SineWave Guardian Technical Reference Manual 380V - 480V
Conventional 3 phase motors operating in volts per Hertz mode
Standard step-up transformer
Harmonic Voltage Distortion
Inverter Switching Frequency
Inverter Operating Frequency
6Hz to 75Hz,
>75Hz to 120Hz with derating
Maximum Ambient
Temperature
-40C to +60C Modular Filter
-40C to +55C Enclosed Filter
-40C to +90C Storage
Modular
NEMA 1 & 2
NEMA 3R
Altitude without derating
3,300 feet above sea level
Maximum Motor Lead Length
100% RMS Continuous
150% for 1 minute Intermittent
4. PRODUCT SPECIFICATIONS
Performance Specifications
Table 4-1: Performance Specifications
Filter does not mitigate any DC bus ripple that may be present.
Form: SWG-TRM-E June 2015 REV. 003 11
SineWave Guardian Technical Reference Manual 380V - 480V
NC Switch opens at 180 Deg. +/- 5 Deg. C
Enclosures
MTE enclosures are designed to provide a degree of protection for electrical components and
prevent incidental personnel contact with the enclosed equipment. Depending on the enclosure
selected, these enclosures meet the requirements of NEMA 1, 2 or 3R.
An approximate cross reference guide between NEMA, UL, CSA and IEC enclosure follows.
Type 1 NEMA / IEC IP20 Enclosure:
Are designed for indoor use and will provide protection against contact with the enclosed
equipment.
Type 2 NEMA / IEC IP20 Enclosure:
Are designed for indoor use and will provide protection against contact with the enclosed
equipment and provide a degree of protection against limited amounts of falling water
and dirt.
Type 3R NEMA / IEC IP21 Enclosure:
Are designed for outdoor use primarily to provide protection against contact with the
enclosed equipment and provide a degree of protection against falling rain sleet and
external ice formation.
Agency Approvals
UL and cUL listed to UL508 Type MX and CSA-C22.2 No 14-95
File E180243
Warranty
Three years from the date of shipment. See www.mtecorp.com for details.
Over Temperature Switch
Table 4-2: Over Temperature Switch
MTE highly recommends the use of the over temperature switch to prevent damage to the filter
in rare instances of overheating from abnormal operating conditions.
Form: SWG-TRM-E June 2015 REV. 003 12