.
Lifting Point
900 mm/
35.43 in.
3800 mm/149.61 in.
1115 mm/
43.90 in.
900 mm/
35.43 in.
450 mm/
17.72 in.
585 mm/
23.03 in.
640 mm/
25.20 in.