General Description, Sizes and Ratings ……… 6
Dimensions ……………………………………..… 7
Chapter 2 - InstallationReceiving, Unpacking and Inspection ………….. 8
SERVICE WARNING! ……………………...……. 8
Mounting Clearances and Cleaning ………….... 9
Power Connection and Terminations .……….… 10
Control Power Requirements …………………… 12
Control Connections …………………………….. 12
Chapter 3 – Sequence of Operation
Starting and Stopping …………………………... 16
18
Chapter 4 – Programming
Introduction …………………………………..…... 17
Digital Interface …………………………………… 17
Display and Program Modes ………… ………. 18
Program Function List …………………...………. 20
Fault Mode ………………………………………… 24
Chapter 5 - Motor Overload ProtectionSolid State Overload Protection ………………… 25
Overload Class Trip Curves …………………..... 27
Page 3 of 27
Page 4
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
Your new VMX Series Soft Starter is factory preset for a wide variety of applications and often can be used with
minimal adjustment.
Try these initial factory presets first and then adjust or enable the more advanced features to meet your
specific starting needs.
Three Step Process:
1. Connect L1, L2, L3 to power lines and T1, T2, T3 to motor (see page 10)
2. Connect control wires and control power (see pages 12-13)
3. Program motor FLA (see page 18).
Your VMX unit is ready to start!
Start-up Check List
MOTOR FLA (F001)
must be programmed
for unit to operate!
Supply voltage matches the rated supply voltage of the unit.
Horsepower and current ratings of the motor and unit match or the unit is higher rating.
Initial ramp time and torque adjustments have been checked.
Power lines are attached to the unit input terminals marked L1, L2 and L3 (R, S, T).
Motor leads are connected to the lower terminals marked T1, T2, and T3 (U, V, W).
Appropriate control power is applied
Control connections have been made.
“Power on” light located on the front of the unit turns on when control power is applied.
Four seven-segment LED readouts are visible.
The motor’s FLA has been programmed in function F001.
The thermal overload is properly set. (Use F003 and F004 to set OL Class.)
The motor area and equipment are clear of people and parts before start-up.
This list provides only the bare minimum settings necessary to make your motor run,
and provides basic levels of motor protection. Safety precautions, listed further on in
this manual, must always be followed. Ramp setting adjustments and additional
protection features may be necessary. Please read further for additional details.
Page 5 of 27
Page 6
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
The VMX Series is a digitally programmable solid state reduced voltage soft starter using a six SCR design. It
features a voltage/current ramp for smooth load acceleration. The SCRs are sized to withstand starting currents
of 350% for 30 seconds and up to 600% for 10 seconds for applications typical to NEMA / UL Class 10 overload
trip curves. The VMX Series features smooth stepless ramp control, which reduces motor inrush current and
excessive wear on the mechanical drive train components. The VMX Series includes a programmable keypad
for setting operating parameters for the ideal starting cycle and protection features, plus easy to understand
diagnostic LEDs. Starting torque, ramp time, current limit, dual ramp, and Decel control are standard features
on the VMX Series. The VMX Series includes solid state electronic overload protection in addition to numerous
other protective features. It requires 120VAC (220VAC optional) control power and uses dry contact inputs for
Start / Stop control. Programmable auxiliary contacts and provisions for interlocking are also included.
Sizes and Ratings
The Motortronics VMX Series starters are current rated controllers. Max. Am p
ratings are for continuous duty and must not be exceeded. Always check the
motor nameplate FLA and Service Factor (if used) to ensure proper sizing.
Each size has an adjustable range of current from 50% to 100% of the Max Amp
rating. Table 1 below shows the Current Ratings available.
Units without Bypass
For NEMA 1 ventilated applications, or for OEM purposes where a bypass
contactor will be added by others, VMX-210 mo dels a n d above can be selected
without the integral Bypass by substituting the -BP suffix with a -P suffix.
See the Product Selection Guide for ordering details.
Examples:
•VMX-210-BP = open unit with integral bypass contactor for NEMA 12 / 4
end-user installati ons
•VMX-210-P = open unit with cooling fans and witho ut b ypass contactor ,
for use in NEMA 1 vented enclosures or OEM packages where a bypass
contactor is installed by others
Page 6 of 27
Page 7
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
Upon receipt of the product, you should immediately do the following:
Carefully unpack the unit from the shipping carton and inspect it for shipping damage (if damaged, notify the
freight carrier and file a claim within 15 days of receipt).
Verify that the model number on the unit matches your purchase order.
Confirm that the ratings sticker on the unit matches or is greater than the motor’s nameplate Full Load Current
(FLC or FLA) rating and Service Factor (if used).
Choosing a Location
Proper location of the VMX Series is necessary to achieve specified performance and normal operation lifetime.
The VMX Series should always be installed in an area where the following conditions exist:
Ambient operating temperature:
Panel (open chassis) unit: 0 to 50°C (32 to 122°F)
Enclosed unit: 0 to 40°C (32 to 104°F)
Protected from rain, moisture and dust. Enclosed units should not be exposed to direct sun.
Humidity: 5 to 95% non-condensing
Free from metallic particles, conductive dust and corrosive gas
Free from excessive vibration (below 0.5G)
Open panel units must be mounted in the appropriate type of enclosure. Enclosure size and type must be
suitable to dissipate heat generated by the soft starter and any other components mounted inside with it.
Units with –BP Bypass Contactors produce less heat than units without. Throughout all sizes, maximum heat
dissipation of the VMX…-BP Series electronics, contactor coils and fans is less than 50W.
Units without the –BP Bypass Contactor (optional on 210A and above), must have ventilation adequate to
account for heat dissipation of the SCRs. This must be estimated at 4.5 watts per running load amp. For
example, on a 200HP 460V motor with 240FLA, the maximum heat dissipation of a starter w/o bypass will
be 240 x 4.5, or 1080 watts of heat. Enclosure ventilation (or air conditioning) must be capable of dispersing
this amount of heat.
Care should always be taken to maximize the available space inside of the enclosure. See “Clearances” below
or contact factory for assistance in sizing enclosures.
Initial Unit Inspection
Make a complete visual check of the unit for damage that may have occurred during shipping and handling. Do
not attempt to continue installation or start up the unit if it is damaged.
Check for loose mechanical assemblies or broken wires which may have occurred during transportation or
handling. Loose electrical connections will increase resistance and cause the unit to function improperly.
Mounting and Cleaning
When drilling or punching holes in the enclosure, cover the electrical assembly to prevent metal filings from
becoming lodged in areas which can cause clearance reduction or actually short out electronics. After work is
complete, thoroughly clean, vacuum the area, and re-inspect the unit for foreign material.
SERVICE WARNING!
Do not service equipment with voltage applied! The unit can be
the source of fatal electrical shocks! To avoid shock hazard,
disconnect main power and control power before working on the
unit. Warning labels must be attached to terminals, enclosure and
control panel to meet local codes. Use Lock Out tags such as the
one shown when servicing equipment.
Page 8 of 27
Page 9
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
When mounting into an enclosure, make sure there is sufficient clearance all around the unit for cooling, wiring
and maintenance purposes. To conserve panel space, the VMX Series –BP models were designed for clos e
horizontal clearances of only 1 inch (25mm) on either side. A minimum vertical clearance of 4” (100 mm) on the
top and bottom is necessary to maximize effective airflow and cooling, and the unit must be installed with its
heat sink ribs oriented vertically and running parallel to the mounting surface. Keep in mind that these are
minimums. Wiring may require more clearance, particularly on the bottom.
1" minimum (2 5 mm)
4" minimum (100 mm)
VMX Series
Starter
1" minimum (25 mm)
4" minimum (100 mm)
Figure 2: VMX minimum mounting clearances
Cleaning:
WARNING!
Remove all sources of power before cleaning the unit.
In dirty or contaminated atmospheres, the unit should be cleaned on a regular basis to ensure proper cooling.
Do not use any chemicals to clean the unit. To remove surface dust use clean, dry compressed air only, 80 to
100 psi. A three inch, high quality, dry paintbrush is helpful to loosen up the dust prior to using compressed air
on the unit. Do not use wire brushes or other conductive cleaning materials
Page 9 of 27
Page 10
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
All line and load power terminations are to be made to plated copper Bus Tabs located on each unit. Bus tabs
are pre-drilled to accept industry standard bolts.
The following power schematic provides the termination points as they are labeled on the unit. This is
diagrammatic only. All power terminations are physically located on the bottom of each unit. Refer to local code
standards for wire sizing and length.
Connect appropriately sized power conductors to the unit input terminals marked L1, L2, L3 (R, S, T for IEC
users). Avoid routing power wires over the control board or display. Note: If control power is present, but line
power is disconnected from L1, L2, L3, the disp lay will show [n3PH]
Disconnect
or
Circuit
Breaker
R /
S /
L1
L2
U /
V /
T1
T2
T /
VMX Starter.
L3
Solid State.
Over Load.
W /
T3
Integral
Bypass
Contactor*
G
indicating “no 3 Phase”.
Connect the motor leads to the unit load terminals marked T1, T2, T3
(U, V, W for IEC users). Soft Starters such as the VMX Series cannot
operate without a load, even for testing. The VMX Series will trip on
“Phase Loss” if any or all of the conductors are disconnected from the
load terminals. Contact the Factory for assistance in no-load testing.
Caution!
Never interchange input and output connections to the
unit. This could cause excessive voltage in the control
logic circuit and may damage the unit.
Bypass Contactor
*Bypass Contactors are integral (built-in) on all VMX…-BP (panel
mount), and all VMX…–E (NEMA 12 enclosed) versions.
Power Factor Correction Capacitors
Power factor correction capacitors can be connected to motors
controlled by VMX Serie s starters, however they must be off-line during
ramping. Connect PFC capacitors to the Line side of the starter with a
separate capacitor control contactor.
WARNING!
Never connect power factor correction capacitors on
the load side of the unit. The SCRs will be seriously
damaged if capacitors are located on the load side.
MTR
Figure 3:
VMX Power Connections
Grounding / Earthing
Connect the ground cable (PE) to the ground terminal as labeled “G” on the unit. Refer to the National Electrical
Code or your local code for the proper ground wire sizing and be sure that the ground connector is connected to
earth ground. In ungrounded systems, it is not necessary to connect a ground to the unit however local codes
should always be consulted.
Page 10 of 27
Page 11
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
Line and Load terminals are bus tabs with pre-drilled holes (see Table 3). Use of appropriate compression or
mechanical lugs for wire connection to these bus tabs is required or highly recommended. For convenience
only, some sizes (as indicated below) come with saddle clamps that can be used directly on stranded wire
without additional lugs, but may not be suitable if larger conductors are needed for voltage drop reduction.
Suggested wire sizes and tightening torques shown in the chart below are for reference when using 75°C rated
conductors. Always consult local codes and industry standard practices for proper wires sizes to accommodate
voltage drop and ambient conditions.
.
Model
Number
VMX-18-BP
VMX-28-BP
VMX-39-BP
VMX-48-BP
VMX-62-BP
VMX-78-BP
VMX-92-BP
VMX-112-BP
VMX-150-BP
VMX-160-BP
VMX-210-BP or -P
VMX-276-BP or -P
VMX-360-BP or -P
VMX-450-BP or -P
VMX-550-BP or -P
VMX-718-BP or -P
VMX-900-BP or -P
Control connections on the VMX Series starter are divided into 2 groups. With the unit oriented vertically, TB1 is
a 12 point DC terminal block (on the left), and TB2 is a 10 point AC terminal block (on the right side). These are
removable terminal blocks for ease of connection and servicing, and are provided with different spacing (pitch)
between the header pins so they are not interchangeable. Following are descriptions of control connection
points.
Terminal numbers are shown on the side of the first and last terminal of each block. An
additional 3 point terminal on the far left side is for serial communication connections.
AC Control Power Supply Connection
Separate AC Control Power supply is required to power the electronics of the VMX Series starter. 120VAC is
standard, order 240 VAC (optional) if necessary for your line power supply configuration. The control voltage
must be connected to terminals marked A1 and A2 of TB-2 as shown
in figure 5 (these are also Terminal #s 21 and 22). This control
voltage must be customer supplied, unless an optional control power
transformer (see table below) has been supplied with the unit.
Control Power Requirements
1
NC NO. C
2
NC NO. C3NO. C
120VAC
Supply
1
A1 A2
When sizing a control power transformer for the VMX…-BP Series
Control Power Supply Connection
Figure 5:
TB-2
starter use the chart below for minimum sizes or supply capacity. Any
additional control devices powered by the same CPT must be added
to the above to ensure proper operation of the Bypass Contactor.
AC Control Power VA Requirements
VMX …-BP
Model
VMX-18 to 48 48 (inc. in PCB) 95 9 100
VMX-62 to 112 48 (inc. in PCB) 220 17 250
VMX-150 to 160 48 (inc. in PCB) 298 12.3 500
VMX- 210 to 276* 48 100 380 11.6 500
VMX-360 to 450* 48 150 571 14 750
VMX-550* 48 200 1000 29 1000
Table 4: VMX Series Control Power Requirements
Note: * -P versions (w/o bypass) still require PCB and fans, plus user supplied bypass (if any).
PC
Boards
Fans
-BP: Bypass
Contactor
Inrush
-BP: Bypass
Contactor
Sealed
Recommended
minimum
CPT
Rating
Page 12 of 27
Page 13
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
Control Fusing
Output relays in TB2 must be protected from currents in excess of 5A, either with a fuse or with other suitable
current protection devices.
A dedicated fault output for use in PLC or interposing relay control is available on TB1. This opto-isolated triac
switch is rated for 50mA max., 10-250V AC/DC. Any circuit connected to it must be fused accordingly.
Three-Wire Control Connection
For standard 3-wire control, connect dry (voltage free) contacts of the Stop / Start buttons as shown on the
diagram directly above the terminal strip. Connect the NO contact of the Start button to Terminal #1 (far left
N C
RAM P2
JOG
PTC
OPTO
terminal), the common point between the Stop and Start to Terminal
nd
#2 (2
from left) and the NC from the Stop button to Terminal #3 (3rd
from left).
1 2 3
Connect 3 wire
control here
as shown
Figure 6:
3 Wire Control Connection
TB-1
Seal In Contact
The VMX Series uses an internally pre-wired “seal-in” contact
around the Start button (Terminals 1 and 2). No external relay or
auxiliary output connection is necessary.
Two Wire Control: Relay / PLC Connection
An alternate connection for automated or unattended operation replaces start/stop push buttons by connecting
a dry (voltage free) maintained contact closure between terminals 1 and 3 as shown in Figure 4.2.3. When this
contact is closed, the VMX Series starter will start and run. When it is
opened, it is the same as a Stop command.
Note:
When a maintained contact is used for start/stop it is
advisable to set the overload relay to the manual reset
position. This will prevent the motor from restarting if
the thermal overload trips and then cools off.
1 2 3
Connect 2 wire
contr ol / PLC
output here
RAM P2
N C
JOG
Figure 7:
2 Wire Control Conn ection
TB-1
PTC
OPTO
CAUTIO N!
Control Terminals 1-10 of TB1 are a 24VDC circuit from an internal power supply of the VMX
Series. Use dry (voltage free) contact closures only. Applying any voltage to these terminals will
result in damage to the control board. If existing 120VAC or other powered control circuit must be
interfaced, use interposin g r elays or control the VMX Series with 2 wire control as shown above.
Interlock Connection:
TB1 provides a connection point for an external N.C. (Normally Closed) interlock device between terminals 4
and 5. A factory installed jumper is provided which allows the unit to operate if external interlocks are not used.
RAM P2
N C
4 5
External Interlock Connection
JOG
Remove factory jumper
and connect external
interl ock device here
Figure 8:
TB-1
PTC
OPTO
not function.
If this jumper is removed and an interlock is not
used, the unit will
Page 13 of 27
Page 14
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
The VMX Series starter is provided with input terminals for connecting a PT C (Po s itive Temperature
Coefficient) Thermistor that may be imbedded in the motor. These are specialized resistors imbedded in some
motor windings that increase resistance as the temperature
RAM P2
N C
JOG
PTC
OPTO
increases. When the VMX Series detects that the PTC input
resistance is too high, it initiates a PT C trip, and disp la ys it on the
9 10
**
readout as [ PTc]. This is independent of the Thermal Register
overload current protection and pr ovid es supp lemental protection
for high motor ambient temperature applications. Terminals for this
PTC Resistor in Motor
input are provided with a factory jumper that must be removed if the
PTC input is used. These terminals are located on TB1, Terminals 9
Figure 9:
PTC Resistor Connection
TB-1
+
** Remove factory jumper
from Terminals 9 and 10
and 10.
Resistance must be less
than or equal to 750 Ω at 25ºC. If multiple
resistors are used in the motor, the sum of all resistors in series
must equal or be under this value.
Fault Signal
An optically isolated Triac output is dedicated as a fault indicator on TB1, terminals 11 and 12. The output Triac
switch is rated for 10 - 250 VAC/DC, 50 mA (maximum). If the three programmable Output Auxiliary Relays are
N C
RAM P2
JOG
PTC
OPTO
being used for other functions, this output can easily be hooked up
to a PLC or small external relay to provide a Fault signal. This Fault
Output operation is permanently fixed at “Any Trip”, duplicating the
11 12
Relay setting #16 as shown in Table 5.6.10.
Control Power or PLC Source
Fault Output Opto-Triac Connection
Figure 10 :
TB-1
R
External Fau lt Relay
or PLC Input
This output is permanently set to this function and is not
programmable.
Dual Ramp and Jog Features
TB1 includes provisions for enabling the Dual Ramp and Jog functions by using external contact closures. Both
features use a common +24VDC from Terminal # 7, however they can be used independently of each other or
N C
RAM P2
JOG
PTC
OPTO
together. See sections 5.6.2 and 5.6.3 of the Advanced Installation,
Operation and Programming Manual for full function descriptions and
setup.
6 7 8
RUN JOG
RAMP 1 RAMP 2
Figure 11:
Dual Ramp / Jog Connections
TB-1
Page 14 of 27
Page 15
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
Dry relay output contacts from three programmable auxiliary relays are available on TB2. Outputs #1 and #2 are
Form C (SPDT), with a Common, N.O. and N.C. Output #3 is a Form A, (SPST), N.O. contact. Motortronics
recommends fusing all contacts with external fuses.
Internal Connections
The relays are rated for 240 VAC, 5 A and 1200 VA.
Factory default settings for these relays are as follows:
K3
K5K4
AUX 1 – Run / Stop (see F060) This contact changes state upon a
Start command, returns to normal on Stop (or Begin Decel if active).
AUX 2 – At-Speed / Stop (see F061) This contact changes state upon
the VMX Series detecting At-Speed, and returns to normal on Stop.
At-Speed is determined by the VMX Series detecting the current
1
NC NO. C
2
NC NO. C3NO. C
1
A1 A2
dropping after reaching End-of-Ramp, or a maximum of 30 seconds
after Start.
AUX 3 – Any Trip (see F062) This contact closes when any trip
13 14 15 16 17 18 19 20
AUX.
RELAY #1
AUX.
RELAY #2
Figure 12:
Auxiliary Relay Connections
TB-2
AUX .
RELAY #3
condition # 5 – 15 (as defined in Table 8) occurs.
All relays can be reprogrammed for a wide variety of functions.
See Section 8 for additional relay programming details.
Note:
It is not necessary to use the programmable output auxiliary relays in the Start / Stop circuit. An
internal seal-in relay is provided elsewhere (see “Three Wire Control Connections” above).
Bypass Contactor Control
On VMX…-BP version (and NEMA 12 enclosed) starters, an internal dedicated connection is used at the factory
for automatically controlling the Bypass Contactor. Field wiring for Bypass Contactor operation is not required.
On units 210A and above ordered without a Bypass Contactor (-P version), the dedicated bypass control
terminals are available for customer use, or any of the above Aux. Relays can be programmed for “At-Speed”
operation.
Independent control of the bypass contactor is available for emergency use. See section 4.2.9.a of the
Advanced Installation, Operation and Programming Manual for details about how to use this feature.
Bypass Control
Terminals
18 - 160A Units
Bypass Control
Terminals:
210 – 1000A without
integral bypass
Page 15 of 27
Page 16
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
1. Apply three phase power to the unit. The motor should not run until a Start command is applied.
2. Apply control power and check that the “Power On” LED comes on.
3. Status Display should read [0000.] showing no current in Phase A (minor flickering of the first digit is
common).
4. Apply the Start (Run) command. The motor should begin to accelerate. Status display will read Phase A
Amps at an increasing rate.
5. When the motor reaches full speed, the “At Speed” LED comes on and the Bypass Contactor will close.
Status display should show a sharp decrease in Phase A Amps.
6. If the motor does not fully accelerate, decelerates, or stops during the acceleration period, hit the Stop
button immediately and open the disconnect line.
Stopping:
If Pump-Flex Decel is Disabled
7. Remove the Run Command (or hit the Stop button).
8. At-Speed LED will go out and Bypass Contactor will open. Status display should read [0000.] indicating
no current on Phase A.
9. Motor will coast to a stop according to load inertia and friction.
If Pump-Flex Decel is Enabled
7. Remove the Run Command (or hit the Stop button).
8. At-Speed LED will go out and Bypass Contactor will open. Status display should briefly read Phase A
Amps increasing
9. Motor should begin to slow down. Status display should begin to show decreasing
10. When motor reaches Stop Level, VMX should turn off. Status display will again show [0000.]
If the unit does not follow this operational sequence please contact the factory refer to the VMX Series
Troubleshooting Guide.
as motor begins to decelerate.
(factory default) in F024:
in F024:
motor amps.
Page 16 of 27
Page 17
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
It is best to operate the motor at its full load starting conditions to achieve the proper time, torque and ramp
settings. Initial factory settings are set to accommodate general motor applications and provide basic motor
protection. Advanced features must be enabled via programming. The only parameter that MUST be set by the
user is motor FLA (F001).
Digital Interface
The VMX Series Soft Starter includes an intuitive, digital keypad with eight LEDs, seven command keys, and an
LED display with four alphanumeric digits.
Keys
Green
LEDs
Figure 13: VMX Operator Interface
Yellow
LEDs
Display
Table 5: VMX Series Display Features
Reset Clears the Trip indication and releases the Trip Relay.
Fn Enters or exits the Program Mode.
Navigates through the Status Display Mode, scrolls up
Up and
Down
Arrows
Right
and Left
Arrows
Power
On
At
Speed
Shunt
Trip
Shorted
SCR
Over
Current
Phase
Loss
Over
Temp
Over
Load
8888.
and down through the Function List, increases or
decreases the value of the active (flashing) digit and
scrolls through the fault history. When entering values,
holding the key down for more than 2 seconds will
activate Auto-step, which increases it’s rate the longer
the key is held down.
Each keypress shifts the active (flashing) digit t o the
right or left by one position, allowing you to change
higher values of functions without waiting to Auto-step
though large numbers.
Control power is available at A1 and A2
The motor is at full power and the Bypass Contactor
has been commanded to pull in.
The SCRs are at full conduction and current has
dropped.
Two or more SCRs in opposing phases have shorted,
and power is flowing to the motor in the Off mode. See
section 8 for additional concerns.
There is no voltage drop across at least one SCR
phase assembly, indicating that at least one SCR is
shorted. See section 8 for additional concerns
Overcurrent LED lights for three sets of fault conditions:
1) During start, the unit saw current exceed the
normal rate of increase in the first 250ms.
2) During Run, current exceeded either the OC
setting in F042 for the delay set in F043. This
LED will be accompanied by oCA, oCC or
oCd on the display.
3) The unit has seen a Short Circuit exceeding
10x FLA for 12.5ms. This LED will be
accompanied by SCA, SCC or SCD display.
One or more of the phase currents dropped below the
threshold during starting or running.
Starter has tripped due to excess heat sink
temperature. This will automatically reset.
Starter has tripped due to the Thermal Register
reaching 0000. The Overload must reset before this
fault can be cleared.
4 digit 7 segment display with a decimal point on the
right side indicating Phase A.
Page 17 of 27
Page 18
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
Display Modes:
There are three modes of display: the Status Display Mode, the Program Mode, and the Fault Mode.
Status Display Mode
(Default Display)
The Status Display Mode displays seven “screens” of information. Motor Currents (3 phases), Remaining
Thermal Capacity, Ground Current, Remaining Time on the Process Timer, and Time Base of the Time Clock
Controller. This is also the entry screen for going into the Program Mode.
[0000.] The initial display on power up is four digits and the decimal. This indicates the motor current for
Phase A of the motor.
[0000] Scroll UP to display four digits only (no decimal). This indicates the motor current for Phase B. While
viewing Phase B, press the UP arrow again to view Phase C current.
[G000] Scroll UP to display the “G”. This indicates that this value is the current flowing to ground on the motor
leads.
[H000] Scroll UP to display the “H”. This indicates that this value is the remaining thermal capacity percentage
of the motor (i.e. H070 = 70% remaining thermal capacity)
[0000] Scroll UP again to display the Process Batch Timer (described in Section 5.6.7). If this entire screen is
flashing, the Timer is active.
[00.00] Scroll UP to display two pairs of digits separated by a point: This indicates the time base of the Time
Clock Controller (described in section 5.6.7 of the Advanced Installation, Operation and Programming
Manual). If the display shows [00.00], the TCC is not enabled. This follows the time settings in F075 – F080.
Program Mode
The starter must be OFF in order to enter the Program Mode. Changes cannot be made while running.
Use the Program Mode to view or change Function (Fn) settings. To enter the Program Mode, press the [Fn]
key once from the Status Screen as described above. The first time you enter the Program Mode after power
has been cycled to the starter, the initial function [F001] should display with the selected digit flashing. If the
VMX Series starter has been programmed and power to the unit has not been cycled, the readout will display
the last function viewed or changed. To change to a different function, use the arrow keys.
Viewing Function Programming and Values
The programming of each individual Function can be viewed without making changes (values can also be
viewed in the Run Mode, however no changes can be made). Each Function is signified by the letter “F” in
beginning of the data, the 4 digit value of the function follows after hitting the [R EAD/ENTER] key
[F001] The “F” indicates the programmable Function.
[0000] This is the present setting of the applicable function. This display may include decimals between digits
depending on the function setting’s range and inc r em enta l steps.
Pressing the [Fn] key again will return to the Function display without making changes.
Changing a Function’s Set Value
From the instructions above, after hitting the [READ/ENTER] key the display will show the value of that function
with one digit flashing (usually the rightmost digit). Flashing indicates this is the digit to be altered (similar to
cursor position). Use the UP arrow key to increment the value of the flashing digit. Use the DOWN arrow key to
decrement the value of the flashing digit. Use the LEFT or RIGHT arrow to select the next digit to be altered.
Values can only be changed within the Adjustment Range of the function parameter.
Pressing the [READ/ENTER] key again will store the new programming for that Function and return to the
Function display.
If the display shows [Inh] when trying to store the changes, the unit is running and must be Stopped, or a
Password has been set up to prevent access and must be entered first. See section 5.6.12 of the Advanced
Installation, Operation and Programming Manual for details about this feature.
Caution! If the Fn key is pressed or power is lost before
the [READ/ENTER] key is pressed,
the VMX Series Starter will not store the new value in memory.
Page 18 of 27
Page 19
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
[F001] Indicates this is Function 001 (Motor FLA).
Press [READ/ENTER] key
to view the F001 value
[0048] Indicates the programmed motor FLA is 0000
Amps, the factory default for a new unit that has
not yet been in service. The farthest left digit (0)
is flashing, indicating that this is the digit that
you will alter (cursor posit ion).
Press
Key...
Fn
Display
Shows...
0000.
F001
Me a ns...
Phase A
Current
Function #1
Selected
Press the UP Arrow key once
to increase this digit value
[0024] Indica tes you ha ve inc reased the value to 24A,
the lowest setting for a 48A unit, which is 1/2 of
the Max. Amps (see Note).
READ
ENTER
0000
0024
Default Setting
of Function #1
Lowest value
for this un it
Press the UP Arrow key twice (2 x)
to increase this digit value
[0026] Indicates you have increased the far left digit
value from 4 to 6,
Press the LEFT Arrow key
x 2
0026
0026
Lowest value
for this unit
Cursor (flashing)
Position Shift
to shift left to the next digit
[0026] The second digit from the left is now flashing,
indicating a new cursor position.
Press the UP Arrow key
to increase this digit value
nd
[0036] Indica tes you ha ve inc reased the 2
to left digit
to a value of 3 (10’s place), indicating a final
setting value of 36A
READ
ENTER
0036
End
F001
New Value of
Second Digit
Value Accepted
(flashes once)
Return to
Function # Display
Press [READ/ENTER] key
to store the new value
[End] The word “End” will flas h briefly to indicate that
Fn
0000.
Returns to Default
Display, Phase A
Current
the new value has been entered and accepted.
After flashing once, the display will revert to
showing the Function number
Press the [Fn] key
[0000.] Returns to the Default Display, indicating Phase
Figure 14:
Changing a Fu nction Value
A is drawing no current
Note: When first entering FLA into a new unit, pressing the Up arrow key will jump the readout value
immediately to ½ of the unit Max. Amp rating, and it will never go below that again. Any unit
thought to be new which has a value other than 0000 in F001 upon setup, has been programmed
previously and should be reset to factory defaults before proceeding.
Page 19 of 27
Page 20
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
F011 Initial Torque (VR) of Ramp 1 0-100% Line Voltage 1% 60%
F012 Initial Torque (CR) of Ramp 1 0-600% Motor Current
F013 Accel Ramp Time of Ramp 1 1-120 seconds 1 second
F014 Max Current Limit of Ramp 1 200 - 600% Motor Current
1% 200%
10
seconds
1% 350%
F015 Initial Torque (VR) of Ramp 2 0-100% Line Voltage 1% 60%
F016 Initial Torque (CR) of Ramp 2 0-600% Motor Current
F017 Accel Ramp Time of Ramp 2 1-120 seconds 1 second
F018 Max Current Limit of Ramp 2 200 - 600% Motor Current
F019
thru
F023
Jog and Kickstart Features
These features are disabled from factory. See Advanced
Installation, Operation and Programming Manual, section 5.6.3 for
details.
1% 200%
10
seconds
1% 350%
0 = Disabled (coast to stop)
F024
Pump Flex Control /
Deceleration Ramp
1 = Enabled, except after OL trip
2 = Enabled, continued Decel even
1
0
Disabled
if there is an OL trip
F025
Begin Decel Level (BDL),
Immediate Drop Down Torque
0 - 100 % of Output Voltage 1% 60%
F026 Decel Shut Off Voltage 0 to (BDL minus 1)% Voltage 1% 30%
F027 Decel Ramp Time 1 – 60 Seconds 1 second
F028
F029
Restart Delay Time
(Sequential Start Delay)
Reserved for Factory Use
0 = Disabled, or
1-999 seconds after a Power Loss (Status can be read in F054)
Page 20 of 27
1 second
10
seconds
0
Disabled
Page 21
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
Fn # Function Description Adjustment / Display Range
F075 Real Time Clock - Year 2000 - 2047 1 year 2000
F076 Real Time Clock - Month 1 - 12 1 Month 1
F077 Real Time Clock - Day 1 - 31 1 Day 1
F078 Real Time Clock - Hour 0 - 23 1 Hour 0
F079 Real Time Clock - Minute 0 - 59 1 Minute 0
F080 Real Time Clock - Second 0 - 59 1 Second 0
F081 Revision # - -
F082 –
Reserved for factory use
F084
F085
thru
Read Only No settings 1 0
F097
F085
thru
Read Only No settings 1 0
F097
Setting
Increments
Factory
Setting
Factory
Setting
Function 51 Internal protection features
Several protection features in the VMX Series are accomplished with internal hardware and use software
switches in Function 51 to enable or disable them. The following chart shows these functions and the factory
default settings. Refer to the Advanced Installation, Operation and Programming Manual, Section 5.6.9.a for
details on how to change these settings.
Protection
Function
Phase Rotation
Trip
Expected Phase
Sequence
Phase Current
Loss
Shorted SCR
Lockout
Shunt Trip
PTC Input Trip PTC Trip function. This can be disabled so that a jumper is not required across the PTC inputs. On
Line Loss Trip
Table 7: Function 51 table of Hardware Protection Features
Phase Rotation protection.
Phase rotation mu st match selection in Bit #2 below . Se ttin g to Off (0) will make the VM X
insensitive for use behind a reversing contactor
2 = A-B-C Phase Rotation Sequence Only
0 = A-C-B Phase Rotation Sequence Only
Phase Current Loss, any phase current reading is less than 12% of unit max amp rating after 3
seconds from Start command.
At least one SCR has shorted; there is no voltage drop across the SCR phase assembly. On
Shunt Trip of the main Circuit Breaker or Isolation Contactor (if provided and wired to an Aux.
relay in F060-F061)). 2 or more SCRs have shorted in opposing phases so current was flowing
to the motor while the VMX was in the Off state.
Protection against loss of input line voltage. Disable when using an In-Line Isolation Cont actor
or any other system that normally removes line power from the starter. Resets automatically
when line voltage returns.
Description
Default
Setting
On
A-B-C
Rotation
On
On
On
Page 22 of 27
Page 23
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
Functions F060 through F062 provide the ability to program the functions of each of the 3 Output Auxiliary
Relays. Factory default programming is provided which covers a wide variety of applications, but any of these
relays can be changed as per the following chart.
Notes:
Check relay wiring before changing programming to avoid unintended consequences.
Relays programmed to some protection features will not operate if function is disabled elsewhere.
Setting
10 Short Circuit Trip 23 Run / Stop with On-delay from F063
11 Current Unbalance Trip 24 At Speed / Stop with On-delay from F063
12 Over Current (Shear-Pin) Trip 25 At Speed / End of Decel w/ On-delay from F063
13 Under Current Trip 26 Start / End of Decel with On-delay from F063
Table 8: Aux. Relay Settings
Relay Operation Description
1 Run / St op (Changes on Start, resets on Stop) 14 Ground Fault Trip
2 At Speed / Stop 15 Phase Rotation Trip
3 At Speed / End of Decel 16 Any Trip (#5 - #15)
4 Start / End of Decel 17
5 Short SCR Trip 18 Coast Down Time Lockout
6 Phase Loss Trip 19 Starts Per Hour Lockout
7 Shunt Trip 20 Time Between Starts Lockout
8 OL (Motor Thermal Overl oad) Tri p 21 Any Lockout (#18-#20)
9 OT (Starter Therm al Over Temperature) Trip 22 Run Timer (F030) Engaged
Setting
*Note: Flash rate for Setting #17 is ½ second On and Off
Relay Operation Description
Any Trip, (#5-#15) flashing output*
Page 23 of 27
Page 24
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
The VMX Series will automatically enter the Fault Mode when a fault occurs in the motor or starter and display
a code indicating the condition that caused a shutdown. Fault codes are three-digits in length and are displayed
in alpha characters. The first and second characters (reading left to right) are the initials for the applicable
English-language fault name. The third or right-most character can be either A, c, or d to denote when the fault
occurred. “A” denotes Acceleration. “c” denotes Constant speed. “d” denotes Decel.
A Fault History of the past 3 events is stored and can be accessed by using the Up or Down Arrow keys before
pressing the Reset button. The first (newest) event is indicated by the decimal point in the lower right corner. A
more detailed history with time and date stamps is also kept in Functions 85 through 93.
Fault Codes:
Basic common fault codes are shown in the chart below. For additional details refer to Chapter 7 of the
Advanced Installation, Operation and Programming Manual, or contact the factory for assistance.
Fault Condition Description
Over Current during Accel; Const spd; Decel ocA; occ: ocd
Phase Loss during Accel; Const spd; Decel PLA; PLc; PLd
Over Temperature during Accel; Const spd; Decel otA; otc; otd
Over Load during Accel; Const spd; Decel oLA; oLc; oLd
Shorted SCR during Accel; Const spd; Decel SSA; SSc; SSd
Shunt Trip during Accel; Const spd; Decel st
Current Imbalance during Accel; Const spd; Decel IBA; Ibc; IBd
Under Current during Accel; Const spd; Decel UcA; Ucc; Ucd
Short Circuit during Accel; Const spd; Decel ScA; Scc; Scd
Ground Fault during Accel; Const spd; Decel GFA; GFc; GFd
Bypass Discrepancy during Accel; Const spd; Decel BP A; BPc; BPd
PTC Trip during Accel; Const spd; Decel PtA; Ptc; Ptd
Rotation Trip during Accel; Const spd; Decel RtA; rtc; rtd
Additional codes that may be displayed
Display Code
Readout
nFLA No Full Load Amps set in F001
Inh
n3Ph No 3 Phase: No input line voltages on one or more phases
Loc
Err
Table 7.1: Fault and Display code list
Inhibit: Starter is still Run mode when you are attempting a change i n programming, or the starter
has Password Protection enabled and you have not entered the password code.
Lockout: The unit has tripped on Overload and you are attempting to Reset before it is ready,
or one of the Duty Cycle Lockout protection features has been enabled.
Error: You are attempting to enter an invalid password
Fault Display Code
Readout
Condition Description
Fault Number Code
used in History,
F085, F088 and
F091
1; 2; 3 Over Current
4; 5; 6 Phase Loss
7; 8; 9 Over Temp
10; 11; 12 Over Load
13; 14; 15 Short ed SCR
16; 17; 18 Shunt Trip
19; 20; 21 --22; 23; 24 --25; 26; 27 Over Current
28; 29; 30 --31; 32; 33 --34; 35; 36 Over Load
37; 38; 39 ---
LED
Indicator
Page 24 of 27
Page 25
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
The VMX Series Starter provides true U.L. listed I
main digital processor for maximum motor protection. It simulates the tripping action of a bi-metallic overload
relay, with the accuracy and repeatability of a digital control system. It is adjustable over a wide range and can
be easily programmed for different trip curves.
Thermal Memory
The VMX Series microprocessor uses a sophisticated “Thermal Register” in the digital memory to keep track of
motor heating and cooling over time regardless of the starter’s power status. By using non-volatile memory, the
VMX Series does not “forget” that the motor has been running even if power to the starter is turned off and back
on. Continuous overload protection is provided based on the true thermal condition of the motor.
Thermal Capacity
The Thermal Register is displayed as a percentage. This percentage is the motor’s remaining
The percentage value begins at 100, showing that the motor is cool (has 100% of its capacity available). As the
motor heats up or moves toward an overload condition, the percentage begins to drop. The Thermal Capacity is
derived from the programmed motor nameplate Full Load Amps (FLA) in Function F001, the Service Factor
rating in Function F002, and the Overload Trip Class in Functions F003 and F004. Setting these functions to the
proper values provides maximum protection and eliminates nuisance tripping.
Examples:
H 100
100% Thermal Capacity
remaining at rest
H057
57% Thermal Capa c ity
remaining after starting
(43% used)
Note:
All VMX Series starters are shipped from the factory with F001 set to a default value of 0000. If
F001 is left at the factory default, the unit will not operate. If the user attempts to start the VMX Series without entering the motor nameplate FLA, the starter will Fault and the display will read
“nFLA” (no Full Load Amps).
Disabling the Overload Protection
The Overload Protection feature can be disabled if necessary. Please refer to the Advanced Installation,
Operation and Programming Manual for instructions and considerations before disabling the Overload
Protection
WARNING!
Do NOT disable Overload Protection unless another Thermal Overload Protection device
exists in the circuit for all three phases. Running a motor without Overload Protection
presents serious risk of motor damage or fire.
The Remaining Thermal Capacity can be viewed by using the UP or DOWN
arrow keys when in the Status Display mode. From the default Phase A
Current screen (dot on right side), press the UP arrow key 4 times to display
[H100] meaning there is 100% of the Thermal Capacity (H = Heat capacity)
remaining in the motor. After starting or running, the motor will use this capacity
and the display will show a lower number. For example, after a cold start, the
display may read [H065] which indicates that the motor has 65% of its thermal
capacity remaining (35% used). The Status Display screens cycle back to the
beginning, so the Down arrow keys can get to this display as well.
Motor Full Load (FLA) Setting
Use Function F001 to enter motor FLA as indicated on the motor nameplate.
(Do not calculate for service factor, this is programmed separately in F002).
2
t Thermal Overload Protection as a built-in function of the
thermal capacity.
Page 25 of 27
Page 26
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
The factory default setting is Manual Reset. This means that when the Overload Trip is activated, the starter
cannot be restarted without pressing the Reset key. The Overload Trip will not reset until the motor cools down
(see 3.1.3.d). The Manual Reset function is also “trip free”. Holding in the Reset key will not prevent the
Overload Trip from activating and protecting the motor.
Note:
When the Overload Trip activates, the Overload LED will glow solid. When the motor cools
down, the LED will begin to flash, indicating that the Overload Trip can be reset.
Automatic Reset
If Automatic Reset is necessary, change from Manual Reset to Automatic Reset by using Function F005. (See
Section 5 for details). In this mode, a 3-wire control circuit will be capable of restart when the VMX Series has
reset itself after the cool down period.
WARNING!
Two-wire control systems may restart without warning when Auto Reset is
selected. Extreme caution should be exercised. To prevent automatic
restarting with 2-wire control systems, use external interlocking to provide
sufficient warning and safety to operators. A Warning Label similar to that
shown below (and the one provided in the packet with this manual) must be
located where visible (on the starter enclosure and/or the driven equipment)
as required by local code.
WARNING: MOTOR CONNECTED TO THIS EQUIPMENT
MAY START AUTOMATICALLY WITHOUT WARNING
NEMA Class Trip Curves
NEMA Class trip curves are based on a common tripping point of 600% of motor Full Load Amps (FLA). Curves
vary by the amount of time before the unit trips. As an example, a Class 20 curve will trip in 20 seconds at 600%
of FLA. The factory default setting of Class 10 will trip in 10 seconds at 600% of FLA.
Dual Overload Trip Curves
The VMX Series Soft Starter provides two separate Overload Trip Protection Curves, one for starting and one
for running conditions. The starter’s At-Speed detection circuit determines when the motor has reached full
speed. When the At-Speed condition is reached, the overload trip curve will shift from the Start to the Run level,
as programmed in Functions F003 and F004. See Section 5.6.1 for programming details.
Starting Overload Trip Curve
During the start mode, Overload Trip Curves are selectable from NEMA Class 5 through Class 20 only. The
default setting of Class 10 allows protection for the overload capacity of the soft starter as well as the motor.
Use a higher Trip Class only if nuisance tripping occurs with the default setting.
Running Overload Curve
During the Run mode, Overload trip curves are selectable from NEMA Class 5, 10, 15, 20, 25, and 30. Program
the appropriate curve according to the characteristics of your motor and load.
Page 26 of 27
Page 27
Basic Installation and Operation Guide VMX Series Digital Solid State Soft Starters 18 – 1000A
When a Bypass Contactor is used to shunt power around the SCRs in the VMX Series (as in the VMX…-BP
version), overload protection is maintained as long as the VMX Series is directly controlling the contactor. No
additional Overload Relay is necessary for normal operation.
Special Consideration for Across-the-Line (Direct-on-Line) Contactors
When the Bypass Contactor on a VMX…-BP Series has been selected to be used for Across-the-Line restart,
supplemental overload protection may be necessary. For this application, refer to the External Overload Relay
Applications supplement and wiring diagram in Appendix 5 and section 4.2.6.a of the Advanced Installation,
Operation and Programming Manual for detailed instructions.
Page 27 of 27
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.