Specifications and part numbers are subject to change
without notice.
PAGE 2 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
Ordering parts has never been easier!
If you have an MQ Account, to obtain a Username
Effective:
PARTS ORDERING PROCEDURES
Choose from three easy options:
January 1st, 2006
Best Deal!
Order via Internet (Dealers Only):
Order parts on-line using Multiquip’s SmartEquip website!
■ View Parts Diagrams
■ Order Parts
■ Print Specifi cation Information
Goto www.multiquip.com and click on
Order Parts
to log in and save!
Order via Fax (Dealers Only):
All customers are welcome to order parts via Fax.
Domestic (US) Customers dial:
1-800-6-PARTS-7 (800-672-7877)
Order via Phone:
Non-Dealer Customers:
Contact your local Multiquip Dealer for
parts or call 800-427-1244 for help in
locating a dealer near you.
and Password, E-mail us at: parts@multiquip.
com.
To ob ta in an MQ Acc o unt , co nt act your
District Sales Manager for more information.
Use the internet and qualify for a 5% Discount
on Standard orders for all orders which include
complete part numbers.*
Fax your order in and qualify for a 2% Discount
on Standard orders for all orders which include
complete part numbers.*
Domestic (US) Dealers Call:
1-800-427-1244
International Customers should contact
their local Multiquip Representatives for
Parts Ordering information.
Note: Discounts Are Subject To Change
Note: Discounts Are Subject To Change
When ordering parts, please supply:
❒ Dealer Account Number
❒ Dealer Name and Address
❒ Shipping Address (if different than billing address)
❒ Return Fax Number
❒ Applicable Model Number
❒ Quantity, Part Number and Description of Each Part
NOTICE
All orders are treated as Standard Orders and will
ship the same day if received prior to 3PM PST.
❒ Specify Preferred Method of Shipment:✓ UPS/Fed Ex ✓ DHL
■ Priority One ✓ Truck
■ Ground
■ Next Day
■ Second/Third Day
www.multiquip.com
WE ACCEPT ALL MAJOR CREDIT CARDS!
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 3
SAFETY INFORMATION
Do not operate or service the equipment before reading the
Potential hazards associated with the operation of this
entire manual. Safety precautions should be followed at all
times when operating this equipment. Failure to read and
understand the safety messages and operating instructions
could result in injury to yourself and others.
SAFETY MESSAGES
The four safety messages shown below will inform you
about potential hazards that could injure you or others. The
safety messages specifi cally address the level of exposure
to the operator and are preceded by one of four words:
DANGER, WARNING, CAUTION or NOTICE.
SAFETY SYMBOLS
DANGER
Indicates a hazardous situation which, if not avoided,
WILL result in DEATH or SERIOUS INJURY.
WARNING
equipment will be referenced with hazard symbols which
may appear throughout this manual in conjunction with
safety messages.
Indicates a hazardous situation which, if not avoided,
COULD result in DEATH or SERIOUS INJURY.
CAUTION
Indicates a hazardous situation which, if not avoided,
COULD result in MINOR or MODERATE INJURY.
NOTICE
Addresses practices not related to personal injury.
PAGE 4 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
SAFETY INFORMATION
GENERAL SAFETY
NEVER use accessories or attachments that are not
recommended by Multiquip for this equipment. Damage
Also, know the
and
This information will be invaluable in
emergency or safety devices.
Disconnection of these devices can cause severe injury,
bodily harm or even death. Disconnection of any of these
ensure generator is on level ground before use.
keep the machine in proper running condition.
store equipment properly when it is not being
used. Equipment should be stored in a clean, dry location
out of the reach of children and unauthorized personnel
CAUTION
NEVER operate this equipment without proper protective
clothing, shatterproof glasses, respiratory protection,
hearing protection, steel-toed boots and other protective
devices required by the job or city and state regulations.
NEVER operate this equipment when not
feeling well due to fatigue, illness or when
under medication.
NEVER operate this equipment under the infl uence of
drugs or alcohol.
ALWAYS check the equipment for loosened threads or
bolts before starting.
DO NOT use the equipment for any purpose other than
its intended purposes or applications.
to the equipment and/or injury to user may result.
ALWAYS know the location of the nearest
fi re extinguisher.
ALWAYS know the location of the nearest
fi rst aid kit.
ALWAYS know the location of the nearest
phone or keep a phone on the job site.
phone numbers of the nearest ambulance, doctor
fi re department.
the case of an emergency.
GENERATOR SAFETY
DANGER
NEVER operate the equipment in an explosive
atmosphere or near combustible materials. An
explosion or fi re could result causing severe
bodily harm or even death.
WARNING
NOTICE
This equipment should only be operated by trained and
qualifi ed personnel 18 years of age and older.
Whenever necessary, replace nameplate, operation and
safety decals when they become diffi cult read.
Manufacturer does not assume responsibility for any
accident due to equipment modifi cations. Unauthorized
equipment modifi cation will void all warranties.
NEVER disconnect any
These devices are inten ded for operator safety.
devices will void all warranties.
CAUTION
NEVER lubricate components or attempt service on a
running machine.
NOTICE
ALWAYS
ALWAYS
Fix damage to machine and replace any broken parts
immediately.
ALWAYS
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 5
SAFETY INFORMATION
ENGINE SAFETY
from the engine exhaust. Spark arresters are qualifi ed
add fuel to equipment if it is placed inside truck
start the engine near spilled fuel or combustible
fl uids. Diesel fuel is extremely fl ammable and its vapors
overfi ll tank, since spilled fuel could ignite if it
comes into contact with hot engine parts or sparks from
to prevent accidental discharge of sparks or fl ames
DANGER
The engine fuel exhaust gases contain poisonous carbon
monoxide. This gas is colorless and odorless, and can
cause death if inhaled.
The engine of this equipment
requires an adequate free
fl ow of cooling air. NEVER
operate this equipment in
any enclosed or narrow area
where free fl ow of the air is
restricted. If the air fl ow is
restricted it will cause injury to people and property and
serious damage to the equipment or engine.
WARNING
NEVER operate the engine with heat shields or
guards removed.
DO NOT remove the engine oil drain plug while
the engine is hot. Hot oil will gush out of the engine
crankcase and severely scald any persons in the general
area of the generator.
and rated by the United States Forest Service for this
purpose. In order to comply with local laws regarding
spark arresters, consult the engine distributor or the
local Health and Safety Administrator.
FUEL SAFETY
DANGER
DO NOT
bed with plastic liner. Possibility exists of explosion or
fi re due to static electricity.
CAUTION
NEVER touch the hot exhaust manifold,
muffl er or cylinder. Allow these parts to cool
before servicing equipment.
NOTICE
NEVER run engine without an air fi lter or with a dirty air
fi lter. Severe engine damage may occur. Service air fi lter
frequently to prevent engine malfunction.
NEVER tamper with the factory settings
of the engine or engine governor. Damage
to the engine or equipment can result
if operating in speed ranges above the
maximum allowable.
State Health Safety Codes and Public Resources
Codes specify that in certain locations, spark arresters
must be used on internal combustion engines that use
hydrocarbon fuels. A spark arrester is a device designed
DO NOT
can cause an explosion if ignited.
ALWAYS refuel in a well-ventilated area, away from
sparks and open fl ames.
ALWAYS use extreme caution when working with
fl ammable liquids.
DO NOT fi ll the fuel tank while the engine is running
or hot.
DO NOT
the ignition system.
Store fuel in appropriate containers, in well-ventilated
areas and away from sparks and fl ames.
PAGE 6 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
SAFETY INFORMATION
NEVER use fuel as a cleaning agent.
Make sure power cables are securely connected to the
make certain that proper power or extension
cord has been selected for the job. See Cable Selection
make sure that electrical circuits are properly
Severe injury or death by
can result from operating an ungrounded
drop the battery. There is a possibility that the
charge battery if frozen. Battery can explode.
keep the battery charged. If the battery is not
environment to avoid the risk of a dangerous concentration
DO NOT smoke around or near the
equipment. Fire or explosion could result
from fuel vapors or if fuel is spilled on a
hot engine.
ELECTRICAL SAFETY
DANGER
Turn generator and all circuit breakers OFF before
performing maintenance on the generator or making
contact with output receptacles.
NEVER insert any objects into the
output receptacles during operation.
This is extremely dangerous. The
possibility exists of electrical shock, electrocution or death.
Backfeed to a utility system can cause
electrocution and/or property damage.
NEVER connect the generator to a
building’s electrical system without
a transfer switch or other approved
device. All installations should be
performed by a licensed electrician in accordance with
all applicable laws and electrical codes. Failure to do so
could result in electrical shock or burn, causing serious
injury or even death.
Power Cord/Cable Safety
DANGER
NEVER let power cords or cables lay in water.
NEVER stand in water while AC power from the
generator is being transferred to a load.
NEVER use damaged or worn cables or cords when
connecting equipment to generator. Inspect for cuts in
the insulation.
NEVER grab or touch a live power
cord or cable with wet hands. The
possibility exists of electrical shock,
electrocution or death.
generator’s output receptacles. Incorrect connections
may cause elect r i cal sho ck and dama ge to the
generator.
NOTICE
ALWAYS
Chart in this manual.
Grounding Safety
DANGER
ALWAYS
grounded to a suitable earth ground (ground rod) per
the National Electrical Code (NEC) and local codes
before operating generator.
electrocution
generator.
NEVER use gas piping as an electrical ground.
BATTERY SAFETY (ELECTRIC START ONLY)
DANGER
DO NOT
battery will explode.
DO NOT expose the battery to open fl ames,
sparks, cigarettes, etc. The battery contains
combustible gases and liquids. If these
gases and liquids come into contact with a
fl ame or spark, an explosion could occur.
DO NOT
When frozen, warm the battery to at least 61°F (16°C).
WARNING
ALWAY S wear sa fety gl a ss e s when
handling the battery to avoid eye irritation.
The battery contains acids that can cause
injury to the eyes and skin.
Use well-insulated gloves when picking up the battery.
ALWAYS
charged, combustible gas will build up.
ALWAYS recharge the battery in a well-ventilated
of combustible gasses.
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 7
If the battery liquid (dilute sulfuric acid) comes into
contact with clothing or skin, rinse skin or clothing
ENVIRONMENTAL SAFETY
pour waste, oil or fuel directly onto the ground,
immediately with plenty of water.
SAFETY INFORMATION
NOTICE
If the battery liquid (dilute sulfuric acid) comes into
contact with eyes, rinse eyes immediately with plenty
of water and contact the nearest doctor or hospital to
seek medical attention.
CAUTION
ALWAYS disconnect the NEGATIVE battery terminal
before performing service on the generator.
ALWAYS keep battery cables in good working condition.
Repair or replace all worn cables.
TRANSPORTING SAFETY
CAUTION
NEVER allow any person or animal to stand underneath
the equipment while lifting.
NOTICE
Before lifting, make sure that the equipment parts (lifting
bail if equipped) are not damaged and screws are not
loose or missing.
Dispose of hazardous waste properly.
Examples of potentially hazardous waste
are used motor oil, fuel and fuel fi lters.
DO NOT use food or plastic containers to
dispose of hazardous waste.
DO NOT
down a drain or into any water source.
Always make sure crane or lifi tng device has been
properly secured to the lifting bail (hook) of the
equipment.
ALWAYS shutdown engine before transporting.
NEVER lift the equipment while the engine is running.
Tighten fuel tank cap securely and close fuel cock to
prevent fuel from spilling.
Use adequate lifting cable (wire or rope) of suffi cient
strength.
Use one point suspension hook and lift straight
upwards.
DO NOT lift machine to unnecessary heights.
ALWAYS tie down equipment during transport by
securing the equipment with rope.
PAGE 8 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
NOTES
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 9
AC Generator
60 Hz AC Power Sourc
SPECIFICATIONS (GENERATOR)
Table 1. Specifications (Generators)
ModelGAC3.6HZ
TypeBrushless Revolving Field Type
ExcitationSolid State, Statically Excited System
Speed3,600 RPM
Cooling SystemSelf-Ventilation
Continuous Power Output3.2 kW
Max Power Output3.6 kW
Rated Voltage120/240V
Current Max/Continuous (120V)30.0/26.6 amps
Current Max/Continuous (240V)15.0/13.3 amps
PhaseSingle Phase (4 wire)
Frequency60 Hz
Power Factor1
Dimensions
(L x W x H)
Dry Net Weight
25.0 x 19.75 X 18.75 in.
(635 X 501 X 476 mm)
165 lbs. (75 kg.)
NOTICE
In keeping with Multiquip's policy of constantly
improving its products, the specifications quoted herein
are subject to change without prior notice.
PAGE 10 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
SPECIFICATIONS (ENGINE)
Table 2. Specifications (Engine)
Engine
Dimensions
(L x W x H)
Dry Net Weight
Model
Type
Air-cooled 4 stroke, Single Cylinder, OHV,
Bore X Stroke
Displacement14.75 cu-in (242 cm
HONDA GX240K1EDN2
HONDA GX240U1EDN2
Horizontal Shaft Gasoline Engine
2.87 in. X 2.28 in.
(73 mm x 58 mm.)
3
)
Max Output8.0 H.P./3600 R.P.M.
FuelUnleaded Automobile Gasoline
Fuel Capacity5 gallons (19 liters)
Lube Oil Capacity1.16 quarts (1.1 liters)
Oil Alert SystemYes
Speed Control MethodCentrifugal Fly-weight Type
Starting MethodRecoil Start
15.0 x 16.9 X 16.6 in.
(380 X 430 X 422 mm)
55.1 lbs. (25 kg.)
Effects of Altitude and Heat
The maximum output of the engines listed above are applicable to supplying electrical power for continuous service at
ambient conditions in accordance with SAE Test cord J607. The above ambient conditions are at standard sea level, with
a barometric reading of 29.92 inches and a temperature of 60° F (15.5° C).
Generally, the engine's output power will decrease 3-1/2% for each 1000 feet (305 meters) of altitude above sea level, and
1% for each 10° F (-12.2° C) above the standard temperature of 60° F (15.5° C).
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 11
18.9 IN
(480 MM.)
AC CIRCUIT BREAKER
INTERRUPTEUR DE
COURANT PRINCIPAL
NEUTRALBONDED TO FRAME
NEUTREMIS A LA MASSEA
LACARCASSE DU MOTEUR
25.0 IN
(635 MM.)
DIMENSIONS
3600
GAC-3.6H
V
ACVOLTMETER
VOLTOMETRECA
POWERED by
Honda Engines
211052
MARCHE
120
ARRET
IDLE
CONTROL
CONTROL
DERALENTI
240V
ON
OFF
GRPRISE DE
TERRE
MARCHE
ARRET
OPERATION
SWITCH
INTERRUPTEUR
DEOPERATION
ON
OFF
OFF
120V
19.68 IN
(500 MM.)
Figure 1. Dimensions
PAGE 12 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
NOTE
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 13
CONNECTING THE GROUND
The nut and ground terminal on the generators should
always be used to connect the generators to a suitable
ground. The ground cable sho uld be #8 size wire
minimum.
At the generator, connect the terminal of the ground cable
between the lock washer and the nut (Figure 2) and tighten
the nut fully. Connect the other end of the ground cable to
a suitable earth ground (ground rod).
OFF
ACCIRCUIT BREAKER
INTERRUPTEURDE
COURANTPRINCIPAL
NEUTRALBONDED TO FRAME
NEUTREMIS A LAMASSE A
LACARCASSE DU MOTEUR
V
ACVOLTMETER
VOLTOMETRECA
GAC-3.6H
POWERED by
Honda Engines
211052
MARCHE
120
ARRET
CONTROL
CONTROL
DERALENTI
IDLE
3600
MARCHE
ON
OFF
ARRET
INTERRUPTEUR
DEOPERATION
OPERATION
SWITCH
INSTALLATION
ON
OFF
GENERATOR
GROUND LUG
GROUND
CABLE
#8 MINIMUM
REFERENCE
NEC 250-52(C)
240V
120V
GRPRISE DE
TERRE
8 FT. MINIMUM
GROUND ROD
FOR EARTH
GROUND
CONNECT TO
BUILDING
GROUND
IF REQUIRED
Figure 2. Generator Grounding
PAGE 14 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
INSTALLATION
OUTDOOR INSTALLATION
If possible install the generator in a area that is free of
debris, bystanders, and overhead obstructions. Make sure
the generator is on secure level ground so that it cannot
slide or shift around.
The installation site must be relatively free from moisture
and dust. All electrical equipment should be protected from
excessive moisture. Failure to do will result in deterioration
of the insulation and will result in short circuits and
grounding.
Foreign materials such as dust, sand, lint and abrasive
materials have a tendency to cause excessive wear to
engine and alternator parts.
INDOOR INSTALLATION
WARNING
Pay close attention to ventilation when
operating the generator inside tunnels
and caves. The engine exhaust contains
noxious elements. Engine exhaust must
be routed to a ventilated area
GENERATOR GROUNDING
To guard against electrical shock and possible damage to
the equipment, it is important to provide a good EARTH
ground.
Article 250 (Grounding) of the National Electrical Code
(NEC) provides guide lines for proper grounding and
specifies that the cable ground shall be connected to the
grounding system of the building as close to the point of
cable entry as practical.
NEC articles 250-64(b) and 250-66 set the following
grounding requirements:
1. Use one of the following wire types to connect the
generator to earth ground.
a. Copper - 10 AWG (5.3 mm2) or larger.
b. Aluminum - 8 AWG (8.4 mm2) or larger.
2. When grounding the generator (Figure 2) connect the
ground cable between the lock washer and the nut on
the generator and tighten the nut fully. Connect the
other end of the ground cable to earth ground.
3. NEC article 250-52(c) specifies that the earth ground rod
should be buried a minimum of 8 ft. into the ground.
Exhaust gases from gas engines are extremely poisonous.
Whenever an engine is installed indoors the exhaust
fumes must be vented to the outside. The engine should
be installed at least two feet from any outside wall. Using
an exhaust pipe which is too long or too small can cause
excessive back pressure which will cause the engine to
heat excessively and possibly burn the valves.
PLACEMENT
The generators should always be placed on a flat level
surface when it is running. DO NOT place the generators
on slopes, the possibility exists that the generators could
slide.
DANGER
An electric shock is apt to happen when
vibrators are used. Pay close attention to
handling when operating vibrators and
always use rubber boots and gloves to
insulate the body from a short circuit.
NOTICE
When connecting the generator to any buildings
electrical system ALWAYS consult with a licensed
electrician.
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 15
GAC3.6HZ FAMILIARIZATION
Generator
The Multiquip GAC3.6HZ generator has been designed
as a portable dual purpose power source for 60 Hz (single
phase) lighting facilities, power tools, submersible pumps
and other industrial and construction machinery.
These generators are mounted on rubber vibration isolators
that have a steel base backplate which is attached to the
protective steel pipe carrying frame. The protective carrying
frame is made of steel tubing and fully wraps around the
generators to protect against damage. See Figures 3, and
4 for the basic controls and indicators for the generator.
These portable generators are supplied with a electrical
control box. To reduce vibration caused by the engine, the
control box is also placed on rubber isolators.
Control Box
GENERAL INFORMATION
DANGER
Before connecting this generators to any building’s
electrical system, a licensed electrician must install an
isolation (transfer) switch.
Serious injury or death may result without this transfer
switch.
PAGE 16 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
COMPONENTS (GENERATOR)
3600
GAC-3.6H
V
ACVOLTMETER
VOLTOMETRECA
POWERED by
Honda Engines
211052
MARCHE
120
ARRET
IDLE
CONTROL
CONTROL
DERALENTI
240V
ON
OFF
GRPRISE DE
TERRE
MARCHE
ARRET
OPERATION
SWITCH
INTERRUPTEUR
DEOPERATION
ON
OFF
2
3
4
5
6
1
OFF
AC CIRCUIT BREAKER
INTERRUPTEUR DE
COURANT PRINCIPAL
NEUTRALBONDED TO FRAME
NEUTREMIS A LA MASSEA
LACARCASSE DU MOTEUR
120V
9
Figure 3. Generator Components
1. Main Breaker – 2-pole, 15 amp circuit breaker protects
the generator from short circuiting or overloading.
When star ting the generator always have circuit
breaker placed in the OFF position.
2. Idle Control Switch – The generator is provided with
an automatic idle control device for noise suppression
and reduced fuel consumption. The automatic idle
control automatically engages under a no-load
condition.
With the automatic idle control switched ON, the
engine revolutions will automatically drop to about
2600 rpm (low-speed operation) within 3 seconds
after the load stops. When the operation is resumed,
the engine speed is automatically increased to about
3600 rpm (high-speed operation) as soon as the load
is connected.
3. Operation Switch – Place switch in ON position (up)
for normal operation. To turn-off the generator, place
switch in OFF position (down).
8
7
4. AC-Voltmeter – Indicates (with a mark) the rated 60 Hz
(single-phase) output voltage. In addition the voltmeter
can also be used as a diagnostic tool. If the voltmeter
indicator (needle) is below the rated voltage, engine
problems may exist (low/high RPM's).
To prevent damage to the generator or power tools
due to low output voltage, turn the generator OFF and
consult your authorized Multiquip service dealer.
5. 240V Output Receptacle – NEMA L6-20R twist-lock
receptacle will provide 240V @ 20 amps, 60 Hz.
6. GFCI Ground – GFCI ground connection point.
7. 120V Output Receptacle – NEMA L5-30R twist-lock
receptacle will provide 120V @ 30 amps, 60 Hz.
8. GFCI Duplex Receptacle – NEMA 5-15R, GFCI
receptacle will provide 120V @ 15 amps.
9. Chassis Ground – This ground connection point
should be connected to a good earth ground (ground
rod).
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 17
COMPONENTS (GENERATOR)
Figure 4. Generator Components (Continued)
10. Spark Plug – Provides spark to the ignition system.
Set spark plug gap to 0.6 - 0.7 mm (0.028 - 0.031 inch)
Clean spark plug once a week.
11. Muffler/Heat Shield – Used to reduce noise and
emissions. NEVER touch this heat shield when the
generator/welder is in use. Always allow time for engine
to cool before servicing.
12. Air Cleaner – Prevents dirt and other debris from
entering the fuel system. Remove wing-nut on top of air
filter cannister to gain access to filter element. NEVER
run the engine without an air cleaner.
13. Fuel Tank Cap – Remove cap to add unleaded
gasoline to the fuel tank. Replenish with clean unleaded
gasoline. Make sure cap is tightened securely. DONOT over fill.
14. Choke Lever – Used for starting the engine. Close
the choke lever when starting a cold engine or in
cold weather conditions. The choke enriches the fuel
mixture. Open the choke lever if starting a warm engine
or in warm weather conditions.
15. Fuel Cock Lever – Turn lever downward to start (down)
the flow of fuel into the carburetor. Turn upward to stop
(up) the flow of fuel.
16. Engine Oil Filler Cap – Remove cap/dipstick when
the adding of engine oil is required. See Table 4 for
recommended type engine oil.
17. Engine Oil Drain Plug – Remove drain plug when
draining of the oil from the engine crankcase is
required. Fill with recommeded type oil as listed in
Table 4.
18. Recoil Starter (pull rope) – Manual-starting method.
Pull the starter grip until resistance is felt, then pull
briskly and smoothly.
19. Fuel Tank – Fuel tank capacity is 5 gallons (19 liters)
20. Fuel Gauge – This gauge is located on top of the fuel
tank. Read this gauge to determine when fuel is low.
NOTICE
This HONDA engine is equipped with a low oil shutdown
capability. A built in sensor will automatically turn off the
engine should the oil level fall below a safe operating
condition. Make sure the generators is placed on level
ground. Placing the generators on level ground will
ensure that the low oil sensor will function properly.
PAGE 18 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
GENERAL INSPECTION PRIOR TO OPERATION
Ground Power Tools
When using power tools or electrical equipment requireing
AC power from the generator, make sure power tool cord
has a ground pin or is double insulated as shown in Figure 5.
INSPECTION/SETUP
NOTICE
Double-insulated power tools and small appliances
have specially insulated housings that eliminate the
need for a ground pin. These types of double-insulated
power cords are designed so that no part of the device
will be electrically live even if the internal insulation fails.
Extension Cable
When electric power is to be provided to various tools or
loads at some distance from the generator, extension cords
are normally used. Cables should be sized to allow for
distance in length and amperage so that the voltage drop
between the generators and point of use (load) is held to
a minimum. Use the cable selection chart (Table 3) as a
guide for selecting proper cable size.
DANGER
NEVER use power tools or equipment that do not
have a ground capability, the possibility exists of
electrocution, electrical shock or burn, which can cause
severe bodily harm or even DEATH!
Main Circuit Breaker
ALWAYS place the main circuit breaker in the OFF position
Figure 5. Ground Pin
Table 3. Cable Selection (60 Hz, Single Phase Operation)
Current In
Amperes
2.53006001000 ft.600 ft.375 ft.250 ft.
56001200500 ft.300 ft.200 ft.125 ft.
7.59001800350 ft.200 ft.125 ft.100 ft.
1012002400250 ft.150 ft.100 ft.
1518003600150 ft.100 ft.65 ft.
2024004800125 ft.75 ft.50 ft.
CAUTION: Equipment damage can result from low voltage.
Load In WattsMaximum Allowable Cable Length
120 Volts240 Volts#10 Wire#12 Wire#14 Wire
prior to starting the engine.
#16 Wire
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 19
Before Starting
1. Read safety instructions at the beginning of manual.
2. Clean the generator, removing dirt and dust, particularly
the engine cooling air inlet, carburetor and air
cleaner.
3. Check the air filter for dirt and dust. If air filter is dirty,
replace air filter with a new one as required.
4. Check carburetor for external dirt and dust. Clean with
dry compressed air.
5. Check fastening nuts and bolts for tightness
Engine Oil Check
1. To check the engine oil level, place the generator on
secure level ground with the engine stopped.
2. Remove the filler dipstick from the engine oil filler hole
(Figure 6) and wipe clean.
INSPECTION/SETUP
Figure 7. Engine Oil Dipstick(Oil Level)
Table 4. Oil Type
SeasonTemperatureOil Type
Summer25°C or HigherSAE 10W-30
Spring/Fall25°C~10°CSAE 10W-30/20
Winter0°C or LowerSAE 10W-10
Fuel Check
Figure 6. Engine Oil Dipstick Removal
3. Insert and remove the dipstick without screwing it
into the filler neck. Check the oil level shown on the
dipstick.
4. If the oil level is low (Figure 7), fill to the edge of the
oil filler hole with the recommended oil type (Table 4).
Maximum oil capacity is 1.16 quarts (1.1 liters).
1. Close the fuel cock before filling the fuel tank.
2. Remove the fuel cap located on top of fuel tank.
3. Read the fuel gauge located on top of the fuel tank
(Figure 8) to determin if the fuel level is low. If fuel is
low, replenish with clean unleaded fuel.
Figure 8. Fuel Gauge
4. When refueling, be sure to use a strainer for filtration.
DO NOT top-off fuel. DO NOT fill the tank beyond
capacity. Wipe up any spilled fuel immediately!
PAGE 20 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
OPERATION
This section is intended to assist the operator with the initial
start-up of the portable generator. It is extremely important
that this section be read carefully before attempting to use
the generators in the field.
Before Starting the Engine
1. Be sure to disconnect all electrical loads from the
generators prior to starting the engine.
2. NEVER start the engine with the main circuit breaker
in the ON position. Always place this circuit breaker
(Figure 9) in the OFF position before starting.
Figure 9. Main Circuit Breaker (OFF)
Starting the Engine
3. Place the choke lever (Figure 11) in the OPEN position
if starting a warm engine or the temperature is warm.
4. Place the generator's operation switch (Figure 12) in
the ON position.
Figure 12. Operation Switch (ON)
5. Grasp the starter grip (Figure 13) and slowly pull it out.
The resistance becomes the hardest at a certain
position, corresponding to the compression point. Pull
the starter grip briskly and smoothly for starting.
1. Place the engine fuel valve lever (Figure 10) to the ON
position.
Figure 10. Engine Fuel Valve Lever (ON)
2. Place the choke lever (Figure 11) in the CLOSED
position if starting a cold engine.
Figure 13. Starter Grip
6. If the engine has started, slowly return the choke lever
(Figure 11) to the OPEN position. If the engine has not
started repeat steps 1 through 5.
NOTICE
DO NOT pull the starter rope all the way to the end.
DO NOT release the starter rope after pulling. Allow it
to rewind as soon as possible..
Figure 11. Choke Lever
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 21
OPERATION
7. Before the generators is placed into operation, run the
engine for 3-5 minutes. Check for abnormal smells,
fuel leaks, and noises that would associate with lose
components.
8. Place the idle control switch (Figure 14) in the OFF
(down) position. This will allow the engine speed to run
at about 3600 RPM's.
Figure 14. Idle Control Switch (OFF)
NOTICE
Placing the idle control switch in the OFF position
(Figure 14) allows the engine to operate at a maximum
speed of about 3600 RPM's.
When the idle control switch (Figure 15) is placed in the
up position (ON), the generator will run at idle speed
(2200 RPM's) until a load is applied, at that time the
engine speed will increase to 3600 RPM's as long as
a load is being applied.
additional verification of voltage, an external voltmeter
can be used to measure the output voltage as shown
in Figure 17.
Figure 17. 120V/GFCI Receptacles
11. Read the voltmeter on the front panel of the generator
(Figure 18) and verify that 240 VAC is present at the
240V twist-lock receptacle. Using an external voltmeter
verify that 240V is present at the 240V twist-lock
receptacle.
When the load is not in use, the engine speed will drop
back to the idle mode after about 3 seconds.
Figure 15. Idle Control Switch (ON)
9. Place main circuit breaker (Figure 16) in the ON
position.
Figure 16. Main Circuit Breaker (ON
10. Read the voltmeter on the front panel of the generator
(Figure 17) and verify that 120 VAC is present at the
120V twist-lock and GFCI duplex receptacles. For
Figure 18. 240V Twist-Lock Receptacle
NOTICE
When using a combination of dual receptacles, total
load should not exceed the rated capacity of the
generator.
12. Connecting of loads (power tools, lighting ect.) to the
generator receptacles can now be done.
PAGE 22 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
OPERATION/SHUTDOWN
Stopping the Engine
1. Place the main circuit breaker (Figure 19) in the OFF
position.
Figure 19. Main Circuit Breaker (OFF)
2. Place the idle control switch (Figure 20) in the OFF
position.
Figure 20. Idle Control switch (OFF)
3. Let the engine run at idle with no load for 2-3 minutes.
4. To shut-down the engine, place the generator's
operation switch (Figure 21) in the OFF position.
1. Place the generator's operation switch (Figure 21) in
the OFF position.
Figure 21. Operation Switch (OFF)
5. Place the engine fuel valve lever (Figure 22) in the OFF
position.
Figure 22. Engine Fuel Valve Lever (OFF)
6. Remove all loads from the generator.
Emergency Shutdown
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 23
PREPARATION FOR LONG TERM STORAGE
Generators Storage
For storage of the generating set for over 30 days, the
following is required:
Drain the fuel tank completely, or add STA-BIL to the
fuel.
Run the engine until the gasoline in the carburetor is
completely consumed.
Completely drain the oil from the crankcase and refill
with fresh oil.
Remove the spark plug, pour 2 or 3 cc of SAE 30 oil into
the cylinder and crank slowly to distribute the oil.
Slowly rotate the engine a few times with the starter rope
and install a new plug.
Pull out the star ter rope slowly and stop at the
compression point.
Clean all external parts of the generating set with a
cloth.
Cover the generating set and store in a clean, dry
place.
PAGE 24 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
MAINTENANCE
Use Table 5 as a general maintenance guideline when
servicing your engine. For more detail engine maintenance
information, refer to the engine owner's manual supplied
with your engine.
Table 5. Engine Maintenance Schedule
DESCRIPTION
(3)
Engine Oil
Air Cleaner
All Nuts & Bolts
Spark Plug
Cooling FinsCHECKX
Spark ArresterCLEANX
Fuel TankCLEANX
Fuel FilterCHECKX
Idle SpeedCHECK-ADJUSTX (2)
Valve ClearanceCHECK-ADJUSTX (2)
Fuel linesCHECKEvery 2 years, replace if necessary (2)
(1) Service more frequently when used in DUSTY areas.
(2) These items should be serviced by your service dealer, unless you have the proper tools and are mechanically
proficient. Refer to the HONDA Shop Manual for service procedures.
(3) For commercial use, log hours of operation to determine proper maintenance intervals.
OPERATIONBEFORE
CHECKX
CHANGE
CHECK
CHANGEX (1)
RETIGHTEN IF
NECESSARY
CHANGEX
XX
X
REPLACE
FIRST
MONTH OR
10 HRS.
EVERY 3
MONTHS
OR 25 HRS.
EVERY 6
MONTHS
OR 50 HRS.
EVERY
YEAR OR
100 HRS.
EVERY
2 YEARS OR
200 HRS.
X
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 25
Maintenance
Perform the scheduled maintenance procedures as defined
by Table 5 and below:
Daily
Thoroughly remove dirt and oil from the engine and
control area. Clean or replace the air cleaner elements
as necessary. Check and retighten all fasteners as
necessary.
Weekly
Remove the fuel filter cap and clean the inside of the
fuel tank.
MAINTENANCE
Figure 24. Draining Engine Oil
Engine Air Cleaner
Remove or clean the filter at the bottom of the tank.
Remove and clean the spark plug (Figure 23), then adjust
the spark gap to 0.024 ~0.028 inch (0.6~0.7 mm). This
unit has electronic ignition, which requires no adjustments.
Figure 23. Spark Plug Gap
Engine Oil
1. Drain the engine oil when the oil is warm as shown in
Figure 24.
2. Remove the oil drain bolt and sealing washer and allow
the oil to drain into a suitable container.
1. Remove the air cleaner cover and foam filter element
as shown in Figure 25.
DANGER
DO NOT use gasoline as a cleaning
solvent, the possibility exists of fire or
explosion which can cause damage to
the equipment and severe bodily harm or
even DEATH!
2. Clean foam elemen t in warm, soapy water or
nonflammable solvent. Rinse and dry thoroughly. Dip
the element in clean engine oil and completely squeeze
out the excess oil from the element before installing.
3. Replace engine oil with recommended type oil as listed
in Table 4. For engine oil capacity, see Table 2 (engine
specifications). DO NOT overfill.
4. Install drain bolt with sealing washer and tighten
securely.
PAGE 26 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
Figure 25. Engine Air Cleaner
GENERATOR WIRING DIAGRAM
SYMBOLPART NAME
ArArmature Winding
Fg-PNField Winding
EXW1~2 Excitation Winding
V AC Voltmeter (120/240)
Re1~2Rectifier
CON1Receptacle L5-30R
CON2Receptacle L6-20R
CON3Receptacle 5-15R
CBUPM-2 20A
CB1CP-31E/15N 15A
SW1Idle Control Switch
SW2Operation Switch
RCIdle Control Device
S Idle Control Solenoid
GRGround Terminal T-3830
CCapacitor 50V @ 1000µf
SymbolColorSymbolColor
BRBROWNYYELLOW
GRGRAYLGLIGHT GREEN
Wiring Color Code
BBLACKRRED
LBLUEWWHITE
GGREEN LBLIGHT BLUE
VVIOLETOORANGE
PPINK
Figure 26. Generator Wiring Diagram
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 27
TROUBLESHOOTING
Table 6. Engine Troubleshooting
SymptomPossible CauseSolution
Spark plug bridging?Check gap, insulation or replace spark plug.
Difficult to start. Fuel is
available but no SPARK
at spark plug.
Difficult to start. Fuel is
available and SPARK
is present at the spark
plug.
Difficult to start. Fuel
is available, SPARK is
present at the spark
plug and compression
is normal.
Difficult to start. Fuel
is available, SPARK is
present at the spark
plug and compression
is low.
Carbon deposit on spark plug?Clean or replace spark plug.
Short circuit due to deficient spark plug
insulation?
Improper spark plug gap?Set to proper gap.
ON/OFF switch is shorted?Check switch wiring. Replace switch.
Ignition coil defective?Replace ignition coil.
Improper spark gap, points dirty?Set correct spark gap and clean points.
Condenser insulation worn or short
circuiting?
Spark plug wire broken or short circuiting?Replace defective spark plug wiring.
Wrong fuel type?
Water or dust in fuel system?Flush fuel system.
Air cleaner dirty?Clean or replace air cleaner.
Suction/exhaust valve stuck or protruded?Reseat valves.
Piston ring and/or cylinder worn?Replace piston rings or piston.
Cylinder head and/or spark plug not
tightened properly?
Head gasket and/or spark plug gasket
damaged?
Check spark plug insulation. Replace if
worn.
Replace condenser.
Flush fuel system and replace with correct
type of fuel.
Torque cylinder head bolts and spark plug.
Replace head and spark plug gaskets.
Fuel not available in fuel tank?Fill with correct type of fuel.
Fuel cock does not open properly?
No fuel present at
carburetor.
Weak in power.
Compression is proper
and does not misfire.
PAGE 28 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
Fuel filter clogged?Replace fuel filter.
Fuel tank cap breather hole clogged?Clean or replace fuel tank cap.
Air in fuel line?Bleed fuel line
Air cleaner dirty?Clean or replace air cleaner.
Improper level in carburetor?Check float adjustment. Rebuild carburetor.
Defective spark plug?Clean or replace spark plug.
Apply lubricant to loosen fuel cock lever.
Replace if necessary.
TROUBLESHOOTING
Table 6. Engine Troubleshooting (Continued)
SymptomPossible CauseSolution
Weak in power.
Compression is proper
but misfires.
Engine overheats.
Rotational speed
fluctuates.
Recoil starter
malfunction.
Water in fuel system?
Dirty spark plug?Clean or replace spark plug
Ignition coil defective?Replace ignition coil.
Spark plug heat value improper?Replace with correct type of spark plug.
Incorrect type of fuel?Replace with correct type of fuel.
Cooling fins dirty?Clean cooling fins.
Governor adjusted correctly?Adjust governor
Governor spring defective?Replace governor spring.
Fuel flow restricted?Check entire fuel system for leaks or clogs.
Recoil mechanism clogged with dust and
dirt?
Spiral spring loose?Replace spiral spring.
Flush fuel system and replace with correct
type of fuel.
Clean recoil assembly with soap and water.
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 29
TROUBLESHOOTING
Table 7. Generator Troubleshooting
SymptomPossible ProblemSolution
Low voltageEngine speed too low?Raise engine speed to rated RPM.
Overload Condition?Reduce load or replace breaker.
Load circuit is shorted?Check load circuit for short.
Stuck solenoid?Check solenoid.
Bad Idle control switch?Check or replace idle control switch.
Check control box wiring.
Check red and green ignition wires.
Replace ignition wires if necessary.
Check full power switch and full power
switch circuit.
Check control box wiring.
Idle control switch malfunction?Check or replace idle control switch.
Does not accelerate from low to high
"LOAD ACTIVE"
Does not decelerate no"VOLTAGE
OUTPUT".
Does not decelerate but has
"VOLTAGE OUTPUT".
PAGE 30 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
Idle control device malfunction?Check or replace idle control device.
Control box interal wiring defective?Check control box wiring.
Defective rotor windings?Check or replace rotor.
Defective solenoid?Check or replace solenoid.
Defective idle control device?Check or replace idle control device.
Defective solenoid?Check or replace idle control device.
Control box wiring malfunction?
Defective solenoid?Check or replace solenoid.
Idle control device malfunction?Check or replace idle control device.
Check control box wiring, replace any
defective components.
NOTES
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 31
EXPLANATION OF CODE IN REMARKS COLUMN
The following section explains the different symbols and
PART NO. Column
QTY. Column
— Item quantity can be indicated by a
A/R (As Required) is generally used for hoses or other
A blank entry generally indicates that the item is not sold
separately. Other entries will be clarifi ed in the “Remarks”
Some of the most common notes found in the “Remarks”
Column are listed below. Other additional notes needed
same unique symbol will be included when this item is
— Used to list an effective serial
— Indicates that the part
part is NOT used on a specifi c model or model number
available items. Examples include battery cables, shims,
— Indicates that an item cannot
be purchased as a separate item and is either part of an
assembly/kit that can be purchased, or is not available
remarks used in the Parts section of this manual. Use the
help numbers found on the back page of the manual if there
are any questions.
Numbers Used
number, a blank entry, or A/R.
NOTICE
The contents and part numbers listed in the parts
section are subject to change without notice. Multiquip
does not guarantee the availability of the parts listed.
4 12349 BEARING ..............1 .....S/N 2345B AND ABOVE
NO. Column
Unique Symbols — All items with same unique
symbol
(@, #, +, %, or >) in the number column belong to the
same assembly or kit, which is indicated by a note in the
“Remarks” column.
Duplicate Item Numbers — Duplicate numbers indicate
multiple part numbers, which are in effect for the same
general item, such as different size saw blade guards in
use or a part that has been updated on newer versions
of the same machine.
NOTICE
When ordering a part that has more than one item
number listed, check the remarks column for help in
determining the proper part to order.
parts that are sold in bulk and cut to length.
Column.
REMARKS Column
to describe the item can also be shown.
Assembly/Kit — All items on the parts list with the
purchased.
Indicated by:
“INCLUDES ITEMS W/(unique symbol)”
Serial Number Break
number range where a particular part is used.
Indicated by:
“S/N XXXXX AND BELOW”
“S/N XXXX AND ABOVE”
“S/N XXXX TO S/N XXX”
Specifi c Model Number Use
is used only with the specifi c model number or model
number variant listed. It can also be used to show a
variant.
Indicated by:
Numbers Used — Part numbers can be indicated by a
number, a blank entry, or TBD.
TBD (To Be Determined) is generally used to show a
part that has not been assigned a formal part number
at the time of publication.
A blank entry generally indicates that the item is not sold
separately or is not sold by Multiquip. Other entries will
be clarifi ed in the “Remarks” Column.
PAGE 32 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
“XXXXX ONLY”
“NOT USED ON XXXX”
“Make/Obtain Locally” — Indicates that the part can
be purchased at any hardware shop or made out of
and certain washers and nuts.
“Not Sold Separately”
for sale through Multiquip.
GAC3.6HZ PORTABLE 60 HZ GENERATOR WITH
HONDA GX240K1EDN2/GX240U1EDN2 GASOLINE
ENGINES
3............17211899000 ........ELEMENT AIR CLEANER
NOTICE
Part numbers on this Suggested Spare Parts list may
supersede/replace the part numbers shown in the
following parts lists.
SUGGESTED SPARE PARTS
♦GX240K1EDN2: Model GAC3.6HZ, SEPTEMBER 2007 AND BELOW
◊ GX160U1EDN2: Model GAC3.6HZ, JANUARY 2008 AND ABOVE
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 33
S/N 5561008 AND BELOW
CAUTION
Do not use in rain or snow.
1
ATTENTION
Ne pas utiliser en cas de
pluie ou neige.
A3520000A
7
FUELCOCK
ROBINET’D ESSENCE
ON/OUVERT
OFF/
FERMER
A90820000
CAUTION/ATTENTION
HOT PARTS can burn skin.
DO NOT touch until the
has sufficiently cooled.lamp
Danger de brûlure, pièces chaudes.
Ne touchez pas avant que l’appareil
ne soit suffisamment refroidi.
WARNING/ATTENTION
Onlyoperate machine in well
ventilatedareas.
Donot inhale exhaust gases.
N’utilizezl’equipment que dans
desendroits bien aérés.
Nerespirez paz les gas d’échappement.
Onlyqualified personnel should install, use,
Dangerous
orservice this equipment.
Gas/Gas
Seulun personnel qualifié devrait avoir
dangereux
l’authorisationd’installer d’utilisier ou
deréparer cet équipement.
A63210090A
NAMEPLATE AND DECALS
3600
8
Insulation System --- B
Maximum ambient
2
A65200040A
3
Temperature --- 40°C (104°F)
Systéme d’insulation --- B
Températureambiante
maximum --- 40°C (104°F)
A33210030A
10
READ OWNER’S SERVICE MANUAL BEFORE OPERATING OR
SERVICING THIS MACHINE.
ALWAYSKEEP UNAUTHORIZED INEXPERICENCED
UNTRAINED PEOPLE AWAYFROM THIS MACHINE.
MAKE SURE ALL SAFETY DEVICES ARE OPERATIONAL
BEFORE THIS MACHINE IS STARTED. MAKE SURE ENGINE
IS TURNED OFF AND SPARK PLUG WIRE DISCONNECTED
BEFORE SERVICING THE MACHINE OR COMINGIN
CONTACTWITH ANY MOVINGPART. IF EQUIPMENT IS
POWERED BY AN ELECTRIC MOTOR DISCONNECT
ELECTRICAL PLUG.
NEVER LEAVE MACHINE UNATTENDED WHEN OPERATING
ALWAYSSTOP ENGINE AND ALLOW ENGINE TO COOL
BEFORE ADDING FUEL OR OIL.
CAUTION
A55200070A
II est impératif de lire le manuel d’utilisation
avant d’utiliser ou de réparer cet équipement.
II est impératif degarder tout personnel non
authorisé ou non qualifié à distance de cet equipement.
Assurez vous que tout equipement de sécurité est
fonctionnel avant d’engager l’equipement. Assurez vous
que le moteur est éteint et que le fil de la bougie
est d’econnecté avant de réparer la machine ou vant
tout contact avec toute pièce en mouvement.
Si l’equipement est alimenté par unmoteur électrique
débranchez l’appareil.
Ne laissez jamis l’appareil sans supervision quand
il est en marche, II est impératif d’arrêter le
motour et de la laisser refroidir avant d’ajouter
de l’huile ou du carburant.
6
S/N 5561009~5582082
THE POSSIBILITY EXISTS OFIF
GENERATOR/WELDER IS NOT PROPERLY GROUNDED.
ALWAYSCONNECT EARTHGROUND (GROUND ROD) TO
GENERATORGROUND POINT.
ILY AURAITUN RISQUE D’ÉLECTROCUTION À MOINS
QUELA GÉNÉRATRICE/SOUDEUSE NESOIT PROPREMENT
MISEA LATERRE. S’ASSURER DE RELIERA LA MASSE
(BARREDE MASSE) LE POINTDE MISE ALA TERRE DE
L’APPAREIL.
CONNECTTO BUILDING
GROUNDIF REQUIRED
ARELIERÀ LAMASSE
D’OUVRAGEEVENTUELLEMENT
8FT.MINIMUM
8PIEDS MINIMUM
GROUNDROD FOR
EARTHGROUND
BARREDE MASSE
REFERENCENEC 250-52(C)
RÉFERÉNCENEC 250-52(C)
ELECTROCUTION
GROUNDTERMINAL
PRISEDE TERRE
GROUNDCABLE
#8MINIMUM
CÂBLEDE MASSE
#8MINIMUM
FORFURTHER GROUNDING
INSTRUCTIONSREAD MANUAL
POURPLUS DEDÉTAILS
CONCERNANTLAMISE Á LA
TERRE,LIRE LEMANUEL
11
A91110020
CAUTION
5
Donot touch output terminals or internal
wiringwhile unit is operating.
Turnoff power before servicing.
Netouchez ni les terminaux externes ou le
cablageelectrique interne lorsque que
l’ quipement est en operation.é
Eteindreavant de réparer.
Onlyqualified personnel should install, use,
orservice this equipment.
Seulun personnel qualifié devrait avoir
l’authorisationd’installer d’utilisier ou
deréparer cet équipement.
4
S/N 5582083~ 5622593S/N 5622594 AND ABOVE
WARNING
Operation of this equipment may create
sparks that can start fires around dry
vegetation.
A spark arrestor may be required.
The operator should contact local fire
agencies for laws or regulation relating
to fire prevention requirements.
Des étincelles pouvant enflammer la
végétation séche environnante peuvent être
produites pendant le fonctionnement de cet
équipement.
Un pare étincelles peut être requis.
L’opérateur doit contacter les agences
anti–incendie locales pour s’ informer
des lois ou feglementations concernant les
exigences de prévention––incendie
A90400020
NEUTRALBONDEDTOFRAME
120V
120
V
GAC-2.2H
NEUTREMISALAMASSEA
15A
LACARCASSEDUMOTEUR
POWEREDby
HondaEngines
211052
ACCIRCUITBREAKER
INTERRUPTEURDE
OFF
GRPRISEDE
COURANTPRINCIPAL
TERRE
DANGER
CAN KILL YOU IN MINUTES
NEUTRALBONDEDTOFRAME
120V
120
V
GAC-2.2H
NEUTREMISALAMASSEA
15A
LACARCASSEDUMOTEUR
POWEREDby
HondaEngines
211052
ACCIRCUITBREAKER
INTERRUPTEURDE
OFF
GRPRISEDE
COURANTPRINCIPAL
TERRE
NEUTRALBONDEDTOFRAME
120V
120
V
GAC-2.2H
NEUTREMISALAMASSEA
15A
LACARCASSEDUMOTEUR
POWEREDby
HondaEngines
211052
ACCIRCUITBREAKER
INTERRUPTEURDE
OFF
GRPRISEDE
COURANTPRINCIPAL
TERRE
ONLYuse outdoors and away from
open windows, doors, and vents.
Utilisation UNIQUEMENTà l’ extér leur
portes et trous d’aération
A9504000104
Using agenerator indoors.
Utilser un générateur à l’ intérieur VOUS TUERA EN QUELQÙES MINUTES.
Exhaust contains carbon monoxide, a poison gas you cannot see or smell.
Les gazd’ échappement contiennent du monoxyde de carbon, un gaz toxique
invisible et inodore.
1213
NEVER use in enclosed orpartially
enclosed areas.
Utilisation INTERDITE dans un
espace clos ou partiellement clos .
PAGE 34 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 79
TERMS AND CONDITIONS OF SALE — PARTS
PAYMENT TERMS
5. Par ts must be in new and resalable
Multiquip reserves the right to quote and
who use our products as integral parts of their
LIMITATIONS OF SELLER’S LIABILITY
liable for loss of profi t or good will or for any
connection with the sale of its products. Apart
statutory, which extend beyond the description
Terms of payment for parts are net 30 days.
FREIGHT POLICY
All parts orders will be shipped collect or
prepaid with the charges added to the invoice.
All ship ments are F.O.B. point of origin.
Multiquip’s responsibility ceases when a
signed manifest has been obtained from the
carrier, and any claim for shortage or damage
must be settled between the consignee and
the carrier.
MINIMUM ORDER
The minimum charge for orders from Multiquip
is $15.00 net. Customers will be asked for
instructions regarding handling of orders not
meeting this requirement.
RETURNED GOODS POLICY
Return shipments will be acce pted and
credit will be allowed, subject to the following
provisions:
1. A Returne d Material Autho riza tion
must be approved by Multiquip prior to
shipment.
2. To obtain a Return Material Authorization,
a list must be provided to Multiquip
Parts Sales that defi nes item numbers,
quantities, and descriptions of the items
to be returned.
a. The parts numbers and descriptions
b. The list must be typed or computer
c. The list must state the reason(s)
d. The list must reference the sales
e. The list must include the name
3. A copy of the Return Material Authorization
must accompany the return shipment.
4. Freight is at the sender’s expense. All
parts must be returned freight prepaid to
Multiquip’s designated receiving point.
must match the current parts price
list.
generated.
for the return.
ord e r ( s) or i n v o i c e( s ) u n de r
which the items were originally
purchased.
and phone number of the person
requesting the RMA.
co ndit ion, in th e origin al Multiq uip
package (if any), and with Multiquip part
numbers clearly marked.
6. The following items are not returnable:
a. Obsolete parts. (If an item is in the
price book and shows as being
replaced by anoth er item, it is
obsolete.)
b. Any parts with a limited shelf life
(such as gaskets, seals, “O” rings,
and other rubber parts) that were
purchased more than six months
prior to the return date.
c. Any line item with an extended
deal e r net pric e of less th an
$5.00.
d. Special order items.
e. Electrical components.
f. Paint, chemicals, and lubricants.
g. Decals and paper products.
h. Items purchased in kits.
7. The sender will be notifi ed of any material
received that is not acceptable.
8. Suc h mat eri al will be held for five
working days from notifi cation, pending
instructions. If a reply is not received
within five days, the material will be
returned to the sender at his expense.
9. Credit on returned parts will be issued
at dealer net price at time of the original
pur ch a s e, less a 15 % restocking
charge.
10. In cases where an item is accepted, for
which the original purchase document
can not be determined, the price will be
based on the list price that was effective
twelve months prior to the RMA date.
11. Credit issued will be applied to future
purchases only.
PRICING AND REBATES
Prices are subject to change without prior
notice. Price changes are effective on a
specifi c date and all orders received on or
after that date will be billed at the revised price.
Rebates for price declines and added charges
for price increases will not be made for stock
on hand at the time of any price change.
sell direct to Government agencies, and to
Original Equipment Manufacturer accounts
own products.
SPECIAL EXPEDITING SERVICE
A $35.00 surcharge will be added to the
invoice for special handling including bus
shipments, insured parcel post or in cases
where Multiquip must personally deliver the
parts to the carrier.
Multiquip shall not be liable hereunder for
damages in excess of the purchase price of
the item with respect to which damages are
claimed, and in no event shall Multiquip be
other special, consequential or incidental
damages.
LIMITATION OF WARRANTIES
No warran ties, expr ess or implie d, are
made in connection with the sale of parts or
trade accessories nor as to any engine not
manufactured by Multiquip. Such warranties
made in connection with the sale of new,
complete units are made exclusively by a
statement of warranty packaged with such
units, and Multiquip neither assumes nor
auth orize s any per son to ass ume for it
any other obligation or liability whatever in
from such written statement of warrant y,
there are no warranties, express, implied or
of the products on the face hereof.
Effective: February 22, 2006
PAGE 80 — GAC3.6HZ 60 HZ GENERATOR• OPERATION AND PARTS MANUAL — REV. #1 (03/31/10)
NOTES
GAC3.6HZ 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/31/10) — PAGE 81
OPERATION AND PARTS MANUAL
HERE’S HOW TO GET HELP
Multiquip Inc and the MQ logo are registered trademarks of Multiquip Inc. and may not be used, reproduced, or altered without written permission. All other trademarks are the property
The information and specifi cations included in this publication were in effect at the time of approval for printing. Illustrations, descriptions, references and technical data contained in
this manual are for guidance only and may not be considered as binding. Multiquip Inc. reserves the right to discontinue or change specifi cations, design or the information published
PLEASE HAVE THE MODEL AND SERIAL
NUMBER ON-HAND WHEN CALLING
UNITED STATES
Multiquip Corporate Offi ceMQ Parts Department
18910 Wilmington Ave.
Carson, CA 90746
Contact: mq@multiquip.com
of their respective owners and used with permission.
This manual MUST accompany the equipment at all times. This manual is considered a permanent part of the equipment and should remain with the unit if resold.