Monessen Hearth CDVT36, CDVR36 User Manual

CDV SERIES
DIRECT VENT GAS FIREPLACE
MODELS:
CDVR33, CDVT33,
CDVR36
IF THE INFORMATION IN THESE INSTRUCTIONS ARE NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
– Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
– WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
– Installation and service must be performed
by a qualified installer, service agency or the gas supplier.
WARNING: Improper installation, adjustment, alteration, services or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
This appliance may be installed in an aftermarket*, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
* Aftermarket: Completion of sale, not for purpose of resale, from
the manufacturer.
WARNINGS
AND CDVT36
CDVT
CDVR
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURE AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
KEEP THE ROOM AREA CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE, AND OTHER FLAMMABLE VAPORS AND LIQUIDS.
READ BEFORE INSTALLING. SAVE THESE INSTRUCTIONS
CONTENTS
Important Safety Information .......................... 3
Product Features .............................................. 5
Code Approval .................................................. 5
Pre-Installation Information
Installing Above 2000 Feet............................ 6
Orifice Sizes, Pressures and BTUs ............... 6
Before You Start............................................ 6
Fireplace Framing - CVDR36 and CDVR33.. 7 Fireplace Framing - CVDT36 and CDVT33 .. 8
Fireplace Dimensions.................................... 9
Fireplace Location ....................................... 10
Clearances ...................................................... 11
Securing Fireplace to Floor or Framing ....... 12
Installation Information .................................. 13
Installation Precautions ............................... 13
Vent Installation .............................................. 14
Rear Vent Installation .................................. 14
Top Vent Installation ................................... 15
Installation Planning .................................... 16
Rear (Through the Wall) Applications ......... 19
Horizontal Termination Configuration.......... 21
Below Grade Installation ............................. 23
Vertical Through-the-Roof Installation......... 24
Installation for Vertical Termination ............. 25
Cathedral Ceiling Installation ...................... 26
Fireplace Installation ...................................... 27
Check Gas Type ......................................... 27
Installing Gas Piping to Fireplace/Burner
System Location.......................................... 27
Checking Gas Pressure ................................. 29
Electrical Installation...................................... 29
Electrical Wiring .......................................... 30
Electronic Pilot Ignition Wiring..................... 31
Remote Wall Switch .................................... 31
Optional Fan/Blower Systems ..................... 32
Glass Removal ................................................ 33
Final Installation ............................................. 34
Rockwool Placement................................... 34
Log Placement ............................................ 34
Lava Rock and Ember Placement............... 34
Millivolt Operating Instructions ..................... 35
What To Do If You Smell Gas ..................... 35
Lighting Pilot for the First Time ................... 35
Lighting Pilot................................................ 36
Lighting Burner ............................................ 37
To Turn Off Gas .......................................... 37
Electronic Ignition Operating Instructions ... 38
What To Do If You Smell Gas ..................... 38
Lighting Electronic Ignition .......................... 38
To Turn Off Gas .......................................... 38
Cleaning and Maintenance ............................ 39
Burner, Pilot and Control Compartment ...... 39
Pilot Flame .................................................. 39
Burner Flame .............................................. 39
Vent System ................................................ 40
Glass Door .................................................. 40
Logs ............................................................ 40
Rock Wool .................................................. 40
Troubleshooting ............................................. 41
Replacement Parts ......................................... 44
Firebox Components ................................... 44
Standing Pilot - Millivolt Control Engine ..... 46
Electronic Ignition Engine ........................... 48
Logs ............................................................ 49
Vent Components ....................................... 50
Massachusetts Requirements ....................... 51
Warranty ...........................................Back Cover
2 69D0023
IMPORTANT SAFETY INFORMATION
INSTALLER
Please leave these instructions with the appliance.
• Read this owner’s manual carefully and completely before trying to assemble, operate, or service this fireplace.
• Any change to this fireplace or its controls can be dangerous.
• Improper installation or use of this fireplace can cause serious injury or death from fire, burns, explosions, electrical shock and carbon monoxide poisoning.
WARNINGS
This fireplace is a vented product. This fireplace must be prop­erly installed by a qualified service person. The glass door must be properly seated and sealed. If this unit is not properly installed by a qualified service person with glass door properly seated and sealed, combustion leakage can occur.
CARBON MONOXIDE POISONING: Early signs of carbon monoxide poisoning are similar to the flu with head­aches, dizziness and/or nausea. If you have these signs, the fireplace may not have been installed properly. Get fresh air at once! Have the fireplace inspected and serviced by a quali­fied service person. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Propane/LP gas and natural gas are both odorless. An odor­making agent is added to each of these gases. The odor helps you detect a gas leak. However, the odor added to these gases can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.
1. This appliance is only for use with the type of gas indi­cated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.
2. For propane/LP fireplace, do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity.
3. If you smell gas
• shut off gas supply.
• do not try to light any appliance.
• do not touch any electrical switch; do not use any
phone in your building .
• immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
OWNER
Please retain these instructions for future reference.
4. Never install the fireplace
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable objects are less than 42" from the front, top, or sides of the fireplace
• in high traffic areas
• in windy or drafty areas
5. This fireplace reaches high temperatures. Keep children
and adults away from hot surfaces to avoid burns or cloth­ing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
6. Carefully supervise young children when they are in the
room with fireplace.
7. Do not modify fireplace under any circumstances. Any
parts removed for servicing must be replaced prior to operating fireplace.
8. Turn fireplace off and let cool before servicing, install-
ing, or repairing. Only a qualified service person should install, service, or repair the fireplace. Have burner system inspected annually by a qualified service person.
9. You must keep control compartments, burners, and cir-
culating air passages clean. More frequent cleaning may be needed due to excessive lint and dust. Turn off the gas valve and pilot light before cleaning fireplace.
10. Have venting system inspected annually by a qualified
service person. If needed, have venting system cleaned or repaired. See Cleaning and Maintenance, page 40.
11. Keep the area around your fireplace clear of combustible
materials, gasoline, and other flammable vapor and liq­uids. Do not run fireplace where these are used or stored. Do not place items such as clothing or decorations on or around fireplace.
Continued on page 4
69D0023 3
IMPORTANT SAFETY INFORMATION
Continued from page 3
12. Do not use this fireplace to cook food or burn paper or other objects.
13. Never place anything on top of fireplace.
14. Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this fireplace. Use only the gas type indicated on rating plate.
15. This appliance, when installed, must be electrically grounded in accordance with local codes or in the absence of local codes, with the National Electrical
Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
16. Do not obstruct the flow of combustion and ventilation air in any way. Provide adequate clearances around air openings into the combustion chamber along with adequate accessibility clearance for servicing and proper operation.
17. When the appliance is installed directly on carpeting, tile or other combustible material other than wood floor­ing, you must set appliance on a metal or wood panel or hearth pad extending the full width and depth of the appliance.
18. Do not use fireplace if any part has been exposed to or has been under water. Immediately call a qualified service person to arrange for replacement of the unit.
19. Do not operate fireplace if any log is broken.
IMPORTANT:
PLEASE READ THE FOLLOWING CAREFULLY
It is normal for fireplaces fabricated of steel to give off some expansion and/or contraction noises during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine.
IMPORTANT:
PLEASE READ THE FOLLOWING CAREFULLY
It is not unusual for gas fireplace to give off some odor the first time it is burned. This is due to the manufacturing process.
Please ensure that your room is well ventilated
during burn off — open all windows.
It is recommended that you burn your fireplace for at least ten (10) hours the first time you use it. Place the fan switch in the “OFF” position during this time.
Never connect unit to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
WARNING
20. Do not use a blower insert, heat exchanger insert, or any other accessory not approved for use with this fire­place.
21. Do not operate the fireplace with glass door removed, cracked, or broken.
We suggest that our gas hearth products be installed and serviced by professionals who are certified in the U.S. by the National Fireplace Institute
®
(NFI) as Gas Specialists.
www.nficertified.org
4 69D0023
PRODUCT FEATURES AND CODE APPROVAL
PRODUCT SPECIFICATIONS
This appliance has been certified for use with either natural or propane gas. See appropriate data plates.
This appliance is not for use with solid fuels.
The appliance is approved for bedroom or bedsitting room installations.
The appliance must be installed in accordance with local codes if any. If none exist use the current installation code.
ANSI Z223.1/NFPA 54 in the USA, CAN/CGA B149 in Canada.
This appliance is mobile home approved.
The appliance must be properly connected to a venting system.
The appliance is not approved for closet installations.
This appliance is approved to be vented with Simpson-Duravent and Selkirk-Metalbestos Direct Vent Components.
NOTE: For illustration purposes only, all drawings show the Simpson-Duravent System.
The efficiency rating of this appliance is a product thermal efficiency rating determined under continuous operating condi­tions and was determined independently of any installed system.
Thermal Efficiency = up to 80%
Remote Control
Hi/Lo Knob
Off/Pilot/On Knob
Ignitor
On/Off/RS Switch
Blower Control
Figure 1 - CDVR33, CDVT33, CDVR36 and CDVT36 Fireplace
CODE APPROVAL
Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe.
These appliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Canada as follows:
LISTED VENTED GAS FIREPLACE HEATER
TESTED TO: ANSI Z21.88/CSA 2.33 STANDARDS
A manufactured home (USA only) or mobile home OEM installation must conform with the Manufactured Home Con­struction and Safety Standard, Title 24 CFR, Part 3280, or when such a standard is not applicable, the Standard for
Manufactured Home Installations, ANSI/NCSBCS A225.1, or Standard for Gas Equipped Recreational Vehicles and Mobile Housing, CSA Z240.4.
69D0023 5
PRE-INSTALLATION INFORMATION
The classification “noncombustible material” includes, but is not limited to stone, brick and mortar. Noncombustibles are safe to overlay the black-painted metal face (including radiant plates) and do not pose a fire hazard. Do not allow any non­combustible finish material to extend past or interfere with fireplace opening.
The classification “combustible material” includes, but is not limited to plywood, drywall and particle board. Combustible materials may contact the sides, bottom or back of firebox. Do not overlay the black painted face with combustible materi­als.
INSTALLING ABOVE 2000 FEET
In the USA, the appliance must be derated 4% for every 1,000 ft above 2,000 ft elevations.
In Canada, these appliances are certified for altitudes of 0 – 2000 ft, and must be de-rated by 10 percent for installations
between 2000 and 4,500 ft. (derate an additional 4% for every 1,000 ft. above 4,500 ft. elevations).
ORIFICE SIZES, PRESSURES AND BTUs
NATURAL GAS PROPANE GAS
Manifold Press: (W.C.) 3.5" Manifold Press: (W.C.) 10" Maximum Supply Pressure 10.5" Maximum Supply Pressure 13" Minimum Supply Pressure 4.5" Minimum Supply Pressure 11"
CDVR36 CDVT36 CDVR33 CDVT33
Model Number
Max. Btu/hr Input 20,000 20,000 20,000 20,000 18,000 18,000 18,000 18,000
Min. Btu/hr Input 15,000 15,000 15,000 15,000
Ori ce size (as shipped)
Natural Propane Natural Propane Natural Propane Natural Propane
10,000–13,000 10,000–13,000 10,000–13,000 10,000–13,000
#44 1.35mm #44 1.35mm #45 1.28mm #45 1.28mm
BEFORE YOU START
Read this homeowner manual thoroughly and follow all instructions carefully. Inspect all contents for shipping damage and immediately inform your dealer if any damage is found. Do not install any unit with damaged, incomplete, or substitute parts. Check your packing list to verify that all listed parts have been received. You should have the following:
• Fireplace (Firebox and Burner System) • Rock Wool
• Log Set • Volcanic Rock
ITEMS REQUIRED FOR INSTALLATION
Tools: Building Supplies:
• Phillips Screwdriver • Framing Materials
• Hammer • Wall Finishing Materials
• Saw and/or saber saw • Caulking Material (Noncombustible)
• Level • Fireplace Surround Material (Noncombustible)
• Measuring Tape • Piping Complying with Local Codes
• Electric Drill and Bits • Tee Joint
• Pliers • Pipe Sealant Approved for use with Propane/LPG
• Square (Resistant to Sulfur Compounds)
• Pipe Wrench
6 69D0023
FIREBOX FRAMING FOR CDVR33/36
FIREPLACE FRAMING
Firebox framing can be built before or after the appliance is set in place. Construct firebox framing following Figure 2 and the chart below for your specific installation require­ments. See Figure 5 on Page 9 for firebox dimensions. The framing headers may rest on the top of the firebox standoffs.
Do not bring headers below top of standoffs.
The firebox may be installed directly on a combustible floor or raised on a platform of an appropriate height. When the firebox is installed directly on carpeting, tile, or other com­bustible material, other than wood flooring, the firebox shall be installed on a metal or wood panel extending the full width and depth of the enclosure.
H
D
F
G
C
A
Do not fill spaces around firebox with insulation or other materials. This could cause a fire.
WARNING
A B C D E F G H
CDVR33
331/4"
35" 211/2" 103/4" 483/4" 241/2" 133/4" 341/2"
C
CDVR36
371/2" 381/8" 223/8"
11" 527/16" 263/16"
151/4"
371/16"
E
CDVR33 and CDVR36 Corner Installation
B
A
CDVR33 and CDVR36
Stud Location
Figure 2 - Framing Dimensions
A
1
/2" or 5/8"
CDVR33 and CDVR36 Inside Chase Installation
C
G
A
CDVR33 and CDVR36 Recessed Installation or
Outside Chase
1
/2" or 5/8"
G
69D0023 7
FIREPLACE FRAMING
FIREBOX FRAMING FOR CDVT33/36
Firebox framing can be built before or after the appliance is set in place. Construct firebox framing following Figure 3 and the chart below for your specific installation requirements. See Figure 4 on Page 10 for firebox dimensions. The framing headers may rest on the top of the firebox standoffs. Do not bring headers below top of standoffs.
The firebox may be installed directly on a combustible floor or raised on a platform of an appropriate height. When the firebox is installed directly on carpeting, tile, or other combustible material, other than wood flooring, the firebox shall be installed on a metal or wood panel extending the full width and depth of the enclosure.
CDVT33 CDVT36
Do not fill spaces around firebox with insulation or other materials. This could cause a fire.
WARNING
H
A33 B 35" 381/8" C21 D10 E48 F24 G13
D
H34
1
/4"37
1
/2"22
3
/4" 11"
3
/4"52
1
/2"26
3
/4"15
1
/2"37
F
7
3
1
1
/2"
3
/8"
/16" /16"
1
/4"
/16"
C
A
E
CDVT33 and CDVT36 Corner Installation
B
G
C
A
CDVT33 and CDVT36 Inside Chase Installation
C
G
1
/2" or 5/8"
G
A
CDVT33 and CDVT36 Stud Location
A
CDVT33 and CDVT36 Recessed Installation or Outside Chase
1
/2" or 5/8"
Figure 3 - Framing Dimensions
8 69D0023
PRE-INSTALLATION INFORMATION
CDVT33 CDVT36
A331/4"37
1
/2" B 35" 381/8" C1311/16"15
1
/4" D 33" 371/16" E343/4"37
143/16"
F G213/8"21 H3111/16"34
I7
3
/8"9"
J273/16"29 K153/16"20
3
/8"
153/4"
7
/8"
1
/2"
1
/16"
3
/8"
L297/8" 32"
7
9
3
/8"
/16"
/16"
M161/2"18 N25/16"2 O73/16"5
Figure 4 - CDVT33 and
CDVT36
Fireplace Dimensions
Finishing
Spacers
2
G
M
C
Framing
Dimension
I
13
1
/16"
1
1
/4"
1
/2"
K
15
/16"
5
/8"
1
/2"
D
L
J
A
Framing Dimension
F
Nailing T abs Will Accommodate
1
/2" or 5/8" Finishing Material
5
/8"
1
/2"
B
Framing
Dimension
H
1
/2"
5
/8"
N
E
O
CDVR33 CDVR36
A331/4"37
1
/2" B 35" 381/8" C133/4"15
1
/4" D 33" 371/16" E343/4"37
F1311/16"15 G213/8"21 H3111/16"34
3
/8"
3
/4"
7
/8"
1
/2"
I2115/16"253/16"
J273/16"29 K153/16"20
1
3
/16"
/8"
L297/8" 32"
7
9
3
/8"
/16"
/16"
M513/16"18 N25/16"2 O73/16"5
Figure 5 - CDVR33 and
CDVR36
Fireplace Dimensions
Finishing
Spacers
M
1
1
/4"
K
15
/16"
Framing Dimension
G
C
Framing
Dimension
5
/8"
1
/2"
D
L
J
A
F
Nailing T abs Will Accommodate
1
/2" or 5/8" Finishing Material
5
/8"
1
/2"
B"
Framing
Dimension
H
1
/2"
5
/8"
N
E
I
O
69D0023 9
PRE-INSTALLATION INFORMATION
FIREPLACE LOCATION
Plan for the installation of your appliance. This includes determining where the unit is to be installed, the vent configuration to be used, framing and finishing details, and whether any optional accessories (i.e. blower, wall switch, or remote control) are desired. Consult your local building code agency to ensure compliance with local codes, including permits and inspec­tions.
The following factors should be taken into consideration:
Clearance to side-wall, ceiling, woodwork, and windows. Minimum clearances to combustibles must be maintained.
This fireplace may be installed along a wall, across a corner, or use an exterior chase. See Figure 6 for suggested loca­tions.
Location should be out of high traffic areas and away from furniture and draperies due to heat from appliance.
Never obstruct the front opening of the fireplace.
• Do not install in the vicinity where gasoline or other flammable liquids may be stored.
Vent pipe routing. See Venting section found in this manual for allowable venting configurations.
These units can be installed in a bedroom. See National Fuel Gas Code ANSI Z233.1/NFPA 54 — (current edition), the Uniform Mechanical Code — (current edition), and Local Building Codes for specific installation requirements.
A Flat on Wall B Cross Corner C Island**
E
Y
A
B
D Room Divider* E Flat on Wall Corner*
C
X
F Chase Installation Y 4" Minimum
D
Y
F
Figure 6 - Locating Gas Fireplace
** Island (C) and room divider (D) installation is possible as long as the horizontal portion of vent system (X)
does not exceed 20'. See Installing Horizontal Termination Configuration on pages 18 and 19.
* When you install your fireplace in (D) room divider or (E) flat on wall corner positions (Y), a minimum of 4"
clearance must be maintained from perpendicular wall and front of fireplace.
10 69D0023
CLEARANCES TO COMBUSTIBLES
Follow these instructions carefully to ensure safe installation. Failure to follow in struc tions exactly can create a fire hazard.
The appliance cannot be installed on a carpet, tile or other combustible material other than wood flooring. If installed on carpet or vinyl flooring, the appliance shall be installed on a metal, wood or noncombustible material panel ex tend ing full width and
WARNING
depth of the appliance.
72” Minimum (CDV33)
71" Minimum (CDV36)
CLEARANCES
12"
Maximum
Depth
12" Min. for CDV33 13” Min. for CDV36
Minimum 6"
from both
side walls (CDV33)
Minimum 4”
from both
side walls (CDV36)
Figure 7 - Clearances
MANTEL CLEARANCES
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it does, it is considered a mantel and must meet the mantel requirements listed in this manual.
69D0023 11
SECURING FIREPLACE TO FLOOR OR FRAMING
The fireplace must be secured to the floor and/or to framing studs as shown in Figure 8. Use two (2) wood screws or masonry/ concrete screws to secure fireplace to the floor. Use four (4) screws to attach fireplace to framing. The side nailing flanges
1
are
/2" or 5/8" to accommodate different wall thickness.
Drywall Support Tabs
(Do Not Use for Framing
or Header)
Framing
Nailing Flange
Screws
Screws
Nailing Flange
Framing
Nailing Flange
Screws
Nailing Flange
Figure 8 - Securing Fireplace to Floor and Framing Studs (CDVT36 shown)
12 69D0023
INSTALLATION INFORMATION
FINISHING MATERIAL
NOTE: Any wiring (i.e. remote control, wall switch, and optional fan) must be done prior to final finishing to avoid costly reconstruction.
Never obstruct or modify the air inlet or outlet grills (louvers). This may create a fire hazard.
WARNING
Only noncombustible materials (i.e. brick, tile, slate, steel, or other materials with a UL fire rating of Zero) may be used to cover the black surface of the appliance. A 300°F minimum adhesive may be used to attach facing materials to the black surface. If joints between the finished wall and the fireplace surround are sealed, a 300°F minimum sealant material (General Electric RTV103 or equivalent) must
be used.
VENT INSTALLATION
Read all instructions completely and thoroughly before attempting installation. Failure to do so could result in serious injury, property damage or loss of life. Operation of improperly installed and maintained venting system could result in serious injury, property damage or loss of life.
WARNING
Failure to follow these instructions will void the warranty.
WARNING
INSTALLATION PRECAUTIONS
Consult local building codes before beginning the installation. The installer must make sure to select the proper vent system for installation. Before installing vent kit, the installer must read this fireplace manual and vent kit instructions.
Only a qualified installer/service person should install venting system. The installer must follow these safety rules:
• Wear gloves and safety glasses for protection.
• Use extreme caution when using ladders or when on rooftops.
• Be aware of electrical wiring locations in walls and ceilings.
The following actions will void the warranty on your venting system:
• Installation of any damaged venting component.
• Unauthorized modification of the venting system.
• Installation of any component part not manufactured or approved by MHS.
• Installation other than permitted by these instructions.
69D0023 13
VENT INSTALLATION
REAR VENT INSTALLATION
This fireplace must be vented to the outside. The venting system must NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each gas appliance must use a separate vent system. Do not use common vent systems.
WARNING
Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the flue and 1" clearance at the sides and bottom until the flue penetrates the outside wall. A minimum 1" clearance all around the flue is acceptable at this point of penetration.
WARNING
Vertical sections of this vent system require
WARNING
a minimum of 1" clearance to combustibles on all sides of the pipe.
3"
A Minimum of 3" Clearance
to the Top Is Required Along
Horizontal Length until Flue
Pipe Penetrates Outside Wall.
1"
1"
1"
A Minimum 1"
Clearance to
Combustibles
Permitted All
Around Flue
at Outside
Wall
Figure 9 -
Combustible
Clearances for
Vent Pipe -
CDVR36 and CDVR33
14 69D0023
TOP VENT INSTALLATION
This fireplace must be vented to the outside. The venting system must NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each gas appliance must use a separate vent system. Do not use common vent systems.
WARNING
VENT INSTALLATION
Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the flue and 1" clearance at the sides and bottom until the flue penetrates the outside wall. A minimum 1" clearance all around the flue is acceptable at this point of penetration.
WARNING
Vertical sections of this vent system require a minimum of 1" clearance to combustibles on all sides of the pipe.
A Minimum of 3" Clearance
to the Top Is Required Along
Horizontal Length until Flue
Pipe Penetrates Outside Wall.
1"
3"
1"
1"
A Minimum 1"
Clearance to
Combustibles
Permitted All
Around Flue
at Outside
Wall
Figure 10 -
Combustible Clearances
for Vent Pipe,
CDVT33 and CDVT36
69D0023 15
VENT INSTALLATION
INSTALLATION PLANNING
There are two basic types of direct-vent installation:
• Horizontal Termination
• Vertical Termination
It is important to select the proper length of vent pipe for the type of termination you choose. It is also important to note the wall thickness.
FOR HORIZONTAL TERMINATION
Select the amount of vertical rise desired. All horizontal run of venting must have
You may use up to three 90° elbows in this vent configuration. See Horizontal Termination Configurations on pages 21 and 22.
FOR VERTICAL TERMINATION
Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical rise in an attic or second story, and allow for sufficient vent height above the roof line.
NOTE: You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when using 45° elbows. The appliance is approved for use with three 90° elbows maximum or a combination of 90° and 45° elbows up to a maximum of 270°.
1
/4" rise for every 12" of run towards the termination.
Never run the vent pipe level or downward. This may cause excessive temperatures which could cause a fire.
WARNING
For two-story applications, firestops are required at each floor level. If an offset is needed in the attic, additional pipe and elbows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house. See Installing Vent System in a Chase below. If pipe is enclosed in chase, it is not exposed.
It is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust. Certain limitations apply to vent configurations and must be strictly followed.
INSTALLING A VENT SYSTEM IN AN OUTSIDE CHASE
A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a building. A chase is required for such venting.
Treatment of firestops and construction of the chase may vary from building type to building type. These instructions are not substitutes for the requirements of local building codes. You must follow all local building codes.
NOTICE
When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially important in cold climates. Insulation should be considered a combustible material. Maintain proper clearances to all combustible materials.
NOTICE
16 69D0023
VENT INSTALLATION
FOR HORIZONTAL TERMINATION
D
E
B
L
V
Vent Terminal Air Supply Inlet Area Where Terminals Not Permitted
C
V
F
V
B
Fixed
Closed
Operable
A
BB
B
Opera-
ble
V
A
V
Fixed
Closed
J
G
V
H
V
A
B
A
I
M
V
Inside Corner Detail
G
A
K
A
Figure 11 - Horizontal Vent Termination Location
MINIMUM DISTANCES
A = Clearance above the grade, a veranda, porch, deck, or balcony [*12" (305mm) minimum]. B = Clearance to window or door that may be opened [*12" (305mm) minimum]. C = Clearance to permanently closed window [*minimum 12" (305mm) recommended to prevent condensation on
window]
D = Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of two (2) feet (610mm)
from the centerline of the terminal [18" (457mm) minimum]. E = Clearance to unventilated soffits [12" (305mm) minimum]. Clearance to vinyl soffit [30" (762mm)]. F = Clearance to an outside corner. See Figure 12. G = Clearance to an inside corner. See Figure 12. H = *Not to be installed above a gas meter/regulator assembly within three (3) feet (914mm) horizontally from the centerl
ine of the regulator. I = Clearance to service regulator vent outlet [*3' (914mm) minimum]. J = Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance [*12" (305mm)
minimum]. K = Clearance to a mechanical air supply inlet [*6' (1829mm) minimum]. L = Clearance above a paved sidewalk or paved driveway located on public property [**7' (2133mm) minimum]. M = Clearance under veranda, porch, deck, or balcony [*12" (305mm) minimum
***
].
N = Clearance above a roof shall extend a minimum of 24" (610mm) above the highest point when it passes through the roof
surface and any other obstruction within a horizontal distance of 18" (457mm).
* As specified in CAN/CGA B149 Installation Codes. Note: Local codes or regulations may require different
clearances. ** A vent must not terminate directly above a sidewalk or paved driveway, which is located between two single-family
dwellings and serves both dwellings. *** Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
Always maintain minimum clearances around vent systems. The minimum clearances to combustibles for horizontal vent pipe are 3" at the top and 1" at the sides and bottom of the vent system until the pipe penetrates the nearest vertical wall (1" required). A 1" minimum clearance all around the pipe must be maintained at outside wall and on vertical runs. Do not pack the open air spaces with insulation or other materials. This
WARNING
could cause high temperatures and may present a fire hazard.
69D0023 17
VENT INSTALLATION
TERMINATION CLEARANCES FOR BUILDINGS WITH COMBUSTIBLE AND NONCOMBUSTIBLE EXTERIORS
G Combustible =
6" (152mm)
V
Noncombustible = 2” (51mm)
Inside Corner
V
Outside Corner
Combustible =
F
6" (152mm)
Noncombustible = 2” (51mm)
H
G
V
Combustible &
G = Combustible 24"(610mm) Noncombustible 18"(457mm)
Balcony with No Side Wall Balcony with Perpendicular
Noncombustible H = 24" (610mm) J = 20" (508mm)
V
J
Side Wall
Figure 12 - Allowable Venting Chart
HOW TO USE THE VENT GRAPH
The Vent Graph should be read in conjunction with the following vent installation instructions to determine the relationship between the vertical and horizontal dimensions of the vent system.
1. Determine the height of the center of the horizontal vent pipe
exiting through the outer wall. Using this dimension on the Sidewall Vent Graph below, locate the point intersecting with the slanted graph line.
2. From the point of this intersection, draw a vertical line to the
bottom of the graph.
3. Select the indicated dimension, and position the fireplace in
accordance with same.
Example: If the vertical dimension from the floor of the
fireplace is 11' (3.4m) the horizontal run to the face of the outer wall must not exceed 14' (4.3m).
Example: If the vertical dimension from the floor of the unit
is 7’ (2.14m), the horizontal run to the face of the outer wall must not exceed 8
Sidewall Vent Graph showing the relationship between vertical and horizontal dimensions for a Direct Vent flue system.
1
/2' (2.6m).
D
C
C
V
E
C = Maximum depth of 48" (1219mm) for alcove location D = Minimum width for back wall of alcove location Combustible - 38" (965mm) Noncombustible - 24" (610mm) E = Clearance from corner in alcove location Combustible - 6" (152mm) Noncombustible - 2" (51mm)
Alcove Location
40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10
8 6 4
20"
2
Horizontal Dimension From the Outside of
Termination to the Back of the Fireplace
Dimensions in
Feet
Horizontal Vent Pipe
eg: A
2 4 6 8 10 1214 16 1820
Figure 13 - Side Wall Venting Graph
Vertical Dimension From the Floor of Unit to the Center of the
18 69D0023
VENTING INSTALLATION
REAR (THROUGH THE WALL) APPLICATIONS
When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance
• The maximum horizontal distance between the rear of the appliance and the outside of termination is 20" (508 m). See
Figure 14.
• Only one 45° elbow is allowed in these installations.
Maximum
20"
Top View Flat Installation
Figure 14 - Rear Vent Application,
Maximum Horizontal Distance
1. Rigid vent pipes and fittings have special twist-lock connections. Assemble the desired combination of pipe and elbows to the appliance adaptor.
Twist-lock Procedure: The female ends of
the pipes and fittings have three locking lugs (indentations). These lugs will slide straight into matching slots on the male end of adja­cent pipes and fittings. Push the pipe sections together and twist one section clockwise approximately one-quarter turn until the sec­tions are fully locked. See Figure 15.
2. Locate and cut the vent opening in the wall. For combustible walls first frame in opening.
Combustible Interior Walls: Cut a 11
1
/2"H x
91/2" W hole through the interior wall.
Combustible Exterior Walls: Cut a 9
1
/2"W square hole through the exterior
x 9
1
/2"H
wall frame. See Figure 16.
Female
Locking Lugs
Note: Horizontal runs of vent must be supported every three feet (914 mm). Use wall straps for this purpose.
Male Slots
Figure 15 - Rigid Vent Pipe Connections
91/2"
(241mm)
91/2"
(241mm)
33/4"
(92mm)
Noncombustible Walls: Hole opening should
be 71/2" (190 mm) in diameter.
3. The center of the hole should line up with the center line of the horizontal rigid vent pipe
1
end. Allow
/4" minimum rise per foot. See
71/2"
(190mm)
Figure 16.
Figure 16 - Exterior Wall Framing Dimensions
69D0023 19
VENT INSTALLATION
REAR WALL VENT INSTALLATION (continued)
4. Apply a bead of non-hardening mastic around the outside edge of vent cap. Position the vent cap in the center of hole on the exterior wall with the word “UP” on the vent cap facing up. Insure proper clearance of 1" to combustibles is maintained to the flue. Attach the vent cap with four wood screws supplied. See Figure 17.
Do not recess vent termination into any wall. This will cause a fire hazard.
WARNING
NOTE: Replace the wood screws with appropriate fasteners for stucco, brick, concrete, or other types of siding.
Vent Cap
HOT
Wood
Screw
Apply Mastic to
All Four Sides
Figure 17 - Installing Horizontal Termination
A vinyl siding standoff must be used with the Simpson or Silkirk Horizontal Termination on vinyl, stucco or wood-clad exterior walls. Monessen termination does not require a standoff. Apply non-hardening mastic around outside edge of the standoff instead of the vent cap assembly. See Figure 18.
5. Slide the firestop over the vent pipe before connecting the horizontal run to the vent cap. See Figure 19.
6. The termination should overlap the flue a minimum of 1
1
/4" Apply silicone to the outer pipe/termination connection.
Fasten termination with screws provided.
7. Slide the firestop against the interior wall surface and attach with screws. See Figure 19.
Cut Vinyl Siding
Away to Fit Standoff
Standoff #950 or 4DT-VS
Interior Wall
Surface
(not required for
Monessen Termination)
Firestop
Termination
Vent Cap
(Horizontal
Apply
Mastic to
All Four
Sides
Nut
Wood Screw
HOT
Bolt
Termination)
Screw
Horizontal
Vent Pipe
Figure 18 - Installing Simpson Vinyl Siding
Standoff and Termination
20 69D0023
Figure 19 - Installing Firestop on
Horizontal Vent Pipe
VENT INSTALLATION
HORIZONTAL TERMINATION CONFIGURATIONS
Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain limita­tions as to vent configurations apply and must be strictly adhered to.
The Vent Graph, showing the relationship between vertical and horizontal side wall venting, will help to determine the various dimensions allowable.
See Figure 20.
NOTE: Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the flue and 1" clearance at the sides and bottom until the flue penetrates the outside wall. A minimum 1" clearance all around the flue is acceptable at this point of penetration.
Vertical sections of this vent system require a minimum of 1" clearance to combustibles on all sides of the pipe.
When vent exits through foundations less than 20" below outcrop, the termi­nation must be flush up with outcropped wall above.
It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace (or the top of the Transition Elbow) to the face of the outer wall.
40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10
8 6 4
20"
2
2 4 6 8 10 1214 16 1820
Horizontal Dimension From the Outside of
Termination to the Back of the Fireplace
eg: A
Vertical Dimension From the Floor of Unit to the Center of the
Horizontal Vent Pipe
Figure 20 - Rear Wall Venting Graph
When installing the appliance as a rear vent unit, the 90° or 45° transition elbow attached directly to the rear of the unit is NOT INCLUDED in the following criteria and calculations, and unless specifically mentioned should be ignored when calculating venting layouts.
WARNING
• The maximum number of 90° elbows per side wall installation is three (3). See Figure 21.
• If a 90° elbow is fitted directly on top of the fireplace flange the maximum horizontal vent run before the termination or a vertical rise is 36” (914 mm). See Figure 22.
3 x 90° Elbows
3 x 90° Elbows
36"
Max.
36"
Max.
Figure 21 - Maximum Three (3) 90° Elbows
Figure 22 - Maximum Horizontal Run with No Rise
Per Installation
69D0023 21
VENT INSTALLATION
HORIZONTAL TERMINATION CONFIGURATION
(Continued)
• If a 90° elbow is used in the horizontal vent run (level height maintained) the horizontal vent length is reduced by 36". See Figures 21 and 22, page 20. This does not apply if the 90° elbows are used to increase or redirect a vertical rise.
See Figure 24.
Example: According to the vent graph (page 20) the maximum horizontal vent length in a system with a 7.5' vertical rise is 20’ (6m) and if a 90° elbow is required in the horizontal vent it must be reduced to 17' (5.2 m).
In Figures 23 and 24, Dimension A plus B must not be greater than 17' (5.2m).
• The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.
• For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (45cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.
• The maximum number of elbow degrees in a system is 270°.
See Figure 25.
B
A
10'
7'
90°
AB
7'6"
Figure 23 - Horizontal Run Reduction
Example: Elbow 1 = 90° Elbow 2 = 45° Elbow 3 = 45° Elbow 4 = 90° Total Angular Variation = 270°
1
2
3
4
90° Elbow = 3'
7'6"
A + B = 17' Maximum
1 + 2 + 3 + 4 = 270°
Figure 24 - Maximum Vent Run with Elbows
22 69D0023
Figure 25 - Maximum Elbow Usage
1
2
3
4
VENT INSTALLATION
BELOW GRADE INSTALLATIONS
When it is not possible to meet the required vent terminal clearances of 12" above grade level, a snorkel kit is recommended. It allows installation depth down to 7" (178mm) below grade level. The 7" (178mm) is measured from the center of the horizontal vent pipe as it penetrates through the wall.
Ensure that sidewall venting clearances are observed. If venting system is installed below ground, we recommend a window well with adequate and proper drainage to be installed around the termination area.
If installing a snorkel, a minimum 24" vertical rise is necessary. The maximum horizontal run with the 24” vertical pipe is 36". This measurement is taken from the collar of the fireplace (or transition elbow) to the face of the exterior wall. See the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 24".
1. Establish vent hole through the wall. See Figure 16, page 18.
2. Remove soil to a depth of approximately 16" below base of snorkel. Install drain pipe. Install window well (not supplied). Refill hole with 12" of coarse gravel leaving a clearance of approximately 4" below snorkel. See Figure 26.
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe coming through the wall.
5. Apply high temperature sealant caulking (supplied) around the 4" and 7" snorkel collars.
6. Slide the snorkel into the vent pipes and secure to the wall.
7. Level the soil so as to maintain a 4" clearance below snorkel. See Figure 26.
• Do not back fill around snorkel.
• A clearance of at least 4" must be maintained between the snorkel and
WARNING
If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to wall first, then secure to snorkel with self drilling #8x1/2 sheet metal screws. It will be necessary to extend vent pipes out as far as the protruding wall face. See Figure 27.
Screws
Firestop
24"
Minimum
the soil.
Minimum
4" Clearance
Ground
Window Well
Gravel
Drain
Foundation Wall
Foundation
Recess
Watertight Seal
Around Pipe
Snorkel
Wall Screws
Sheet Metal
Screws
Figure 27 - Snorkel Installation,
Figure 26 - Below Grade Installation
69D0023 23
Recessed Foundation
VENT INSTALLATION
VERTICAL (THROUGH-THE-ROOF) APPLICATIONS
This Gas Fireplace has been approved for,
• Vertical installations up to 40' (12m) in height. Up to a 10' (3m) horizontal vent run can be installed within the vent system using a maximum of two 90° elbows. See Figure 28.
NOTE: Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the flue and 1" clearance at the sides and bottom until the flue penetrates the outside wall. A minimum 1" clearance all around the flue is acceptable at this point of penetration.
Vertical sections of this vent system require a minimum of 1" clearance to combustibles on all sides of the pipe.
Support
10'
Maximum
40' Maximum Height
8' Minimum Height
• Up to two 45° elbows may be used within the horizontal run. For each 45° elbow used on the horizontal plane, the maximum horizontal length must be reduced by 18" (450mm).
Support Straps
Every 3'
Straps
Every
5'Vertical
Figure 28 - Support Straps for Horizontal Runs
40' Maximum Height
8' Minimum Height
1
2
3
4
10'
Maximum
Support Straps
Every 3'
Example: Maximum horizontal length
No elbows = 10’ (3m)
1x45° elbows = 8.5’ (2.6m)
2x45° elbows = 7’ (2.1m)
• A minimum of an 8' (2.5m) vertical rise is required.
• Two sets of 45°elbows offsets may be used within the vertical sections. From 0 to a maximum of 8' (2.5 m) of vent pipe can be used between elbows.
See Figure 29.
• The maximum angular variation allowed in the system is 270°. See Figure 29.
• The minimum height of the vent above the high­est point of penetration through the roof is 2' (610mm).
24 69D0023
Example: Elbow 1 = 45° Elbow 2 = 45° Elbow 3 = 90° Elbow 4 = 90° Total Angular Variation = 270°
Figure 29 - Maximum Elbow Usage
1
2
3
4
INSTALLATION FOR VERTICAL TERMINATION
1. Determine the route your vertical venting will take. If ceiling joist, roof rafters or other framing will obstruct the venting system, consider an offset. See Figure 30 to avoid cutting load bearing members.
VENT INSTALLATION
Roof
Flashing
For optimal flame appearance, a restrictor disk is necessary on straight vertical runs of 20' of more.
• Runs may not incorporate elbows.
• The disk is part number 45D0551 and is included in installa-
tion manual packet.
• Drop the disk into a 4" inner collar before installing the first
section of flue or install at the last section before installing the termination.
• An additional disk may be installed on runs of 35' or more.
Rotate disks perpendicular to each other.
NOTE: Pay special attention to these installation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations. Offsets must fall within the parameters shows in Figure 13, page 20.
2. Set fireplace in desired location. Drop a line plumb down from the ceiling to the position of the flue exit. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole a this point.
Wall
Strap
45° Elbows
Ceiling Firstop
Figure 30 - Offset with Wall Strap and 45°
Elbows
Nails
Drop a plumb line from the inside of the roof to the ceiling locat-
ing hole in the ceiling. Mark the center point where the vent will
Firestop
penetrate the roof. Drill a small locating hole at this point.
Figure 31 - If Area Above is a Room, Install
FLAT CEILING INSTALLATION
1
1. Cut a 9
/2" (241mm) square hole in the ceiling using the locating hole as a center point The opening should be framed to 91/2"x91/2" (241mm x 241mm) inside dimensions as shown in Figure 32using
Firestop above Framed Hole as Shown
1
"
1
2
/
9
9
/
2
"
framing lumber the same size as the ceiling joist. If the area above the ceiling is an insulated ceiling or a room, nail firestop from the top side. This prevents loose insulation from falling into the required clearance space. See Figure 31. Otherwise, install firestop below the framed hole. See Figure 32.
2. Assemble the desired lengths of pipe and elbows necessary to reach from the burner system flue up through the firestop. Be sure pipe and elbow connections are fully twist-locked. See Figure
15, page 19.
Continued
Figure 32 - If Area Above is Not a Room, Install
Nails
Firestop
Firestop under Framed Hole as Shown
69D0023 25
VENT INSTALLATION
3. Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in
1/
roof). The 91/2"x9
2
" (241mm x 241mm) hole must be measured on the horizontal. Actual length may be larger depending on the pitch of the roof. There must be a 1" minimum clearance from the vent pipe to combustible materials. (Insulation should be considered a combustible material).
4. Connect a section of pipe and extend up through the hole.
NOTE: If an offset is needed to avoid obstructions, you must support the vent pipe every three (3) feet. Use wall straps for this purpose. See Figure 28, page 23. Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of the flue gases and intake air.
5. Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and framing with roofing nails. Be sure roofing material overlaps the top edge of the flashing. There must be a 1" clearance from the vent pipe to combustible materials.
6. Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements.
NOTE: You must increase vent height for steep roof pitches. Nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem.
NOTE: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction material. Make sure to meet the minimum allowable clearances to combustibles. Do not fill any of the required clearance spaces with insulation.
CATHEDRAL CEILING INSTALLATION
IMPORTANT: Review all information on previous
Level
Cathedral
Ceiling
Support Box
page before planning this installation. Cathedral ceiling installations can be very tricky.
1. Remove shingles or other roof covering as necessary to
cut the rectangular hole for the support box. Mark the outline of the cathedral ceiling support box on the roof
2" Minimum
Below
Finished
Ceiling
sheathing using the locating hole as a center point.
2. Cut the hole 1/ 8" larger than the support box outline. See
Figure 33.
Cut Hole 1/8"
Larger than
Support Box when
3. Lower the support box through the hole in the roof until
the bottom of the box extends at least 2" ( mm) below
Projected onto
Roof line.
the ceiling. See Figure 33. Align the support box verti­cally and horizontally using a level. Temporarily tack the support box in place through the inside walls and into the
Figure 33 - Cathedral Ceiling Support Box
Installation
roof sheeting.
4. Using tin snips, cut the support box from the top corners
down to the roof line and fold the resulting flaps over the roof sheeting. See Figure 34. Apply a bead of non-hard­ening mastic around the top edges of the support box to make a seal between the box and the roof. Nail in place with roofing nails. Remove any combustible material that might be inside the support box.
5. Complete the cathedral ceiling installation by following
the same procedures outlines in steps 2 through 6 for Flat Ceiling Installation, page 25 and above.
26 69D0023
Figure 34 - Installed Cathedral Ceiling
Support Box
Apply Non-hardening
Mastic Under all Edges
of Support Box before
Nailing
FIREPLACE INSTALLATION
CHECK GAS TYPE
Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install fireplace. See dealer where you purchased the fireplace for proper fireplace for your gas type or conversion kit.
INSTALLING GAS PIPING TO FIREPLACE / BURNER SYSTEM LOCATION
A qualified installer or service person must connect appliance to gas supply. Follow all local codes.
WARNING
All electric heaters have hot and arcing or sparking parts inside. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
CAUTION
INSTALLATION ITEMS NEEDED
Before installing fireplace and burner system, make sure you have the items listed below.
• External regulator (supplied by installer) • Piping (check local codes) • Sealant (resistant to propane/LP gas)
• Equipment shutoff valve* • Test gauge connection* • Sediment trap (recommended)
• Tee joint • Pipe wrench
• approved flexible gas line with gas connector (if allowed by local codes — not provided)
1
* A CSA design-certified equipment shutoff valve with Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 35. Pointing the vent down protects it from freezing rain or sleet.
External
Regulator
100 lb. (min)
Propane/LP
Supply Tank
/8" NPT tap is an acceptable alternative to test gauge connection.
Use only new black iron or steel pipe. Internally tinned copper or copper tubing can be used per National Fuel Code, section 2.6.3, providing gas meets hydrogen sulfide limits, and where permitted by local codes. Gas piping system must be sized to
CAUTION
provide minimum inlet pressure (listed
Vent
Pointing
Down
on data plate) at the maximum flow rate (BTU/hr). Undue pressure loss will occur if the pipe is too small.
When using copper of flex connectors use only fittings
Figure 35 - External Regulator with Vent Pointing
Down (Propane/LP Only)
69D0023 27
approved for gas connections. The gas control inlet is
3
/8" NPT.
FIREPLACE INSTALLATION
Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.
WARNING
NOTE : The gas line connection may be made using 1/2" rigid tubing or an approved flex connector. Since some municipalities have additional local codes it is always best to consult your local authorities and the current edition of the National Fuel Gas Code ANSI.Z223.1, NFPA54. In Canada CAN/CGA-B149 (1 or
2) Installation Code.
A listed manual shutoff valve must be installed upstream of the appliance. Union tee and plugged 1/8" NPT pressure tapping point should be installed upstream of the appliance. See Figure 36.
A manual shutoff valve must be installed upstream of the appliance. Union tee and plugged 1/8" NPT pressure tapping point should be installed upstream of the appliance.
CAUTION
See Figure 36.
Use pipe joint sealant that is resistant to liquid
IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location. The main gas valve is for turning on or shutting off the gas to the fireplace.
Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged burner system valves.
petroleum (LP) gas.
CAUTION
We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 36. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and burner system. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap collects moisture and contaminants and keeps them from going into the burner system gas controls. If sediment trap/drip leg is not installed or is installed wrong, burner system may not run properly.
Approved Flexible
Gas Line
Sediment Trap/Drip Leg
CSA Design-Certified Equipment
Shutoff Valve with
Tee Joint Pipe Nipple Cap
1
/8" NPT Tap*
3" Minimum
Natural Gas
From Gas Meter
(4.5" W.C. to 10.5" W.C. Pressure)
Propane/LP
From External Regulator
(11" W.C. to 13" W.C. Pressure)
Figure 36 - Gas Connection
28 69D0023
CHECKING GAS PRES SURE AND ELECTRICAL INSTALLATION
1. Check gas type. The gas supply must be the same as stated on the appliance’s rating decal. If the gas supply is different from the fireplace, STOP! Do not install the appliance. Contact your dealer immediately.
2. To ease installation, a 30" (mm) flex line with manual shut-off valve has been provided with this appliance. Install and attach
3. After completing gas line connection, purge air from gas line and test all gas joints from the gas meter to the fireplace for leaks. Use a solution of 50/40 water and soap or a gas sniffer.
4. To adjust flame height, turn HI/LO knob to HI to get maximum pressure to burner. Turn HI/LO knob to LO to get minimum pressure.
5. To check gas pressures at valve, turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point. Turn unit to high. See Figure 37. After taking pressure reading, be sure and turn captured screw clockwise firmly to reseal. Do not over torque. Check test points for gas leaks.
1
/2" gas line onto shut-off valve.
Pressure Test “IN”
Pressure
Test “OUT”
HI/LO
Knob
Figure 37 - Gas Pressure Check at Gas Valve
Pilot Adjustment
Screw
Do not use open flame to check for gas leaks.
WARNING
ELECTRICAL WIRING
This fireplace will work without any electrical supply. Electricity is only needed to operate blower.
NOTE: If installed in mobile home, fireplace must be bolted securely to floor.
Electrical connections should only be performed by a qualified, licensed electrician. Main power must be off when connecting to main electrical power supply or performing service. All wiring shall be in compliance with all local, city, and state codes. The appliance, when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code ANSI/ NFPA
WARNING
70 (latest edition) and Canadian Electrical Code, CSA C22.1.
Label all wires before disconnecting when servicing controls. Wiring errors can cause improper and dangerous operation.
CAUTION
Verify proper operation after servicing.
69D0023 29
ELECTRICAL INSTALLATION
REMOTE WALL MOUNTED SWITCH
A remote wall switch and up to fifteen (15) feet of 18 Ga. wire may be used with this appliance. Attach the wall switch in a junc­tion box at the desired location on the wall. See Figure 38. Do not extend beyond the wall switch wire length provided.
NOTE: Extended lengths of wire may cause the fireplace not to function properly. Longer length of wire is permitted if the wire is made out of larger gauge (diameter) wire. Always check with local code.
Do not connect wall switch to heater (110V) circuit.
WARNING
OPTIONAL REMOTE
WALL SWITCH
ON
PILOT
HI
ON
OFF
O
L
TH TP
TH/TP
ON
OFF
RS
OFF
OPTIONAL REMOTE
WALL SWITCH
ON
OFF
Figure 38 - Wiring Diagram for Wall Switch
30 69D0023
ELECTRONIC PILOT IGNITION WIRING
Do not connect 110-120 VAC to the Remote Wall Switch. The appliance will malfunction.
WARNING
Ignition Module (Synetek)
ELECTRICAL INSTALLATION
Pilot Assembly
Spark Sense
WHITE
To Junction Box
GREEN BLACK
#1 #2 #3 #4 #5 #6 7#
RED #2
WHITE #3
Electronic Valve
EV1 EV2
15’ Wall Switch Wire
BLACK
WHITE
Figure 39 - Remote Wall Switch Wiring Diagram
REMOTE WALL SWITCH
Position the wall switch. Do not extend beyond the 15 feet of wire.
OPTIONAL DC REMOTE SYSTEMS
MAGENTA #5
RED #2
HI
LO
GRAY #7
GREEN #6
BLACK #4
BLUE #1
WHITE
BLUE
BLACK
Primary - 120V
Transformer
Secondary
24V
YELLOW
RS OFF
Switch
ON
YELLOW
See section entitled Hearth Mount in the Millivolt hand held remote instructions supplied with the remote.
1. Using a flat head screw driver, bend the “remote” tabs up from the bottom of the fireplace. See
Figure 40.
“Remote” Tabs
2. Follow the instructions on remote control to snap the remote cover plate to the remote receiver
3. Connect the wire terminal from the remote receiver. This replaces the 15' wall switch con-
Remote Control
nection to the switch. See Figure 39.
4. Use the screws that came with the remote control to mount the remote receiver cover to the bent
Figure 40 - Remote Control Location
up “remote” tabs. See Figure 40.
69D0023 31
ELECTRICAL INSTALLATION
OPTIONAL FAN/BLOWER SYSTEMS
The junction box for the fan/blower systems has been factory installed. This system requires that 110-120 VAC to be wired to the factory installed junction box before the fireplace is permanently installed. See Figure 41.
120VAC
Receptacle
Junction
Box
BLACK
GREEN
BLACKBLACK
Speed Control
TANTANWHITE
Optional Thermostatic Switch
Figure 41 - Blower Wiring Diagram
Speed Control
Figure 42 - Speed Control Location
32 69D0023
GLASS FRAME REMOVAL
1. Remove upper and lower louvers.
2. Release two clamps on bottom of fireplace.
See Figures 43 and 44.
3. Tilt glass frame out and lift glass frame up until it clears the hook on top of the frame.
4. Set glass frame aside.
Glass Frame
GLASS REMOVAL
Glass
Frame
Clamps
Figure 44 - Removing Glass Frame - CDVT33 and CDVT36
Each clamp has a quick spring force. When reinstalling clamps, keep fingers clear.
CAUTION
Clamps
Figure 43 - Removing Glass Frame
- CDVR36 and CDVR33
69D0023 33
FINAL INSTALLATION
ROCK WOOL PLACEMENT
1. Place rock wool on burner to provide glowing embers. For best results, pull the rock wool apart into pieces the size of a nickel or smaller.
2. Distribute one layer of rock wool to cover the entire burner. See Figure 45.
Burner
3. Place the logs on the burner. See Log Placement below. Light unit and after 15 minutes, check burner flame and glow. See Burner Flame, page 39.
If the flame is blue and only in the center, turn off unit and let cool. After unit cools, remove logs. If the back holes are clear, add more rock wool to the center of the burner. Replace logs and check flame again. Save left over rock wool to refresh when cleaning later. Too much rock wool can disturb the flame and cause sooting on the glass or logs.
LOG PLACEMENT
1. Place rear log (#1) on grate assembly. Log should rest firmly on the two log mounting pins shown. See Figure 46.
2. Place top right log (#2) on the rear log. Rest the right back side of the log in the flat area of the rear log. Place the narrow front end of the log next to the center vertical grate bar. See
Figure 46.
3. Place the top left log (#3) on the rear log. Nest the forked end of the top left log into the fork or the rear log. Rest the narrow end of the top left log behind the center vertical grate bar. See Figure 46.
Cover with Rock Wool
Figure 45 - Placement of Rock Wool on Burner
Do not use the entire bag of rock wool to cover the burner. This could cause the flame to burn poorly and may lead to sooting.
WARNING
(#3) Top
Left Log
(#1) Rear
Log
(#2) Top
Right Log
Area
Flat
LAVA ROCK AND EMBER PLACEMENT
Sprinkle lava rock on the floor of the inner combustion chamber. Evenly distribute the rock. Do not pile the lava rock up in front of grate. Do not place lava rock on the burner. If desired, purchase optional embers to decorate the floor of the fireplace.
Log Mounting Pins
Left Vertical
Grate Bar
Center Vertical
Grate Bar
Do not sprinkle the lava rock or ember chunks on top of the burner. This may cause potential sooting, glass breakage and a fire hazard.
WARNING
Figure 46 - Log Placement
34 69D0023
Right
Vertical
Grate Bar
MILLIVOLT OPERATING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
If you do not follow these instruction exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
WARNING
A. This appliance is equipped with a pilot which must be lit with built-in piezo ignitor while following these
instructions exactly.
B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Turn off all gas to the appliance.
• Open windows.
Do not attempt to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in, or turn the gas control knob. Never use tools. If the knob will not push in or
turn by hand, don't try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part of it has been under water. Immediately call a qualified service tech-
nician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
LIGHTING PILOT FOR THE FIRST TIME
INITIAL LIGHTING
Purge air from the supply line as follows:
Open main shutoff valve.
Unscrew main pressure test point.
Leave inlet test screw open until gas comes in.
When gas is flowing, tighten inlet screw immediately.
LEAK TESTING
1. Follow the pipe from the gas supply line connection to the gas valve. Check connection for leaks with soap and water mixture.
2. Next check for gas leaks at the burner with soap and water mixture.
Never use an open flame to check for gas leak.
DANGER
3. Check the pilot for gas leaks with soap and water mixture.
69D0023 35
MILLIVOLT OPERATING INSTRUCTIONS
LIGHTING PILOT FOR THE FIRST TIME
APPROVED LEAK TESTING METHOD
You may check for gas leaks with the following methods only:
• Soap and water solution
If using a soap and water solution to test for leaks, DO NOT spray solution
• An approved leak testing spray
onto control body.
WARNING
• Electronic sniffer
NOTE: Remove any excessive pipe compound from the connections.
Never use an open flame to check for
Excessive pipe compound can set off electronic sniffers.
gas leak.
DANGER
Check for gas leaks in each of the following locations:
• Pipe from the gas supply line connection to the gas valve
• Burner connections • Field made joints / gas shutoff valve
• Pilot • Factory made joints
• Each joint or connection • All joints on valve and control body
LIGHTING PILOT
1. Depress and turn knob counterclockwise to pilot position.
2. Depress fully and hold pilot gas knob. Depress piezo ignitor as many times as needed to ignite the pilot. Keep knob fully depressed for a few seconds. Release and check that pilot continues to burn.
If the pilot does not stay lit, repeat steps 1 and 2.
O
N
T
O
L
I
P
F
F
O
PILOT
Figure 47 - Pilot Position
Continued on next page
36 69D0023
MILLIVOLT OPERATING INSTRUCTIONS
LIGHTING BURNER
MAIN BURNER SWITCH
The “ON/OFF/RS” switch for the main burner can be found behind door of the fireplace. This switch allows you to turn on and to turn off the main burner without using the gas valve knob. Make sure the button is in the “ON” position to light the main burner. See Figure 48.
LIGHTING THE BURNER
Depress and turn the knob counterclockwise to the “ON” position. See Figure 49. It will take less than four (4) seconds for the burner to ignite.
PILOT POSITION
Depress and turn knob to pilot position to keep burner off while maintaining the pilot light. See Figure 50.
O
N
T
O
L
I
P
F
F
O
PILOT
ON
OFF
RS
N
O
T
I
L
O
PILOT
O
F
F
P
T
Figure 48 -
On/Off/RS Switch
Depress and turn knob clockwise
The control is fitted with a safety interlock device which prevents unsafe ignition of the pilot burner after the control knob has been turned to the OFF position. The knob may only be rotated back to the PILOT position after the safety magnet has been released (approximately 60 seconds). You will hear a
WARNING
“click” when the safety magnet releases.
Figure 49 - On Position
TO TURN OFF GAS
to “OFF” position. See Figure 51.
Figure 50 - Pilot Position
P
I
L
O
T
F
F
O
O
N
PILOT
Figure 51 - Off Position
69D0023 37
ELECTRONIC IGNITION OPERATING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
A. This appliance is equipped with an ignition device
(Piezo) which automatically lights the pilot. Do NOT try to light the burner by hand.
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Turn off all gas to the appliance.
• Open windows.
Do not attempt to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
C. Turn off all electric power to appliance.
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
WARNING
Never use an open flame to check for gas leak.
DANGER
D. Do not use this appliance if any part of it has been under water. Immediately call a qualified service tech-
nician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
LIGHTING ELECTRONIC IGNITION
1. STOP! Read the safety information above.
2. Set switch to off.
3. Turn off electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
5. Wait 5 minutes to clear out any gas. Then smell for gas,
Figure 52 - Electronic Gas Valve
including near the floor. If you smell gas STOP! Follow “B” —
What to Do if You Smell Gas above. If you do not smell gas, go to the next step.
6. Turn on all electric power to appliance.
7. Turn RS-OFF-ON rocker switch to “ON”.
8. If the appliance will not operate, follow the instruction To Turn Off Gas below and call your service techni­cian or gas supplier.
LO
HI
ON
OFF
PILOT
TO TURN OFF GAS
1. Open lower door.
2. Turn RS-OFF_ON rocker switch to “OFF”.
3. Turn off all electric power to the appliance if service is to be performed.
4. Close lower door.
38 69D0023
CLEANING AND MAINTENANCE
Turn off gas before servicing fireplace. It is recommended that a qualified service technician perform these check-ups at the beginning of each heating season
WARNING
BURNER, PILOT AND CONTROL COMPARTMENT
Keep the control compartment, logs, and burner areas surrounding the logs clean by vacuuming or brushing at least twice a year. Make sure the burner porting, pilot air opening and burner air opening are free of obstructions at all times.
PILOT FLAME
The flames from the pilot should be visually checked as soon as the heater is installed and periodically during normal operation. The pilot flame must always be present when the fireplace is in operation. See Figure 53. The pilot flame has three distinct flames, one engulfing the thermopile, one engulfing the thermocouple, and the other reaching to the main burner..
BURNER
Inspect area around the injector. Remove any lint or foreign material with a brush or vacuum.
BURNER FLAME
The flames from the burner should be visually checked as soon as the heater is installed and periodically during normal operation. In normal operation, at full rate, and after operating for about 15 to 30 minutes, the flame should be yellow and slightly taller than the rear log.
See Figure 54.
Thermocouple
Thermopile
Figure 53 - Pilot Flame
If the flame is blue and only in the center, turn off unit and let cool. After unit is cool, remove logs and check to make sure rock wool is placed correctly. Replace logs.
NOTE: The type of installation, vent system configuration, and wind effects may cause the flame patterns to vary.
Figure 54 - Burner Flame Appearance
69D0023 39
CLEANING AND MAINTENANCE
VENT SYSTEM
The fireplace and venting system should be inspected before initial use and at least annually by a qualified field service person. Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the airflow. Inspect entire venting system to ensure proper function.
GLASS DOOR
Thoroughly clean the inside of the glass door after using the fireplace for ten hours. Periodically clean the glass door as necessary.
When cleaning the glass, remember:
Do not remove the glass when hot. Allow glass to cool before removal.
NEVER use abrasive materials.
Keep children and pets a safe distance away.
Never operate the fireplace without the glass door properly secured.
Never operate the fireplace if the glass is broken.
Replace any glass that is chipped, cracked, or broken. Replacement glass door assemblies MUST be supplied by the
fireplace manufacturer – No substitute materials may be used.
Handle glass door with care to avoid striking or scratching it on hard objects.
To clean glass door, follow “Glass Removal” procedure outlined in the Final Installation section. Film deposit on the inside of the glass should be cleaned off using a nontoxic, non-corrosive, non-abrasive, mild-cleaning solution. Simply apply an adequate amount to the glass and wipe off with a damp cloth. After all maintenance has been completed, re-install glass door.
LOGS
Leave logs installed in the fireplace for cleaning. Vacuum surface of the logs with a brush attachment. If logs must be removed for cleaning, handle carefully by holding gently at each end. Gloves are recommended to prevent skin irritation from ceramic fibers. If skin becomes irritated, wash gently with soap and water. Vacuum surface of logs with brush attachment or brush logs with a soft bristle brush (i.e. clean, dry paintbrush). To place logs back in the fireplace, see “Log Placement” found in the Final Installation section.
NOTE: Do not use fluids to clean ceramic fiber logs.
ROCK WOOL
Replace or add rock wool as required following installation instructions in the Final Installation section of this manual.
40 69D0023
STANDING PILOT IGNITION
SYMPTOM POSSIBLE CAUSE ACTION
1. Spark ignitor will not light pilot after repeated trig­gering of piezo.
2. Pilot will not stay lit after carefully fol­lowing light­ing instruc­tions.
3. Pilot burning, valve knob turned to “ON”, switch is turned to “ON” or “RS”, but burner will not ignite.
4. Frequent pilot outage prob­lem.
A. Wire disconnected.
B. Defective ignitor.
C. No gas or low gas pressure.
D. No Propane/LPG in tank
A. Defective thermocouple
B. Defective valve
A. Defective switch, wall switch,
remote control or wire
B. Pilot flame too small
C. Defective or malfunctioning ther-
mopile
D. Defective valve
A. Pilot flame may be too high or too
low, causing pilot safety to drop out
A. Open door and check to make sure wire is connected to ignitor. B. Check for spark at electrode and pilot. If no spark and electrode
wire is properly connected, replace pilot assembly.
C. Check remote/manual shut off valve from fireplace. Low pressure
can be caused by bent lines, restricted lines, low pressure line pressure. Consult with plumber or gas supplier.
D. Check Propane/LPG tank. Refill tank.
A. Check that thermocouple flame impinges on thermocouple. Clean
and/or adjust pilot for maximum flame impingement. Ensure that the thermocouple connection at the gas valve is fully inserted and tight.
Disconnect the thermocouple from the valve, place one millivolt
lead wire on the tip of the thermocouple and the other meter lead wire on the thermocouple copper lead. Start the pilot and hold the valve knob in. If the millivolt reading is less than 15 mV, replace pilot assembly.
B. If thermocouple is producing more than 15 mV, replace faulty
valve.
A. Check switch and wire for proper connection. Place jumper wires
across terminals of switch. If burner comes on, replace defective switch.If the switch is OK, repeat the same procedure on remote control If burner comes on, replace remote control.
Place jumper wire across wire at gas valves (terminals marked TH
and TP/TH). If burner comes on, wires are faulty or connections are bad. Replace wire.
B. If pilot flame is not close enough to the thermopile, adjust pilot
flame.
C. Check thermopile wire connections to make sure all are tight and
that the thermopile is fully inserted into pilot assembly. Check thermopile with a millivolt meter. Connect leads to TP and TP/TH terminals on the control valve. If meter reading is below 325 mV, replace pilot assembly.
D. Turn valve knob to “On” and switch to “ON.” Take a reading at
the thermopile leads (TP & TP/TH) on the valve. If the meter reads greater than 175 mV and the burner does not light, replace defective valve.
A. Clean and adjust the pilot flame for maximum flame impingement
on thermocouple.
TROUBLESHOOTING
5. The pilot and main burner extinguish while in oper­ation
69D0023 41
A. Inner vent pipe leaking exhaust
gases back into system
B. Horizontal vent improperly pitched
C. Improper vent cap installation
A. Check for flue product leak. Replace defective pipe section.
B. Check horizontal-venting piping is running upward 1/4" per foot.
Do not run the pipe level or downward.
C. Check for proper installation and freedom from debris or blockage
TROUBLESHOOTING
ELECTRONIC IGNITION
START
1. Turn gas supply off.
2. Turn ON/OFF switch to “ON” Power to module (24V Normal)
YES
Is there a spark across
ignitor sensor gap?
YES
Turn on gas.
Does pilot burner light?
YES
NO
NO
NO
Check: Line voltage (120VAC) Low voltage transformer (19.5 minimum VAC) ON/OFF switch Wiring connections
Unplug ignition lead and check spark at module (24VAC normal).
Is spark OK? NO Replace module
YES
A. Check ignition cable ground wiring, ceramic insulator and gap.
Correct if necessary.
B. Does ignition cable show signs of melting or buckling?
Take protective action to shield cable and boot from excessive temperatures.
A. Are all manual gas valves open? Are supply tubing and pressure good? Are pilot burner orifies blocked? B. Check electrical connections between module and pilot
operator on gas control. C. Check for 24VAC across PV-MVPV terminals. If voltage is correct, replace gas control.
If voltage is not correct, replace module.
NO
Does spark stop when pilot is lit?
YES
NO
Does main burner light?
YES
NO
Does system run until ON/OFF switch
is in “OFF” position?
YES
END OF TROUBLESHOOTING
42 69D0023
NOTE: If module goes into lockout, reset system.
A. Check continuity of ignition cable and ground wire. B. Clean flame rod. C. Check electrical connections between flame rod and module. D. Is ceramic flame rod insulator cracked? E. Is pilot flame a steady blue? Does flame cover flame rod? If not, adjust pilot flame. Replace module if problem persists.
A. Check for 24VAC across MV-MVPV terminal. Replace module if there is no voltage. B. Are electrical connections between module and gas
control good?
If connections are good, replace gas control or gas
control operator.
NOTE: If module goes into lockout, reset system.
A. Check continuity of ignition cable and ground wire.
NOTE: If ground is poor or erratic, shutdown may
occasionally occur even though operation is normal at
time of checkout.
B. Is pilot flame a steady blue? Does flame cover flame rod?
If above checks out, replace module.
GENERAL TROUBLESHOOTING
SYMPTOM POSSIBLE CAUSE ACTION
1. Glass Soots A. Flame impingement on logs A. Install log set per the instructions Inspect the injector and air intake area. Make sure this area does
not have any blockage from debris and clean.
Check gas supply.
2. Flame burn
blue and lifts off burner (ghosting)
A. Insufficient oxygen being supplied A. Ensure that the vent cap is installed properly and free of debris.
Ensure that the vent system joints are tight and have no leaks. Ensure that no debris has been blocking the inner air intake at the bottom back of the combustion chamber. Ensure that the glass is properly secure and latched.
TROUBLESHOOTING
69D0023 43
ILLUSTRATED PARTS LISTS
FIREBOX COMPONENTS
3
9
2
5
(CDVT33
AND
CDVT36)
6
6
5
6
(CDVR33
AND
CDVR36)
1
7
10
6
4
44 69D0023
FIREBOX COMPONENTS
ILLUSTRATED PARTS LISTS
Item Description
Standard Features
1 Junction Box Assembly 2 Black Louver 3 Glass Frame Assembly
Factory Installed Service Parts
2 Brass Louver 4 Thermostat Sensor (Blower) 5 Cottage Clay Firebrick Rear 5 Cottage Clay Firebrick Rear 5 Tavern Brown Firebrick Rear 5 Tavern Brown Firebrick Rear 6 Cottage Clay Firebrick Right/Left 6 Tavern Brown Firebrick Right/Left 7 Blower Motor
Accessories/Field Installed Options
2 Brass Louver
2 Pewter Louver 9 Curved Design - Brass Trim 9 Curved Design – Pewter Trim
10 T-stat Blower with Speed Control
Qty CDVR33
1 26D2128K 6 54D0246 1
6 54D0249K 1 26D2870 1 69D0221 1 1 69D0222 1— 2 26D7068 2 54D0285 1 26D0748
1 L30BR
1 L30PW 1 BRTK30C 1 1 BLOT
69D0238 69D0238
PWTK30C PWTK30C
CDVT33
26D2128K
54D0246
54D0249K
26D2870 26D7069
54D0284
— 26D7068 54D0285 26D0748
L30BR
L30PW
BRTK30C
BLOT
CDVR36 CDVT36
26D2128K 26D2128K
26D0695 26D0695 69D0028 69D0028
26D0701K 26D0701K
26D2870 26D2870 69D0040
69D0041
69D0044
69D0045 69D0042 69D0042 69D0046 69D0046 26D0748 26D0748
L32BR L32BR
L32PW L32PW
BRTK32C BRTK32C
PWTK32C PWTK32C
BLOT BLOT
69D0023 45
ILLUSTRATED PARTS LISTS
STANDING PILOT — MILLIVOLT CONTROL
1
3
4
2I2C
2T
2
5
6
7
8
8
11,12,13, 14
10
46 69D0023
STANDING PILOT – MILLIVOLT CONTROL
ILLUSTRATED PARTS LISTS
Item Description Qty
1 Gas Valve
Assembly
2 Pilot Assembly 1 37D0018 37D0019 37D0018 37D0019 37D0018 37D0019 37D0018 37D0019
2C Replacement
Thermocouple
2I Replacement
Igniter and Wire
2T Replacement
Thermopile
3 Burner Tube 1 54D0288 54D0288 69D0083 69D0083 54D0288 54D0288 69D0083 69D0083
4 Flexhose with
Shutoff Valve
5 Rocker Switch 1 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048
6 Piezo Igniter 1 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503
7 Injector 1
8 Burner Assembly 1 54D0200 54D0200 54D0001 54D0001 54D0200 54D0200 54D0001 54D0001
9 Venturi 1 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600
10 Wire Assembly 1 44D0500 44D0500 44D0500 44D0500 44D0500 44D0500 44D0500 44D0500
10 Wire Assembly 1 44D0501 44D0501 44D0501 44D0501 44D0501 44D0501 44D0501 44D0501
Conversion Kit (Not Shown)
Conversion NG to LPG
Conversion LPG to NG
CDVR33NV CDVR33PV CDVR36NV CDVR36PV CDVT33NV CDVT33PV CDVT36NV CDVT36PV
1 37D0117 37D0118 37D0117 37D0118 37D0117 37D0118 37D0117 37D0118
1 37D1067 37D1067 37D1067 37D1067 37D1067 37D1067 37D1067 37D1067
1 37D1069 37D1069 37D1069 37D1069 37D1069 37D1069 37D1069 37D1069
1 37D1068 37D1068 37D1068 37D1068 37D1068 37D1068 37D1068 37D1068
1 69D0030 69D0030 69D0030 69D0030 69D0030 69D0030 69D0030 69D0030
58D0371 69D0226
CDV33CKP CDV36CKP CDV33CKP CDV36CKP
1
1
CDV33CKN CDV36CKN CDV33CKN CDV36CKN
59D0062 69D0079
58D0371 69D0226
59D0062 69D0079
Accessories
Item Description Qty
PART NUMBER
11 Thermostatic Remote Control 1 RCT/TRC 12 Remote Control On/Off 1 RCM/MRC 13 Wall Switch Kit 1 MVWS 14 Wall Thermostat Kit 1 MVWTS
69D0023 47
ILLUSTRATED PARTS LISTS
ELECTRONIC IGNITION
Item Description Qty
1 Gas Valve
Assembly
2 Pilot Assem-
bly
3 Burner Tube 1 54D0288 54D0288 69D0083 69D0083 54D0288 54D0288 69D0083 69D0083
4 Flexhose with
Shutoff Valve
5 Rocker Switch 1 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048
6 Injector 1
7 Burner
Assembly
8 Venturi 1 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600
9 Wire Assem-
bly
10 Ignition
Module
CDVR33NE CDVR33PE CDVR36NE CDVR36PE CDVT33NE CDVT33PE CDVT36NE CDVT36PE
1 37D0016 37D0017 37D0016 37D0017 37D0016 37D0017 37D0016 37D0017
1 37D0020 37D0021 37D0020 37D0021 37D0020 37D0021 37D0020 37D0021
1 69D0030 69D0030 69D0030 69D0030 69D0030 69D0030 69D0030 69D0030
58D0371 69D0226
1 54D0200 54D0200 54D0001 54D0001 54D0200 54D0200 54D0001 54D0001
1 54D0207 54D0207 54D2007 54D2007 54D0207 54D0207 54D2007 54D2007
1 37D0325 37D0325 37D0325 37D0325 37D0325 37D0325 37D0325 37D0325
59D0062 69D0079
58D0371 69D0226
59D0062 69D0079
1
3
5
LO
HI
6
2
8
4
7
11
10
9
#1 #2 #3 #4 #5 #6 7#
48 69D0023
LOGS
ILLUSTRATED PARTS LISTS
Item
1 2 3
Description
Rear Log 54D0121 54D0181 Right Log 54D0147 54D0116 Left Log 54D0146 54D0115
CDVR33 and CDVT33 CDVR36 and CDVT36
3
2
1
69D0023 49
ILLUSTRATED PARTS LIST
VENT COMPONENTS
1
HOT
2
4
7
8
3
9
10
11
5
Qty/
Item
Box Description
1 1 Simpson Horizontal High Wind Termination Cap 985 4DT-HC
Horizontal Square Termination Cap with Built-In Vinyl Siding Standoff, Heat
11
11
11 2 1 Vertical Termination 980 4DT-VC 3 6 6” Pipe Length 908 4DT-06 3 6 9” Pipe Length 907 4DT-09 3 6 12” Pipe Length 906 4DT-12 3 6 24” Pipe Length 904 4DT-24 3 6 36” Pipe Length 903 4DT-36 3 6 48” Pipe Length 902 4DT-48 4 6 11” To 14 5/8” Pipe, Adjustable 911 4DT-AJ 4 6 17" To 24" Pipe, Adjustable 917 4DT-AJ14 5 6 45° Elbow 945 4DT-EL45 5 6 45° Swivel Elbow 945G 4DT-EL45 6 6 90° Elbow 990 4DT-EL90 6 6 90° Swivel Elbow 990G 4DT-EL90 7 6 Flashing, 0/12 To 6/12 Roof Pitch 943 4DT-AF6 8 6 Storm Collar 953 4DT-SC
9 6 Firestop 963 4DT-FS 10 1 Vinyl Siding Standoff 950 4DT-VS 11 1 Restrictor Disk 45D0551
Deflector and Firestop Horizontal Rigid Pipe Termination Kit with Horizontal Termination Cap with
Built-In Vinyl Siding Standoff, Heat Deflector, Firestop, 90° Elbow and 11"x145/8" Adjustable Pipe
Horizontal Flexible Pipe Termination Kit with Horizontal Termination Cap with Built-In Vinyl Siding Standoff, Heat Deflector, Firestop, 20" to 40" Flex­ible Pipe Adapter
6
Simpson
Duravent OR
Selkirk P/N
MHS P/N
BHRTK
BHSTK
BHSFTK
50 69D0023
Massachusetts Residents Only — Please read and follow these special requirements
NOTE REGARDING VENTED PRODUCTS
This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massachusetts.
Any residence with a direct vent product must have a CO detector installed in the residence.
Installation of the fireplace or vented gas log in the State of Massachusetts requires the damper to be permanently removed or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have a T shutoff valve.
NOTE REGARDING VENT FREE PRODUCTS
This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massachusetts.
In addition, vent free products may not be installed in a bedroom or bathroom regardless of size or type in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have a T shutoff valve.
CARBON MONOXIDE DETECTOR REQUIREMENTS
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. Installation of carbon monoxide detectors. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. Approved Carbon Monoxide Detectors. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. Signage. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. Inspection. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) Exemptions: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) Manufacturer requirements — Gas Equipment Venting System Provided. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) Manufacturer requirements — Gas Equipment Venting System Not Provided. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems,” the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design
LIMITED LIFETIME WARRANTY POLICY
LIFETIME WARRANTY
The following components are warranted for life to the original owner, subject to proof of purchase: Firebox, Combustion Chamber, Heat Exchanger, Grate and Stainless Steel Burners.
FIVE YEAR WARRANTY
The following components are warranted five (5) years to the original owner, subject of proof of purchase: Ceramic Fiber Logs.
BASIC WARRANTY
MHS warrants the components and materials in your gas appliance to be free from manufacturing and material defects for a period of two years from date of installation. After installation, if any of the components manufactured by MHS in the appliance are found to be defective in materials or workmanship, MHS will, at its option, replace or repair the defective components at no charge to the original owner. MHS will also pay for reasonable labor costs incurred in replacing or repair­ing such components for a period of two years from date of installation. Any products presented for warranty repair must be accompanied by a dated proof of purchase.
This Limited Lifetime Warranty will be void if the appliance in not installed by a qualified installer in accordance with the installation instructions. The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance, and does not extend to (1) firebox/burner assembly damage by accident, neglect, misuse, abuse, alterations, negligence of others, including the installation thereof by unquali­fied installers, (2) the costs of removal, reinstallation or transportation of defective parts on the appliance, or (3) incidental or consequential damage. All service work must be performed by an authorized service representative.
This warranty is expressly in lieu of other warranties, express or implied, including the warranty of merchantability of fitness for purpose and of all other obligations or liabilities. MHS does not assume for it any other obligations or liabilities in con­nection with sale or use of the appliance. It states that do not allow limitations on how long an implied warranty lasts, or do not allow exclusion of indirect damage, those limitations of exclusions may not apply to you. You may also have additional rights not covered in the Limited Lifetime Warranty.
MHS reserves the right to investigate any and all the claims against the Limited Lifetime Warranty and decide upon method of settlement.
For information about this warranty, contact:
Technical Services
MHS
149 Cleveland Drive
Paris, Kentucky 40361
AUGUST 2007 P/N 69D0023 • Rev. 6
Loading...