Before you begin______________________________________________________________________________________________ 4
Documentation structure________________________________________________________________________________________ 5
Software enhancements________________________________________________________________________________________ 6
Steps for setting up the braking unit_______________________________________________________________________________ 8
Factory configuration __________________________________________________________________________________________ 9
Application functions__________________________________________________________________________________________ 10
Setup - Preliminary recommendations ____________________________________________________________________________ 14
Graphic display terminal_______________________________________________________________________________________ 16
Description of terminal __________________________________________________________________________________ 16
Description of the graphic screen__________________________________________________________________________ 17
First power-up - [5. LANGUAGE] menu _____________________________________________________________________ 20
Subsequent power ups__________________________________________________________________________________ 21
Programming: Example of accessing a parameter_____________________________________________________________ 22
Quick navigation_______________________________________________________________________________________ 23
Functions of the display and the keys_______________________________________________________________________ 26
Accessing menus ______________________________________________________________________________________ 27
Read and understand these instructions before performing any procedure on this drive.
DANGER
HAZARDOUS VOLTAGE
• Read and understand the Installation Manual before installing or operating the MT Series drive. Installation,
adjustment, repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical standards in force concerning
protective grounding of all equipment.
• Many parts of this variable speed drive, including the printed circuit boards, operate at the line voltage. DO NOT
TOUCH.
Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Install and close all the covers before applying power or starting and stopping the drive.
• Before servicing the variable speed drive
- Disconnect all power.
- Place a “DO NOT TURN ON” label on the variable speed drive disconnect.
- Lock the disconnect in the open position.
• Disconnect all power including external control power that may be present before servicing the drive. WAIT 15
MINUTES to allow the DC bus capacitors to discharge. Then follow the DC bus voltage measurement procedure
given in the Installation Manual to verify that the DC voltage is less than 45 V. The drive LEDs are not accurate
indicators of the absence of DC bus voltage.
Electric shock will result in death or serious injury.
CAUTION
DAMAGED EQUIPMENT
Do not operate or install any drive that appears damaged.
Failure to follow this instruction can result in equipment damage.
The following MT Series technical documents are available on the CD-ROM supplied with the drive.
Installation Manual
This describes how to assemble and connect the drive.
Programming manual
This describes the functions, parameters and use of the drive keypads (integrated display keypad and graphic display keypad).
The communication functions are not described in this manu al. This can be found in the Modbus (or other protocol) manual.
Communication Parameters Manual
This manual describes:
• The drive parameters with specific information for use via a bus or communication network.
• The operating modes specific to communication (state chart).
• The interaction between communication and local control.
Manual for Modbus
This manual describes the assembly, connection to the bus or network, signaling, diagnostics, and configuration of the communicationspecific parameters via the graphic display keypad.
5
Page 5
St
tti
eps for se
ng up the Drive
INSTALLATION
v 1 Consult the Installation Manual
PROGRAMMING
Tips:
• Before you start programming, complete
the user setting tables, page 267
• Perform an auto-tuning operation to
optimize performance, page 39
• If you get lost, return to the factory
settings, page 240
.
.
.
b 2 Power up without run command
v If you are using a separate power
supply for the control section, follow
the instructions on page 12.
b 3 Select the language
b 4 Configure the [SIMPLY START]
(SIM-) menu
v 2-wire or 3-wire control
v Macro configuration
v Motor parameters
) Perform an auto-tuning
operation
v Motor thermal current
v Acceleration and deceleration
ramps
v Speed variation range
Note: Check that the wiring of the
drive is compatible with its
configuration.
The tables on the following pages show the most common combinations of functions and applications, in order to guide your selection.
The applications in these tables relate to the following machines in particular:
• High inertia: centrifuges, mixers, unbalanced machines (beam pumps, presses)
• Process
Each machine has its own special features, and the combinations listed here are neither mandatory nor exhaustive.
Some functions are designed specifically for a particular application. In this case, the application is identified by a tab in the
margin on the relevant programming pages.
Motor control functions
Applications
FunctionsPage
V/f ratio
Sensorless flux vector control
Flux vector control with sensor
2-point vector control
Open-loop synchronous motor
Output frequency of up to 1600 Hz
Motor overvoltage limiting
DC bus connection (see User's Manual)
Motor fluxing using a logic input
Switching frequency of up to 16 kHz
Auto-tuning
Power Removal (safety function, see User's Manual)
Deferred stop on thermal alarm216
Alarm handling109
Fault management208 to 230
IGBT tests219
Catch a spinning load212
Braking resistor thermal protection228
Motor protection with PTC probes208
Undervoltage management218
4-20mA loss220
Uncontrolled output cut (output phase loss)214
Automatic restart211
Use of the "Pulse input" input to measure the speed of
rotation of the motor.
Load variation detection226
• Before turning on and configuring the MT Series, check that the PWR (POWER REMOVAL) input is deactivated
(programmed to 0) in order to prevent unintended operation.
• Before turning on the drive, or when exiting the configuration menus, check that the inputs assigned to the run
command are deactivated (programmed to 0) since they can cause the motor to start immedia tely.
Failure to follow these instructions will result in death or serious injury.
INCOMPATIBLE LINE VOLTAGE
Before turning on and configuring the drive, ensure that the li ne voltage is compatible with the sup ply voltage range shown
on the drive nameplate. The drive may be damaged if the line voltage is not compatible.
Failure to follow this instruction can result in equipment damage.
DANGER
CAUTION
Separate control section power supply
When the drive control section is powered independently of the power section (P24 and 0V terminals), whenever an option card is added
or replaced, only the power section must be supplied with power next time the drive is powered up.
By default the new card would not be recogniz ed and it wo uld be impossi ble to confi gure it, th ereby causing the dri ve to lock in fau lt mode.
Power switching via line contactor
CAUTION
• Avoid operating the contactor frequently (premature ageing of the filter capacitors).
• Cycle times < 60 s may result in damage to the pre-charge resistor.
Failure to follow this instruction can res u lt in equ ip m e nt da m a ge.
User adjustment and extension of functions
• The display unit and buttons can be used to modify the settings and t o extend the functions described in the following pages.
• Return to factory settings is made easy by the [1.12 FACTORY SETTINGS](FCS-) menu, see page 238
• There are three types of parameters:
- Display: Values displayed by the drive
- Adjustment: Can be changed during operation or when stopped
- Configuration: Can only be modified when stopped and no braking is taking place. Can be displayed during operation.
.
DANGER
UNINTENDED EQUIPMENT OPERATION
• Check that changes made to the settings during operation do not present any danger.
• We recommend stopping the drive before making any changes.
Failure to follow these instructions will result in death or serious injury.
• In factory settings mode, the motor can only be supplied wit h power once t he “forward”, “reverse” an d “DC injection sto p” commands
have been reset:
- On power-up or a manual fault reset or after a stop command
If they have not been reset, the drive will display "nSt" but will not start.
• If the automatic restart function has been configured ([Automatic restart](Atr) parameter in the [1.8-FAULT MANAGEMENT](FLt-)
menu, see page 214
Test on a low power motor or without a motor
• In factory settings mode, [Output Phase Loss] detection (OPL) page 214 is active (OPL = YES). To check the drive in a test or
maintenance environment without having to switch to a moto r with the same rating as the drive (part icularly useful in t he case of high
power drives), deactivate [Output Phase Loss] (OPL = no).
• Configure [Motor control type] (Ctt) = [V/F 2pts](UF2) or [V/F 5pts](UF5) ([1.4-MOTOR CONTROL](drC-) menu, see page 66
• Motor thermal protection will not be provided by the drive if th e motor current is less t han 0.2 times the rate d drive
current. Provide an alternative means of thermal protection.
), these commands are taken into account without a reset being necessary.
CAUTION
)
Failure to follow this instruction can res u lt in equ ip m e nt da m a ge.
Using motors in parallel
• Configure [Motor control type] (Ctt) = [V/F 2pts](UF2) or [V/F 5pts](UF5) ([1.4-MOTOR CONTROL](drC-) menu, see page 66)
CAUTION
• Motor thermal protection is no longer provided b y the drive. Provide an alternative means of thermal protection on
every motor.
Failure to follow this instruction can res u lt in equ ip m e nt da m a ge.
The graphic display keypad is standard on all series drives. The graphic display keypad can be disconnected and reconnected remotely
(on the door of an enclosure for example) using the cables and accessories available as options (see catalog).
Description of keypad
1 Graphic display
2 Function keys
F1, F2, F3, F4,
see page 15
3 STOP/RESET
button
.
7 ESC key: Aborts a value, a
parameter or a menu to return
to the previous selection
4 RUN button
5 Navigation button:
• Press (ENT):- To save the current value
- To enter the selected menu or parameter
• Turn CW/
CCW:
- To increment or decrement a value
- To go to the next or previous line
- To increase or decrease the reference if control via
the terminal is activated
When only one selection is possible, the selection made is indicated by
Example: Only one language can be chosen.
When multiple selection is possible, the selections made are indicated by
Example: A number of parameters can be chosen to form the [USER MENU].
Example configuration window for one value:
RDY Term +0.00Hz0A
Acceleration
RDY Term +0.00Hz0A
Acceleration
>>
9.51 s
Min = 0.01 Max = 99.99
<<>>Quick
Min = 0.01 Max = 99.99
951 s
<<>>Quick
The << and >> arrows (keys F2 and F3) are used to select the digit to be modified, and the navigation button is rotated to increase or
decrease this number.
The first time the drive is powered up, the user will automatically be guided through the menus as far as [1. DRIVE MENU].
The parameters in the [1.1 SIMPLY START] submenu must be configured and auto-tuning performed before the motor is started up.
MOTORTRONICS
2.2kW/3HP 380/480V
3 seconds
MT403U22N4
Config. n°1
Displays for 3 seconds following power-up
English
5 LANGUAGE
Français
Deutsch
Español
Italiano
Chinese
RDY Term +0.00Hz 0.0A
2 ACCESS LEVEL
Basic
Standard
Advanced
Expert
RDY Term +0.00Hz 0.0A
1 DRIVE MENU
1.1 SIMPLY START
1.2. MONITORING
1.3. SETTINGS
1.4. MOTOR CONTROL
1.5. INPUTS / OUTPUTS CFG
Code<<>>Quick
Automatically switches to [5 LANGUAGE]
menu 3 seconds later.
Select the language and press ENT.
Switches to [2 ACCESS LEVEL] menu
(see page 27
)
Select the access level and press ENT.
Switches to [1 DRIVE MENU]
(see page 23
)
ESC
RDY Term +0.00Hz 0.0A
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
- Turn the navigation button to scroll vertically.
• To modify a parameter:
- Use the << and >> keys (F2 and F3) to scroll horizontally and select the digit to be modified (the selected digit chan ges to white
on a black background).
If the "Quick" function is displayed above the F4 key, you can gain quick access to a parameter from any screen.
Example:
RDY Term +0.00Hz0A
1.4 MOTOR CONTROL
Standard mot. freq: 60Hz
Rated motor power: 0.37 kW (0.5 HP)
Rated motor volt.: 206 V
Rated mot. current: 1.0 A
Rated motor freq.: 60.0 Hz
Code<<>>Quick
Press F4 to access the Quick screen, which contains
4 selection options.
• [HOME]: Return to [MAIN MENU].
RDY Term +0.00Hz0A
QUICK NAVIGATION
RETURN TO MAIN MENU
DIRECT ACCESS TO...
10 LAST MODIFICATIONS
GOTO MULTIPOINT SCREEN
Code
See page 255
ENT
RDY Term +0.00Hz0A
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
MAIN MENU
• [DIRECT ACCESS TO...] : Opens the direct access window, which
will contain the text "1". The function keys << and >> (F2 and F3)
can be used to select each of the numbers and the navigation
button to increment or decrement the numbers: 1.3 in the example
below.
RDY Term +0.00Hz0A
DIRECT ACCESS TO...
1.3
SETTINGS
<<>>
RDY Term +0.00Hz0A
Ramp increment: 01
ENT
Acceleration9.51 s
Deceleration: 9.67 s
Acceleration 2: 12.58 s
Deceleration 2: 13.45 s
1.3 SETTINGS
Code<<>>Quick
• [10 LAST MODIFICATIONS]: Opens a window in which the l ast 10
parameters modified can be accessed directly.
RDY Term +0.00Hz0A
10 LAST MODIFICATIONS
Acceleration: 10 s
ENA prop.gain: 1.2
Rated mot. current: 15 A
Preset speed 4: 20 Hz
Preset speed 5: 30 Hz
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
6 MONITORING CONFIG.
7 DISPLAY CONFIG.
MAIN MENU
RDY Term +0.00Hz0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
Code<<>>Quick
1.6 COMMAND
1.7 APPLICATION FUNCT.
1.8 FAULT MANAGEMENT
1.9 COMMUNICATION
1.10 DIAGNOSTICS
1.11 IDENTIFICATION
1.12 FACTORY SETTINGS
1.13 USER MENU
1.14 PROGRAMMABLE CARD
Content of [MAIN MENU] menus
[1 DRIVE MENU]See next page
[2 ACCESS LEVEL]Defines which menus can be accessed (level of complexity)
[3 OPEN / SAVE AS]Can be used to save and recover drive configuration files
[4 PASSWORD]Provides password protection for the configuration
[5 LANGUAGE]Language selection
[6 MONITORING CONFIG.]Customization of information displayed on the graphic display terminal during operation
[7 DISPLAY CONFIG.] • Customization of parameters
• Creation of a customized user menu
• Customization of the visibility and protection mechanisms for menus and parameters
[1.1 SIMPLY START]:Simplified menu for a quick start
[1.2 MONITORING]:Visualization of current, motor and input/output values
[1.3 SETTINGS]:Accesses the adjustment parameters, which can be modified during operation
[1.4 MOTOR CONTROL] :Moto r parame ters (motor nameplate, auto-tuning, switching frequency, control algorithms, etc.)
[1.5 INPUTS / OUTPUTS CFG]:I/O configuration (scaling, filtering, 2-wire control, 3-wire control, etc.)
[1.6 COMMAND]:Configuration of command and reference channels (graphic d isplay t ermi nal, t ermin als , bus, e tc.)
[1.7 APPLICATION FUNCT.] :Configuration of application functions (e.g., preset speeds, PID, brake logic control, etc.)
[1.8 FAULT MANAGEMENT]:Configuration of fault management
[1.9 COMMUNICATION]:Communication parameters (fieldbus)
[1.10 DIAGNOSTICS]:Motor/drive diagnostics
[1.11 IDENTIFICATION]:Identifies the drive and the internal options
[1.12 FACTORY SETTINGS]:Access to configuration files and return to factory settings
[1.13 USER MENU]:Specific menu set up by t he user in the [7. DISPLAY CONFIG.] menu
[1.14 PROGRAMMABLE CARD]: : N/A
All MT Series drives also include an integrate d displ ay terminal with a 7-segme nt 4-dig it displ ay. Th e graphic displa y keypad described on
the previous pages and the integrated keypad are included as standard.
Functions of the display and the keys
• 2 Modbus status LEDs
• Four 7-segment displays
• Returns to the previous
menu or parameter, or
increases the displayed
value
• Goes to the next menu
or parameter, or
decreases the
displayed value
Note:
• Pressing or does not store the selection.
• 2 CANopen status LEDs
• Exits a menu or paramete r,
or aborts the displayed
value to return to the
previous value in the
memory
• Enters a menu or
parameter, or saves the
displayed parameter or
value
• Press and hold down (>2 s) or to scroll through the data quickly.
Save and store the selection: ENT
The display flashes when a value is stored.
Normal display, with no fault present and no startup:
- 43.0 : Display of the parameter selected in the SUP menu (default selection: motor frequency)
- CLI: Current limit
- CtL: Controlled st op on in pu t ph ase loss
- dCb: DC injection braking in progress
- FLU: Motor fluxing in progress
- FSt: Fast stop.
- nLP: No line power (no line supply on L1, L2, L3)
- nSt: Freewheel stop
- Obr: Auto-adapted deceleration
- PrA: Power Removal function active (drive locked)
- rdY = Drive ready
- SOC: Controlled output cut in progress
- tUn: Auto-tuning in progress
- USA: Undervoltage alarm
The display flashes to indicate the presence of a fault.
All the menus are "drop-down" type menus, which means that after the last pa rameter, if
you continue to press, you will return to the first parameter and, conversely, you can
switch from the first parameter to the last parameter by pressing.
Menu
ENT
ESC
st
1
th
n
last
Selection of multiple assignments for one parameter
I-O-
Example: List of group 1 alarms in [INPUTS / OUTPUTS CFG]
ENT
ESC
Alarm not selected
Alarm selected
menu (I-O-)
A number of alarms can be selected by "checking" them as
follows.
The digit on the right indicates: selected
not selected.
The same principle is used for all multiple selections.
Basic
Access to 5 menus only, and access to 6 submenus only in the
[1. DRIVE MENU] menu.
A single function can be assigned to each input.
RDY Term +0.00Hz0A
2 ACCESS LEVEL
Basic
Standard
Advanced
Expert
<<>>Quick
RDY Term +0.00Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
Code<<>>Quick
RDY Term +0.00Hz0A
1. DRIVE MENU
1.1 SIMPLY START
1.2. MONITORING
1.3. SETTINGS
1.11. IDENTIFICATION
1.12. FACTORY SETTINGS
Code<<>>Quick
1.13 USER MENU
Standard
This is the factory-set level. Access to 6 menus only, and access to all
submenus in the [1. DRIVE MENU] menu.
A single function can be assigned to each input.
RDY Term +0.00Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
6 MONITORING CONFIG.
Advanced
Access to all menus and submenus.
Several functions can be assigned to
each input.
RDY Term +0.00Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
6 MONITORING CONFIG.
7 DISPLAY CONFIG.
RDY Term +0.00Hz0A
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
1.6 COMMAND
1.7 APPLICATION FUNCT.
1.8 FAULT MANAGEMENT
1.9 COMMUNICATION
1.10 DIAGNOSTICS
1.11 IDENTIFICATION
1.12 FACTORY SETTINGS
1.13 USER MENU
1.14 PROGRAMMABLE CARD
1 DRIVE MENU
Code<<>>Quick
Expert
Access to all menus and submenus as for [Advanced] level, and access to
additional parameters.
Several functions can be assigned to each input.
RDY Term +0.00Hz0A
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
The parameter tables in the descriptions of t he various menus c an be used wit h both th e graphic dis play keypad and the integ rated display
keypad. They, therefore, contain information for these two keypads in accordance with the description below.
Example:
5
[1.7 APPLICATION FUNCT.](FUn-)
1
CodeName/DescriptionAdju s t ment ran ge Factory setting
2
UPd-
3
4
USP
LI1
b [+/- SPEED]
Function can be accessed for reference channel [Ref.2 channel] (Fr2) = [+/- speed] (UPdt) ,
see page 120
M [+ speed assignment]
no
v [No] (nO): function inactive
v [LI1](LI1)
6
7
8
[No] (nO)
1. Name of menu on 4-digit 7-segment display.
2. Submenu code on 4-digit 7-segment display.
3. Parameter code on 4-digit 7-segment display.
4. Parameter value on 4-digit 7-segment display.
Note :
• The text in square brackets [ ] indicates what you will see on the graphic disp lay keypad.
• The factory settings correspond to [Macro configuration](CFG) = [Start/Stop](StS). This is the macro configuration set at
the factory.
The configuration of certain parameters modifies the a dju stme nt range of ot her p aramet ers, in order to redu ce t he risk of error s. This may
result in the modification of a factory setting or a value you have already selected.
Example:
1. [Current Limitation] (CLI) page 56 set to 1.6 In or left at its factory setting, 1.5 In
2. [Switching freq.] (SFr) page 56
3. If [Switching freq.] (SFr) is increased to 4 kHz, [Current limitation] (CLI) is no longer restricted, but remains at 1.36 In. If you require
1.6 In, you must reset [Current Limitation] (CLI).
set to 1 kHz (and confirmed with "ENT") restricts [Current Limitation] (CLI) to 1.36 In
The following assistance with finding explanations on a parameter is provided:
ocumen
• With the integrated display keypad: Direct use of the parameter code index, page 266
displayed parameter.
• With the graphic display keypad: Select the required parameter and press : [Code]. The parameter code is displayed instead
of its name while the key is held down.
Example: ACC
RDY Term +0.00Hz0A
Ramp increment: 01
Acceleration9.51 s
Deceleration: 9.67 s
Acceleration 2: 12.58 s
Deceleration 2: 13.45 s
Then use the parameter code index, page 266
1.3 SETTINGS
Code
Code<<>>Quick
RDY Term +0.00Hz0A
1.3 SETTINGS
Ramp increment: 01
ACC9.51 s
Deceleration: 9.67 s
Acceleration 2: 12.58 s
Deceleration 2: 13.45 s
Code<<>>Quick
, to find the page giving details of the displayed parameter.
Using graphic display keypad:(use this approach for fast and easy setup)
RDY Term +0.00Hz0A
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
MAIN MENU
ENT
Using integrated display keypad:
Power-up
Displays the state of the drive
XXX
ENT
ESC
ESC
ESC
SIM-
SUP-
LAC-
ENT
ESC
SIMPLY START
RDY Term +0.00Hz0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
Code<<>>Quick
ENT
RUN Term+50.00Hz 80A
1.1 SIMPLY START
2/3 wire control
Macro configuration
Customized macro
Standard mot. freq
Input phase loss
Code<<>>Quick
The [1.1-SIMPLY START](SIM-) menu can be used for fast startup, which is sufficient for the majority of applications.
The parameters in this menu can only be modified when the d rive is stopped a nd no run command is present, with the f ollowing exceptions:
• Auto-tuning, which causes the motor to start up
• The adjustment parameters on page 40
Note : The parameters of the [1.1 SIMPLY START](SIM-) menu must be entered in the order in which they appear, as the later
ones are dependent on the first ones.
For example [2/3 wire control](tCC) must be configured before any other parameters.
The [1.1 SIMPLY START](SIM-) menu should be configured on its own or before the other drive configuration menus. If a modification
has previously been made to any of them, in particular in [1.4 MOTOR CONTROL] (drC-), some [1.1 SIMPLY START](SIM-) parameters
may be changed, for example, the motor parameters, if a synchronous motor has been selected. Returning to the [1.1 SIMPLY START]
(SIM-) menu after modifying another drive configuration menu is unneces sary but does not pose any risk. Changes fol lowing modifi cation
of another configuration menu are not described, to avoid unnecessary complication in this section.
Macro configuration
Macro configuration provides a means of speeding up the configuration of functions for a specific field of application.
7 macro configurations are available:
• Start/stop (factory configuration)
• Handling
• General use
•Hoisting
• PID regulator
• Communication bus
•Master/slave
Selecting a macro configuration assigns the parameters in this macro conf iguration.
Each macro configuration can still be modified in the other menus.
• [Low speed](LSP) = Rated motor slip calculated by the drive, page 40
• [Output Phase Loss](OPL) = [Yes](YES) page 214. No further modifications can be made to this parameter.
• [Catch on the fly](FLr) = [No] (nO) page 212
Mast./slave:
• [Motor control type](Ctt) = [SVC I](CUC) page 66
. No further modifications can be made to this parameter.
Note: These assignments are forced every time the macro configuration changes, except for [Motor control type](Ctt) for the Mast./slave
macro configuration, if it is configured in [FVC](FUC).
Return to factory settings:
Returning to factory settings with [Config. Source](FCSI) = [Macro-Conf](InI) page 240
configuration. The [Macro configuration](CFG) parameter does not change, although [Customized macro](CCFG) disappears.
Note :
• The factory settings that appear in the parameter tables correspond to [Macro configuration](CFG) = [Start/Stop](StS).
This is the macro configuration set at the factory.
Example diagrams for use with the macro configurations
[Hoisting] (HSt) diagram
3
L1L3
L2
MT Series
ATV71H
UWV
Forward
(Ascend)
LI1LI2+24
AI1
Reverse
(Descend)
R2A
R2C
(1)
2
KM10
Electromagnetic brake
M
3
(1)A contact on the auxilliary safety relay must be inserted in the brake control circuit to engage it safely when t he "Power Removal" safet y
function is activated (see connection diagrams in the Installation Manual).
[Mast./slave] (MSL) diagram
TorqueSpeed
3
3
L2
L1L3
MT Series
UWV
LI1LI2+24
pppp
Master drive
ReverseForward
Forward
AI1
COMA01
Reverse
LI1+24
LI2
AI1
COMAI2UWV
LI3L1L3L2
MT Seriespppp
Slave drive
M1
3
M2
3
When the two motors are mechanically connected , the Speed/torque contact closing results in operation in Mast./slave mode. The master
drive regulates the speed and controls the slave drive in torque mode t o ensure distribution of the load.
2-wire control: This is the input state (0 or 1) or edge (0 to 1 or 1 to 0), which controls running or stopping.
Example of "source" wiring:
3-wire control (pulse commands): A "forward" or "reverse" pulse is sufficient to command starting, a "stop"
pulse is sufficient to command stopping.
Example of "source" wiring:
UNINTENDED EQUIPMENT OPERATION
To change the assignment of [2/3 wire control] (tCC) press and hold down the “ENT” key for 2 s.
The following function will be returned to factory settings: [2 wire type] (tCt) page 83
functions which assign logic inputs.
The macro configuration selected will also be reset it if h as been customized (loss of custom settings).
Check that this change is compatible with the wiring diagram used.
Failure to follow these instructions can result in death or serious injury.
ATV 71
MT Series
+24 LI1 LIx
ATV 71
MT Series
+24 LI1 LI2 LIx
[2 wire] (2C)
LI1: forward
LIx: reverse
LI1: stop
LI2: forward
LIx: reverse
WARNING
as will all
CFG
StS
HdG
HSt
GEn
PId
nEt
MSL
CCFG
YES
M [Macro configuration]
v [Start/Stop] (StS): Start/stop
v [M. handling] (HdG): Handling
v [Hoisting] (HSt): Hoisting
v [Gen. Use] (GEn): General use
v [PID regul.] (PId): PID regulation
v [Network C.] (nEt): Communication bus
v [Mast./slave] (MSL): Master/slave
UNINTENDED EQUIPMENT OPERATION
To change the assignment of [Macro configuration ] (CFG) press and hold down the “ENT” key for 2 s.
Check that the selected macro configuration is compatible with the wiring diagram used.
Failure to follow these instructions can result in death or serious injury.
M [Customized macro]
Read-only parameter, only visible if at least one macro configuration parameter has been modified.
This parameter modifies the presets of the following parameters:[Rated mo tor volt.](UnS) below, [High speed]
(HSP) page 40
M [Input phase loss]
nO
v [Ignore] (nO): Fault ignored, to be used when the drive is supplied via a single-phase supply or by the
DC bus.
v [Freewheel] (YES): Fault, with freewheel stop.
If one phase disappears, the drive switches to fault mode [Input phase loss] (IPL), but if 2 or 3 phases
disappear, the drive continues to operate until it trips on an undervoltage fault.
This parameter is only accessible in this menu on MT2P5037M3 to MT201075M3 dri ves (used with a single
phase supply).
M [Rated motor power]
Rated motor power given on the nameplate, in kW if [Standard mot. freq] (bFr) = [50Hz IEC](50), in HP if
[Standard mot. freq] (bFr) = [60Hz NEMA](60).
M [Rated motor volt.]
Rated motor voltage given on the nameplate.
MT Series
MT Series
M [Rated mot. current]
Rated motor current given on the nameplate.
M [Rated motor freq.]
Rated motor frequency given on the nameplate.
The factory setting is 60 Hz, or preset to 50 Hz if [Standard mot. freq] (bFr) is set to 50 Hz.
M [Rated motor speed]
Rated motor speed given on the nameplate.
0 to 9999 rpm then 10.00 to 60.00 krpm on the integrated display terminal .
If, rather than the rated speed, the nameplate indicates the sy nchronous speed and the slip in Hz or as a %,
calculate the rated speed as follows:
• Nominal speed = Synchronous speed x
or
• Nominal speed = Synchronous speed x (50 Hz motors)
or
• Nominal speed = Synchronous speed x (60 Hz motors)
[60Hz Nema](50 IEC)
, [Freq. threshold](Ftd) page 62, [Rated motor freq.] (FrS ) and [Max frequency] (tFr) .
According to drive
rating
According to drive
rating
According to drive
rating
ppp : 100 to 240 V
ppp : 200 to 480 V
0.25 to 1.5 In (1)According to drive
10 to 600 Hz60 Hz
0 to 60000 RPMAccording to drive
100 - slip as a %
100
50 - slip in Hz
50
60 - slip in Hz
60
According to drive
rating
According to drive
rating and [Standard
mot. freq] (bFr)
rating and [Standard
mot. freq] (bFr)
rating
tFr
(1)In corresponds to the rated drive current indicated in the Installation Manual and on the drive nameplate.
38
M [Max frequency]
The factory setting is 72 Hz, or preset to 60 Hz if [Standard mot. freq] (bFr) is set to 50 Hz.
The maximum value is limited by the following conditions:
• It must not exceed 10 times the value of [Rated motor freq.] (FrS)
• It must not exceed 500 Hz if the drive rating is higher than MT2P5037M3 (values between 500 Hz and
1600 Hz are only possible for powers limited to 37 kW (50 HP).
v [No] (nO): Auto-tuning not performed.
v [Yes] (YES): Auto-tuning is performed as soon as possible, then the parameter automatically changes to [Done]
(dOnE).
v [Done] (dOnE) : Use of the values given the last time auto-tuning was performed.
Caution:
• It is essential that all motor parameters ([Rated motor volt.] (UnS), [Rated motor freq.] (FrS), [Rated mot.
current] (nCr), [Rated motor speed] (nSP), [Rated motor power] (nPr)) are configured correctly before
starting auto-tuning.
If at least one of these parameters is modified after auto-tuni ng has been performed, [Aut o tun ing] (tU n) will
return to [No] (nO) and must be repeated.
• Auto-tuning is only performed if no stop command has been activated. If a "freewheel stop" or "fast stop"
function has been assigned to a logic input, this input must be set to 1 (active at 0).
• Auto-tuning takes priority over any run or prefluxing commands, which will be taken into account after the
auto-tuning sequence.
• If auto-tuning fails, the drive displays [No] (nO) and, depending on the configuration of [Autotune fault mgt]
(tnL) page 228
• Auto-tuning may last for 1 to 2 seconds. Do not interrupt the process. Wait for the display to cha nge to
"[Done] (dOnE)" or "[No] (nO)".
Note: During auto-tuning the motor operates at rated current.
M [Auto tuning status]
(for information only, cannot be modified)
, may switch to [Auto-tuning] (tnF) fault mode.
[Not done] (tAb)
v [Not done] (tAb): The default stator resistance value is used to control the motor.
v [Pending] (PEnd): Auto-tuning has been requested but not yet performed.
v [In Progress] (PrOG): Auto-tuning in progress.
v [Failed] (FAIL): Auto-tuning has failed.
v [Done] (dOnE) : The stator resistance measured by the auto-tuning function is used to control the motor.
M [Output Ph rotation]
[ABC](AbC)
v [ABC] (AbC): Forward
v [ACB] (ACb): Reverse
This parameter can be used to reverse the direction of rotation of the motor witho ut reversing the wiring.
Parameters that can be changed during operation or when stopped
CodeName/DescriptionFactory setting
ItH
ACC
dEC
LSP
HSP
(1)In corresponds to the rated drive current indicated in the Installation Manual and on the drive nameplate.
M [Mot. therm. current]
Motor thermal protection current, to be set to the rated current indicated on the nameplate.
M [Acceleration]
Time to accelerate from 0 to the [Rated motor freq.] (FrS) (page 38). Make sure that this value is compatible
with the inertia being driven.
M [Deceleration]
Time to decelerate from the [Rated motor freq.] (FrS) (page 38) to 0. Make sure that this value is compatible
with the inertia being driven.
M [Low speed]
Motor frequency at minimum reference, can be set between 0 and [High speed] (HSP).
M [High speed]
Motor frequency at maximum reference, can be set betwe en [Low speed] (LSP) and [Max frequency] (tFr). The
factory setting changes to 50 Hz if [Standard mot. freq] (bFr) = [50 IEC NEMA] (50).
[COMMUNICATION MAP] indicates the types of bus used for control or reference, the
corresponding command and reference values, the status word, the words selected in
the [DISPLAY CONFIG.] menu, etc.
The display format (hexadecimal or decimal) can be configured in the [DISPLAY
CONFIG.] menu.
RUNTerm+50.00Hz 80A
COM. SCANNER INPUT MAP
Com Scan In1 val.: 0
Com Scan In2 val.: 0
Com Scan In3 val.: 0
Com Scan In4 val.: 0
Com Scan In5 val.: 0
CodeQuick
Com Scan In6 val.: 0
Com Scan In7 val.: 0
Com Scan In8 val.: 0
RUNTerm+50.00Hz 80A
COM SCAN OUTPUT MAP
Com Scan Out1 val.: 0
Com Scan Out2 val.: 0
Com Scan Out3 val.: 0
Com Scan Out4 val.: 0
Com Scan Out5 val.: 0
CodeQuick
Com Scan Out6 val.: 0
Com Scan Out7 val.: 0
Com Scan Out8 val.: 0
[COM. SCANNER INPUT MAP] and [COM SCAN OUTPUT MAP]:
Visualization of registers exchanged periodically (8 input and 8 output) for integrated Modbus and for fieldbus cards.
Current alarm group numbers
in Hz. Frequency reference via the graphic display keypad (can be accessed if the function has been
configured).
as a process value. PID reference via graphic display keypad (can be accessed if the function has been
configured).
as a % of the rated torque. Torque reference via graphic display keypad.
as a % (can be accessed if [Multiplier ref. -] (MA2,MA3) page 130
in Hz
as a % of the rated torque (can be accessed if the function has been configured)
in Hz
in Hz: The measured motor speed is displayed if an encoder card has been inserted and configured in
speed feedback mode, otherwise 0 appears.
in Hz: Frequency of the "Pulse input" input used by the [FREQUENCY METER] (FqF-) function, page 225
in A
in Hz: The parameter can be accessed if [ENA system] (EnA) = [Yes] (YES) (see page 75
in rpm
in V
as a % of the rated power
as a % of the rated torque
in V. Line voltage from the point of view of the DC bus, motor running or stopped.
as a %
as a %
as a % (can only be accessed on high rating drives)
in Wh, kWh or MWh (accumulated consumption)
in seconds, minutes or hours (length of time the motor has been switched on)
in seconds, minutes or hours (length of time the drive has been switched on)
in seconds (length of time the "IGBT temperature" alarm has been active)
as a process value (can be accessed if the PID function has been configured)
as a process value (can be accessed if the PID function has been configured)
as a process value (can be accessed if the PID function has been configured)
in Hz (can be accessed if the PID function has been configured)
Current date and time
Active configuration [Config. n°0, 1 or 2]
[Set n°1, 2 or 3] (can be accessed if parameter switching has been enabled, see page 192
List of current alarms. If an alarm is present, a appears.
List of secondary states:
-[In motor fluxing] (FLX): In motor fluxing
-[PTC1 alarm] (PtC1): Probe alarm 1
-[PTC2 alarm](PtC2): Probe alarm 2
-[LI6=PTC alarm] (PtC3): LI6 = PTC probe alarm
-[Fast stop in prog.] (FSt): Fast stop in progress
Can be used to display the functions assigned to each input. If no functions have been assigned, nO is
displayed.
Use the and arrows to scroll through the functions. If a number of functions have been assigned
to the same input, check that they are compatible.
b State of logic inputs LI1 to LI8
Can be used to visualize the state of logic inputs LI1 to LI 8
(display segment assignment: high = 1, low = 0)
State 1
State 0
LI1 LI2 LI3 LI4 LI5 LI6 LI7 LI8
Example above: LI1 and LI6 are at 1; LI2 to LI5, LI7 and LI8 are at 0.
b State of logic inputs LI9 to LI14 and Power Removal
Can be used to visualize the state of logic inputs LI9 to LI14 and PR (Power Removal)
(display segment assignment: high = 1, low = 0)
State 1
AIA-
AI1A
AI2A
AI3A
AI4A
State 0
LI9 LI10 LI11 LI12 LI13 LI14 PR
Example above: LI9 and LI14 are at 1, LI10 to LI13 are at 0 and PR (Power Removal) is at 1.
b Analog input functions
Can be used to display the functions assigned to each input. If no functions have been assigned, nO is
displayed. Use the and arrows to scroll through the functions. If a number of functio ns have been
assigned to the same input, check that they are compatible.
Using integrated display keypad: Drive-internal states and values
CodeName/DescriptionUnit
ALGr
rPI
MFr
FrH
trr
rFr
MMF
FqS
LCr
AUS
SPd
UOP
OPr
Otr
ULn
tHr
tHd
tHb
APH
rtH
PtH
tAC
rPC
rPF
rPE
rPO
CnFS
CFPS
Alarm groups: Current alarm group numbers
Internal PID reference: PID reference via graphic display keypad (can be ac cessed if the fun ction has been
configured).
Multiplication coefficient (can be accessed if [Multiplier ref. -] (MA2,MA3) page 130
Frequency ref.Hz
Torque reference: Can be accessed if the function has been configured%.
Output frequencyHz
The measured motor speed is displayed if an encoder card has been inserted and configured in speed
feedback mode, otherwise 0 appears.
Frequency of the "Pulse input" input used by the [FREQUENCY METER] (FqF-) function, page 225
Motor currentA
ENA avg
Motor speedrpm
Motor voltageV
Motor power%
Motor torque%
Line voltage: Line voltage from the point of view of the DC bus, motor running or stopped.V
Motor thermal state%
Drv thermal state %
DBR thermal state: Can be accessed on high rating drives only. %
Power consumptionWh, kWh or
Run time: Length of time the motor has been turned onseconds,
Power on time: Length of time the drive has been turned on
IGBT alarm counter: Length of time the "IGBT temperature" alarm has been activeseconds
PID reference: Can be accessed if the PID function has been configuredas a process
PID feedback: Can be accessed if the PID function has been configured
PID error: Can be accessed if the PID function has been configured
PID Output: Can be accessed if the PID function has been configuredHz
Config. active: CnF0, 1 or 2 (can be accessed if motor or configuration switching has been enabled, see
page 196
Utilised param. set: CFP1, 2 or 3 (can be accessed if parameter switching has been enabled, see page 192
SPEED: The parameter can be accessed if EnA = YES (see page 75)Hz
v [0,01]: ramp up to 99.99 seconds
v [0,1]: ramp up to 999.9 seconds
v [1]: ramp up to 6000 seconds
This parameter is valid for [Acceleration] (ACC), [Deceleration] (dEC ), [Acceleration 2] (AC2) and [Deceleration
2] (dE2).
M [Acceleration]
Time to accelerate from 0 to the [Rated motor freq.] (FrS) (page 64). Make sure that this value is compatible
with the inertia being driven.
M [Deceleration]
Time to decelerate from the [Rated motor freq.] (FrS) (page 64) to 0. Make sure that this value is compatible
with the inertia being driven.
M [Acceleration 2]
See page 133
Time to accelerate from 0 to the [Rated motor freq.] (FrS). Make sure that this value is compatible with the
inertia being driven.
M [Deceleration 2]
See page 133
Time to decelerate from the [Rated motor freq.] (FrS) to 0. Make sure that this value is compatible with the
inertia being driven.
M [Begin Acc round]
See page 132
Rounding of start of acceleration ramp as a % of the [Acceleration] (ACC) or [Acceleration 2] (AC2) ramp time.
M [End Acc round]
See page 132
- Rounding of end of acceleration ramp as a % of the [Acceleration] (AC C ) or [Acceleration 2] (AC2) ramp
time.
- Can be set between 0 and (100% - [Begin Acc round] (tA1))
M Begin Dec round]
See page 132
Rounding of start of deceleration ramp a s a % of the [Deceleration] (dEC) or [Deceleration 2] (dE2) ramp time.
0,01 - 0,1 - 10,1
0.01 to 6000 s (1)3.0 s
0.01 to 6000 s (1)3.0 s
0.01 to 6000 s (1)5.0 s
0.01 to 6000 s (1)5.0 s
0 to 100%10%
10%
0 to 100%10%
(1)Range 0.01 to 99.99 s or 0.1 to 999.9 s or 1 to 6000 s according to [Ramp increment] (Inr).
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
g
50
also be accessed and adjusted from within the configura tion menu for the c orresponding fu nction, their descri ption is deta iled
in these menus, on the pages indicated, to aid programming.
Parameter settings for [K speed loop filter](SFC), [Speed prop. gain](SPG) and
[Speed time integral](SIt)
• The following parameters can only be accessed in vector control profi les: [Motor control type](Ctt) page 66 = [SVC V](UUC), [SVC I]
(CUC), [FVC](FUC) and [Sync. mot.](SYn) and if [ENA system](EnA) page 75
• The factory settings are suitable for most applications.
General case: Setting for [K speed loop filter](SFC) = 0
The regulator is an "IP" type with filtering of the speed reference, for applications requiring flexibility and stability (hoisting or high inertia,
for example).
See page 135
Level of DC injection braking current activated via logic input or selected as stop mode.
1 to 9999250
0 to 9999100
25 to 200%100%
0 to 300%100%
0 to 104
0.1 to 1.41 In (1)0.64 In (1)
CAUTION
tdI
g
IdC2
g
tdC
g
Check that the motor will withstand this current without overheating.
Failure to follow this instruction can result in equipment damage.
M [DC injection time 1]
See page 135
Maximum current injection time [DC inject. level 1] (IdC). After this time the injection current becomes
[DC inject. level 2] (IdC2).
M [DC inject. level 2]
See page 135
Injection current activated by logic input or selected as stop mode, once period of time [DC injection time 1] (tdI)
has elapsed.
Check that the motor will withstand this current without overheating.
Failure to follow this instruction can result in equipment damage.
M [DC injection time 2]
See page 135
Maximum injection time [DC inject. level 2] (IdC2) for injection selected as stop mode only.
CAUTION
0.1 to 30 s0.5 s
0.1 In (2) to [DC inject.
level 1] (IdC)
0.1 to 30 s0.5 s
0.5 In (1)
(1)In corresponds to the rated drive current indicated in the Installation Manual or on the drive nameplate.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
g
54
also be accessed and adjusted from within the configura tion menu for the c orresponding fu nction, their descri ption is deta iled
in these menus, on the pages indicated, to aid programming.
Level of standstill DC injection current. This parameter can be accessed if [Auto DC injecti on] (AdC) pa ge 136
is not [No] (nO)
This parameter is forced to 0 if [Motor control type] (Ctt) page 66
-
0 to 1.2 In (1)0.7 In (1)
= [Sync. mot.] (SYn).
CAUTION
Check that the motor will withstand this current without overheating.
Failure to follow this instruction can res u lt in equipment damage.
tdCI
g
SdC2
g
tdC2
g
AdCSdC2Operation
YESx
Ct
Ct= 0
M [Auto DC inj. time 1]
Standstill injection time. This para meter can be accessed if [Auto DC injection] (AdC) page 136 is not [No] (nO)
If [Motor control type] (Ctt) page 66
maintenance time.
M [Auto DC inj. level 2]
2nd level of standstill DC injection current.
This parameter can be accessed if [Auto DC injection] (AdC) page 136
This parameter is forced to 0 if [Motor control type] (Ctt) page 66
M [Auto DC inj. time 2]
2nd standstill injection time.
This parameter can be accessed if [Auto DC injection] (AdC) page 136
I
SdC1
SdC2
≠ 0
I
SdC1
SdC2
I
SdC1
0.1 to 30 s0.5 s
= [FVC] (FUC) or [Sync. mot.] (SYn) this time corresponds to the zero speed
0 to 1.2 In (1)0.5 In (1)
is not [No] (nO)
= [Sync. mot.] (SYn).
CAUTION
Check that the motor will withstand this current without overheating.
Failure to follow this instruction can res u lt in equipment damage.
0 to 30 s0 s
= [Yes] (YES)
Note: When [Moto r control type] (Ctt) page 66
= [FVC] (FUC):
[Auto DC inj. level 1] (SdC1), [Auto DC inj.
level 2] (SdC2) and [Auto DC inj. time 2]
tdC1tdC1 + tdC2
tdC1
t
t
(tdC2) are not accessible. Only [Auto DC inj.
time 1] (tdC1) can be accessed. This then
corresponds to a zero speed maintenance
time.
t
Run command
Speed
(1)In corresponds to the rated drive current indicated in the Installation Manual or on the drive nameplate.
Switching frequency setting.
Adjustment range: This can vary between 1 and 16 kHz, but the minimum and maximum values, as well as
the factory setting, can be limited in accordance with the type of drive (MT Series ), the rating and the
configuration of the [Sinus filter](OFI) and [Motor surge limit] (SUL) parameters, page 77
-
According to ratingAccording to rating
.
CLI
CL2
g
If the value is less than 2 kHz, [Current Limitation] (CLI) and[I Limit. 2 value] (CL2) page 56
1.36 In.
Adjustment with drive running:
- If the initial value is less than 2 kHz, it is not possible to increase it above 1.9 kHz while running.
- If the initial value is greater than or equal to 2 kHz, a minimum of 2 kHz must be maintai ned while running.
Adjustment with the drive stopped: No restrictions.
Note: In the event of excessive temperature rise, the drive will automatically reduce the switching
frequency and reset it once the temperature returns to normal.
Note: If [Motor control type] (Ctt) page 66
frequency to a value less than 2 kHz (in order to avoid speed instability).
.
= [FVC] (FUC), we do not recommend setting the switching
CAUTION
On MT401 to MT405, drives, if the RFI filters are disconnected (operation on an IT system), the drive's
switching frequency must not exceed 4 kHz.
Failure to follow this instruction can result in equipment damage.
M [Current Limitation]
Used to limit the motor current.
The adjustment range is limited to 1.36 In if [Switching freq.] (SFr) page 56
Note: If the setting is less than 0.25 In, the driv e may lock in [Out put Phase Loss ](OPF) fault mode if
this has been enabled (see page 214
has any effect.
M [I Limit. 2 value]
See page 181
The adjustment range is limited to 1.36 In if [Switching freq.] (SFr) page 56 is less than 2 kHz.
Note: If the setting is less than 0.25 In, the driv e may lock in [Out put Phase Loss ](OPF) fault mode if
this has been enabled (see page 214
has any effect.
). If it is less than the no-load motor c urrent, the limitation no longer
). If it is less than the no-load motor c urrent, the limitation no longer
0 to 1.65 In (1)1.5 In (1)
is less than 2 kHz.
0 to 1.65 In (1)1.5 In (1)
are limited to
(1)In corresponds to the rated drive current indicated in the Installation Manual or on the drive nameplate.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
g
56
also be accessed and adjusted from within the configura tion menu for the c orresponding fu nction, their descri ption is deta iled
in these menus, on the pages indicated, to aid programming.
v [Not cont.] (FnC): Non-continuous mode
v [Continuous] (FCt): Continuous mode. This option is not possible if [Auto DC injection] (AdC) page 136 is
[Yes] (YES) or if [Type of stop] (Stt) page 134
v [No] (FnO): Function inactive This option is not possible if [Motor control type] (Ctt) page 66 = [SVCI] (CUC)
or[FVC] (FUC).
If [Motor control type] (Ctt) page 66
replaced by [Not cont.] (FnC).
In order to obtain rapid high torque on startup, magnetic flux nee ds to already have been established in the
motor.
•In [Continuous] (FCt) mode, the drive automatically builds up flux when it is powered up.
•In [Not cont.] (FnC) mode, fluxing occurs when the motor starts up.
The flux current is greater than nCr (configured rated motor current) when the flux is established and is then
adjusted to the motor magnetizing current...
-
[No] (FnO)
is [Freewheel] (nSt).
= [SVCI] (CUC), [FVC] (FUC) or [Sync. mot.] (SYn) the factory setting is
CAUTION
Check that the motor will withstand this current without overheating.
Failure to follow this instruction can result in equipment damage.
If [Motor control type] (Ctt) page 66
alignment of the rotor and not the fluxing.
If [Brake assignment] (bLC) page 154
tLS
JGF
g
JGt
g
(1)In corresponds to the rated drive current indicated in the Installation Manual or on the drive nameplate.
M [Low speed time out]
Maximum operating time at [Low speed](LSP) (see page 40)
Following operation at LSP for a defined period, a motor stop is request ed automatically. The mot or will restart
if the reference is greater than LSP and if a run comman d is still present.
Caution: A value of 0 indicates an unlimited period of time.
Note: If [Low speed time out]
(only if a ramp stop can be configured).
M [Jog frequency]
See page 138
Reference in jog operation
M [Jog delay]
See page 138
Anti-repeat delay between 2 consecutive jog operations.
= [Sync. mot.] (SYn), the [Motor fluxing](FLU) parameter causes the
is not [No] (nO), the [Motor fluxing](FLU) parameter has no effect.
0 to 999.9 s0 s
(tLS) is not 0, [Type of stop](Stt) page 134 is forced to [Ramp stop] (rMP)
0 to 10 Hz10 Hz
0 to 2.0 s0.5 s
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
g
also be accessed and adjusted from within the configura tion menu for the c orresponding fu nction, their descri ption is deta iled
in these menus, on the pages indicated, to aid programming.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
g
58
also be accessed and adjusted from within the configura tion menu for the c orresponding fu nction, their descri ption is deta iled
in these menus, on the pages indicated, to aid programming.
Multiplying coefficient, can be accessed if [Multiplier ref.-] (MA2,MA3) page 130 has been assigned to the
graphic terminal
M [+/-Speed limitation]
See page 145
Limitation of +/- speed variation
M [PID prop. gain]
See page 170
Proportional gain
M [PID integral gain]
See page 171
Integral gain
M [PID derivative gain]
See page 171
Derivative gain
M [PID ramp]
See page 171
PID acceleration/deceleration ramp, defined to go from [Min PID reference] (PIP1) to [Max PID reference]
(PIP2) and vice versa.
M [Min PID output]
See page 171
Minimum value of regulator output in Hz
M [Max PID output]
See page 171
Maximum value of regulator output in Hz
M [Min fbk alarm]
See page 171
Minimum monitoring threshold for regulator feedback
M [Max fbk alarm]
See page 171
Maximum monitoring threshold for regulator feedback
0 to 1600 Hz90 Hz
0 to 1600 Hz100 Hz
0 to 100%100%
0 to 50%10%
0.01 to 1001
0.01 to 1001
0.00 to 1000
0 to 99.9 s0
- 500 to 500 or -1600
to 1600 according to
rating
0 to 500 or 1600
according to rating
See page 171 (1)100
See page 171 (1)1000
0 Hz
60 Hz
(1)If a graphic display terminal is not in use, values greater than 9999 will be displayed on the 4-digit display with a period mark after the
thousand digit, e.g., 15.65 for 15650.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
g
also be accessed and adjusted from within the configura tion menu for the c orresponding fu nction, their descri ption is deta iled
in these menus, on the pages indicated, to aid programming.
See page 172
Multiplying coefficient for predictive speed input.
M [Preset ref. PID 2]
See page 174
Preset PID reference
M [Preset ref. PID 3]
See page 174
Preset PID reference
M [Preset ref. PID 4]
See page 174
Preset PID reference
M [Brake release I FW]
See page 154
Brake release current threshold for lifting or forward movement
M [Brake release I Rev]
See page 154
Brake release current threshold for lowering or reverse movement
M [Brake Release time]
See page 155
Brake release time dela y
M [Brake release freq]
See page 155
Brake release frequency threshold
M [Brake engage freq]
See page 155
Brake engage frequency threshold
M [Brake engage delay]
See page 155
Time delay before request to engage brake. To delay the engaging of the brake, for horizontal movement only, if
you wish the brake to engage when the drive comes to a complete stop.
0 to 65535 (1)100
1 to 100%100%
See page 174 (1)300
See page 174 (1)600
See page 174 (1)900
0 to 1.32 In (2)0
0 to 1.32 In (2)0
0 to 5.00 s0 s
[Auto](AUtO)
0 to 10 Hz
[Auto](AUtO)
0 to 10 Hz
0 to 5.00 s0 s
[Auto](AUtO)
[Auto](AUtO)
(1)If a graphic display terminal is not in use, values greater than 9999 will be displayed on the 4-digit display with a period mark after the
thousand digit, e.g., 15.65 for 15650.
(2)In corresponds to the rated drive current indicated in the Installation Manual or on the drive nameplate.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
g
60
also be accessed and adjusted from within the configura tion menu for the c orresponding fu nction, their descri ption is deta iled
in these menus, on the pages indicated, to aid programming.
See page 155
Brake engage time (brake response time)
M [Jump at reversal]
See page 156
M [Time to restart]
See page 156
Time between the end of a brake engage sequence and the start of a brake release sequence
M [Motoring torque lim]
See page 179
Torque limitation in generator mode, as a % or in 0.1% incremen ts of the rate d torq ue in accorda nce with the
[Torque increment](IntP) parameter, page 179
M [Gen. torque lim]
See page 179
Torque limitation in generator mode, as a % or in 0.1% increments of the rated torque in accordance with the
[Torque increment](IntP) parameter, page 179
M [Traverse freq. high]
See page 202
0 to 5.00 s0 s
[Auto](AUtO)
0 to 10 Hz
0 to 5.00 s0 s
0 to 300%100%
.
0 to 300%100%
.
0 to 10 Hz4 Hz
[Auto](AUtO)
trL
g
qSH
g
qSL
g
Ctd
ttH
ttL
(1)In corresponds to the rated drive current indicated in the Installation Manual or on the drive nameplate.
M [Traverse freq. low]
See page 202
M [Quick step High]
See page 202
M [Quick step Low]
See page 202
M [Current threshold]
Current threshold for [I attained](CtA) function assigned to a re lay or a logic output (see page 97).
M [High torque thd.]
High current threshold for [High tq. att.](ttHA) function assigned to a relay or a logic output (see page 97), as
a % of the rated motor torque.
M [Low torque thd.]
Low current threshold for [Low tq. att.](ttLA) function assigned to a relay or a logic o utp ut (see page 97), a s a
% of the rated motor torque.
0 to 10 Hz4 Hz
0 to [Traverse freq.
high](trH)
0 to [Traverse freq.
low](trL)
0 to 1.5 In (1)In (1)
-300% to +300%100%
-300% to +300%50%
0 Hz
0 Hz
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
g
also be accessed and adjusted from within the configura tion menu for the c orresponding fu nction, their descri ption is deta iled
in these menus, on the pages indicated, to aid programming.
Speed threshold measured by the FREQUENCY METER]FqF-) function, page 225, assigned to a relay or a
logic output (see page 97
M [Freq. threshold]
Frequency threshold for [Freq.Th.att.](FtA) function assigned to a relay o r a logic output (see page 97), or used
by the [PARAM. SET SWITCHING] (MLP-) function, page 192
M [Freq. threshold 2]
Frequency threshold for [Freq. Th. 2 attain.](F2A) function assigned to a relay or a logic output (see page 97),
or used by the [PARAM. SET SWITCHING] (MLP-) function, page 192
M [Freewheel stop Thd]
See page 134
This parameter supports switching from a ramp stop or a fast stop to a freewheel stop below a low speed
threshold.
It can be accessed if [Type of stop] (Stt) = [Fast stop] (FSt) or [Ramp stop] (rMP).
v 0.0: Does not switch to freewheel stop.
v 0,1 to 1600 Hz: Speed threshold below w h ich the motor will switch to freewheel stop.
M [Motor therm. level]
See page 214
Trip threshold for motor thermal alarm (logic output or relay)
0 Hz to 30.00 kHz0 Hz
).
0.0 to 1600 Hz[High speed] (HSP)
.
0.0 to 1600 Hz[High speed] (HSP)
.
0.0 to 1600 Hz0.0 Hz
0 to 118%100%
LbC
g
M [Load correction]
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configura tion menu for the c orresponding fu nction, their descri ption is deta iled
in these menus, on the pages indicated, to aid programming.
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
MAIN MENU
ENT
With integrated display keypad:
Power-up
Displays the state of the drive
XXX
ENT
ESC
SIM-
RDYTerm +0.00Hz0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
Code<<>>Quick
ENT
RUNTerm+50.00Hz 80A
1.4 MOTOR CONTROL
Standard mot. freq
Rated motor power
Rated motor volt.
Rated mot. current
Rated motor freq.
Code<<>>Quick
ESC
ESC
ESC
drC-
I-O-
LAC-
ENT
ESC
MOTOR CONTROL
63
Page 63
[1.4 MOTOR CONTROL]
(
drC
)
The parameters in the [1.4 MOTOR CONTROL](drC-) menu can only be modified when the drive is stopped and no run command is
present, with the following exceptions:
Tin the code column, which can be modified with the drive running or stopped.
-
bFr
nPr
UnS
nCr
FrS
M [Standard mot. freq]
50
60
v [50Hz IEC](50): IEC
v [60Hz NEMA](60) : NEMA
This parameter modifies the presets of the following paramete rs: [High speed](HSP) page 40
(Ftd) page 62
M [Rated motor power]
The parameter cannot be accessed if [Motor control type](Ctt) page 66 = [Sync. mot.](SYn).
Rated motor power given on the nameplate, in HP if [Standard mot. freq] (bFr) = [60Hz NEMA](60), in KW if
The parameter cannot be accessed if [Motor control type](Ctt) page 66 = [Sync. mot.](SYn).
Rated motor voltage given on the nameplate.
MT2
ppp : 100 to 240 V
MT4
ppp : 200 to 480 V
M [Rated mot. current]
The parameter cannot be accessed if [Motor control type](Ctt) page 66 = [Sync. mot.](SYn).
Rated motor current given on the nameplate.
M [Rated motor freq.]
The parameter cannot be accessed if [Motor control type](Ctt) page 66 = [Sync. mot.](SYn).
Rated motor frequency given on the nameplate.
The factory setting is 60 Hz, or preset to 50 Hz if [Standard mot. freq] (bFr) is set to 50 Hz.
The maximum value is limited to 500 Hz if [Motor co ntrol type] (Ctt ) (page 66
higher than MT450
Values between 500 Hz and 1600 Hz are only possible in V/F control and for powers limited to 37 kW (50 HP).
In this case configure [Motor control type] (Ctt) before [Rated motor freq.] (FrS).
[60Hz Nema](60)
, [Rated motor volt.](UnS), [Rated motor freq.] (FrS) and [Max frequency] (tFr).
According to drive
rating
According to drive
rating
0.25 to 1.5 In (1)According to drive
10 to 1600 Hz60 Hz
) is not V/F or if the drive rating is
According to drive
rating
According to drive
rating and [Standard
mot. freq] (bFr)
rating and [Standard
mot. freq] (bFr)
, [Freq. threshold]
InSP
nSP
(1)In corresponds to the rated drive current indicated in the Installation Manual and on the drive nameplate.
64
M [rpm increment]
Increment of parameter [Rated motor speed](nSP).
1
10
v [x1 rpm](1): Increment of 1 rpm, to be used if [Rated motor speed](nSP) does not exceed 65535 rpm.
v [x10 rpm](10) : Increment of 10 rpm, to be used if [Rated motor speed](nSP) exceeds 65535 rpm.
M [Rated motor speed]
The parameter cannot be accessed if [Motor control type](Ctt) page 66 = [Sync. mot.](SYn).
Rated motor speed given on the nameplate. Adjustable between 0 and 65535 rpm i f [rpm increment] (InSP) =
[x1 rpm](1) or between 0.00 and 96.00 krpm if [rpm increment](InSP) = [x10 rpm](10).
0 to 9999 rpm then 10.00 to 65.53 or 96.00 krpm on the integrated display termi nal.
If, rather than the rated speed, the nameplate indicates the sy nchronous speed and the slip in Hz or as a %,
calculate the rated speed as follows:
• Nominal speed = Synchronous speed x
or
• Nominal speed = Synchronous speed x (50 Hz motors)
or
• Nominal speed = Synchronous speed x (60 Hz motors)
[x1 rpm](1)
Note: Changing [rpm increment](InSP) will restore [Rated motor speed](nSP) to its factory setting.
The factory setting is 72 Hz, or preset to 60 Hz if [Standard mot. freq] (bFr) is set to 50 Hz.
The maximum value is limited by the following conditions:
• It must not exceed 10 times the value of [Rated motor freq.] (FrS)
• It must not exceed 500 Hz if [Motor control type] (Ctt) (page 66
MT450
Values between 500 Hz and 1600 Hz are only possible in V/F control and for powers limited to 37 kW
(50 HP). In this case configure [Motor control type] (Ctt) before [Max frequenc y] (tFr).
M [Auto tuning]
) is not V/F or if the drive rating is higher th an
10 to 1600 Hz
[No] (nO)
v [No] (nO): Auto-tuning not performed.
v [Yes] (YES): Auto-tuning is performed as soon as possible, then the parameter automatically changes to [Done]
(dOnE).
v [Done] (dOnE) : Use of the values given the last time auto-tuning was performed.
Caution:
• It is essential that all the motor parameters are correctly configured before starting auto-tuning.
- Induction motor: [Rated motor volt.](UnS), [Rated motor freq.] (FrS), [Rated mot. current] (nCr), [Rated
motor speed] (nSP), [Rated motor power] (nPr)
- Synchronous motor: [Nominal I sync.] (nCrS), [Nom motor spdsync] (nSPS), [Pole pairs] (PPnS), [Syn.
EMF constant] (PHS), [Autotune L d-axis] (LdS), [Autotune L q-axis] (LqS)
If one or more of these parameters is modified after auto-tuning has been performed, [Auto tuning] (tUn) will
return to [No] (nO) and the procedure must be repeated.
• Auto-tuning is only performed if no stop command has been activated. If a "freewheel stop" or "fast stop"
function has been assigned to a logic input, this input must be set to 1 (active at 0).
• Auto-tuning takes priority over any run or prefluxing commands, which will be taken into account after the
auto-tuning sequence.
• If auto-tuning fails, the drive displays [No] (nO) and, depending on the configuration of [Autotune fault mgt]
(tnL) page 228
• Auto-tuning may last for 1 to 2 seconds. Do not interrupt the process. Wait for the display to cha nge to
"[Done] (dOnE)" or "[No] (nO)".
, may switch to [Auto-tuning] (tnF) fault mode.
AUt
tUS
PEnd
PrOG
FAIL
dOnE
PHr
nO
YES
tAb
CUS
AbC
ACb
Note: During auto-tuning the motor operates at rated current.
M [Automatic autotune]
[No] (nO)
v [No] (nO): Function inactive
v [Yes] (YES): Auto-tuning is performed on every power-up.
Caution: Same comments as for [Auto tuning] (tUn) above.
M [Auto tuning state]
For information only, cannot be modified.
[Not done] (tAb)
v [Not done] (tAb): The default stator resistance value is used to control the motor.
v [Pending] (PEnd): Auto-tuning has been requested but not yet performed.
v [In Progress] (PrOG): Auto-tuning in progress
v [Failed] (FAIL): Auto-tuning has failed.
v [Done] (dOnE) : The stator resistance measured by the auto-tuning function is used to control the motor.
v [Customized] (CUS): Auto-tuning has been performed, but at least one parameter set by this auto-tuning
operation has subsequently been modified. The [Auto tuning] (tUn) parameter then returns to [No] (nO). The
following auto-tuning parameters are affected:
v [SVC V] (UUC): Open-loop voltage flux vector control. It supports operation with a number of motors
connected in parallel on the same drive.
v [SVC I] (CUC): Open-loop current flux vector control. This type of control is re commended when replacing an
ATV58F used in an open-loop configuration. It does not support operation with a number of motors connected
in parallel on the same drive.
v [FVC] (FUC) : Closed-loop current flux vector control for motor wi th incremental encoder type sensor, can only
be selected if an encoder card has been inserted. This type of control is recommended when using in a closedloop configuration. It provides better performance in terms of spee d and torque accuracy and enables torque
to be obtained at zero speed. It does not support operation with a number of motors connected in parallel on
the same drive.
It is essential that the encoder check page 73
(FUC).
is performed successfully before selecting [FVC]
v [V/F 2pts] (UF2): Simple V/F profile without slip compensation. It supports operation with:
- Special motors (wound rotor, tapered rotor, etc.)
- A number of motors in parallel on the same drive
- High-speed motors
- Motors with a low power rating in comparison to that of the drive
Voltage
UnS
The profile is defined by
the values of parameters
UnS, FrS and U0.
UF5
SYn
U0
Frequency
FrS
v [V/F 5pts] (UF5): 5-segment V/F profile: As V/F 2 pts profile but also supports the avoidance of resonance
(saturation).
Voltage
UnS
U5
The profile is defined
U4
U3
U1
U2
U0
F1F2
F3
F4 F5
FrS
by the values of
parameters UnS, FrS,
U0 to U5 and F0 to F5.
FrS > F5 > F4 > F3 > F2 > F1
Frequency
v [Sync. mot.] (SYn): For synchronous permanent magnet motors with sinusoidal electromotive force (EMF)
only. This selection makes the Induction motor parameters inaccessible, and the synchronous motor
parameters accessible
The parameter can be accessed if [Motor control type] (Ctt) is not [Sync. mot.] (SYn).
v [No] (nO): Function inactive
v [Yes] (YES): Function active.
Used in applications in which the motor rated speed and frequency need to be exceeded in order to optimize
operation at constant power, or when the maximum voltage of the motor needs to be limited to a value below
the line voltage.
The voltage/frequency profile must then be adapted in accordance with the motor's capabilities to operate at
maximum voltage UCP and maximum frequency FCP.
Motor voltage
Max. voltage UCP
Rated motor volt. UnS
M [V. constant power]
The parameter can be accessed if [Vector Control 2pt] (UC2) = [Yes] (YES)
M [Freq. Const Power]
The parameter can be accessed if [Vector Control 2pt] (UC2) = [Yes] (YES)
Rated motor freq.
Frequency
Freq. Const Power FCP
According to drive
rating
According to drive
rating and [Rated
motor freq.] (FrS)
[No] (nO)
According to drive
rating and [Standard
mot. freq] (bFr)
= [Standard mot. freq]
(bFr)
68
Page 68
[1.4 MOTOR CONTROL]
(
drC
)
-
Synchronous motor parameters:
These parameters can be accessed if [Motor control type](Ctt) page 66 = [Sync. mot.](SYn). In this case, the Induction motor parameters
cannot be accessed.
Rated synchronous motor current given on the nameplate.
M [Nom motor spdsync]
Rated motor speed given on the nameplate.
On the integrated display unit: 0 to 9999 rpm then 10.00 to 60.00 krpm.
M [Pole pairs]
Number of pairs of poles on the synchronous motor.
M [Syn. EMF constant]
Synchronous motor EMF constant, in mV per rpm (peak voltage per phase).
On the integrated display unit: 0 to 9999 then 10.00 to 65.53 (10000 to 65536).
M [Autotune L d-axis]
Axis "d" stator inductance in mH (per phase).
On motors with smooth poles [Autotune L d-axis](LdS) = [Autotune L q-axis](LqS) = Stator inductance L.
M [Autotune L q-axis]
Axis "q" stator inductance in mH (per phase).
On motors with smooth poles [Autotune L d-axis](LdS) = [Autotune L q-axis](LqS) = Stator inductance L.
M [Cust. stator R syn]
Cold state stator resistance (per winding) The factory setting is replaced by the result of the auto-tuning
operation, if it has been performed.
The value can be entered by the user, if he knows it.
Value in milliohms (m
On the integrated display unit: 0 to 9999 then 10.00 to 65.53 (10000 to 65536).
Ω) up to 75 kW (100 HP), in hundredths of milliohms (mΩ/100) above 75 kW (100 HP).
(1)The parameter can also be accessed in the [1.3 SETTINGS] (SEt-) menu.
(2)In corresponds to the rated drive current indicated in the Installation Manual and on the drive nameplate.
T
M [IR compensation]
The parameter can be accessed if [Motor control type] (Ctt) is not [V/F 2pts] (UF2) and [V/F 5pts] (UF5).
Used to optimize the torque at very low speed (increase [IR compensation](UFr) if the torque is insufficient).
Check that the [IR compensation] (UFr) value is not to o high when t he motor is warm (risk of i nstabili ty).
M [Slip compensation]
The parameter can be accessed if [Motor control type] (Ctt) is not [V/F 2pts] (UF2), [V/F 5pts] (UF5) and
[Sync. mot.](SYn).
Adjusts the slip compensation around the value set by the rated motor speed.
The speeds given on motor nameplates are not necessarily exact.
• If slip setting < actual slip: The motor is not rotating at the correct speed in steady state, but at a speed lower
than the reference.
• If slip setting > actual slip: The motor is overcompensated and the speed is unstable.
Parameter that can be modified during operation or when stopped.
Cold state stator resistance (per winding), in read-only mode. This is the drive factory setting or the result
of the auto-tuning operation, if it has been performed.
Value in milliohms (m
On the integrated display unit: 0 to 9999 then 10.00 to 65.53 (10000 to 65 536).
M [Nominal freq sync.]
Motor frequency at rated speed in Hz, calculated by the drive (rated motor frequency), in read-only mode.
Ω) up to 75 kW (100 HP), in hundredths of milliohms (mΩ/100) above 75 kW (100 HP).
Check encoder feedback See the procedure below.
The parameter can be accessed if an encoder card has been inserted (1).
nO
v [Not done] (nO) Check not performed.
v [Yes] (YES): Activates monitoring of the encoder.
v [Done] (dOnE) : Check performed successfully.
The check procedure checks:
- The direction of rotation of the encoder/motor
- The presence of signals (wiring continuity)
- The number of pulses/revolution
If a fault is detected, the drive locks in [Encoder fault](EnF) fault mode.
M [Encoder usage]
The parameter can be accessed if an encoder card has been inserted (1).
nO
v [No] (nO): Function inactive
v [Fdbk monit.] (SEC): The encoder provides speed fe edback for monitoring only.
v [Spd fdk reg.] (rEG): The encoder provides speed feedback for regulation and monitoring. This
configuration is automatic if the drive is configured for closed-loop operation ([Motor co ntrol type] (Ctt) = [FVC]
(FUC). If [Motor control type] (Ctt) = [SVC V] (UUC) the encoder operates in speed feedback mode and enables
static correction of the speed to be performed. Th is configuration is not accessible f or other [Motor control type]
(Ctt) values.
v [Speed ref.] (PGr) : The encoder provides a reference.
≈ 15% of the rated speed for at least 3 seconds, and use the [1.2-MONITORING](SUP-) menu
.
) or the encoder signals.
[Not done] (nO)
[No] (nO)
(1)The encoder parameters can only be accessed if the encoder card has been inserted, and the available selections will depend on the
type of encoder card used. The encoder configuration can also be accessed in the [1.5- INPUTS / OUTPUTS CFG] (I/O) menu.
ENA SYSTEM is a control profile designed for rotating machines with unbal anced load.
It is used primarily for oil pumps. The operating principle applied:
- Allows operation without a braking resistor
- Reduces mechanical stress on the motor shaft
- Reduces line current fluctuations
- Reduces energy consumption by improving the electric power/current ratio
Beam pumps
[ENA prop.gain]
This setting is used to achieve a compromise between the reduced energy consumption (and/or line current fluctuations) and the
mechanical stress to which the motor shaft is subject.
Energy is saved by reducing current fluctuations and increasing the current while retaining the same average speed.
[ENA integral gain]
This setting is used to smooth the DC bus voltage.
Start up the machine with a low integral and proportional gain (proportional 25% and integral 10%) in order to avoid an overvoltage trip in
the absence of a braking resistor. See if these settings are suitable.
Recommended adjustments to be made during operation:
• To eliminate the braking resistor and, therefore, the increase in the DC bus voltage:
Display the machine speed on the graphic display keypad.
Reduce the integral gain value until the machine speed dr ops. When this point is reached, increase the int egral gain until the machine
speed stabilizes.
Use the graphic display keypad or an oscilloscope to check that the DC bus voltage is stable.
• To save energy:
Reducing the proportional gain (gradually) may increase energy savings by reduci ng the maximum value of the line current, but it will
increase speed variations and, therefore, mechanical stress.
The aim is to identify settings that will enable energy to be saved and minimize mechanical stress.
When reducing the proportional gain, it may be necessary to readjust t he integral gain in order to avoid an overvoltage trip.
Note: Once the adjustments are complete, check that t he pump starts up correctly. I f the ENA inte gral gain sett ing is to o low, this may lead
to insufficient torque on startup.
[Reduction ratio]
This setting corresponds to the motor speed ahead of gearbox/speed after gearbox ratio. This parameter is used to display the average
speed in Hz and the machine speed in customer units (e.g., in strokes per minute) on the graphic display keypad. In order to be displayed
on the graphic display, these values must be selected in the [1.2 MONITORING](SUP-) menu.
v [No] (nO): No filter
v [Yes] (YES): Use of a filteror an AC reactor on the output of the drive , to li mi t ove rvol tages on t he mo tor an d
reduce the ground fault leakage current.
[Sinus filter](OFI) is forced to [No] (nO) on MT2P5 and MT401.
Note: The sett ings for [Current Limitation] (CL I) and [I Limit. 2 value] (CL2) page 56
[Sinus filter](OFI) has been se t to [Yes](YES) and [Motor control type] (Ctt) page 66
F 2pts] (UF2) or [V/F 5pts] (UF5). This is due to the fact that for certain ratings, this configuration will
result in a reduced factory setting (1.36 In) for current limitations.
must be made once
has been set to [V/
CAUTION
If [Sinus filter](OFI) = [Yes](YES), [Motor control type] (Ctt) page 66 must be [V/F 2pts] (UF2), [V/F 5pts] (UF5),
or[SVC V] (UUC) only, and [Max frequency] (tFr) must not exceed 100 Hz.
Failure to follow this instruction can result in equipment damage.
M [Switching freq.]
Switching frequency setting.
Adjustment range: This can vary between 1 and 16 kHz, but the minimum and maximum values, as well as
the factory setting, can be limited in accordance with the type of drive (MT Series or W), the rating and the
configuration of the [Sinus filter](OFI) and [Motor surge limit] (SUL) parameters, page 77
If the value is less than 2 kHz, [Current Limitation] (CLI) and[I Limit. 2 value] (CL2) page 56
1.36 In.
Adjustment with drive running:
- If the initial value is less than 2 kHz, it is not possible to increase it above 1.9 kHz while running.
- If the initial value is greater than or equal to 2 kHz, a minimum of 2 kHz must be maintai ned while running.
Adjustment with the drive stopped: No restrictions.
(1)According to ratingAccording to rating
.
are limited to
Note: In the event of excessive temperature rise, the drive will automatically reduce the switching
frequency and reset it once the temperature returns to normal.
Note: If [Motor control type] (Ctt) page 66
frequency to a value less than 2 kHz (in order to avoid speed instability).
= [FVC] (FUC), we do not recommend setting the switching
CAUTION
On MT401 to MT405, drives, if the RFI filters are disconnected (operation on an IT system), the drive's
switching frequency must not exceed 4 kHz.
Failure to follow this instruction ca n result in equipment damage.
CLI
T
(1)The parameter can also be accessed in the [1.3 SETTINGS] (SEt-)menu.
(2)In corresponds to the rated drive current indicated in the Installation Manual and on the drive nameplate.
T
M [Current Limitation]
Used to limit the motor current.
The adjustment range is limited to 1.36 In if [Switching freq.] (SFr) is less than 2 kHz.
Note: If the setting is less than 0.25 In, the driv e may lock in [Out put Phase Loss ](OPF) fault mode if
this has been enabled (see page 214
has any effect.
Parameter that can be modified during operation or when stopped.
(1)0 to 1.65 In (2)1.5 In (2)
). If it is less than the no-load motor c urrent, the limitation no longer
v [No] (nO): Fixed frequency. Factory setting at and above 55 kW (75 HP) and at and above 90 kW (125 HP)
v [Yes] (YES): Frequency with random modulation. Factory setting up to 45 kW (60 HP) and up to 75 kW (100
HP)
Random frequency modulation prevents any resonance, which may occur at a fi xed frequency.
M [Motor surge limit.]
This function limits motor overvoltages and is useful in the following applications:
-NEMA motors
- Japanese motors
- Spindle motors
- Rewound motors
[No] (nO)
v [No] (nO) : Function inactive
v [Yes] (YES) : Function active
This parameter is forced to [No](nO) if [Sinus filter](OFI) previous page = [Yes](YES).
This parameter can remain = [No](nO) for 230/40 0 V mot ors used at 2 30 V, orif the length of cable between
the drive and the motor does not exceed:
- 4 m with unshielded cables
- 10 m with shielded cables
M [Volt surge limit. opt]
Optimization parameter for transient overvoltages at the motor terminals. Can be accessed if [Motor surge
limit.] (SUL) = [Yes] (YES).
Set to 6, 8, or 10
µs, according to the following table.
10 µs
The value of the "SOP" parameter corresponds to the attenuation time of the cable used. It is defined to prevent the superimposition of
voltage wave reflections resulting from long cable lengths. It limits overvoltages to twice the DC bus rated voltage.
The tables on the following page give examples of correspo ndence be tween th e "SOP" parameter and the l ength of t he cabl e between the
drive and the motor. For longer cable lengths, a sinusoidal fil ter or a dV/dt protection filter must be used.
• For motors in parallel, the sum of all the cable lengths must be taken into consideration. Compare the length given in the table row
corresponding to the power for one motor with that corresponding to the total power, and select the shorter length. Example: Two
7.5 kW (10 HP) motors - take the lengths on the 15 kW (20 HP) table row, which are shorter than those on the 7.5 kW (10 HP) row,
and divide by the number of motors to obtain the length per motor (with unshielded "GORSE" cable and SOP = 6, the result is
40/2 = 20 m maximum for each 7.5 kW (10 HP) motor).
In special cases (for example, different types of cable, different motor powers in parallel, different cable lengths in parallel, etc.), we
recommend using an oscilloscope to check the overvoltage values obtained at the motor terminals.
To retain the overall drive performance, do not increase the SOP value unnecessarily.
DC bus voltage threshold above which the braking transistor cuts in to limit this voltage.
MT2: factory setting 395 V.
MT4: factory setting 785 V.
The adjustment range depends on the voltage rating of the drive and the [Mains voltage] (UrES) parameter,
page 218
M [Braking balance]
nO
v [No] (nO) : Function inactive
v [Yes] (YES) : Function active, to be used on drives connected in parallel via their DC bus. Used to balance
the braking power between the drives. The [Braking level] (Ubr) parameter must be set to the same value on
the various drives.
The value[Yes] (YES) is possible only if [Dec ramp adapt.] (brA) = [No] (nO) (see page 133
.
-
According to drive
voltage rating
[No] (nO)
)
LbA
LbC
T
nO
YES
M [Load sharing]
When 2 motors are connected mechanically and therefor e at the same speed, and each is controlled by a drive,
this function can be used to improve torque distri bution between the two mo tors. To do this, it varies the speed
based on the torque.
v [No] (nO) : Function inactive
v [Yes] (YES) : Function active
The parameter can only be accessed if [Motor control type] (Ctt) page 66
(UF5).
M [Load correction]
Rated correction in Hz.
The parameter can be accessed if [Load sharing] (LbA) = [Yes] (YES)
Torque
Nominal torque
0
Nominal torque
[No] (nO)
is not [V/F 2pts](UF2) or [V/F 5pts]
(1)0 to 1000 Hz0
LbC
Frequency
LbC
(1)The parameter can also be accessed in the [1.3 SETTINGS] (SEt-)menu.
T
Parameter that can be modified during operation or when stopped.
The parameter can be accessed if [Load sharing] (LbA) = [Yes] (YES)
Minimum speed for load correction in Hz. Below this threshold, no corrections are made. Used to prevent
correction at very low speed if this would hamper rotation of the motor.
M [Correction max spd]
The parameter can be accessed if [Load sharing] (LbA) = [Yes] (YES)
Speed threshold in Hz above which maximum load correction is applied.
M [Torque offset]
The parameter can be accessed if [Load sharing] (LbA) = [Yes] (YES)
Minimum torque for load correction as a % of th e rated t orque. Below t his threshold, no c orrections are made.
Used to avoid torque instabilities when the torque direction is not constant.
M [Sharing filter]
The parameter can be accessed if [Load sharing] (LbA) = [Yes] (YES)
Time constant (filter) for correction in ms. Used in the even t of flexible mechanical coupling in order to avoid
instabilities.
Parameter that can be modified during operation or when stopped.
2-wire control: This is the input state (0 or 1) or edge (0 to 1 or 1 to 0), which controls running or stopping.
Example of "source" wiring:
3-wire control (pulse commands): A "forward" or "reverse" pulse is sufficient to command starting, a "stop"
pulse is sufficient to command stopping.
Example of "source" wiring:
UNINTENDED EQUIPMENT OPERATION
To change the assignment of [2/3 wire control] (tCC) press and hold down the “ENT” key for 2 s.
It causes the following functions to return to fac to ry sett i ng: [2 wire type] (tCt) and [R everse as sig n.]
(rrS) below, and all functions which assign logic inputs and anal og inputs.
The macro configuration selected will also be reset it if has been customized (loss of custom settings).
It is advisable to configure this parameter before configuring the [1.6 COMMAND] (CtL-) and [1.7
APPLICATION FUNCT.] (FUn-) menus.
Check that this change is compatible with the wiring diagram used.
Failure to follow these instructions can result in death or serious injury.
ATV 71
MT Series
+24 LI1 LIx
ATV 71
MT Series
+24 LI1 LI2 LIx
[2 wire] (2C)
LI1: forward
LIx: reverse
LI1: stop
LI2: forward
LIx: reverse
WARNING
tCt
LEL
trn
PFO
rrS
LI1
C101
Cd00
M [2 wire type]
v [Level] (LEL): State 0 or 1 is taken into account for run (1) or stop (0).
v [Transition] (trn): A change of state is necessary to init iate operation, in order to prevent accidental re starts
after a break in the power supply.
v [Fwd priority] (PFO): State 0 or 1 is taken into account for run or stop, but th e "forward" input alway s takes
priority over the "reverse" input.
M [Reverse assign.]
nO
v [No] (nO): Not assigned
v [LI1] (LI1) to [LI6] (LI6)
-
-
v [LI7] (LI7) to [LI10] (LI10): If MT-VW3A3201 logic I/O card has been inserted
v [LI11] (LI11) to [LI14] (LI14): If MT-VW3A3202 extended I/O card has been inserted
v [C101] (C101) to [C115] (C115): With integrated Modbus in [I/O profile] (IO)
-
-
-
v [C201] (C201) to [C215] (C215): With integrated CANopen in [I/O profile] (IO)
v [C301] (C301) to [C315] (C315): With a communication card in [I/O profile] (IO)
v [CD00] (Cd00) to [CD13] (Cd13): In [I/O profile] (IO) can be switched with possible logic inputs
v [CD14] (Cd14) to [CD15] (Cd15): In [I/O profile] (IO) can be switched without logic inputs
Read-only parameter, cannot be configured.
It displays all the functions that are assigned to input LI1 in order to check for multiple assignments.
M [LI1 On Delay]
This parameter is used to take account of the change of the logic input to st ate 1 with a delay that can be
adjusted between 0 and 200 milliseconds, in order to fil ter out possibl e interfe rence. The change to state 0
is taken into account without delay.
UNINTENDED EQUIPMENT OPERATION
Check that the delay set does not pose a risk or lead to undesired operation.
The relative order in which these inputs a re taken into account may be modified a ccording to the delay
values of the various logic inputs, and thus lead to unintended operation.
Failure to follow these instructions can result in death or serious injury.
b [LIx CONFIGURATION]
All the logic inputs available on th e d rive are p roc essed a s i n t he examp le fo r LI 1 a bove, u p t o L I6, LI1 0 o r
LI14, depending on whether or not option cards have been inserted.
The minimum and maximum input values (in volts, mA, etc.) are converted to % in order to adapt the references to the application.
Minimum and maximum input values:
The minimum value corresponds to a reference of 0% and the maximum value to a reference of 100%. The minimum value may be greater
than the maximum value:
erence
Reference
100%
Current or
voltage or
frequency
0%
[Min value]
(CrLx or
ULx or PIL)
For +/- bidirectional inputs, the min. and max. are relative to the absolute value, for example, +/- 2 to 8 V.
[Max value]
(CrHx or
UHx or PFr)
20 mA or
10 V or
30.00 kHz
input
100%
0%
[Max value]
(CrHx or
UHx or PFr)
[Min value]
ULx or PIL)
Negative min. value of Pulse input:
Reference
100%
Frequency
-30,00
kHz
[RP min
value]
(PIL)
0%
[RP max value]
(PFr)
30.00
kHz
input
(CrLx or
Current or
voltage or
frequency
input
20 mA or
10 V or
30.00 kHz
Range (output values): For analog inputs only
This parameter is used to configure the reference range to [0% V100%] or [-100% V +100%] in order to obtain a bidirectional output from
a unidirectional input.
This operation is the same as [ Standard] (bSd),
except that in the following cases at zero
reference, the frequency = 0:
• The signal is less than [Min value], which is
greater than 0 (example 1 V on a 2 - 10 V input)
• The signal is greater than [Min value], which is
greater than [Max value] (example 11 V on a
10 - 0 V input).
If the input range is configured as
"bidirectional", operation remains identical to
[Standard] (bSd).
This parameter defines how the speed reference is taken into account, for analog inputs and Pulse
input only. In the case of the PID regulator, this is the PID output reference.
The limits are set by the [Low speed] (LSP) and [High speed] (HSP) parameters, page 40
Read-only parameter, cannot be configured.
It displays all the functions associated with input AI1 in order to check, for example, for compatibility
problems.
M [AI1 Type]
v [Voltage] (10U): Positive voltage input (negative values are interpreted as zero: the input is
unidirectional).
v [Voltage +/-] (n10U): Positive and negative voltage input (the input is bidirectional).
M [AI1 min value]
M [AI1 max value]
M [AI1 filter]
Interference filtering.
M [AI1 Interm. point X]
Input delinearization point coordinate.
• 0% corresponds to [AI1 min value] (UIL1).
• 100% corresponds to [AI1 max value] (UIH1).
M [AI1 Interm. point Y]
Output delinearization point coordinate (frequency reference).
Read-only parameter, cannot be configured.
It displays all the functions associated with input AI2 in order to check, for example, for compatibility
problems.
M [AI2 Type]
v [Voltage] (10U): Voltage input
v [Current] (0 A): Current input
M [AI2 min value]
The parameter can be accessed if [AI2 Type] (AI2t) = [Current] (0 A)
M [AI2 min value]
The parameter can be accessed if [AI2 Type] (AI2t) = [Voltage] (10U)
M [AI2 max. value]
The parameter can be accessed if [AI2 Type] (AI2t) = [Current] (0 A)
M [AI2 max. value]
The parameter can be accessed if [AI2 Type] (AI2t) = [Voltage] (10U)
M [AI2 filter]
Interference filtering.
M [AI2 range]
v [0 - 100%] (POS): Unidirectional input
v [+/- 100%] (nEG): Bidirectional input
Example: On a 0/10 V input
- 0 V corresponds to reference -100%
- 5 V corresponds to reference 0%
- 10 V corresponds to reference + 100%
M [AI2 Interm. point X]
Input delinearization point coordinate.
• 0% corresponds to [Min value] if the range is 0
• 0% corresponds to if the range is -100%
[Max value] + [Min value]
[Current] (0 A)
0 to 20.0 mA0 mA
0 to 10.0 V0 V
0 to 20.0 mA20.0 mA
0 to 10.0 V10.0 V
0 to 10.00 s0 s
[0 - 100%] (POS)
0 to 100%0%
V 100%.
V
2
+ 100%.
• 100% corresponds to [Max value].
AI2S
M [AI2 Interm. point Y]
Output delinearization point coordinate (frequency reference).
Can be accessed if a MT-VW3A3202 option card has been inserted
M [AI3 assignment]
Read-only parameter, cannot be configured.
It displays all the functions associated with input AI3 in order to check, for example, for compatibility
problems.
M [AI3 Type]
Read-only parameter, cannot be configured.
v [Current] (0 A): Current input
M [AI3 min. value]
M [AI3 max. value]
M [AI3 filter]
Interference filtering.
M [AI3 range]
v [0 - 100%] (POS): Unidirectional input
v [+/- 100%] (nEG): Bidirectional input
Example: On a 4 - 20 mA input
- 4 mA corresponds to reference -100%
- 12 mA corresponds to reference 0%
- 20 mA corresponds to reference + 100%
Since AI3 is, in physical terms, a b idirectio nal i nput, the [+/- 100%] (nEG) configuration must only be us ed
if the signal applied is unidirectional. A bidirectional signal is not compatible with a bidirectional
configuration.
M [AI3 Interm. point X]
Input delinearization point coordinate.
• 0% corresponds to [Min value] (CrL3) if the range is 0
• 0% corresponds to if the range is -100%
[AI3 max. value] (CrH3) - [AI3 min. value]
(CrL3)
0 to 20.0 mA0 mA
0 to 20.0 mA20.0 mA
0 to 10.00 s0 s
0 to 100%0%
V 100%.
[Current] (0 A)
[0 - 100%] (POS)
V
+100%.
• 100% corresponds to [AI3 max. value] (CrH3).
AI3S
90
M [AI3 Interm. point Y]
Output delinearization point coordinate (frequency reference).
Can be accessed if a MT-VW3A3202 option card has been inserted
M [AI4 assignment]
Read-only parameter, cannot be configured.
It displays all the functions associated with input AI4 in order to check, for example, for compatibility
problems.
M [AI4 Type]
v [Voltage] (10U): Voltage input
v [Current] (0 A): Current input
M [AI4 min value]
The parameter can be accessed if [AI4 Type] (AI4t) = [Current] (0 A)
M [AI4 min value]
The parameter can be accessed if [AI4 Type] (AI4t) = [Voltage] (10U)
M [AI4 max value]
The parameter can be accessed if [AI4 Type] (AI4t) = [Current] (0 A)
M [AI4 max value]
The parameter can be accessed if [AI4 Type] (AI4t) = [Voltage] (10U)
M [AI4 filter]
Interference filtering.
M [AI4 range]
v [0 - 100%] (POS): Unidirectional input
v [+/- 100%] (nEG): Bidirectional input
Example: On a 0/10 V input
- 0 V corresponds to reference -100%
- 5 V corresponds to reference 0%
- 10 V corresponds to reference + 100%
M [AI4 Interm.point X]
Input delinearization point coordinate.
• 0% corresponds to [Min value] if the range is 0
• 0% corresponds to if the range is -100%
[Max value] + [Min value]
[Voltage] (10U)
0 to 20.0 mA0 mA
0 to 10.0 V0 V
0 to 20.0 mA20.0 mA
0 to 10.0 V10.0 V
0 to 10.00 s0 s
[0 - 100%] (POS)
0 to 100%0%
V 100%.
2
V + 100%.
• 100% corresponds to [Max value].
AI4S
M [AI4 Interm.point Y]
Output delinearization point coordinate (frequency reference).
Virtual input.
This parameter can also be accessed in the [PID REGULATOR] (PId-)submenu page 170
[No] (nO): Not assigned (in this case, the virtual input does not appear in the analog input assignment
parameters for the functions)
v [Modbus] (Mdb): Integrated Modbus
v [CANopen] (CAn): Integrated CANopen
v [Com. card] (nEt): Communication card (if inserted)
v [C.Insid. card] (APP): Not applicable
Scale: the value 8192 transmitted by this input is equiva lent to 10 V on a 10 V input.
UNINTENDED EQUIPMENT OPERATION
If the equipment switches to forced local mode (see page 234), the virtual input remains fix ed at the last
value transmitted.
Do not use the virtual input and forced local mode in the same configuration.
Failure to follow these instructions can result in death or serious injury.
Can be accessed if a MT-VW3A3202 option card has been inserted
M [RP assignment]
Read-only parameter, cannot be configured.
It displays all the functions associated with the Pulse In input in order to check, for example, for compatibility
problems.
Configuration of the encoder input serving as a reference with a frequency generator
This reference is not assigned, therefore the directions of opera tion must be given via the control channel (logic inputs, for example).
Minimum and maximum values (input values):
The minimum value corresponds to a minimum reference of 0% and the maximum value to a maximum reference of 100%. The minimum
value may be greater than the maximum value. It may also be negative.
erence
100 %
0
[Freq. min. value]
(EIL)
[Freq. max. value]
(EFr)
100 %
[Freq. min. value]
(EIL)
300 kHz
erence
0
Frequency
input
[Freq. max. value]
(EFr)
Reference
100 %
0
[Freq. max. value]
300 kHz
(EFr)
Frequency
input
[Freq. min. value]
(EIL)
Frequency
input
300 kHz
A reference can be obtained at zero frequency by assigning a negative value to the minimum value.
The encoder parameters can only be accessed if the encoder card has been i nserted. The available selections
will depend on the type of encoder card used.
M [Encoder type]
The parameter can be accessed if an encoder card has been inserted.
To be configured in accordance with the type of encoder used.
v [----] (nO): Card missing.
v [AABB] (AAbb): For signals A, A-, B, B-.
v [AB] (Ab): For signals A and B.
A
v [A] (A) : For signal A. Value cannot be accessed if [Encoder usage] (EnU) page 96 = [Spd fdk reg.] (rEG).
M [Encoder check]
Checks the encoder feedback. See procedure page 74.
The parameter can be accessed if an encoder card has been inserte d and if [Encoder usage] (EnU) page
96
is not [Speed ref.] (PGr).
v [Not done] (nO): Check not performed.
v [Yes] (YES): Activates monitoring of the encoder.
v [Done] (dOnE): Check performed successfully.
The check procedure checks:
- The direction of rotation of the encoder/motor
- The presence of signals (wiring continuity)
- The number of pulses/revolution
If a fault is detected, the drive locks in [Encoder fault](EnF) fault mode.
The parameter can be accessed if an encoder card has been inserted.
[No] (nO)
v [No] (nO): Function inactive. In this case, the other parameters cannot be access ed.
v [Fdbk monit.] (SEC): The encoder provides speed feedback for monitoring only.
v [Spd fdk reg.] (rEG): The encoder provides speed feedback for regulation and monitoring. This
configuration is automatic if the d rive has been confi gured for closed-loo p operation, and i s only possibl e in
this case.
v [Speed ref.] (PGr): The encoder provides a reference.
M [Number of pulses]
Number of pulses per encoder revolution.
The parameter can be accessed if an encoder card has been inserted.
M [Reference type]
The parameter can be accessed if [Encoder usage] (EnU) = [Speed ref.] (PGr).
100 to 50001024
[Encoder] (EnC)
v [Encoder] (EnC) : Use of an encoder.
v [Freq. gen.] (PtG): Use of a frequency generator (unsigned reference).
M [Freq. min. value]
The parameter can be accessed if [Encoder usage] (EnU) = [ Speed ref.] (PGr) and if [Reference type]
(PGA) = [Freq. gen.] (PtG).
Frequency corresponding to the minimum speed
M [Freq. max value]
The parameter can be accessed if [Encoder usage] (EnU) = [Speed ref.] (PGr) and if [Reference type]
(PGA) = [Freq. gen.] (PtG).
Frequency corresponding to the maximum speed
M [Freq. signal filter]
The parameter can be accessed if [Encoder usage] (EnU) = [Speed ref.] (PGr).
Interference filtering.
AG1
AG2
AG3
P1A
P2A
PLA
EFA
USA
UPA
AnA
tHA
bSA
bCA
SSA
rtA
tJA
bOA
APA
AP3
AP4
rdY
b [R1 CONFIGURATION]
M [R1 Assignment]
nO
v [No] (nO): Not assigned
v [No drive flt] (FLt): Drive not faulty (relay normally energized, and de-energized if there is a fault)
v [Drv running] (rUn): Drive running
v [Freq. Th. attain.] (FtA): Frequency threshold attained ([Freq. threshold](Ftd) page 62)
v [HSP attain.] (FLA): High speed attained
v [I attained] (CtA): Current threshold attained ([Current threshold](Ctd) page 61)
v [Freq.ref.att] (SrA): Frequency reference attained
v [Th.mot. att.] (tSA): Motor 1 thermal state attained
v [PID error al] (PEE): PID error alarm
v [PID fdbk al] (PFA): PID feedback alarm
v [AI2 Al. 4-20] (AP2): Alarm indicating absence of 4-20 mA signal on input A12
v [Freq. Th 2 attain.] (F2A): Frequency threshold 2 attained ([Freq. threshold 2](F2d) page 62)
v [Th. drv. att.] (tA d): Drive thermal state attained
v [Rope slack ] (rSdA ) : Ro pe sl a ck (s ee [Rope slack config.] parameter (rSd) page 165)
v [High tq. att.] (ttHA): Motor torque overshooting high threshold[High torque thd.] (ttH) page 61.
v [Low tq. att.] (ttLA): Motor torque undershooting low threshold[Low torque thd.] (ttL) page 61.
v [Forward] (MFrd): Motor in forward rotation
v [Reverse] (MrrS): Motor in reverse rotation
v [Th.mot2 att] (tS2): Motor 2 thermal state attained
v [Th.mot3 att] (tS3): Motor 3 thermal state attained
v [Neg Torque] (AtS): Negative torque (braking)
v [Cnfg.0 act.] (CnF0): Configuration 0 active
v [Cnfg.1 act.] (CnF1): Configuration 1 active
v [Cnfg.2 act.] (CnF2): Configuration 2 active
v [Set 1 active] (CFP1): Parameter set 1 active
v [Set 2 active] (CFP2): Parameter set 2 active
v [Set 3 active] (CFP3): Parameter set 3 active
v [DC charged] (dbL): DC bus charging
v [In braking] (brS): Drive braking
v [P. removed] (PRM): Drive locked by "Power removal" input
v [Fr.met. alar.] (FqLA): Measured speed threshold attained: [ Pulse warning thd.] (FqL) page 62.
v [I present] (MCP): Motor current present
v [Limit sw. att] (LSA): Limit switch attained
v [Load alarm] (dLdA): Load variation detection (see page 227).
v [Alarm Grp 1] (AGI): Alarm group 1
v [Alarm Grp 2] (AG2): Alarm group 2
v [Alarm Grp 3] (AG3): Alarm group 3
v [PTC1 alarm] (P1A): Probe alarm 1
v [PTC2 alarm] (P2A): Probe alarm 2
v [LI6=PTC al.] (PLA): LI6 = PTC probe alarm
v [Ext. fault al] (EFA): External fault alarm
v [Under V. al.] (USA): Undervoltage alarm
v [Uvolt warn] (UPA): Undervoltage warning
v [slipping al.] (AnA): Slipping alarm
v [Al. °C drv] (tHA): Drive overheating
v [Load mvt al] (bSA): Braking speed alarm
v [Brk cont. al] (bCA): Brake contact alarm
v [Lim T/I att.] (SSA): Torque limit alarm
v [Trq. ctrl. al.] (rtA): Torque control alarm
v [IGBT al.] (tJA): IGBT alarm
v [Brake R. al.] (bOA): Braking resistor temperature alarm
v [Option al.] (APA): Not aplicable.
v [AI3 Al. 4-20] (AP3): Alarm indicating absence of 4-20 mA signal on input AI3
v [AI4 Al. 4-20] (AP4): Alarm indicating absence of 4-20 mA signal on input AI4
v [Ready] (rdY): Drive ready
The change in state only takes effect once the conf igured time has elapsed, when t he information becomes
true.
The delay cannot be set for the [No drive flt] (FLt) assignment, and remains at 0.
M [R1 Active at]
Configuration of the operating logic:
v [1] (POS): State 1 when the information is true
v [0] (nEG): State 0 when the information is true
Configuration [1] (POS) cannot be modified for the [No drive flt] (FLt), assignment.
M [R1 Holding time]
The change in state only takes effect once the conf igured time has elapsed, when t he information becomes
false.
The holding time cannot be set for the [No drive flt] (FLt) assignment, and remains at 0.
b [R2 CONFIGURATION]
M [R2 Assignment]
Identical to R1 (see page 97) with the addition of (shown for information only as these selections can only
be configured in the [1.7 APPLICATION FUNCT.] (Fun-)) menu:
v [Brk control] (bLC): Brake contactor control
v [Input cont.] (LLC): Line contactor control
v [Output cont] (OCC): Output contactor control
v [End reel] (EbO): End of reel(traverse control function)
v [Sync. wobble] (tSY): "Counter wobble" synchronization
v [DC charging] (dCO): DC bus precharging contactor control.
M [R2 Delay time]
The delay cannot be set for the [No drive flt] (FLt), [Brk control] (bLC), [Output cont.] (OCC), [DC charging]
(dCO), and [Input cont.] (LLC) assignments, and remains at 0.
The change in state only takes effect once the conf igured time has elapsed, when t he information becomes
true.
M [R2 Active at]
Configuration of the operating logic:
v [1] (POS): State 1 when the information is true
v [0] (nEG): State 0 when the information is true
The configuration [1 ] (POS) cannot be modified for the [No drive flt] (FLt), [Brk control] (bLC), [DC charging]
(dCO), and [Input cont.] (LLC) assignments.
M [R2 Holding time]
The holding time cannot be set for the [No drive flt] (FLt), [Brk control] (bLC), [DC charging] (dCO), and
[Input cont] (LLC) assignments, and remains at 0.
The change in state only takes effect once the conf igured time has elapsed, when t he information becomes
false.
Can be accessed if a MT-VW3A3201 option card has been inserted
M [LO1 assignment]
Identical to R1 (see page 97) with the addition of (shown for information only as these selections can only
be configured in the [1.7 APPLICATION FUNCT.] (Fun-)) menu:
v [Brk control] (bLC): Brake contactor control
v [Input cont.] (LLC): Line contactor control
v [Output cont] (OCC): Output contactor control
v [End reel] (EbO): End of reel(traverse control function)
v [Sync. wobble] (tSY): "Counter wobble" synchronization
v [DC charging] (dCO): DC bus precharging contactor control.
M [LO1 delay time]
The delay cannot be set for the [No drive flt] (FLt), [Brk control] (bLC), [Output cont.] (OCC), [DC charging]
(dCO), and [Input cont.] (LLC) assignments, and remains at 0.
The change in state only takes effect once the conf igured time has elapsed, when t he information becomes
true.
M [LO1 active at]
Configuration of the operating logic:
v [1] (POS): State 1 when the information is true
v [0] (nEG): State 0 when the information is true
The configuration [1 ] (POS) cannot be modified for the [No drive flt] (FLt),[Brk control] (bLC), [DC charging]
(dCO), and [Input cont.] (LLC) assignments.
M [LO1 holding time]
The holding time cannot be set for the [No drive flt] (FLt), [Brk control] (bLC), [DC charging] (dCO), and
[Input cont] (LLC) assignments, and remains at 0.
The change in state only takes effect once the conf igured time has elapsed, when t he information becomes
false.
[No] (nO)
0 to 9999 ms0
[1 ] (POS)
0 to 9999 ms0
LO2-
LO2
LO2d
LO2S
LO2H
POS
nEG
b [LO2 CONFIGURATION]
Can be accessed if a MT-VW3A3201 option card has been inserted
M [LO2 assignment]
Identical to LO1.
M [LO2 delay time]
The delay cannot be set for the [No drive flt] (FLt), [Brk control] (bLC), [Output cont.] (OCC), [DC charging]
(dCO), and [Input cont.] (LLC) assignments, and remains at 0.
The change in state only takes effect once the conf igured time has elapsed, when t he information becomes
true.
M [LO2 active at]
Configuration of the operating logic:
v [1] (POS): State 1 when the information is true
v [0] (nEG): State 0 when the information is true
The configuration [1 ] (POS) cannot be modified for the [No drive flt] (FLt),[Brk control] (bLC), [DC charging]
(dCO), and [Input cont.] (LLC) assignments.
M [LO2 holding time]
The holding time cannot be set for the [No drive flt] (FLt), [Brk control] (bLC), [DC charging] (dCO), and
[Input cont] (LLC) assignments, and remains at 0.
The change in state only takes effect once the conf igured time has elapsed, when t he information becomes
false.