GENERAL
Read the entire contents of this manual before beginning installation. Multiaqua assumes no responsibility for equipment installed contradictory to any code requirement or installation instructions.
The components of this fan coil have been inspected at the factory and readied for shipment. Upon receiving the shipment a visual inspection of the packaging must be performed.
If any damage to the packaging is discovered, an inspection of the components must be performed and noted on the delivery documents. If component damage is found a damage claim must be filed by the receiving party against the delivery party immediately.
This product is designed and manufactured to permit installation in accordance with national codes. It is the
installer’s responsibility to install the
product in accordance with national codes and/or prevailing local codes and regulations. Care must be taken to ensure the structural integrity of the supporting members, clearances and provisions for servicing, power supply, coil connections and/or condensate removal. Before the installation ensure the structural strength of the supporting members is sufficient. See Figure 1 for hanging weights of the fan coils.
-------------------------------------- CAUTION --------------------------------------
Care must be taken when handling sheet metal. Sheet metal parts have sharp edges and could cause injury.
This unit is designed to be installed in a horizontal configuration only and into an enclosure assembly. The enclosure assembly is provided by others or field fabricated by the installing contractor.
The coil hand of connection is field reversible. See figures 4-6 for converting the coil hand of connection.
FAN COIL
APPROXIMATED
MODEL NUMBER
WEIGHTS (LBS)
MHNCCW-04-03
66.0
MHNCCW-06-03
68.2
MHNCCW-08-03
72.6
MHNCCW-10-03
74.8
MHNCCW-12-03
83.6
Figure 1
2
INSTALLATION & OPERATING
MANUAL
MHNCCW Fan Coil 1- 3 Tons
FAN COIL DIMENSIONS
Fan Coil
A B C D E
F
Model Number
MHNCCW-04-03
37.72
34.56
31.41
10.00
5.51
21.65
MHNCCW-06-03
37.72
34.56
31.41
10.00
5.51
21.65
MHNCCW-08-03
37.72
34.56
31.41
10.00
5.51
21.65
MHNCCW-10-03
43.70
40.55
37.40
10.00
5.51
21.65
MHNCCW-12-03
49.68
46.53
43.38
10.00
5.51
21.65
E
D
Hot Water Supply
1”
.75” (MPT)
Condensate Drain Connection (Both Ends)
.5”
Air Vents
Coil Drains
A
Drain Pan
Mounting Notches
Figure 3
Hot Water Return
Chilled Water
Supply
Chilled Water
Return
C
B
F