MTP 3100 Instruction Manual

Page 1
INSTRUCTION MANUAL
Wireless Electricity Monitor
MTP 3100
(2
Generation)
Page 2
TABLE OF CONTENTS
1. Introduction 1
2. Safety and Maintenance Information 1
3. Features / Specifications 2
4. Components in the Box 2
5. Product Layout 3
6. Linking the MTP 3100 – Energy Monitoring System 4
7. Display Information 5
8. History Data Clearance and Factory Reset 7
9. Getting into Setting Mode & Set-up Instructions 9
10. Operation 18
11. Installation (Single Phase System) 25
12. Installation (3 Phase System) 26
13. Frequently Asked Questions (FAQ) 27
Page 3
www.mtpinc.com 1
INTRODUCTION / SAFETY
CAUTION! This symbol indicates that the operator must refer to an explanation in the Operating Instructions to avoid personal injury or damage to the meter.
WARNING! It is recommended you contact a qualified electrician to install the clamps on the electrical panel. We will not be held responsible for damage as a result of a wrong connection which may cause injury or death.
1. Introduction
Congratulations on the purchase of your new smart wireless electricity monitor, Model MTP-3100. This product was designed to help you monitor and better manage electricity consumption. This guide is aimed at helping you in the set-up of the wireless monitoring system. Careful use of this device will provide years of reliable service.
Please note this manual will refer to the below devices in the following manner:
Receiver = Monitor (M)
Sender = Transmit (T)
2. Safety and Maintenance Information
Before installation, please pay attention to the following information:
Please read all instructions before you use the monitoring system. Please shake the display unit and the power transmitter first, before installation. Do not use if you hear
any loose parts and communicate with your authorized distributor for replacement.
Do not allow children or people unfamiliar with these instructions use the system. Keep the monitor, transmitter and sensor clamp away from sources of heat, water or any other liquid. Place the monitor, transmitter and sensor clamp where children can not touch or pull. Do not try to disassemble or modify any parts of the monitoring system. In case of problem, please
consult your representative.
Do not use the monitoring system if you find that your electric wire is in an abnormal condition, such as
loose wire, exposed copper wire, burnt mark on wire insulation layer, holes on wire layer or damage on electric meter. In case of such abnormalities, please consult a professional electrician immediately.
Periodically check all wires and components to ensure there is no damage. Use a dry cloth to clean. Do not use solvent, abrasive cleaners or water.
FCC Declaration of conformity: Tested to comply with FCC standards. This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, inlcuding interference that may cause undesired operation. Complies with Industry Canada ES-003l.
This instrument conforms to UL STD # 61010-1 / # 61010-2 certified to CSA STD C22.2 # 61010-1 / # 61010-2
Page 4
www.mtpinc.com 2
FEATURES/ SPECIFICATIONS/INCLUDED COMPONENTS IN THE BOX
3. Features
Model Name / Number: MTP-3100 Frequency: 433MHz Transmission Time: 10s, 15s, 20s (settable)
Transmission Range: ≤70m
Voltage Range: 90V to 600V Measuring Current: 200A (max) Accuracy: 0.2A-1A ± 20% / 1A-150A ± 7% / 150A-200A ±15% Tariff Periods: TOU and NMP Temperature: Celsius and Fahrenheit History: Instant, Daily, Weekly, Monthly Display: Instant Energy (kW), Energy Consumed (kWh), Dollar Value ($), Pollution (kg.
CO2)
Backlight: Yes, see page 17 Warranty: One (1) year
Specifications
Certifications: IC, FCC, ETL Country of Origin: China Size of Monitor: 145 x 109 x 60mm Size of Transmitter: 92 x 72 x 43mm Weight of Monitor: 300g with "AA" batteries Weight of Transmitter: 320g with 2 type "C" batteries Diameter of Clamps: 18mm Operating Temperature: 0°C to 50°C Storage Temperature: -10°C to 50°C
4. Components in the box
If any of the parts listed below are missing, please contact your authorized distributor immediately.
1 x Display Unit (Monitor) 1 x Wireless Transmitter (includes x 2 type "C" batteries) 2 x Sensor Clamps w/ 18mm diameter 1 x Data Cable RJ45-USB 3m 1 x Power Adapter 1 x User Manual in English and French 1 x Mini CD for Software
NOTE : Batteries for Monitor are not included. Monitor requires (x03) “AA” batteries. It is recommended to use Lithium batteries.
Page 5
www.mtpinc.com 3
PRODUCT LAYOUT
5. Product Layout
TRANSMITTER
Page 6
www.mtpinc.com 4
LINKING THE MTP 3100 - ENERGY MONITORING SYSTEM
6. Linking the MTP 3100 – Energy Monitoring System
Transmitter Monitor
Remove plastic tab on Transmitter (Found on back of transmitter)
Power the Monitor with batteries OR using the power adaptor
IMPORTANT
During the Linking process, STEPS #3 and #4 must be performed seconds apart.
Begin by activating the signal search on the monitor,
followed soon after by activating the signal search on the transmitter. The signal search on the monitor has a duration of 1 minute.
IMPORTANT
During the Linking process, STEPS #3 and #4 : Keep the Monitor and Transmitter as close as possible.
Press and hold down the linking
button on the MONITOR for approx. 3 seconds, until the LED light starts blinking then release the button.
Press and hold down the linking button
on the front of the TRANSMITTER for 15 seconds, then release. A red LED will flash rapidly on the transmitter during the linking period.
SUCCESSFUL linking is demonstrated by an
antenna in the top left corner of the screen. FAILED Linking will not display an antenna on the left corner of the screen.
00
PASS FAIL
Note : During the linking process, keep the transmitter as close as possible to the monitor.
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5
COMPONENTS
Page 7
www.mtpinc.com 5
DISPLAY INFORMATION
7. Display Information
Soon after successfully pairing the monitor and transmitter, the LCD screen will automatically return to the default display.
The LCD screen will depend on user’s tariff choice, TOU (Time of Use) tariff or NMP (Normal Meter Pricing), the default tariff mode is TOU. See pages 10-12 on how to setup tariff mode.
TOU (Time of Use): This tariff setting allows you to set tariff rates according to two seasons, Summer and Winter rates. For each season you can set four (4) tariff rates applicable to every day in the weekday, Monday to Friday and a fifth tariff rate for the weekend, Saturday and Sunday. TOU is based on the Ontario
tariff rate system.
NMP (Normal Meter Pricing): Program from 1 to 3 tariffs per day, for every day of the week.
Normal Meter Pricing
Time of Use
Page 8
www.mtpinc.com 6
Default Display Under Normal Working Conditions
The image below is the Default Display, it appears automatically once the pairing is successful. LCD screen also returns automatically to this display if there is no button operation for a period of time.
Page 9
www.mtpinc.com 7
HOW TO CLEAR DATA
8. History Data Clearance and Factory Reset
History Data Clearance
To reset only the History data, please follow the instructions below. Note that this does not perform a factory reset.
1. Press and release the HISTORY button to enter in the HISTORY mode.
2. In the HISTORY mode, keep pressed the UP and DOWN buttons simultaneously for about 5 seconds (until
red light flashes).
3. The history data (including histogram) are now cleared while all other settings such as date, time, tariff
selection are kept the same.
Note: At step 2, the data clearance can be performed under any history data interface (daily/weekly/monthly: kWh, $, kg CO2)
STEP 1
STEP 2
History
Data
Cleared
Page 10
www.mtpinc.com 8
Factory Reset
1. When the default screen is displayed, simultaneously press and hold down the MODE/SET and HISTORY
keys. The full LCD screen will appear after 10 seconds.
2. When the red LED starts blinking, release MODE/SET and HISTORY keys and the ʺSoftware Versionʺ will
appear.
3. Memory Reset done = Factory setting Date: 01/01/2011 and Time: 00:00.
* The user should do the pairing again.
Hold
simultaneously
for 10 seconds
MODE/SET &
HISTORY
keys
STEP 1
Software Version
Full LCD
STEP 3
Memory
Cleared
STEP 2
Release
the keys when
the RED LED
starts blinking
The Full LCD
will appear
The Software
Version will
appear after
releasing the
keys
IMPORTANT: A Factory Reset will permanently delete all the data in the monitor, including the history.
Page 11
www.mtpinc.com 9
SET-UP INSTRUCTIONS
9. Getting into Setting Mode & Set-up Instructions
While the default screen is displayed, press and hold down the SET/MODE key for 3 seconds, until the red LED starts blinking, then release the SET/MODE key. The monitor is now in Setting Mode.
Scrolling Through the Setting Modes
To scroll through the setting modes (Voltage, Currency, TOU, NMP, CO₂, Max.P, Time, Date, Temperature
and Buzzer), press the UP or DOWN arrow keys.
Selecting a Specific Setting Mode
To select a Specific Setting Mode (Voltage, Currency, TOU, NMP, CO₂, Max.P, Time, Date, Temperature or Buzzer), use the UP and Down keys to select, followed by the MODE/SET key to enter the selection.
Press
MODE/SET key
to enter the Setting
Selection
Settings to choose from :
● Voltage ● Time, Date
● Currency ● Temperature
● TOU (Tariff) ● Buzzer
● NMP (Tariff)
KgCO₂
● Max.P
Press
UP or DOWN keys
to scroll through
setting modes
PRESS UP
PRESS DOWN
OR
Hold
MODE/SET
for
3 seconds
Entering
SETTING MODE
The Voltage
symbol blinks
STEP 1
Voltage
NOTE : To exit the Setting Mode and return to the default display press the HISTORY button.
Page 12
www.mtpinc.com 10
Changing Values
To change the values of any particular setting, begin by selecting the setting (eg. Voltage) and follow the instructions below.
VOLTAGE
The Voltage symbol should blink, confirming that you are now in Setting Mode.
1. Press SET/ MODE key to enter into Voltage Selection
The first digit “1” will start flashing.
2. Press the or key to increase or decrease value, then press the MODE/SET key to confirm
(validate) this digit and move on to the next digit.
3. Repeat the same steps for other digits. After validation of the last digit, the screen returns to the
default ʺSetting Modeʺ screen and the Currency symbol starts flashing. If you need to go back to Voltage settings, use or key to reselect Voltage symbol then confirm.
Press
MODE/SET
when the Setting (eg.
Voltage) is blinking
MODE
STEP 1
STEP 2
Voltage
120 V
Press the
▲ or ▼
to increase or decrease
value
To confirm the value
press MODE/SET
Increase
Decrease
MODE SET= Confirm & move to Next Digit
STEP 3
Repeat the same steps as
STEP 2 for other digits
After the last digit is
validated, the next setting will appear
flashing
HISTORY = Quit & Save only
in ʺSetting Modeʺ screen
Voltage
120
V
Page 13
www.mtpinc.com 11
Kr $ £
Currency Setting
1. When in Setting Mode, If necessary, use or key to select ʺKrʺ currency symbol
then press MODE/ SET key to confirm and enter in selection.
2. While in Currency Setting Mode, use or key to select the desired currency
symbol (symbol will blink).
3. When the currency symbol is blinking, press the SET/MODE key to confirm
TOU (Time-Of-Use) Tariff setting
Time-of-Use (TOU) tariff setting, allows you to set tariff rates according to two seasons, Summer and Winter rates. You can set four (4) tariff rates for four seasons which are applicable to every weekday, Monday to Friday; and a fifth tariff rate for the weekend, Saturday and Sunday. TOU is based on the
Ontario tariff rate system (Canada).
Default Factory Setting : The default factory tariff setting is Time-of-Use (TOU). The tariff rates are based
on the Ontario Hydro tariff system for the period May 1st, 2014 to April 30th, 2015. Please take the time to verify if the tariffs have changed with your local electricity provider and perform the changes, if necessary. For instructions on how to change TOU tariff settings, please refer to TOU Tariff Setting on this page.
Summer Season (from May 1
st
2014 to October 31st 2014)
Weekdays (Monday to Friday) :
o 19:00 – 07:00 (Tariff 01 : 7.7 cents/kWh, off-peak) o 07:00 – 11:00 (Tariff 02 : 11.4 cents/kWh, mid-peak) o 11:00 – 17:00 (Tariff 03 : 14 cents/kWh, on-peak) o 17:00 – 19:00 (Tariff 04 : 11.4cents/kWh, mid-peak)
Weekend (Saturday and Sunday):
o 00:00 Saturday to 23:59 Sunday (Tariff 05 : 7.7 cents/kWh, off-peak)
Winter Season (from November 1
st
, 2014 to April 30th, 2015)
Weekdays (Monday to Friday) :
o 19:00 – 07:00 (Tariff 01 : 7.7 cents/kWh, off-peak) o 07:00 – 11:00 (Tariff 02 : 14 cents/kWh, on-peak) o 11:00 – 17:00 (Tariff 03 : 11.4 cents/kWh, mid-peak) o 17:00 – 19:00 (Tariff 04 : 14 cents/kWh, on-peak)
Weekend (Saturday and Sunday):
o 00:00 Saturday to 23:59 Sunday (Tariff 05 : 7.7 cents/kWh, off-peak)
NOTE : The TOU tariff setting can be modified by following the instructions. If the TOU tariff system does not meet your actual situation, please ignore the TOU Tariff mode by pressing key to move on to NMP tariff mode, on page 11.
Page 14
www.mtpinc.com 12
01 / 05
Summer
Changing Default (Factory) Settings for TOU :
The default factory setting ʺTOUʺ tariff (based on Ontario Hydro tariff System) is as described on page 11. To make changes, please follow the instructions below.
NOTE : When in Setting Mode, use or key to select TOU symbol, then press MODE/ SET key to confirm and enter in selection. Refer to instructions ‘Scrolling Through the Setting Modes’ on page 8 to learn how to enter selection.
1. Set the Starting Month for Season 1 (Summer), use the or key to select the value for the Month,
followed by the MODE/SET key to confirm.
2. Select the Starting Day for Season 1 (Summer), use the ▲ or key to select the value for the Day,
followed by the MODE/SET key to confirm.
3. Starting with Tariff 1 (Summer), set the four tariff rate periods applicable to every day in the Weekday,
Monday to Friday. To change the tariff rate value use the or key, to confirm the value press the
MODE/SET key. Do this until all values for the Tariff 1 are selected.
4. After Tariff 1 is set, the Start Time for Tariff 01 (Summer) needs to be set. To set the Hour, use the or
key to select the Hour value and press the MODE/SET key to confirm.
5. Now set the Minutes value for the Start Time of Tariff 01 (Summer). To set the Minutes, use the or
key to select the Minutes value and press the MODE/SET key to confirm.
6. After completing Tariff 04, you will need to set Tariff 05. Since it is a fixed tariff for the weekend,
Saturday and Sunday, only the tariff rate needs to be set. To change the tariff rate value, use the or key; to confirm the value, press the MODE/SET key. See top of page 11.
Set Starting DAY/MONTH
( For TOU – Summer / Winter Periods )
Set TARIFF 01 - 04 for Weekdays (Monday to Friday)
( For TOU – Summer / Winter Periods )
Summer
(Season 1)
Press
or
To select
Month
Then press
MODE
SET
to confirm
Press
or
To select
Day
Then press
MODE
SET
to confirm
Tariff 01
Press
or
To select
Tariff Rate
Then press
MODE
SET
to confirm
Press
or
To select
Hour
Then press
MODE
SET
to confirm
Press
or
To select
Minutes
Then press
MODE
SET
to confirm
STEP 1
STEP 2
STEP 3
STEP 4
Summer
$0.063
19:00 01
IMPORTANT : After completing the configurations for the Summer season, the Winter rates need to be configured by repeating the same steps as the Summer season.
IMPORTANT : After completing STEP 5, you will automatically be invited to repeat STEPS 3 to 5 for the remaining weekday tariff rate periods 2, 3, and 4.
Page 15
www.mtpinc.com 13
NMP1
NMP12
NMP
123
Summer
$0.063
05
NMP (Normal Meter Pricing) Tariff setting
Normal Meter Pricing (NMP) includes three different tariff setting modes, applicable to every day of the week. These tariff modes are :
Single Tariff Setting : Set one fixed tariff rate throughout the day, for every day of the week Two Tariff Setting : Set two tariff rates for different periods of the day, for every day of the week. Three Tariff Setting : Set three tariff rates for different periods of the day, for every day of the week.
1. When in Setting Mode, use or key to select NMP symbol, then press MODE/SET key to confirm
and enter in selection. Refer to instructions ‘Scrolling Through the Setting Modes’ on page 7 to learn how to enter selection.
2. Once in the NMP selection, you must now select a (Single-Tariff (NMP1), 2-Tariff (NMP12) or 3-tariff
(NMP123), by using the or key. See instructions below.
Setting the Number of Tariff(s)–per–Day
Single Tariff
Press
or
To select
Then press
MODE
SET
to confirm
Two Tariff
Press
or
To select
Then press
MODE
SET
to confirm
Three Tariff
Press
or
To select
Then press
MODE
SET
to confirm
Set TARIFF 05 for Weekend ( Saturday / Sunday )
( For TOU - Summer/Winter Period )
Tariff 05
Press
or
To select
Tariff Rate
Then press
MODE
SET
to confirm
IMPORTANT :
After completing STEP 6,
you are now ready to
configure the setting for
the Winter Season
Repeat STEPS 1 through 6
(Summer Period), for the
Winter Season.
NMP1
NMP12
NMP
123
STEP 6
NOTE : If the NMP tariff system does not meet your actual situation, please ignore the NMP Tariff setting by
pressing key to go back to TOU tariff.
Page 16
www.mtpinc.com 14
$0.163
NMP1
Setting a Single Tariff Rate (NMP1) :
When selecting a single tariff (NMP1):
1. Press the orkey and select NMP1 by pressing MODE/SET key.
2. Adjust the tariff rate by setting the values (0-9) for each flashing digit. Use the
SET/MODE key to confirm each digit.
3. Once the tariff rate is completed, press the SET/MODE key to confirm the tariff
setting and return to the Setting Mode. Note : There is no need to set starting time for single tariff.
Setting a Two Tariff Rate (NMP12) :
When setting a two tariff rate ʺNMP12ʺ, each period 1 and 2 must be set separately. Begin by setting the tariff rate for period 1, followed by the second.
1. When setting a two period tariff rate (NMP12), begin by setting the first tariff rate period by using the
or key. Adjust the tariff rate by setting the values (0-9) for each flashing digit. (Use the MODE/SET) key to confirm each digit).
2. When setting a two period tariff rate (NMP12), begin by setting the first tariff rate period by using the
or key. Adjust the tariff rate by setting the values (0-9) for each flashing digit. (Use the MODE/SET key to confirm each digit).
Set Tariff Rate for Period 1
Tariff Rate
Period 1
Press
or
to set Rate
Values (0-9)
Then press
MODE
SET
to confirm
for each
Time
Period 1
Press
or
to set
Start Time
Press
MODE
SET
to confirm
Hour and
Minutes
3. Using the or▼key, adjust the Second tariff rate by setting the values (0-9) for each flashing digit. (Use
the SET/MODE key to confirm each digit).
4. When the tariff rate for the second period has been set (confirmed), use the or▼key to select the
starting time of the second tariff period. Set the hour (00-23) and minutes (00-59) and press the
SET/MODE key to confirm
STEP 1
STEP 2
Page 17
www.mtpinc.com 15
Set Tariff Rate for Period 2
Tariff Rate
Period 2
Press
or
to set Rate
Values (0-9)
Then press
MODE
SET
to confirm
for each
Time
Period 2
Press
or
to set
Starting Time
Press
MODE
SET
to confirm
Hour and
Minutes
Setting a 3 Period Tariff Rate (NMP3):
For a 3 period tariff rate, select NMP123. Follow the same instructions as for NMP12 (Please refer to ‘Setting a Two Tariff Rate NMP12’ on page 11), except that this time, there is a third tariff period to set. For each period, begin by setting the tariff rate value ($) followed by the time-period for the respective rate.
Note : To set Tariff Rate and Periods 1 and 2, refer to ‘Setting a Two Tariff Rate (NMP12)’ on page 11. It is very important to choose NMP123.
Set Tariff Rate for Period 3
Tariff Rate
Period 3
Press
or
to set Rate
Values (0-9)
Then press
MODE
SET
to confirm
for each
Time
Period 3
Press
or
to set
Starting Time
Press
MODE
SET
to confirm
Hour and
Minutes
STEP 3
STEP 4
STEP 5
STEP 6
Page 18
www.mtpinc.com 16
Max. P.
9999 W
0.54 kg co2
CO2 Calculating Factor Setting ( Greenhouse Gas Emission)
Please contact your local electricity provider to determine the Greenhouse Gas
Emission per kWh consumed. Depending on the electricity production method (Hydro, Wind, Coal, Nuclear, etc.), the CO₂ emission will vary.
1. While kg co
2
is blinking, press MODE/ SET key to access the kg co2 Setting Interface.
The first digit “0” will start flashing.
2. Press the or key to increase or decrease the value.
3. Press the MODE/ SET key to confirm this digit and move on to the next digit.
4. Repeat the same steps for the other digits.
5. After the last digit is validated, the general setting mode screen will show up.
NOTE : If you need to go back to kg co2 setting, use or key to select kg co2 symbol again.
Max. P. (Maximum Power Alarm)
When setting the Maximum Power Alarm, if the actual power is larger than the maximum power value, the LED light (on the monitor) will quickly flash twice every 30 seconds. If the buzzer setting is ON, a beep sound will also be heard once every 60 seconds.
1. While Max. P. is blinking, press MODE/ SET key to access the Max. P. Setting
Interface.
The first digit “9” will start flashing.
2. Press the or key to increase or decrease the value.
3. Press the MODE/ SET key to confirm this digit and move on to the next digit.
4. After the last digit validation, press the or key to choose between ʺWʺ and
ʺkWʺ, then press MODE/ SET key to select. After doing so, the general setting mode display will appear
NOTE : If you need to go back to Max. P. setting, use or key to select Max. P. symbol again.
Greenhouse Gas Emission
From the Different Generating Options
Source : http://hydroforthefuture.com
Page 19
www.mtpinc.com 17
TIME (Clock) Setting
1. While Clock is blinking, press MODE/ SET key to access the Clock Setting Interface.
The Hour value will start flashing.
2. Press the or key to increase or decrease value.
3. Press the MODE/ SET key to confirm these digits and move on to minute value.
4. Repeat the same steps you have done for Hour value. After the last digit has been
validated, the general setting mode screen will show up.
NOTE : If you need to go back to Clock setting, use or key to select the Clock Symbol again.
DATE Setting
1. While 01/01/2011 is blinking, press MODE/ SET key to enter into Date Setting
Interface. The Year value will start flashing.
2. Press the or key to increase or decrease value to set the Year.
3. Press the MODE/SET key to confirm this digit and move on to the next digit. After
Year value has been set, the Month value will start to flash.
4. Press the or key to increase or decrease value to set the Month. Press
MODE/SET key to confirm. After the Month value has been set, the Day value will
start to flash.
5. Press the or key to increase or decrease value to set the Day. Press
MODE/SET key to confirm. After the last digit has been confirmed, the general setting mode screen will show up. NOTE : If you need to go back to Date setting, use or key to reselect Date value.
TEMPERATURE UNITS
1. While Temp is blinking, press MODE/ SET key to enter into Temp. Unit Setting
Interface. The Celsius (°C) symbol will flash.
2. Press or key to choose between °C and °F units, then press MODE/ SET key
to confirm. The general setting mode screen will show up.
BUZZER ON/OFF
1. While bOFF is blinking, press MODE/ SET key to access the Buzzer Setting
Interface.
2. Press or key to choose between ON and OFF status, then press MODE/ SET
key to confirm. The general setting mode screen will show up.
Note : When the buzzer is set to ON, the bell icon will appear on the top right corner of the display screen.
05:40
Clock
01/01/2011
°C
°F
Temp.
b ON
Page 20
www.mtpinc.com 18
10. Operation Viewing History and Average Data
When the default screen is displayed, press the HISTORY key to view the data that have been gathered up to present time for various time periods (Day, Week and Month).
Press the
HISTORY key once
Daily Mode
Accumulated data up to now from 00:00 of today.
Accumulated data up to now from 00:00 Monday of current week.
Accumulated data up to now from 00:00 the 1st of current month.
The Average for each time period is displayed on the top line. The average for a time period is the forecast of a complete day, week or month based on data accumulated during a smaller time frame. E.g. Current day has an accumulated data of 8kWh in 20 hours, so the forecast of the complete day should be 8/20*24=9.6kWh, displayed as 10kWh.
E.g. of Average value for the current week : displays an accumulated consumption of 80kWh in 6 days meaning the daily average kWh is 80/6, hence the forecast of the complete week should be 80/6*7=93kWh.
Weekly Mode
Press the
HISTORY
key twice
Monthly Mode
Press the
HISTORY
key three
times
Note: When viewing the history data, if there is no button operation for 20 seconds, the display will return to default screen.
Page 21
www.mtpinc.com 19
Switching Data Type (History)
When viewing the History (up to now), press the MODE/SET key at any time to change the type of data history displayed amongst any of the following options: Energy consumption (kWh) Currency ($) and CO2 emission (kg CO2).
Press
HISTORY
key.
Default kWh
will appear
on screen
Energy Consumption
(kWh)
Currency
Press
MODE/SET
key one time.
Currency will
appear on
screen
CO₂ Emission
(kG CO₂)
Press
MODE/SET
key another
time and
Kg CO2 will
appear on
screen
Page 22
www.mtpinc.com 20
Retrieving History and Average Data (Past Consumption)
Retrieve and View History Data of the Last 7 Days
From the default display screen, click the HISTORY key one time and notice that the word "Daily" will appear on the screen (See picture below). The "Daily" function stores the past 7 days of data, as well as the accumulated data up to now, from 00:00 of today.
Retrieve and View the History Data of the Last 52 Weeks
From the default display screen, click on the HISTORY key twice and notice that "Weekly" will be displayed on the screen (See picture below). The ʺWeeklyʺ function stores the past 52 weeks of data, as well as the accumulated data up to now, from 00:00 Monday of current week.
Press
HISTORY
key
STEP 2
STEP 1
Note : Repeat Step 2 to review the last 52 weeks of data. Press key to step back 1 week.
Average value = (This Week’s Average Data + All Past Weeks’ Real Data)/Number of Weeks (including this week).
This Week
Last Week
Press
HISTORY key
twice for
Weekly
History
Press key
to retrieve
data for
the past
52 weeks
Press key
to retrieve
data for the
past 7 days
Press
HISTORY
key
Press
HISTORY
key once for
Daily History
Mode
STEP 2
STEP 1
Note : Repeat Step 2 to review the last 7 days of data. Press key to step back 1 day.
Average Value = (Today’s Average Data + All Past Days’ Real Data)/Number of days (including today).
Today
Yesterday
Page 23
www.mtpinc.com 21
Retrieve and View the History Data of the Last 24 Months
From the default display screen, click on the HISTORY key three times and notice that "Monthly" will be displayed on the screen (See picture below).
Antenna Icon and Clamp on Sensor Icon on the Display
When the monitor successfully receives a signal from the transmitter, the antenna icon appears on the top left corner of the display screen. Located beside the antenna icon on the display, is the clamp-on sensor icon which indicates the number of clamp-on sensors connected to the transmitter.
7. Battery Status
The default screen also indicates the battery status of the Monitor (Battery icon with an "M"), located at the top of the screen. The icon displays battery condition as full, half-full
and weak (corresponding to 3.9V, <3.9V and >3.1V, <3.1V respectively).
Only when the total battery power for the Transmitter / Sender is below 2.3V will the low battery warning icon appear. The low battery indicator for the transmitter is represented by a battery icon with a "T". The warning icon will flash once every second to remind the user to replace the batteries
Press
HISTORY
key
STEP 2
STEP 1
Note : Repeat Step 2 to review the last 24 months of data. Press key to step back 1 month.
The Average value = (This month’s Average Data + All Past Months’ Real Data)/Number of Months (including this month).
This Month
Last Month
Press
HISTORY key
three times
for Monthly
History
Mode
Press key
to retrieve
data for
the past
24 months
Page 24
www.mtpinc.com 22
Backlight
When powered with batteries, the backlight of the monitor is available only between 6:00 p.m. and 8:00 a.m. when there is key operation.
On the other hand, when the monitor is powered by the external power adapter, the display backlight goes on whenever there is a key operation.
Histogram
The purpose of the histogram (on the default display screen) is to demonstrate the energy consumption tendency for the week. The number of bars displayed on the histogram for each day can range between zero (meaning no energy consumption) to five (5). The bars appear once the value has reached more than 1/3 of the real value.
Depending of the energy consumption, if the highest consumption is equal to or below 10kWh, the full scale of the histogram will be displayed as 10kWh. This means that each bar in the histogram has a value of 2kWh or (10kWh/5 = 2kWh)
If the highest daily energy consumption is between 10kWh and 100kWh, the scale on the histogram will be displayed as 100kWh. This means that the value of each bar is 20kWh.
If the highest daily energy consumption exceeds 100kWh, the scale on the histogram will be displayed as 1000kWh. This means each bar has a value of 200kWh.
Note: The histogram will appear once sufficient data has been gathered.
Page 25
www.mtpinc.com 23
Signal Frequency Setting (Transmitter)
Push and hold the button (on transmitter) for 3 seconds, the LED light will change color. To change the light color again, release the button and push again for 3 seconds. Once set, the LED will flash in the selected color. The light color codes represent the following signal frequencies.
Red light = 10s Blue light = 15s Blue + Red light = 20s
Sensor Clamps
Each transmitter can support up to 3 sensor clamps. All sensor clamps are detachable from the transmitter. The measurement range of 18mm clamp is 0.2amps to 200amps. Accuracy: for range 0.2-1amps, 20%; for 1-150amps, 7%; for 150-200amps, 15%
Transmitter can be used with 25mm clamp, sold separately. The measurement range of the 25mm clamp is 0.2amps to 200amps. Accuracy: for range 0.2-1amps, 35%; for range 1-200amps, 15%.
The transmitter for 18mm clamp cannot be used with 25mm clamp and vice versa.
Page 26
www.mtpinc.com 24
IMPORTANT NOTICE: Please contact a qualified electrician to carry out the installation. We will not be held responsible for damage as a result of a wrong connection which may cause injury or death. Please note that the monitor displays the apparent Power (VA) and not the Active Power (Watts).
“Before making any connection to a Live Circuit”, connect all clamp sensors to
transmitter.
*** IMPORTANT NOTE *** This is very important because when current is flowing through the sensor clamp, the resulting voltage induced in the secondary can be quite high.
The sensor needs to be fitted to the live feed cable. You should not force
the cable to fit.
2. Push the release cap to open the sensor.
3. Select the correct feed cable and then place the feed cable into the top of the sensor.
4. Close the sensor. The sensor is secure when a
“click” is heard.
INSTALLATION
Page 27
www.mtpinc.com 25
Installation on standard 200A panel
Unscrew the four corners to remove the electrical panel
protection cover.
Fit the two enclosed 200A clip-on sensors (sensors are
suitable for use with wire diameters up to 18mm) to the live feed cables of the electrical panel.
Insert each plug on the end of the white wire into any of
the input sockets of transmitter.
The clip-on sensor acts as a current sensor and relays the
current being drawn into the home to the transmitter. From there, it is sent wirelessly to the monitor display unit. Clip the sensor clamp around the "Live Wire" of the electricity panel. The live wire is usually located behind a metal cover. (Please contact a qualified electrician).
Transmitter
Monitor
Please refer to this manual for set-up of monitor.
Important: Select 120V as reference voltage.
Please note that monitor displays the Apparent Power (VA) and not the Active Power (watts).
11. Installation (Single Phase System)
IMPORTANT NOTICE: Please contact a qualified electrician to carry out the installation. We will not be held responsible for damage as a result of a wrong connection which may cause injury or death. Please note that monitor displays the Apparent Power (VA) and not the Active Power (watts).
INSTALLATION
Page 28
www.mtpinc.com 26
12. Installation (3 Phase System)
IMPORTANT NOTICE: Please contact a qualified electrician to carry out the installation. We will not be held responsible for damage as a result of a wrong connection which may cause injury or death. Please note that monitor displays the Apparent Power (VA) and not the Active Power (watts).
* Regarding 3 phase 4 wire supply (Diagram 2), a third sensor clamp is needed (sold separately).
Page 29
www.mtpinc.com 27
13. Frequently Asked Questions (FAQ)
Q: How can the data stored in the receiver be cleared? A: Please refer to the section 8, History Data Clearance & Factory Reset, on pages 7 and 8 of this manual
Q: What is the maximum distance the device can transmit signals?
A: ≤ 70 meters
Q: The transmitter and receiver do not seem to communicate with one another, what should be done? A: Please refer to page 4 for Linking Instructions.
Q: The backlight on the monitor does not always work, is there a reason? A: When powered with power adapter, the backlight goes on whenever there is key operation.
When powered with batteries, the backlight is only available between 18:00 and 24:00 with key operation.
Q: Can the Energy Monitoring System be used to compare with my local utility provider? A: The Energy Monitoring System is meant to raise electricity consumption awareness. It is not meant to compare with your local utility provider bill.
Limited Warranty and Limitations of Liability
MTP Instruments warrants this instrument to be free of defects in parts and workmanship for
one (1) year from date of shipment. This warranty does not apply to defects resulting from action of the user such as misuse, improper wiring, operation outside of specification, improper maintenance or repair, or unauthorized modification. MTP Instruments specifically disclaims any implied warranties or merchantability or fitness for a specific purpose and will not be held liable for any direct, indirect, incidental or consequential damages. MTP Instruments total liability is limited to repair or replacement of the product.
FREQUENTLY ASKED QUESTION
Page 30
www.mtpinc.com 28
4409 Charleroi street
Montreal-North, Quebec
H1H 1T6
Telephone: (514) 326-7167 Fax: (514) 326-7835
Toll Free Number: 1-888-326-7167
Web Site : www.mtpinc.com E-mail : info@mtpinc.com
Distributed by :
Loading...