
1 2 3 4 5 6 7 8 9
RUN
Customer Terminals TBC on TCB3000 PCB
1 2 3 4 5 6 7 8 9
STOP
START
Customer Terminals TBC on TCB3000 PCB
See page 3.
TCB3000 Terminal Control Board
See page 3.
TCB3000 Terminal Control Board
Manual Addendum for VMX-B Configured Soft Start Packages
For use with wiring diagram # 93-3880 Rev B (CB/FS), or 93-3881 Rev B (MLO), and VMX2 user manual.
Introduction: The VMX-B is a configured enclosed soft start, available as a Combination (with C/B or
Fused disconnect) package, or as an MLO (Main Lug Only) package, intended for use in Industrial,
Commercial, Agricultural, or Infrastructure applications.
Line Voltage:
By default units are set-up for 460VAC line power, but can be adjusted to operate on 230VAC or
208VAC at the reduced HP rating. To adjust the operating voltage simply move wire #1L2B from the
480V (H4) terminal to the 230V (H3) or 208V (H2) terminal.
Power Connections:
Line Power input is connected directly to the bottom terminals of the Circuit Breaker, or line terminals
on MLO (Main Lug Only) units, and the motor is connected to the lugs at the bottom of the VMX2 soft
start.
Remote Start / Stop Control connections:
The VMX-B is set up for 2 or 3 wire remote control using dry contacts rated at 120VAC (0.1Amp).
Remote Two Wire Control:
Connect a dry (voltage free) maintained contact closure between terminals 1 and 3 of the customer
terminal strip as shown here.
Remote Three Wire Control:
For standard 3-wire control, connect dry (voltage free) contacts for the Stop / Start buttons as shown
below of the customer terminal strip. Connect the normally closed “STOP” pushbutton across terminals
1 & 2, and the normally open “START” pushbutton across terminals 2 & 3 of the customer terminal
strip. Note: the unit can be operated in the “Local” position without any external control.
1 REV-02 100418

OVERLOAD RELAY OPERATION
WHEN IN HAND (H) POSITION: USER MUST RESET OL
(BY PUSHING GREEN BUTTON)
WHEN IN AUTO (A) POSITION: RELAY WILL
AUTOMATICALLY RESET AFTER TRIPPING
NOTE: YELLOW
OVERLOAD DIAL MUST BE
SET IN ACCORDANCE
WITH THE MOTOR “FULL
LOAD AMPS” PER MOTOR
NAME PLATE DATA
YELLOW OVERLOAD
ADJUSTMENT DIAL
There are 3 programmable Aux contacts
available on TB2 of the VMX2 soft start (2
form-C and 1 form-A). The function of these
contacts are labeled on the wiring diagrams,
but can be changed in the VMX2
programming. Note however, that the
contacts may not function properly when
operating in the X-LINE mode. (see
description below).
X-LINE Operation:
VMX-B packages are supplied with a SOFT/XLINE selector switch, located on the TCB3000
PCB that allows the operator to select Full
Voltage operation of the motor via the bypass
contactor for emergency operation when the
soft start may be inoperable.
When operated in the X-LINE mode full
start/stop control is maintained, and the “Run
Status Output Contacts” will function correctly.
During X-LINE operation, the motor will be
protected by the external Bi-Metal overload
relay which must be set according to the motor
FLA and the Current transformer ratio of the
unit.
Important:
Motor FLA and Service Factor must be
entered prior to a start attempt see next
section on how to set Motor FLA and
Service Factor parameters.
1 2 3 4 5 6 7 8 9
Customer Terminals TBC on TCB3000 PCB
Run Status
Output Contacts
See page 3.
TCB3000 Terminal Control Board
Run Status Output Contacts
The VMX-B unit offers 2 Form-C (N.O and N.C.) “RUN” contacts located on the customer terminal strip, terminals 4
(NC), 5 (NO), 6 (Common), and terminals 7 (NC), 8 (NO) 9 (Common). These contacts reflect a successful RUN
command in “SOFT” or “X-LINE” mode, and should be used for any required “Run / Running” status outputs.
VMX2 Auxiliary Contacts
(TB2 of Soft Starter)
2 REV-02 100418

Green LED
- Control Power ON
- E-Stop Not Active
- Fuse OK
Yellow LED
X-Line Mode Enabled
(D.O.L. Start)
Red LED
Fault
(Unit Tripped requires
Reset Command)
Red LED
External O/L Tripped
(Reset O/L Manually
by pressing green
button on overload
relay).
TCB3000 Terminal Board
3 REV-02 100418

50-100% of Max Amp Rating.
Motor Nameplate Service Factor
FLA value
(0000 is default)
Set value of ones
digit (flashing)
Set value of
remaining FLA digits
Cursor Position Shift
(tens digit flashing)
Value Accepted
(flashes once)
Use up arrow to scroll to F002 and repeat process
to set Service Factor. When programming is
complete press Fn key to exit programming mode.
For Complete Installation instructions see VMX Operation & Installation Manual
Programming Instructions
This document is intended for use with Models: VMX-B Soft Start Packages
Motor FLA and Service Factor must be entered prior to start attempt
For complete parameter list see pages 6-7 of this document
4 REV-02 100418

Operation and Troubleshooting
No Full Load Amps set in F001
Parameter change attempted when in Run Mode or without password
Line Voltage Loss (no 3 phase prior to start)
Lockout Starter is in overload or duty cycle lockout
Incorrect Password Entered
Over Current during Acceleration; Constant speed; Deceleration
Phase Loss during Acceleration; Constant speed; Deceleration
Over Temperature during Acceleration; Constant speed; Deceleration
Over Load during Acceleration; Constant speed; Deceleration
Shorted SCR during Acceleration; Constant speed; Deceleration
Shunt Trip during Acceleration; Constant speed; Deceleration
Current Imbalance during Acceleration; Constant speed; Deceleration
Under Current during Acceleration; Constant speed; Deceleration
Short Circuit during Acceleration; Constant speed; Deceleration
Ground Fault during Acceleration; Constant speed; Deceleration
Bypass Discrepancy during Acceleration; Constant speed; Deceleration
Normally closed external lockout is open
Rotation Trip during Acceleration; Constant speed; Deceleration
Voltage Imbalance during Acceleration; Constant speed; Deceleration
Overvoltage during Acceleration; Constant speed; Deceleration
Undervoltage during Acceleration; Constant speed; Deceleration
Power Factor trip during Acceleration; Constant speed; Deceleration
Power (kW) trip during Acceleration; Constant speed; Deceleration
Control Power Loss during Acceleration; Constant speed; Deceleration
Keypad Operation
Display Mode (Default) Fault Mode
*NOTES:
“PLd” can be caused by a Grounded delta power system. If one input leg measures ZERO volts to ground, reduce
the setting of F051 to “0054” for operation on a “Grounded Delta”.
“SSd” can be caused by operating without a motor connected, ensure the motor is firmly connected.
“LcA, Lcc, or Lcd” indicates that the Surge absorber is damaged; see NOTE 1 on wiring diagram.
5 REV-02 100418

50-100% of Max Amp Rating (less Service Factor)
Overload Class During Start
Overload Class During Run
0=Manual, 1=Auto, 2=Disabled
Ramp Type (If Ramp 2 is not being used, unit
will ignore all settings referenced to Ramp 2)
Setting = 1
Setting = 2
Setting = 3
Setting = 4
Voltage Voltage
Current Current
Voltage Current
Current Voltage
Initial Voltage of Ramp 1
Initial Current of Ramp 1
Accel Ramp Time of Ramp 1
Max Current Limit of Ramp 1
Initial Voltage of Ramp 2 (if Ramp 2 is used)
Initial Current of Ramp 2 (if Ramp 2 is used)
Accel Ramp Time of Ramp 2 (if Ramp 2 is used)
Max Current Limit of Ramp 2 (if Ramp 2 is used)
0=Disabled or 10-100% Line Voltage
Deceleration Ramp (Pump Control)
0=Disabled (Coast to Stop)
1=Enabled (except after OL trip)
0 - 100 % of Output Voltage
0 to (BDL minus 1)% Voltage
0=Disabled or 1-999sec after Power Loss
Voltage Imbalance Trip Delay
Under Voltage Trip on Start %
Under Voltage Trip on Run %
Shorted SCR and Trip Delay
0, 1-10 seconds [0=Disabled]
0, 1-10 seconds [0=Disabled]
0=Disabled or 5-30% imbalance
Current Imbalance Trip Delay
0=Disabled or 100-300% of Motor FLA
0=Disabled or 10-90% of Motor FLA
Ground Fault Current Trip Value
0=Disabled or 5-90% of CT ratio from Fn74
Ground Fault Current Trip Delay
0=Disabled or 1-60 minutes
0=Disabled or 1-10 Starts
Minimum Time Between Starts
0=Disabled or 1-60 minutes
nCP Trip (No Control Power)
0, 1 [0=Disabled, 1=Enabled]
6 REV-02 100418

Auto Reset Selected Trips
Reset after Over Temperature Trip only
Reset after Over Current (Shear Pin) Trip only
Reset after Under Current Trip only
Reset after Phase Loss Trip only
Reset after Current Unbalance Trip only
Reset after Ground Fault Trip only
Reset after Short Circuit Trip only
Reset after OT Trip or Over/Under Current Trip
Reset after Phase Loss, Current Unbal, or GF Trip Reset after
all Except Short Circuit Trip
Reset after all Except GF or Short Circuit Trip
Reset after any Trip
1
2
3
4 (Default)
5
6
7
8
9
10
11
12
0=Disabled, 1-10 = # of Attempts
Auto Restart Delay Readout
Coast Down Lockout Time Readout
Starts Per Hour Timer Readout
Time Value Between Starts Readout
Thermal Capacity to Start Readout
0=Disabled or 1-999 seconds
0=Disabled
1=Enabled(11bit)
2=Enabled(10 bit)
Remote Starter Control from Communications
0=Disabled
1=Enabled w/Start PB
2=Enabled w/o Start PB
3=Enabled via Remote Jog Input
Parameter Lock/ Level 1 Password
System Clear / Factory Reset
0=Disabled, 1=Clear Lockouts
2=Reset to Factory Default
Software rev # (info purposes only)
Fault History #1 (most recent fault code)
0=No Fault History, or Fault # 1-27
(full manual for fault code descriptions)
Fault History #2 (previous fault code)
0=No Fault History, or Fault # 1-27
(full manual for fault code descriptions)
Fault History #3 (oldest fault code)
0=No Fault History, or Fault # 1-27
(full manual for fault code descriptions)
7 REV-02 100418

Run Time in 1,000s of hours
Run Counts in 10,000s of counts
0000-9999 (0001 would equal 10,000 counts)
0, 1 or 2
0=Disabled, 1=ABC, 2=ACB]
Phase Rotation Trip Delay
Phase Loss Trip Delay during Stop
0 - 20 seconds
[0 = Disabled]
Phase Loss Trip Delay during Running
0 - 20 seconds
[0 = Disabled]
0 - 2
0 = Disabled
1 = Over kW Trip
2 = Under kW Trip
20 - 100% of full load KW
0, 1 - 3 [0=Disabled, 1=lag, 2=lead, 3= lead/lag]
Power Factor Trip Delay Time
0 - 12
[0: OFF; 1 - 12]
(See Table of Default Display)
1-12 (See Table of Default Display)
Alternate functions for Ramp2/Jog inputs
Setting Dual Ramp Input Jog Input
0 Dual Ramp Jog
1 Dual Ramp Remote / Local
2 Dual Ramp Ext. Lockout N/O button
3 Dual Ramp Ext. Lockout N/C button
4 RESET Jog
5 RESET Remote / Local
6 RESET Ext. Lockout N/O button
7 RESET Ext. Lockout N/C button
8 REV-02 100418

VMX-B Door Mounted Operators
Illuminated E-Stop Pushbutton:
Removes control power from all circuits and VMX2 soft start.
Push to activate, twist and pull to release.
Button Lights when E-stop is pressed.
Start/Stop Pushbutton and Run Light Assembly:
Provides Start/Stop control in "Local" mode.
Provides "Motor Running" indication in all operating modes.
Local/Off/Remote Selector:
Local" selects door mounted Start/Stop control.
Remote" selects Start/Stop control from customer supplied signals at terminals 1-3 on TBC.
Off' Turns motor off.
Power ON Light:
Indicates presence of 120VAC control power, derived from main (L1 & L2) line voltages.
Fault Light/Reset Pushbutton:
When lit, indicates that the unit has tripped, and requires "Reset".
In "Soft" (normal) mode, the "trip" will be displayed on the VMX2 keypad (inside), and will reset
upon activation of the reset pushbutton.
In "X-Iine" mode, the light indicates that the X-line overload inside the panel is tripped, and must be
reset manually by pressing the (green) reset key on the overload itself. Then the unit can be reset,
using the pushbutton on the door.
Note: If the green reset key on the X-line overload is turned to the "A" (auto) position, the O/L relay will
reset itself after the required cooldown, after that the unit can be reset by pushing the reset pushbutton
without opening the enclosure door.
9 REV-02 100418