Moniteur 50 User Manual

SIPART PS2 6DR400x-xx SIPART PS2 PA 6DR410x-xx
Electropneumatic Positioner for Linear and Rotary Actuators
Manual Order No. C79000-G7476-C158-1
SIPART, SITRANS, SIMATIC are Siemens registered trademarks. All other product or system names are (registered) trademarks of their respective owners and must be treated accordingly .
The reproduction, transmission or use of this document or its contents is not permitted without express written authority . Offenders will be liable for damages. All rights created by the granting of patents or registration of a design are reserved.
Technical data subject to change without notice.
2
Contents
0 Information for the Operator 0-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0.1 General information 0-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0.2 Warning notes 0-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0.3 Qualified personnel 0-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0.4 Use as intended 0-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0.5 Technical documentation 0-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0.6 Warranty information 0-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0.7 Information about delivery 0-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0.8 Standards and regulations 0-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Introduction 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 General information about the device 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 The PROFIBUS 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1 PROFIBUS DP and PROFIBUS PA 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2 Properties of the PROFIBUS PA 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Design and Method of Operation 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Overview 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Components 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1 Motherboard 2-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.2 Electrical connections 2-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.3 Pneumatic connections 2-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.4 Mounting kit 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.5 Purging air switchover 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.6 Restrictors 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Method of operation 2-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4 State as supplied 2-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5 Optional modules 2-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5.1 HART module (devices without PROFIBUS PA only) 2-16. . . . . . . . . . . . . . .
2.5.2 Alarm module 2-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5.3 Jy module 2-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5.4 Accessories 2-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AG 1198 MG 124 en
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C158–01
i
3 Preparing for Operation 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Instrument identification (type code) 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Dimension drawings 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Assembly 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.1 Mounting kit “Linear Actuator” 6DR4004–8V 3-4. . . . . . . . . . . . . . . . . . . . . .
3.3.2 Assembly Sequence (see Fig. 3-5) 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.3 Mounting kit “Rotary Actuator” 6DR4004–8D 3-7. . . . . . . . . . . . . . . . . . . . . .
3.3.4 Assembly Sequence (see Fig. 3-6) 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Electrical connection 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.1 Connections variations not ex-proof (devices without
PROFIBUS P A) 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.2 Connection variants not protected from explosion hazard (devices with PRO-
FIBUS P A) 3-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.3 Connection variations options not ex-proof 3-15. . . . . . . . . . . . . . . . . . . . . . .
3.4.4 Connection variations ex-proof 3-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.5 Connection variations ex-proof (devices with PROFIBUS PA) 3-18. . . . . . .
3.4.6 Connection variations options ex-proof (devices with
PROFIBUS P A) 3-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Pneumatic connection 3-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6 Commissioning 3-21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operation 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Display 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Control pushbuttons 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Modes 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4 Parameters 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5 Operation via PROFIBUS P A 4-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.1 Useful data via PROFIBUS 4-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.2 Diagnostics acc. to PROFIBUS DP (DDLM_Slave_Diag) 4-31. . . . . . . . . . .
5 Service and Maintenance 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Technical Data 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 Supply Range 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1 Supply range of basic instrument 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Supply range of options 7-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3 Supply range of accessories 7-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A Appendix A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A 1 Index A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A 2 Device master data file (GSD) A-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A 3 SIMATIC object table A-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A 4 References and catalogs A-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Positioner SIP ART PS2/SIPART PS2 PA
ii
C79000-G7476-C158–01
Information for the Operator
Information for the Operator
Dear customer,
Before you start work, please read this manual! It contains important information and data that you must observe to ensure the availability of the device and save yourself service costs. This will make it consider­ably easier to use this control equipment and lead to reliable results.
You have acquired a device that can be set up in different configura­tions:
SIPART PS2 without PROFIBUS PA 6DR400x–xxSIPART PS2 with PROFIBUS PA 6DR401x–xx
This manual takes each of these possibilities into consideration. Any differences between the devices are indicated specially.
0.1 General information
0
The product described in this manual left the factory in a perfectly safe and tested condition. To maintain this condition and to achieve perfect and reliable operation of this product, it must only be used in the way described by the manufacturer. Successful and safe operation of this equipment is dependent on proper handling, installation, operation and maintenance.
This manual contains the information required for use as intended of the product it describes. It is addressed to technically qualified person­nel specially trained or having relevant knowledge of instrumentation and control technology, hereafter called automation technology.
Familiarity with and proper technical observance of the safety notes and warnings contained in this manual are essential for safe installation and commissioning and for safety in operation and maintenance of the product described. Only qualified personnel as defined in Section 0.3 has the necessary specialist knowledge to interpret the general safety notes and warnings given in this document in specific cases and to take the necessary action.
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C150–01
0-1
Information for the Operator
The documentation supplied with the instrument is listed in Section 0.5.
This manual is not a permanent part of the scope of supply. For rea­sons of clarity, it does not contain every detail about every version of the product described and cannot take every eventuality in installation, operation, maintenance and use in systems into account. If you require further information or if problems occur that have not been dealt with in sufficient detail in this document, please request the required informa­tion from your local Siemens office or the office responsible for you.
Functionality, commissioning and operation are described in this ma­nual.
Please pay special attention to the Warning and Note texts. These are separated from the remaining text by horizontal lines and specially marked with symbols (see Section 0.2).
0.2 Warning notes
Safety information and warnings are intended to avert danger from the life and health of users and maintenance personnel and to prevent ma­terial damage. They are highlighted in this manual by the headings de­fined here. They are also marked by warning symbols next to where they appear. The headings used have the following meaning for the purposes of this manual and the product labels:
Danger
!
!
!
indicates death, severe personal injury or substantial property damage will result if proper precautions are not taken.
Warning
indicates death, severe personal injury or substantial property damage can result if proper precautions are not taken.
Caution
indicates minor personal injury or property damage can result if proper precautions are not taken.
0-2
Positioner SIP ART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Information for the Operator
Note
indicates important information about the product itself or the respec­tive part of the instruction manual which it is essential to highlight.
0.3 Qualified personnel
The result of unqualified intervention in the instrument or nonobser­vance of the warnings given in this manual or on product labels can be severe personal injury and/or serious material damage. Therefore only properly qualified personnel must make changes and settings in the instrument.
For the purpose of the safety information in this manual and on the product labels, qualified personnel are those who
S if they are configuration personnel, are familiar with the safety con-
cepts of automation technology
S if they are operating personnel, have been instructed in the handling
of automation equipment and know the content of this manual relat­ing to operation
S if they are commissioning and/or service personnel, are trained to re-
pair such automation equipment and authorized to energize, de-ener­gize, clear ground and tag circuits and equipment in accordance with established safety practices
S and are trained in first aid S and, in the case of ex-proof equipment, are trained and authorized
to carry out work on electrical circuits of equipment subject to explo­sion hazard.
Warning
!
The instrument must only be installed and commissioned by qualified personnel.
The instrument is designed for connection to functional and safety ex­tra low voltage.
Electrical safety depends only on the power supply equipment. Pneumatic actuators exert considerable positioning forces. The safety
precautions of the actuator used must therefore be scrupulously ob­served during installation and commissioning in order to prevent inju­ries. We explicitly draw your attention to the necessity of observing safety regulations regarding operation in zones subject to explosion hazard, if applicable.
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C150–01
0-3
Information for the Operator
0.4 Use as intended
Use as intended for the purpose of this manual means that this product must only be used for the applications described in the technical de­scription (see also Section 3 of this manual).
The product described in this manual has been developed, manufac­tured, tested and documented observing the relevant safety standards. If the handling rules and safety information for configuration, installa­tion, use as intended and maintenance are observed, there is normally no danger with regard to material damage or for the health of person­nel. Extra low voltages that are connected must be fed in by safe isola­tion.
0.5 Technical documentation
In addition to this manual, the following documentation is also supplied with the instrument:
Leaflet “Operation – Concise Overview”
Order No. C73000–B7400–C151 (German) without PROFIBUS PA Order No. C73000–B7476–C151 (English) without PROFIBUS P A Order No. C79000–B7400–C160 (German) with PROFIBUS PA Order No. C79000–B7476–C160 (English) with PROFIBUS PA
explains in visualized form the principle of operation and parameter­ization and automatic commissioning.
“Assembly and Installation Instructions”
Order No. C79000–M7474–C156 (German/English) contains the information required for assembly and installation. It is an Instruction Manual as defined in the Directive of the Council
of the European Communities dtd. 23 March 1994 (94/9/EC).
0.6 Warranty information
We should like to point out that the content of this manual is not part of and does not modify a previous or current agreement, undertaking or legal relationship. Siemens is bound solely by the contract of sale, which also contains the complete and exclusive warranty. The contrac­tual warranty conditions are neither extended nor restricted by this document.
0-4
Positioner SIP ART PS2/SIPART PS2 PA
C79000-G7476-C150–01
0.7 Information about delivery
The scope of delivery is listed on the dispatch papers accompanying the delivery in accordance with the valid contract of sale.
When you open the packaging please observe the information on the packaging. Check that the delivery is complete and undamaged. If pos­sible, compare the order number on the rating plates with the ordering data.
For the supply range please see Section 7.
0.8 Standards and regulations
As far as possible, the harmonized European standards were used to specify and manufacture this equipment. If harmonized European stan­dards have not been applied, the standards and regulations of the Fed­eral Republic of Germany apply (see also the Technical Data in Sec­tion 6).
Information for the Operator
If this product is used outside the area of applicability of these stan­dards and regulations, please observe the standards and regulations in force in the country where the product is operated.
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C150–01
0-5
Information for the Operator
0-6
Positioner SIP ART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Introduction
Introduction
1.1 General information about the device
The SIPART PS2 positioner is used to position and control pneumatic actuators. The instrument operates electropneumatically, compressed air is used as the auxiliary power.
SIPART PS2 P A
Purpose
In the SIPART PS2 P A version, the positioner is used as a component in a digital process automation system. It communicates with the mas­ter as a slave via the PROFIBUS PS field bus. The field bus is used not only for communication but also to supply the positioner with electri­cal power.
The positioner can be used to control, for example values with
1
Models
a linear actuator (Fig. 1-3) ora rotary actuator VDI/VDE 3845 (Fig. 1-4).
Different ways of mounting are available for linear actuators
NAMUR or IEC 534integrated mounting (ARCA, SAMSON)
so that the positioner can be mounted and used on all common types of actuators.
The instrument is available for
double-acting andsingle-acting
actuators, and for applications
subject to explosion hazard ornot subject to explosion hazard.
and the variants
without PROFIBUSwith PROFIBUS.
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C150–01
1-1
Introduction
Housing
Degree of protec­tion
Explosion protec­tion
Options
The electronics including the display and the position feedback and the valve manifold are integrated in the housing.
The housing is available in two variations:
Plastic housing for double-acting actuatorsMetal housing for single-acting actuators
The instrument has degree of protection IP65.
The intrinsically safe version can be operated in hazard area zone 1 or zone 2.
The instrument can be expanded with different option modules (see Section 2.5). The following modules are available and can be operated both singly and in any combination.
module: 2–wire current output 4 to 20 mA for position feedback
J
y
Alarm module: 3 binary outputs and 1 binary inputHART module: HART communication (devices without
PROFIBUS P A only)
Accessories
Manometer block: 2 or 3 manometers for single and double-acting
Flange (NAMUR) for safety valve block
Environmental protection
Only environmentally compatible materials were used in the packaging system of this instrument.
The manual is printed on paper bleached using a chlorine–free method.
1.2 The PROFIBUS
The PROFIBUS (Process Field Bus)
is an open communication system for automationis in use all over the world in thousands of applicationsis specified in the European standard EN 50170
positioner
1-2
Positioner SIP ART PS2/SIPART PS2 PA
C79000-G7476-C150–01
1.2.1 PROFIBUS DP and PROFIBUS PA
Introduction
Transmission technology
Topology
The PROFIBUS P A ( PA = Process Automation) is a variant of the PROFIBUS DP (DP = Distributed Peripherals) which is widely used in manufacturing.
The PROFIBUS PA makes use of special transmission technology and therefore meets the requirements of process automation and process engineering. This transmission technology is defined in the international standard IEC 1158–2. The low transmission rate reduces the power loss and therefore permits intrinsically safe technology for use in zones subject to explosion hazard.
Moreover, almost any bus topology can be selected, so that bus, star, tree, and mixed structures are possible. All types of field devices such as transducers, actuators, analyzers, etc. can be connected to the PROFIBUS P A.
The main advantages are:
saving in installation coststhe option of more detailed diagnostics thus increasing the availabil-
ity of plant sections
the option of automatic correction of plant documentationthe option of plant optimization during running operation
In an automation system, several PROFIBUS PA trains are usually connected to the fast PROFIBUS DP via coupling units. The process control system is also connected to the PROFIBUS DP.
Both bus systems make use of a standard protocol layer. That makes the PROFIBUS PA a ”communication compatible” extension of PROFI­BUS DP into the field.
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C150–01
1-3
Introduction
Master
(class 1)
PROFIBUS DP
Slaves
(field devices, distributed I/Os, lower–level controls,
gateway to PROFIBUS P A)
Fig. 1-1 Typical PROFIBUS automation system
Fig. 1-1 shows a section of a typical PROFIBUS automation system. The control system consists of two masters with distributed tasks:
Master
(class 2)
PROFIBUS P A
J
The master class 1 performs open–loop and closed–loop control tasks, master class 2 is used for HMI functions. Exchange of measuring and positioning data is performed cyclically between master 1 and the field devices. Parallel with this data, the status information of the field de­vices is transmitted and evaluated in master 1. Parameterization of the field devices or reading of further device information is not performed in cyclic operation.
The control system obtains the information required to establish com­munication from the device–specific device master data files GSD (see Appendix).
In addition to cyclic operation one or more masters of class 2 can ac­cess the field devices non–cyclically. By this method of communication, further information can be fetched from the devices or settings made in the devices.
1.2.2 Properties of the PROFIBUS PA
The PROFIBUS PA permits bidirectional communication from a bus master with the field devices via a shielded, twisted pair. At the same time the two–wire field devices are powered via the same lines (current J in Fig. 1-1).
1-4
Positioner SIP ART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Introduction
Profiles
PLS, PC
In addition to the EN standard 50170, the PNO (PROFIBUS user orga­nization) has defined the functionality of the individual field device types in a profile description. These profiles define minimum functional re­quirements and optional extensions. The device–internal ”device man­agement” provides the configuration tool of the control system with all basic information necessary to locate the profile parameters. In that way, one parameterizing tool can operate all profile–compliant devices, whatever their type or manufacturer.
The system must be implemented with one or more PROFIBUS PA trains depending on the automation task and therefore the number of field units and the required time response. One PROFIBUS PA train consists of the components shown in Fig. 1-2.
Control room Field
PROFIBUS DP
Coupler
T
Power supply
PROFIBUS PA
FG FG
T
additional line termination
Fig. 1-2 PROFIBUS PA architecture
Link
Control is performed by the central process control system PCS or for low requirements, by a PC. Usually, the functional signal conversion DP–PA, bus feed, and bus termination are combined into one linking module. Depending on the number PROFIBUS PA field devices to be operated in the automation system and the required time response, a DP/PA coupler or for higher requirements, a more powerful DP/PA link is used.
For transmission reasons, the bus must also be fitted with a terminating resistor T at the remote end. If the recommended bus cable is used, the theoretically possible maximum line length (sum of all line sections) is 1900 m.
During configuration, the power requirement of the individual stations and the voltage drop on the cable must also be taken into account. The individual FG field devices can be connected to almost any point in the bus system. For further information see the ”PNO–Leitfaden PROFI­BUS P A”/1/.
DP/PA couplers or DP/PA links are powered from a power supply unit with SEL V (safety extra–low voltage). This power supply unit must have sufficient back–up reserves to provide back–up power during short power interruptions.
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C150–01
1-5
Introduction
The maximum number of devices that you can connect to a bus train depends on the current consumption and the application conditions. During operation in a safe zone, the couplers or links supply up to 400 mA to the bus.
In zones subject to explosion hazard, intrinsic safety is only ensured if the maximum power fed into the bus does not exceed certain voltage and current values.
These are usually: EEx ia IIC Current I
Warning
!
To power the intrinsically safe PROFIBUS only certified power supply units (DP/PA couplers or links) must be used. See the Ex conformity declaration for the requirements (see Assembly and Installation Instructions).
< 128 mA, voltage U0<15V
S
From the sum of the maximum current consumption of the connected devices (acc. to standard = 10 mA per device) and the available cur­rent, it is possible to calculate the number of devices that can be con­nected to a bus train. For safety reasons, a current reserve must be planned because otherwise there is a risk that a defective device could overload the bus by increased current consumption and that therefore the power supply and communication with all the other non–defective stations could collapse. The size of the required reserve depends on the current increase in case of fault stated by the device manufacturer.
The electronic current limitation additionally installed in the SIPART PS2 with PROFIBUS P A ensures a maximum increase of the current consumption by 3 mA for a defective device.
In order to distinguish the connected process devices from one another, each device has its own address. The address setting is de­scribed in Section 3.6 ”Commissioning”.
For more detailed information about the components, assembly guide­lines and configuration, see the technical description of the field technology package /2/.
1-6
Positioner SIP ART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Introduction
1
4
2
3
1 Actuator 2 Positioner, single acting in metal housing 3 Intermediate bracket 4 Manometer block, single acting 5 Valve
Fig. 1-3 Positioner mounted on linear actuator (single acting)
5
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C150–01
1-7
Introduction
1
3
2
1 Positioner, double acting in plastic housing 2 Rotary actuator 3 Manometer block, double acting
Fig. 1-4 Positioner mounted on rotary actuator (double acting)
1-8
Positioner SIP ART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Design and Method of Operation
Design and Method of Operation
This Section describes the mechanical and electrical design, the com­ponents of the instrument and the principal method of operation of the instrument.
2.1 Overview
Introduction
Devices without PROFIBUS P A
The SIPART PS2 electropneumatic positioner forms a closed-loop con­trol system together with an actuator. The current position of the actua­tor is acquired via a servo-potentiometer and returned as actual value x. The setpoint and actual values are output simultaneously on the dis­play.
Setpoint w is formed by a current fed to the SIPART PS2 positioner which is also used to power the instrument in 2-wire operations. In 3/4–wire operation the power supply is taken from a 24V power input.
2
Devices with PROFIBUS P A
The setpoint is supplied to the positioner by the control system digitally via PROFIBUS P A.
The PROFIBUS PA variant of the SIPART PS differs from previous ver­sions by its bus interface. The basic functions including operation and display have remained almost unchanged. The interface tasks are per­formed by function blocks 1 to 6 (see Fig. 2-13).
The positioner functions as a predictive 5-step controller, the output quantity ±y of which is used to operate the integrated control valves with pulse-width-modulated pulses.
These positioning signals effect differences in pressure in the actuator chamber(s) and consequently adjustment of the actuators until the sys­tem deviation is reduced to zero.
Process operation (automatic and manual mode) and configuring (structuring, initialization and parameterization) is performed with the three pushbuttons and the display when the housing cover is removed.
The standard version of the basic instrument also has a binary input (BE1). This input can also be configured individually and is primarily intended for blocking operating levels.
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C150–01
2-1
Design and Method of Operation
The actuator position can be output as 2–wire signal Jy = 4 to 20 mA using the Jy option module.
The actuator can also be monitored for two programmable limit values. Limit value alarms are output via the alarm option module that can also monitor and signal the function of the positioner and the actuator. In automatic operation the system deviation is monitored as a function of the actuating time. The three binary outputs are implemented as semi­conductor outputs and feature self–annunciation, i.e. the outputs re­spond even if the auxiliary power or the electronics fails.
Depending on how it is configured, the actuator can be blocked, for ex­ample, or put into its final position by an external event via the binary input (BE2) which is also located on the alarm module.
Devices without PROFIBUS P A
2.2 Components
1 2 3 4 5
6 7 8 9
10
10
Via the optional HART module it is possible to communicate with the controller.
90°
33°
89
3
6.1
6
6.2
7
11
1 Input: inlet air 2 Output: positioning
pressure Y1
3 Display
2
138
4 Output: positioning
pressure Y2
**)
5 Control pushbuttons 6 Restrictor Y1
1
8
6.1 Restrictor Y1
6.2 Restrictor Y2
**) **)
7 Transmission ratio selector 8 Adjusting wheel clutch
4
238
9 Terminals
Basic instrument
10 Terminals
5
Optional modules
1 1 Purging air selector
**)
for double-acting actuators
Fig. 2-1 View of the instrument (cover open), devices without PROFIBUS PA
2-2
Positioner SIP ART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Design and Method of Operation
3
11
1 Input: inlet air 2 Output: positioning
90°
3 7
9
10
138
8
3 Display 4 Output: positioning
2
5 Control pushbuttons 6 Restrictor Y1
6.1 Restrictor Y1
1
6.2 Restrictor Y2 7 Transmission ratio selector 8 Adjusting wheel clutch 9 Terminals
238
4
10 Terminals 1 1 Purging air selector
**)
for double-acting
10
33°
89
6
7
6.1
5
6.2
actuators
Fig. 2-2 View of the instrument (cover open), devices with PROFIBUS PA
2.2.1 Motherboard
The motherboard contains all electronic elements such as CPU, memory, ADC. It also contains the display and the control pushbuttons.
pressure Y1
pressure Y2
**)
**) **)
Basic instrument Optional modules
The terminal blocks for connecting the option modules are also located on the motherboard.
2.2.2 Electrical connections
The terminals of the basic instrument, the Jy and the alarm option mo­dule are located on the front on the left–hand side and are offset in a step–shaped arrangement.
A cover protects the modules from being pulled out and prevents incor­rect installation.
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C150–01
2-3
Design and Method of Operation
2.2.3 Pneumatic connections
The pneumatic connections (G1/4) are located on the right-hand side of the positioner (Fig. 2-3).
Positioning pressure Y1 for single and double–acting actuators Feedback shaft
Inlet air P
Positioning pressure Y2 for double–acting actuators
Outlet air E with silencer on the underside of the instrument
Fig. 2-3 Pneumatic connection
Z
Two pneumatic connections for the integrated installation of single–ac­ting linear actuators are located on the rear of the positioner:
Positioning pressure Y1Air outlet E
These connections are locked with screws when supplied (see Fig. 3-2 and Fig. 3-4).
Outlet air E is used to ensure a flow of dry instrument air through the pick–off area and the spring chamber to prevent corrosion.
Fig. 2-4 shows pneumatic connection options for various types of ac­tuators with the positioning action and the safety position after auxiliary power failure.
2-4
Positioner SIP ART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Design and Method of Operation
Positioning pressure Connection
Y1
Y1
Y2
Y1
Y1
Y2
Actuator type
OpenClosed
OpenClosed
OpenClosed
OpenClosed
Safety position after auxiliary power failure
electrical pneumatic
Closed Closed
Open Open
Open
Undefined
Closed
On rotary actuators the counter–clock­wise direction of ro­tation – looking at the actuating shaft of the valve – is defined as “open”
Closed
.
Open
Y1
up
down down
down
Y1
up down
up up
Y2 Y1
up down
up
Y1 Y2
up down
down
Fig. 2-4 Pneumatic connection and positioning action
up down
Undefined
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C150–01
2-5
Design and Method of Operation
2.2.4 Mounting kit
The positioner can be mounted on nearly all common types of actua­tors using the appropriate mounting kit.
2.2.5 Purging air switchover
The purging air changeover switch above the pneumatic terminal block (Fig. 2-5) on the valve manifold can be accessed when the housing is open. When the switch is in position IN the interior of the housing is purged with very small quantities of clean and dry instrument air. In po­sition OUT the purging air is led directly out of the instrument.
Fig. 2-5 Purging air changeover switch above the pneumatic terminal block, view of the device on the
pneumatic connection side with the cover open
2.2.6 Restrictors
The air flow can be reduced with restrictors Y1 and Y2 (Fig. 2-6) to achieve actuating times of > 1.5 s on small actuators. Turning the re­strictors in the clockwise direction reduces the air flow until it is shut off. To set the restrictors we recommend closing them first and then ope­ning them again slowly (see Initialization RUN3).
Y1 Y2
Fig. 2-6 Restrictors
2-6
Positioner SIP ART PS2/SIPART PS2 PA
C79000-G7476-C150–01
2.3 Method of operation
The electropneumatic positioner SIPART PS together with the pneuma­tic actuator forms a control loop in which the actual value x is the posi­tion of the actuator rod on linear actuators and the position of the ac­tuator shaft on rotary actuators and the reference variable w is the actuating current of a controller or manual control station of between 0/4 and 20 mA.
With devices with PROFIBUS PA, the command variable w is set digi- tally via a bus system.
The stroke or rotational movement of the actuator is transferred to a servopotentiometer via the necessary mounting accessories, the feed­back shaft and reversible gear train without play and then sent to the analog input of the microcontroller.
This corrects the angular error of the stroke pick–off, if necessary, com­pares the potentiometer voltage as an actual value x with the setpoint x fed in via terminals 3 and 7 and calculates the manipulated variable increments " Dy. Depending on the size and the direction of the sy­stem deviation (x–w) the piezoelectric pre–controlled air inlet and air outlet valve is opened. The volume of the actuator integrates the cor­recting increments up to actuating pressure y which moves the actua­tor rod or the actuator shaft approximately proportionally. These cor­recting increments continue to change the actuating pressure until the system deviation is zero.
Design and Method of Operation
The pneumatic actuators are available as single–acting and double–ac­ting versions. In the single–acting version only one volume is ventilated or vented. The resulting pressure is exerted against a spring. In the double–acting version two volumes act against each other. One volume is ventilated as the other volume is vented. See block diagrams in Fig. 2-7 and 2-9.
The control algorithm is an adaptive predictive five–point controller. The valves are actuated with a maintained contact for large system
deviations (high–speed zone). The valves are actuated with pulse– width–modulated pulses for medium system deviations (short–step zone).
No positioning pulses are output in the zone of low system deviation (self-adjusting dead band). The dead-band adaptation and the continual adaptation of the minimum pulse length in automatic operation allow the best possible control accuracy to be achieved with the minimum switching frequencies. The start parameters are determined during the initialization phase.
Figs. 2-7 to 2-10 show the block diagrams for single and double-acting actuators, in this example on a linear actuator.
Note
When not under power, the air discharge valve is always open.
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C150–01
2-7
Design and Method of Operation
1 2
E
H+
E
H–
J
+
E
H–
J
w+
1.5 k
3
9.2 V
4 5
6
HART module
J
w–
J
w–
BE1
BE1
10
40
7 8
9
#
Basic instrument
A
w
D
Setpoint
BE1
Actual value
A
x=y
D
Positioning increments
3V
24V
"dy
3V
24V
A1
A2
y
BE2
3V
3V
3V
D
22
21
#
11 12
31 32
41 42
51 52
Alarm module
A
U
U
61
J
62
Jy module
Piezoelectric pre–control
3/3 way valve
Y1
Outlet air
E
Y1
138
PZ
Inlet air
8
manometer block
Positioning pressure Y1
up
down
Option
Fig. 2-7 Block diagram diagram for single-acting actuators (2-wire operation, state as supplied), devices
without PROFIBUS PA
2-8
Positioner SIP ART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Design and Method of Operation
Bus interface
BE1
BE1
10
Bus coupling
3
7
9
#
Piezoelectric pre–control
Basic instrument
w
Setpoint
BE1
Actual value
A
x=y
D
3/3 way valve
Positioning increments
3V
24V
"dy
3V
24V
A1
A2
y
BE2
3V
3V
3V
D
22
21
#
Alarm module
A
U
U
Jy module
11 12
31 32
41 42
51 52
61
J
62
Y1
Outlet air
E
Y1
138
Positioning pressure Y1
up
down
PZ
8
Inlet air
manometer block
Option
Fig. 2-8 Block diagram diagram for single-acting actuators (2-wire operation, state as supplied), devices
with PROFIBUS PA
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C150–01
2-9
Design and Method of Operation
1 2
10
1.5 k
3
9.2 V
4 5
6
40
7 8
9
#
E
H+
E
H–
J
E
+
H–
J
w+
J
w–
J
w–
BE1+
BE1–
Basic instrument
HART module
A
w
D
Setpoint
BE1
Actual value
x=y
A
D
Positioning increments
3V
24V
"dy
3V
24V
A1
A2
y
BE2
3V
3V
3V
D
21 22
#
#
11 12
31 32
41 42
51 52
Alarm module
A
U
U
61 62
J
Jy module
Piezoelectic pre–control
Outlet air
E
Y2
Y2
4/3 way valve
Positioning
Y1
138
Y1
PZ
Inlet air
8
manometer block
pressure Y1
Positioning
up
pressure Y2
down
Option
Fig. 2-9 Block diagram for double-acting actuators (2-wire operation, state as supplied), devices with-
out PROFIBUS PA
2-10
Positioner SIP ART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Design and Method of Operation
Bus interface
BE1
BE1
Outlet air
10
Bus coupling
3
7
9
#
Setpoint
Actual value
Piezoelectic pre–control
Basic instrument
w
BE1
x=y
A
D
Positioning increments
3V
24V
"dy
3V
24V
A1
A2
21 22
BE2
3V
3V
3V
y
D
A
#
#
Alarm module
U
U module
J
y
11 12
31 32
41 42
51 52
61 62
J
E
Y2
Y2
238
4/3 way valve
Positioning pressure Y1
Y1
Y1
138
Positioning
up
pressure Y2
down
PZ
8
Inlet air
manometer block
Option
Fig. 2-10 Block diagram for double-acting actuators (2-wire operation, state as supplied), devices with
PROFIBUS PA
Positioner SIP ART PS2/SIPART PS2 PA C79000-G7476-C150–01
2-11
Design and Method of Operation
Bus interface
12 3 4 5 6
Fig. 2-1 1 Block diagram of the bus coupling unit, devices with PROFIBUS PA
Devices with PROFIBUS P A
1. The EMC filter prevents malfunctions due to electromagnetic interference.
2. The reverse polarity protection permits connection of the bus cables in any way and makes installation errors almost impossible.
3. The electronic protection ensures that no impermissibly high current
flows in the event of a fault. That avoids overloading the bus, but
data exchange between the remaining stations not subject to interference is still possible.
4. The bus interface contains the transmit and receive circuits for the bus system and the control for the auxiliary power generation.
5. The device internal electronics are isolated by galvanic isolation from the PROFIBUS PA.
6. The microprocessor interprets the bus commands, initiates device internal actions and provides position signals, status, and device data on the bus.
MC
2.4 State as supplied
In the state as supplied no mechanical mounting components are at­tached to the positioner. These have to be ordered and mounted for the specific application in accordance with the “Assembly and Installation Instructions”.
The connections for single and double-acting versions are prepared in the factory as ordered.
The pneumatic connections on the rear are closed.
2.5 Optional modules
The optional modules are protected and mechanically fixed by a mo­dule cover ((1), see Fig. 2-12)
Note
To install the option modules you must first open the housing. As long as the instrument is open, degree of protection IP65 is not ensured.
2-12
Positioner SIP ART PS2/SIPART PS2 PA
C79000-G7476-C150–01
Loading...
+ 94 hidden pages