Multiaqua CFFZ Instructions Manual

INSTALLATION
&
OPERATING INSTRUCTIONS
CHILLED WATER FANCOIL
FLOOR/CEILING
CFFZ SERIES
Installation and servicing of air conditioning equipment can be hazardous due to system pressure
and electrical components. Only trained and qualied service personnel should install, repair or
service air conditioning equipment.
When working on air conditioning equipment, observe precautions in the literature and labels attached
to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing
operations. Have a re extinguisher available for all brazing operations
WARNING
Before preforming service or maintenance operations on the system, turn off the main power switches
to the indoor and outdoor unit. Electrical shock could cause personal injury.
! !
INITIAL CHECK
(1) The carton should not be removed from unit until reaching nal location to avoid damage. (2) Inspect unit for shipping damage and le a claim with the transport agency if necessary. (3) Check eld electrical works: (a) Proper size of fuses and wire, correct wiring connections and grounding as specied
by the local electrical codes.
(b) Also check supply voltage, which must be within the limits shown on the nameplate. (4) Check for a proper condensate ow.
(5) Be sure piping insulation is adequate.
(6) Conrm there are no obstructions to air ow for indoor and outdoor units. Also check for sufcient clearances for servicing the unit.
MODEL A L 12-24 1024 927 30-36 1324 1227 48-60 1925 1828
1
LOCATION & MOUNTING
105
(1) The unit should be installed for horizontal and vertical discharge application only.
(2) Select position for unit and dene direction of water pipe, drain pipe and electrical wire.
(3) Prepare mounting bolt for mounting unit under ceiling or on a wall at the distance
dened in Fig. 1.
642
330
SIDE VIEW
105
48.5
TOP VIEW
L
BRACKET HANGER
A
FRONT VIEW
330
48.5
Fig. 1
(4) Remove unit from carton and carefully place the unit into the position and tighten the (4) bolts.
Fig. 2
Fig. 3
Fig. 4
2
INSTALLATION
When mounting the indoor unit on the ceiling, oor or wall, follow the instructions below:
(1) Select a location that permits the air current to circulate evenly throughout the room.
O GOOD LOCATION EVENLY COOLED X BAD LOCATION OBLIQUE - LINE
Fig. 5
(2) Select a location that has enough service space when the unit is mounted under the ceiling.
300 MM300 MM
(3) Select a location that has enough service space when the unit is mounted on the
oor/wall.
Fig. 7Fig. 6
3
Loading...
+ 8 hidden pages