Monessen Hearth BDV500, BDV400, BDV600, BDV300 User Manual

MODELS:
BDV300, BDV400, BDV500, BDV600
BDV SERIES
DIRECT VENT GAS
FIREPLACE
INST ALLATION AND OPERATING
INSTRUCTIONS
IF THE INFORMA TION IN THESE INSTRUCTIONS ARE NOT FOLLOWED EXACTLY , A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
– Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any other appliance.
– WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the re department.
– Installation and service must be performed
by a qualifi ed installer, service agency or the gas supplier.
WARNING: Improper installation, adjustment, alteration, services or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualifi ed installer, service agency or the gas supplier.
This appliance may be installed in an aftermarket*, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
* Aftermarket: Completion of sale, not for purpose of resale,
from the manufacturer.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURE AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MA TERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
KEEP THE ROOM AREA CLEAR AND FREE FROM COMBUSTIBLE MA TERIALS, GASOLINE, AND OTHER FLAMMABLE V APORS AND LIQUIDS.
READ BEFORE INSTALLING. SAVE THESE INSTRUCTIONS
CONTENTS
Important Safety Information ..........................3
Product Features .............................................. 5
Code Approval ..................................................5
Pre-Installation Information
Installing Above 2000 Feet ............................ 6
Orifi ce Sizes, Pressures and BTUs ............... 6
Before You Install .......................................... 6
Fireplace Framing ......................................... 7
Fireplace Dimensions.................................... 8
Fireplace Location ......................................... 9
Clearances ...................................................... 10
Securing Fireplace to Floor or Framing ........11
Installation Information .................................. 12
Vent Installation .............................................. 13
Installation Precautions ............................... 13
Optional Top Vent Application ..................... 14
Installation Planning .................................... 15
Rear (Through the Wall) Applications ......... 18
Horizontal Termination Confi guration .......... 20
Below Grade Installation ............................. 22
Vertical Through-the-Roof Installation ......... 23
Installation for Vertical Termination ............. 24
Fireplace Installation ...................................... 26
Check Gas Type .......................................... 26
Installing Gas Piping to Fireplace/Burner
System Location.......................................... 26
Checking Gas Pressure ................................. 28
Electrical Installation...................................... 29
Electrical Wiring ..........................................29
Electronic Pilot Ignition Wiring..................... 30
Remote Wall Switch .................................... 31
Glass Removal ................................................ 32
Final Installation ............................................. 33
Rockwool Placement................................... 33
Log Placement ............................................ 33
Lava Rock and Ember Placement............... 33
Operating Instructions (Milli-Volt) ................. 34
What To Do If You Smell Gas ...................... 34
Lighting Milli-Volt Pilot for the First Time ..... 35
Lighting Milli-Volt Pilot ................................. 35
Lighting Burner ............................................ 36
To Turn Off Gas ........................................... 36
Operating Instructions (Electronic Ignition) 37
What To Do If You Smell Gas ...................... 37
Lighting Electronic Ignition ......................... 37
To Turn Off Gas ........................................... 37
Cleaning and Maintenance ............................ 38
Burner, Pilot and Control Compartment ...... 38
Pilot Flame .................................................. 38
Burner Flame .............................................. 39
Vent System ................................................ 39
Glass Door .................................................. 39
Logs ............................................................ 39
Rock Wool .................................................. 39
Troubleshooting .............................................40
Replacement Parts ......................................... 42
Firebox Components ................................... 42
Standing Pilot Engine ................................. 44
Electronic IGN Engine ................................ 44
Vent Components........................................47
Logs ............................................................ 49
Mass Residents Requirements ..................... 50
Warranty ...........................................Back Cover
2 54D0700
IMPORTANT SAFETY INFORMATION
INSTALLER
Please leave these instructions with the appliance.
• Read this owner’s manual carefully and completely before trying to assemble, operate, or service this fi replace.
• Any change to this fi replace or its controls can be dangerous.
• Improper installation or use of this fi replace can cause serious injury or death from
WARNING
re, burns, explosions, electrical shock and carbon monoxide poisoning.
This fireplace is a vented product. This fireplace must be properly installed by a qualified service person. The glass door must be properly seated and sealed. If this unit is not properly installed by a qualified service person with glass door properly seated and sealed, combustion leakage can occur.
CARBON MONOXIDE POISONING: Early signs of
carbon monoxide poisoning are similar to the flu with head­aches, dizziness and/or nausea. If you have these signs, the fireplace may not have been installed properly. Get fresh air at once! Have the fireplace inspected and serviced by a quali­fied service person. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Propane/LP gas and natural gas are both odorless. An odor­making agent is added to each of these gases. The odor helps you detect a gas leak. However, the odor added to these gases can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.
1. This appliance is only for use with the type of gas indi­cated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.
2. For propane/LP fireplace, do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capac­ity.
3. If you smell gas
• shut off gas supply.
• do not try to light any appliance.
• do not touch any electrical switch; do not use any
phone in your building .
• immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
OWNER
Please retain these instructions for future reference
4. Never install the fireplace
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable objects are less than 42" from the front, top, or sides of the fireplace
• in high traffic areas
• in windy or drafty areas
5. This fireplace reaches high temperatures. Keep children
and adults away from hot surfaces to avoid burns or cloth­ing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
6. Carefully supervise young children when they are in the
room with fireplace.
7. Do not modify fireplace under any circumstances. Any
parts removed for servicing must be replaced prior to operating fireplace.
8. Turn fireplace off and let cool before servicing, install-
ing, or repairing. Only a qualified service person should install, service, or repair the fireplace. Have burner system inspected annually by a qualified service person.
9. You must keep control compartments, burners, and cir-
culating air passages clean. More frequent cleaning may be needed due to excessive lint and dust. Turn off the gas valve and pilot light before cleaning fireplace.
10. Have venting system inspected annually by a qualified
service person. If needed, have venting system cleaned or repaired. See Cleaning and Maintenance, page 32.
11. Keep the area around your fireplace clear of combustible
materials, gasoline, and other flammable vapor and liq­uids. Do not run fireplace where these are used or stored. Do not place items such as clothing or decorations on or around fireplace.
Continued on page 4
.
54D0700 3
IMPORTANT SAFETY INFORMATION
Continued from page 3
12. Do not use this fireplace to cook food or burn paper or other objects.
13. Never place anything on top of fireplace.
14. Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this fireplace. Use only the gas type indicated on rating plate.
15. This appliance, when installed, must be electrically grounded in accordance with local codes or in the absence of local codes, with the National Electrical Code, ANSI/ NFPA 70, or the Canadian Electrical Code, CSA C22.1.
16. Do not obstruct the flow of combustion and ventilation air in any way. Provide adequate clearances around air openings into the combustion chamber along with adequate accessibility clearance for servicing and proper operation.
17. When the appliance is installed directly on carpeting, tile or other combustible material other than wood flooring, you must set appliance on a metal or wood panel or hearth pad extending the full width and depth of the appliance.
IMPORTANT:
PLEASE READ THE FOLLOWING CAREFULLY
It is normal for fi replaces fabricated of steel to give off some expansion and/or contraction noises during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine.
IMPORTANT:
PLEASE READ THE FOLLOWING CAREFULLY
It is not unusual for gas fi replaces to give off some odor the fi rst time it is burned. This is due to the manufacturing process.
Please ensure that your room is well ventilated
during burn off — open all windows.
It is recommended that you burn your fi replace for at least ten (10) hours the fi rst time you use it. Place the fan switch in the “OFF” position during this time.
18. Do not use fireplace if any part has been exposed to or has been under water. Immediately call a qualified service person to arrange for replacement of the unit.
19. Do not operate fireplace if any log is broken.
20. Do not use a blower insert, heat exchanger insert, or any other accessory not approved for use with this fireplace.
21. Do not operate the fireplace with glass door removed, cracked, or broken.
Never connect unit to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
WARNING
We suggest that our gas hearth products be installed and serviced by professionals who are certifi ed in the U.S. by the National Fireplace Institute (NFI) as Gas Specialists.
www.nfi certifi ed.org
®
4 54D0700
PRODUCT SPECIFICATIONS
• This appliance has been certi­fied for use with either natural or propane gas. See appropriate data plates.
This appliance is not for use with solid fuels.
• The appliance is approved for bedroom or bedsitting room installations.
The appliance must be installed in accordance with local codes if any. If none exist use the current installation code. ANSI Z223.1/ NFPA 54 in the USA, CAN/CGA B149 in Canada.
• This appliance is mobile home approved.
PRODUCT FEATURES AND CODE APPROVAL
The appliance must be properly connected to a venting system.
The appliance is not approved for closet or recessed installations.
The efficiency rating of this appli­ance is a product thermal efficiency rating determined under continuous operating conditions and was deter­mined independently of any installed system.
Thermal Efficiency = up to 80%
Hi/Lo Knob
Off/Pilot/On Knob
On/Off/RS Switch
Ignitor
Blower Control
Optional Remote
Receiver
Figure 1 - BDV300, 400, 500, 600 Fireplace
CODE APPROV AL
Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe.
These appliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Canada as follows:
LISTED VENTED GAS FIREPLACE HEATER
TESTED TO: ANSI Z21.88-2002/CSA 2.33-2002 STANDARDS
A manufactured home (USA only) or mobile home OEM installation must conform with the Manufactured Home Con­struction and Safety Standard, Title 24 CFR, Part 3280, or when such a standard is not applicable, the Standard for
Manufactured Home Installations, ANSI/NCSBCS A225.1, or Standard for Gas Equipped Recreational Vehicles and Mobile Housing, CSA Z240.4.
54D0700 5
PRE-INSTALLATION INFORMATION
INSTALLING ABOVE 2000 FEET
In the USA, the appliance must be derated 4% for every 1,000 ft above 2,000 ft elevations.
In Canada, these appliances are certified for altitudes of 0 – 2000 ft, and must be de-rated by 10 percent for installations between 2000 and 4,500 ft. (derate an additional 4% for every 1,000 ft. above 4,500 ft. elevations).
ORIFICE SIZES, PRESSURES AND BTUs
NATURAL GAS PROPANE GAS
Manifold Press: (W.C.) 3.5" Manifold Press: (W.C.) 10" Maximum Supply Pressure 10.5" Maximum Supply Pressure 13" Minimum Supply Pressure 4.5" Minimum Supply Pressure 11"
Model Number BDV300 BDV400 BDV500 BDV600
Natural Propane Natural Propane Natural Propane Natural Propane Max. Btu/hr Input 21,000 21,000 24,000 24,000 26,000 26,000 26,000 26,000 Min. Btu/hr Input 15,000 15,000 17,000 17,000 20,000 20,000 20,000 20,000 Orifi ce size #43 #54 #41 #53 #40 1.55mm #40 1.55mm
BEFORE YOU ST ART
Read this homeowner manual thoroughly and follow all instructions carefully. Inspect all contents for shipping damage and immediately inform your dealer if any damage is found. Do not install any unit with damaged, incomplete, or substitute parts. Check your packing list to verify that all listed parts have been received. You should have the following:
• Fireplace (Firebox and Burner System)
• Rock Wool
• Log Set
ITEMS REQUIRED FOR INSTALLATION Tools: Building Supplies:
• Phillips Screwdriver • Framing Materials
• Hammer • Wall Finishing Materials
• Saw and/or saber saw • Caulking Material (Noncombustible)
• Level • Fireplace Surround Material (Noncombustible)
• Measuring Tape • Piping Complying with Local Codes
• Electric Drill and Bits • Tee Joint
• Pliers • Pipe Sealant Approved for use with Propane/LPG
• Square (Resistant to Sulfur Compounds)
• Pipe Wrench
6 54D0700
"
FIREPLACE FRAMING
FIREBOX FRAMING
Firebox framing can be built before or after the appliance is set in place. Construct firebox framing following Figure 2 and the chart below for your specific installation requirements. See Figure 3 on Page 8 for firebox dimensions. The framing headers may rest on the top of the firebox standoffs. Do not bring headers below top of standoffs.
The firebox may be installed directly on a combustible floor or raised on a platform of an appropriate height. When the firebox is installed directly on carpeting, tile, or other combustible material, other than wood flooring, the firebox shall be installed on a metal or wood panel extending the full width and depth of the enclosure.
Do not fi ll spaces around fi rebox with insulation or other materials. This could cause a fi re.
WARNING
D
H
C
A E
Corner Installation
G
A 331/2" 371/2" 411/2" 471/2" B 371/4" 407/8" 407/8" 407/8" C 281/4" 291/4" 331/4" 391/4" D 141/8" 145/8" 165/8" 195/8" E 5511/16" 607/8" 647/8" 707/8" F 2713/16" 307/16" 327/16" 357/16" G 133/4" 153/4" 153/4" 153/4" H 393/8" 431/16" 457/8" 501/8"
300 400 500 600
F
C
G
A
Inside Chase Installation
C
B
A
Stud Location
Figure 2 - Framing Dimensions
54D0700 7
Recessed Installation
A
G
1
/2" or 5/8
PRE-INSTALLATION INFORMATION
FIREPLACE DIMENSIONS
E
H
N
1
5
/2"
/8"
A B
5
/8"1/2"
D
Drywall Support Tabs
K
5
/8"
1
L
/2"
I
C
G
F
1
/2"
5
/8"
J
81/4"
M
Figure 3 - Fireplace Dimensions
DESCRIPTION Key Letter BDV300 BDV400 BDV500 BDV600
Overall Front Width A 331/16" 371/16" 411/16" 471/16" Inside Width B 297/8" 32" 36" 42" Glass Width C 27" 29" 33" 39" CTR Pipe D 161/2" 181/2" 201/2" 231/2" Rear Width E 28" 29" 33" 39" Glass Height F 18" 203/8" 203/8" 203/8" Chassis Height G 337/8" 371/2" 371/2" 371/2" Depth H 14" 16" 16" 16" Height to Standoffs I 37" 401/2" 401/2" 401/2" CTR Height J 295/8" 331/8" 331/8" 331/8" Top Face K 21/8" 11/4" 11/4" 11/4" Side Face L 11/2" 21/2" 21/2" 21/2" Bottom Face M Overall Front Height N 315/8" 343/4" 343/4" 343/4"
8 54D0700
15
/16"
31/2"
15
/16"
15
/16"
15
/16"
PRE-INSTALLATION INFORMATION
FIREPLACE LOCATION
Plan for the installation of your appliance. This includes determining where the unit is to be installed, the vent configuration to be used, framing and finishing details, and whether any optional accessories (i.e. blower, wall switch, or remote control) are desired. Consult your local building code agency to ensure compliance with local codes, including permits and inspec­tions.
The following factors should be taken into consideration:
Clearance to side-wall, ceiling, woodwork, and windows. Minimum clearances to combustibles must be maintained.
This fireplace may be installed along a wall, across a corner, or use an exterior chase. See Figure 4 for suggested loca­tions.
Location should be out of high traffic areas and away from furniture and draperies due to heat from appliance.
Never obstruct the front opening of the fireplace.
• Do not install in the vicinity where gasoline or other flammable liquids may be stored.
Vent pipe routing. See Venting section found in this manual for allowable venting configurations.
These units can be installed in a bedroom. See National Fuel Gas Code ANSI Z233.1/NFPA 54 — (current edition), the Uniform Mechanical Code — (current edition), and Local Building Codes for specific installation requirements.
A Flat on Wall B Cross Corner C Island**
E
Y
A
B
D Room Divider* E Flat on Wall Corner*
C
X
F Chase Installation Y 4" Minimum
D
Y
F
Figure 4 - Locating Gas Fireplace
** Island (C) and room divider (D) installation is possible as long as the horizontal portion of vent system (X)
does not exceed 20'. See Installing Horizontal Termination Con guration on pages 18 and 19.
* When you install your fi replace in (D) room divider or (E) fl at on wall corner positions (Y), a minimum of 6"
clearance must be maintained from perpendicular wall and front of fi replace.
54D0700 9
CLEARANCES
CLEARANCES TO COMBUSTIBLES
Follow these instructions carefully to ensure safe installation. Failure to follow in struc tions exactly can create a fi re hazard.
The appliance cannot be installed on a carpet, tile or other combustible material other than wood fl ooring. If installed on carpet or vinyl fl ooring, the appliance shall be installed on a metal, wood or noncombustible material panel ex tend ing full width and depth of
WARNING
the appliance.
71"Minimum
12"
Maximum
Depth
11"Minimum
Minimum 4"
From Both Side Walls
Figure 6 - Clearances
MANTEL CLEARANCES
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it does, it is considered a mantel and must meet the mantel requirements listed in this manual.
10 54D0700
SECURING FIREPLACE TO FLOOR OR FRAMING
The fireplace must be secured to the floor and/or to framing studs as shown in Figure 5. Use two (2) wood screws or masonry/ concrete screws to secure fireplace to the floor. Use four (4) screws to attach fireplace to framing. The side nailing flanges are 1/2" or 5/8" to accommodate different wall thickness.
Drywall Support Tabs
(Do Not Use for Framing
or Header)
Framing
Nailing Flange
Screws
Screws
Nailing Flange
Framing
Nailing Flange
Screws
Nailing Flange
Figure 5 - Securing Fireplace to Floor and Framing Studs
54D0700 11
INSTALLATION INFORMATION
FINISHING MATERIAL
NOTE: Any remote wiring (i.e. remote control, wall switch, and optional fan) must be done prior to nal nishing to avoid costly reconstruction.
Never obstruct or modify the air inlet or outlet grills (louvers). This may create a re hazard.
WARNING
Only noncombustible materials (i.e. brick, tile, slate, steel, or other materials with a UL fire rating of Zero) may be used to cover the black surface of the appliance. A 300°F minimum adhesive may be used to attach facing materials to the black surface. If joints between the finished wall and the fireplace surround are sealed, a 300°F minimum sealant material (General Electric RTV103 or equivalent) must be used.
VENT INSTALLATION
Read all instructions completely and thoroughly before attempting installation. Failure to do so could result in serious injury, property damage or loss of life. Operation of improperly installed and maintained venting system could result in serious injury, property damage or loss of life.
WARNING
Failure to follow these instructions will void the warranty.
NOTICE
INSTALLATION PRECAUTIONS
Consult local building codes before beginning the installation. The installer must make sure to select the proper vent system for installation. Before installing vent kit, the installer must read this fireplace manual and vent kit instructions.
Only a qualified installer/service person should install venting system. The installer must follow these safety rules:
• Wear gloves and safety glasses for protection.
• Use extreme caution when using ladders or when on rooftops.
• Be aware of electrical wiring locations in walls and ceilings.
The following actions will void the warranty on your venting system:
• Installation of any damaged venting component.
• Unauthorized modification of the venting system.
• Installation of any component part not manufactured or approved by MHS.
• Installation other than permitted by these instructions.
12 54D0700
VENT INSTALLATION
This fi replace must be vented to the outside. The venting system must NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each gas appliance must use a separate vent system. Do not use common vent systems.
WARNING
Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the fl ue and 1" clearance at the sides and bottom until the ue penetrates the outside wall. A minimum 1" clearance all around the fl ue is acceptable at this point of penetration.
WARNING
Vertical sections of this vent system require a minimum of 1" clearance to combustibles on all sides of the pipe.
3"
A Minimum of 3" Clearance
to the Top Is Required Along
Horizontal Length until Flue
Pipe Penetrates Outside Wall.
1"
1"
1"
A Minimum 1"
Clearance to
Combustibles
Permitted All
Around Flue
at Outside
Wall
Figure 7 - Combustible Clearances for Vent Pipe
54D0700 13
VENT INSTALLATION
OPTIONAL TOP VENT APPLICATION
The appliance is shipped as a rear vent unit. If the installation layout requires the unit to be a top vent configuration the appli­ance can be converted by following the steps below.
When removing and refitting the plates and adapter be sure the associated gaskets are undamaged and refitted as required.
1. Remove the eight (8) screws securing the flue pipe adapter to the fireplace body. See Figure 8.
2. Set the flue pipe adapter aside, complete with the gasket. Do not damage the gaskets as the adapter and gasket must be refitted.
3. Remove the eight (8) screws securing the flue pipe cover to the top of the intake box and remove the cover and gasket.
See Figure 8.
4. Remove the six (6) screws securing the flue pipe to the back of the intake box and remove the pipe and gasket.
See Figure 9.
5. Replace flue pipe to top of firebox. Ensure the gasket is in place and undamaged. Secure with six (6) screws. See
Figure 10.
6. Place the flue pipe cover and gasket removed in step 3 over the flue opening in back of the intake box.
After conversion to top vent confi guration the 4" (100mm) fl ue pipe should be concentric within the 6 (175mm) outer collar (within
1
WARNING
Flue Pipe
Cover
Flue Pipe
Adapter
/4").
5
/8"
Screws
7. Refit the flue pipe adapter and gasket to the top of fire­place. Secure the adapter with eight (8) screws removed in step 1.
Flue
Cover
Flue Pipe
Screws
Figure 8 - Removing sixteen (16) Screws from
Flue Pipe Adapter and Flue Pipe Cover
Flue Pipe
Screws
Figure 9 - Removing Flue Pipe
14 54D0700
Figure 10 - Attaching Flue Pipe to Top
Vent Confi gurations
VENT INSTALLATION
INSTALLATION PLANNING
There are two basic types of direct-vent installation:
• Horizontal Termination
• Vertical Termination
It is important to select the proper length of vent pipe for the type of termination you choose. It is also important to note the wall thickness.
FOR HORIZONTAL TERMINATION
Select the amount of vertical rise desired. All horizontal run of venting must have termination.
You may use up to three 90° elbows in this vent configuration. See Horizontal Termination Configurations on pages 20 and 21.
FOR VERTICAL TERMINATION
Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical rise in an attic or second story, and allow for sufficient vent height above the roof line.
NOTE: You may use two 45° elbows in place of a 90° elbow . Y ou must follow rise to run ratios when using 45° elbows. The appliance is approved for use with three 90° elbows maximum or a combination of 90° and 45° elbows up to a maximum of 270°.
For two-story applications, firestops are required at each floor level. If an offset is needed in the attic, additional pipe and elbows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house. See Installing Vent System in a Chase below. If pipe is enclosed in chase, it is not exposed.
It is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust. Certain limitations apply to vent configurations and must be strictly followed.
INSTALLING A VENT SYSTEM IN AN OUTSIDE CHASE
A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a building. A chase is required for such venting.
1
/4" rise for every 12" of run towards the
Never run the vent pipe level or downward. This may cause excessive temperatures which could cause a fi re.
WARNING
Treatment of fi restops and construction of the chase may vary from building type to building type. These instructions are not substitutes for the requirements of local building codes. You must follow all local building codes.
NOTICE
When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially important in cold climates. Insulation should be considered a combustible material. Maintain proper clearances to all combustible materials.
NOTICE
54D0700 15
VENT INSTALLATION
Inside Corner Detail FOR HORIZONTAL TERMINATION
G
V
H
D
E
B
L
Vent Terminal Air Supply Inlet Area Where Terminals Not Permitted
V
C
Fixed
V
Closed
F
Operable
V
B
A
BB
B
Opera-
ble
V
A
V
Fixed
Closed
J
V
A
B
Figure 11 - Horizontal Vent Termination Location
MINIMUM DISTANCES
A = Clearance above the grade, a veranda, porch, deck, or balcony [*12" (305mm) minimum]. B = Clearance to window or door that may be opened [*12" (305mm) minimum]. C = Clearance to permanently closed window [*minimum 12" (305mm) recommended to prevent condensation on
window]
D
= Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of two (2) feet (610mm)
from the centerline of the terminal [18" (457mm) minimum]. E = Clearance to unventilated soffits [12" (305mm) minimum]. Clearance to vinyl soffit [30" (762mm)]. F = Clearance to an outside corner. See Figure 12. G = Clearance to an inside corner. See Figure 12. H = *Not to be installed above a gas meter/regulator assembly within three (3) feet (914mm) horizontally from the
centerline of the regulator. I = Clearance to service regulator vent outlet [*3' (914mm) minimum]. J = Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance [*12"
(305mm)minimum]. K = Clearance to a mechanical air supply inlet [*6' (1829mm) minimum]. L = Clearance above a paved sidewalk or paved driveway located on public property [**7' (2133mm) minimum].
* As specified in CAN/CGA B149 Installation Codes. Note: Local codes or regulations may require different
clearances. ** A vent must not terminate directly above a sidewalk or paved driveway, which is located between two single-family
dwellings and serves both dwellings. *** Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
A
G
I
M
V
A
K
A
Always maintain minimum clearances around vent systems. The minimum clearances to combustibles for horizontal vent pipe are 3" at the top and 1" at the sides and bottom of the vent system until the pipe penetrates the nearest vertical wall (1" required). A 1" minimum clearance all around the pipe must be maintained at outside wall and on vertical runs. Do not pack the open air spaces with insulation or other materials. This
WARNING
could cause high temperatures and may present a fi re hazard.
16 54D0700
TERMINATION CLEARANCES FOR BUILDINGS WITH COMBUSTIBLE AND NONCOMBUSTIBLE EXTERIORS
VENT INSTALLATION
G G=6" (152mm)
V
Inside Corner
V
F
Outside Corner
F=6" (152mm)
H
G
V
Combustible &
G = Combustible 24"(610mm)
Noncombustible 18"(457mm)
Balcony with No Side Wall Balcony with Perpendicular
Noncombustible H = 24" (610mm) J = 20" (508mm)
V
J
Side Wall
Figure 12 - Allowable Venting Chart
HOW TO USE THE VENT GRAPH
The Vent Graph should be read in conjunction with the following vent installation instructions to determine the relationship between the vertical and horizontal dimensions of the vent system.
1. Determine the height of the center of the horizontal vent pipe
exiting through the outer wall. Using this dimension on the Sidewall Vent Graph below, locate the point intersecting with the slanted graph line.
2. From the point of this intersection, draw a vertical line to the
bottom of the graph.
3. Select the indicated dimension, and position the fireplace in
accordance with same.
Example: If the vertical dimension from the oor of the
replace is 11' (3.4m) the horizontal run to the face of the outer wall must not exceed 14' (4.3m).
Example: If the vertical dimension from the fl oor of the unit
is 7’ (2.14m), the horizontal run to the face of the outer wall must not exceed 8
Sidewall Vent Graph showing the relationship between vertical and horizontal dimensions for a Direct Vent flue system.
1
/2' (2.6m).
D
C
C
V
E
C = Maximum depth of 48" (1219mm)
for alcove location
D = Minimum width for back wall of
alcove location Combustible - 38" (965mm) Noncombustible - 24" (610mm)
E = Clearance from corner in alcove
location Combustible - 6" (152mm) Noncombustible - 2" (51mm)
Alcove Location
40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10
8 6 4
20"
2
Horizontal Dimension From the Outside of
Termination to the Back of the Fireplace
Dimensions in
Feet
Horizontal Vent Pipe
eg: A
2 4 6 8 10 12 14 16 1820
Figure 13 - Rear Wall Venting Graph
Vertical Dimension From the Floor of Unit to the Center of the
54D0700 17
VENTING INSTALLATION
REAR (THROUGH THE WALL) APPLICATIONS
When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance
• The maximum horizontal distance between the rear of the appliance and the outside of termination is 20" (508 m). See
Figure 14.
• Only one 45° elbow is allowed in these installations.
Maximum
20"
Top View Flat Installation
Figure 14 - Rear Vent Application,
Maximum Horizontal Distance
Sealant is not required to assemble BDV/DVB fireplace venting. Do not use silicone sealant at the flue exhaust connections.
1. Find the pipe section’s direction label. The label arrow shall be pointed away from the firebox and toward the termination. Firmly insert the initial rigid section/elbow into the firebox outer collar. Simpson “GS” and Selkirk “DT” outer walls are hemmed and will snap into the collar’s tabs. Attach Simpson’s Direc­tVent Pro by fully inserting into the collar and securing with self tapping screws. The screws shall only penetrate the flue outer wall.
Female
Locking Lugs
Note: Horizontal runs of vent must be supported every three feet (914mm). Use wall straps for this purpose.
Male Slots
Figure 15 - Rigid Vent Pipe Connections
91/2"
(241mm)
Refer to vent manufacturer’s installation
instructions to properly assemble flue.
2. Locate and cut the vent opening in the
wall. For combustible walls first frame in opening.
Combustible Interior Walls: Cut a 11
1
x 9
2" W hole through the interior wall.
Combustible Exterior Walls: Cut a 9
1
2"H
1
2"H
91/2"
(241mm)
33/4"
(92mm)
x 912"W square hole through the exterior wall frame. See Figure 16.
Noncombustible Walls: Hole opening
71/2"
(190mm)
should be 712" (190mm) in diameter.
3. The center of the hole should line up with the center line of the horizontal rigid vent pipe end. Pipe shall always run level or uphill on
Figure 16 - Exterior Wall Framing Dimensions
horizontal runs. Never run pipe down hill. See Figure 16.
18 54D0700
VENT INSTALLATION
REAR WALL VENT INSTALLATION (continued)
4. Apply a bead of non-hardening mastic around the outside edge of vent cap. Position the vent cap in the center of hole on the exterior wall with the word “UP” on the vent cap facing up. Insure proper clearance of 1" to combustibles is maintained to the flue. Attach the vent cap with four wood screws supplied. See Figure 17.
Do not recess vent termination into any wall. This will cause a re hazard.
HOT
Apply Mastic to
All Four Sides
Vent Cap
Wood
Screw
WARNING
Figure 17 - Installing Horizontal Termination
NOTE: Replace the wood screws with appropriate fasteners for stucco, brick, concrete, or other types of siding.
A vinyl siding standoff (part #950) must be used with the Simpson/Selkirk Horizontal Termination (part #985) on vinyl, stucco or wood-clad exterior walls. Apply non-hardening mastic around outside edge of the standoff instead of the vent cap assembly. See Figure 18.
5. Slide the firestop over the vent pipe before connecting the horizontal run to the vent cap. See Figure 19.
6. The termination should overlap the flue a minimum of 1
1
/4" Apply silicone to the outer pipe/termination connection.
Fasten termination with screws provided.
7. Slide the firestop against the interior wall surface and attach with screws. See Figure 19.
Cut Vinyl Siding
Away to Fit Standoff
Interior Wall
Surface
Standof #950
Firestop
Simpson
Termination
#985
Vent Cap
(Horizontal
Apply
Mastic to
All Four
Sides
Nut
Wood Screw
HOT
Bolt
Termination)
Screw
Horizontal
Vent Pipe
Figure 18 - Installing Simpson/Selkirk Vinyl
Siding Standoff and Termination
54D0700 19
Figure 19 - Installing Firestop on
Horizontal Vent Pipe
VENT INSTALLATION
HORIZONTAL TERMINATION CONFIGURATIONS
Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain limita­tions as to vent configurations apply and must be strictly adhered to.
The Vent Graph, showing the relationship between vertical and horizontal side wall venting, will help to determine the various dimensions allowable. See Figure 20.
NOTE: Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the fl ue and 1" clearance at the sides and bottom until the fl ue penetrates the outside wall. A minimum 1" clearance all around the fl ue is acceptable at this point of penetration.
Vertical sections of this vent system require a minimum of 1" clearance to combustibles on all sides of the pipe.
When vent exits through foundations less than 20" below outcrop, the termi­nation must be flush up with outcropped wall above.
It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace (or the top of the Transition Elbow) to the face of the outer wall.
40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10
8 6 4
20"
2
2 4 6 8 10 12 14 16 1820
Horizontal Dimension From the Outside of
Termination to the Back of the Fireplace
eg: A
Vertical Dimension From the Floor of Unit to the Center of the
Horizontal Vent Pipe
Figure 20 - Rear Wall Venting Graph
When installing the appliance as a rear vent unit, the 90° or 45° transition elbow attached directly to the rear of the unit is NOT INCLUDED in the following criteria and calculations, and unless specifi cally mentioned should be ignored when calculating venting layouts.
WARNING
• The maximum number of 90° elbows per side wall installation is three (3). See Figure 21.
• If a 90° elbow is fitted directly on top of the fireplace flange the maximum horizontal vent run before the termination or a vertical rise is 36” (914 mm). See Figure 22.
3 x 90°
Elbows
3 x 90° Elbows
36"
Max.
36"
Max.
Figure 21 - Maximum Three (3) 90° Elbows
Figure 22 - Maximum Horizontal Run with No Rise
Per Installation
20 54D0700
VENT INSTALLATION
HORIZONTAL TERMINATION CONFIGURATION
(Continued)
• If a 90° elbow is used in the horizontal vent run (level height maintained) the horizontal vent length is reduced by 36". See Figures 21 and 22, page 20. This does not apply if the 90° elbows are used to increase or redirect a vertical rise.
See Figure 24.
Example: According to the vent graph (page 20) the maximum horizontal vent length in a system with a 7.5' vertical rise is 20’ (6m) and if a 90° elbow is required in the horizontal vent it must be reduced to 17' (5.2 m).
In Figures 23 and 24, Dimension A plus B must not be greater than 17' (5.2m).
• The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.
• For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (45cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.
• The maximum number of elbow degrees in a system is 270°.
See Figure 25.
B
A
10'
7'
90°
AB
7'6"
Figure 23 - Horizontal Run Reduction
Example: Elbow 1 = 90° Elbow 2 = 45° Elbow 3 = 45° Elbow 4 = 90° Total Angular Variation = 270°
1 2 3 4
90° Elbow = 3'
7'6"
A + B = 17' Maximum
1 + 2 + 3 + 4 = 270°
Figure 24 - Maximum Vent Run with Elbows
54D0700 21
Figure 25 - Maximum Elbow Usage
1 2 3 4
VENT INSTALLATION
BELOW GRADE INSTALLATIONS
When it is not possible to meet the required vent terminal clearances of 12" above grade level, a snorkel kit is recommended. It allows installation depth down to 7" (178mm) below grade level. The 7" (178mm) is measured from the center of the horizontal vent pipe as it penetrates through the wall.
Ensure that sidewall venting clearances are observed. If venting system is installed below ground, we recommend a window well with adequate and proper drainage to be installed around the termination area.
If installing a snorkel, a minimum 24" vertical rise is necessary. The maximum horizontal run with the 24” vertical pipe is 36". This measurement is taken from the collar of the fireplace (or transition elbow) to the face of the exterior wall. See the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 24".
1. Establish vent hole through the wall. See Figure 16, page 18.
2. Remove soil to a depth of approximately 16" below base of snorkel. Install drain pipe. Install window well (not supplied). Refill hole with 12" of coarse gravel leaving a clearance of approximately 4" below snorkel. See Figure 26.
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe coming through the wall.
5. Apply high temperature sealant caulking (supplied) around the 4" and 7" snorkel collars.
6. Slide the snorkel into the vent pipes and secure to the wall.
7. Level the soil so as to maintain a 4" clearance below snorkel. See Figure 26.
• Do not back fi ll around snorkel.
• A clearance of at least 4" must be maintained between the snorkel and the soil.
WARNING
If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to wall first, then secure to snorkel with self drilling #8x1/2 sheet metal screws. It will be necessary to extend vent pipes out as far as the protruding wall face. See Figure 27.
Screws
Firestop
24"
Minimum
Foundation Wall
Minimum
4" Clearance
Ground Window Well Gravel
Drain
Foundation
Recess
Watertight Seal
Around Pipe
Snorkel
Wall Screws
Sheet Metal
Screws
Figure 27 - Snorkel Installation,
Figure 26 - Below Grade Installation
22 54D0700
Recessed Foundation
VENT INSTALLATION
VERTICAL (THROUGH-THE-ROOF) APPLICATIONS
This Gas Fireplace has been approved for,
• Vertical installations up to 40' (12m) in height. Up to a 10' (3m) horizontal vent run can be installed within the vent system using a maximum of two 90° elbows. See Figure 28.
NOTE: Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the fl ue and 1" clearance at the sides and bottom until the ue penetrates the outside wall. A minimum 1" clearance all around the fl ue is acceptable at this point of penetration.
Vertical sections of this vent system require a minimum of 1" clearance to combustibles on all sides of the pipe.
Support
10'
Maximum
40' Maximum Height
8' Minimum Height
• Up to two 45° elbows may be used within the horizontal run. For each 45° elbow used on the horizontal plane, the maximum horizontal length must be reduced by 18" (450mm).
Support Straps
Every 3'
Straps
Every
5'Vertical
Figure 28 - Support Straps for Horizontal Runs
40' Maximum Height
8' Minimum Height
1 2 3 4
10'
Maximum
Support Straps
Every 3'
Example: Maximum horizontal length No elbows = 10’ (3m)
1x45° elbows = 8.5’ (2.6m) 2x45° elbows = 7’ (2.1m)
• A minimum of an 8' (2.5m) vertical rise is required.
• Two sets of 45°elbows offsets may be used within the vertical sections. From 0 to a maximum of 8' (2.5 m) of vent pipe can be used between elbows.
See Figure 29.
• The maximum angular variation allowed in the system is 270°. See Figure 29.
54D0700 23
Example: Elbow 1 = 90°
Elbow 2 = 45° Elbow 3 = 45° Elbow 4 = 90° Total Angular Variation = 270°
Figure 29 - Maximum Elbow Usage
1 2 3 4
VENT INSTALLATION
INSTALLATION FOR VERTICAL TERMINATION
1. Determine the route your vertical venting will take. If ceiling joist, roof rafters or other framing will obstruct the venting system, consider an offset. See Figure 30 to avoid cutting load bearing members.
Roof
Flashing
For optimal flame appearance, a restrictor disk is necessary on straight vertical runs of 20' of more.
Runs may not incorporate elbows.
The disk is part number 45D0551 and is included in instal­lation manual packet.
Drop the disk into a 4" inner collar before installing the first section of flue or install at the last section before installing the termination.
An additional disk may be installed on runs of 35' or more. Rotate disks perpendicular to each other.
NOTE: Pay special attention to these installation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations. Offsets must fall within the parameters shows in Figure 13, page 20.
2. Set fireplace in desired location. Drop a line plumb down from the ceiling to the position of the flue exit. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole a this point.
Wall
Strap
45° Elbows
Ceiling Firstop
Figure 30 - Offset with Wall Strap and 45°
Elbows
Nails
Drop a plumb line from the inside of the roof to the ceiling
locating hole in the ceiling. Mark the center point where the
Firestop
vent will penetrate the roof. Drill a small locating hole at this point.
Figure 31 - If Area Above is a Room, Install
Firestop above Framed Hole as Shown
FLAT CEILING INSTALLATION
1
1. Cut a 9
/2" (241mm) square hole in the ceiling using the locating
hole as a center point The opening should be framed to 91/2"x91/2"
"
1
2
/
9
1
9
/
2
"
(241mm x 241mm) inside dimensions as shown in Figure 32using framing lumber the same size as the ceiling joist. If the area above the ceiling is an insulated ceiling or a room, nail firestop from the top side. This prevents loose insulation from falling into the required clearance space. See Figure 31. Otherwise, install firestop below the framed hole. See Figure 32.
2. Assemble the desired lengths of pipe and elbows necessary to reach from the burner system flue up through the firestop. Be sure pipe and elbow connections are fully twist-locked. See Figure
15, page 18.
Figure 32 - If Area Above is Not a Room, Install
Nails
Firestop
Firestop above Framed Hole as Shown
24 54D0700
VENT INSTALLATION
3. Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting
1/
hole in roof). The 91/2"x9
2
" (241mm x 241mm) hole must be measured on the horizontal. Actual length may be larger depending on the pitch of the roof. There must be a 1" minimum clearance from the vent pipe to combustible materials. (Insulation should be considered a combustible material).
4. Connect a section of pipe and extend up through the hole.
NOTE: If an offset is needed to avoid obstructions, you must support the vent pipe every three (3) feet. Use wall straps for this purpose. See Figure 28, page 23. Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the fl ow of the fl ue gases and intake air.
5. Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and framing with roofing nails. Be sure roofing material overlaps the top edge of the flashing. There must be a 1" clearance from the vent pipe to combustible materials.
6. Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements.
NOTE: You must increase vent height for steep roof pitches. Nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem.
NOTE: If the vent pipe passes through any occupied areas above the fi rst fl oor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction material. Make sure to meet the minimum allowable clearances to combustibles. Do not fi ll any of the required clearance spaces with insulation.
Termination
Storm collar
H
Cone fl ashing
CATHEDRAL CEILING INSTALLATION
1. Remove shingles or other roof covering as necessary to cut the rect­angular hole for the support box. Mark the outline of the cathedral
X
ceiling support box on the roof sheathing using the locating hole as a center point.
2. Cut the hole 1/8" larger than the support box outline. See Figure 32.
Figure 35 - Minimum Chimney Clearance
12"
3. Lower the support box through the hole in the roof until the bottom of the box extends at least 2" below the ceiling. See Figure 32. Align the support box vertically and horizontally using a level. Temporarily tack the support box in place through the inside walls and into the roof sheeting.
4. Using tin snips, cut the support box from the top corners down to the roof line and fold the resulting flaps over the roof sheeting. See Figure 33. Apply a bead of non-hard­ening, mastic around the top edges of the support box to make a seal between the box and the roof. Nail in place with roofing nails. Remove any combustible material that might be inside the support box.
5. Complete the cathedral ceiling installation by following the same procedures outlines in steps 2 through 6 for Flat Ceiling Installation,
Use this table to determine the minimum height above the roof.
Minimum Height Roof Pitch Feet Meters
Flat to 7/12 1 0.3 Over 7/12 to 8/12 1.5 0.46 Over 8/12 to 9/12 2 0.61 Over 9/12 to 10/12 2.5 0.76 Over 10/12 to 11/12 3.25 0.99 Over 11/12 to 12/12 4 1.22 Over 12/12 to 14/12 5 1.52
TERMINATION HEIGHT TABLE
page 24 and above.
54D0700 25
FIREPLACE INSTALLATION
CHECK GAS TYPE
Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install fireplace. See dealer where you purchased the fireplace for proper fireplace for your gas type or conversion kit.
INSTALLING GAS PIPING TO FIREPLACE / BURNER SYSTEM LOCATION
A qualifi ed installer or service person must connect appliance to gas supply . Follow all local codes.
WARNING
For propane/LP units, never connect fi replace directly to the propane/LP supply. This burner system requires an external regulator (not supplied). Install the external regulator between the burner system and propane/LP supply.
CAUTION
INSTALLATION ITEMS NEEDED
Before installing fireplace and burner system, make sure you have the items listed below.
• External regulator (supplied by installer) • Piping (check local codes) • Sealant (resistant to propane/LP gas)
• Equipment shutoff valve* • Test gauge connection* • Sediment trap (recommended)
• Tee joint • Pipe wrench
• approved flexible gas line with gas connector (if allowed by local codes — not provided)
1
* A CSA design-certified equipment shutoff valve with
Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 33. Pointing the vent down protects it from freezing rain or sleet.
External
Regulator
100 lb. (min)
Propane/LP
Supply Tank
/8" NPT tap is an acceptable alternative to test gauge connection.
Use only new black iron or steel pipe. Internally tinned copper or copper tubing can be used per National Fuel Code, section 2.6.3, providing gas meets hydrogen sulfide limits, and where permitted by local codes. Gas piping system must be sized to provide
CAUTION
Vent
Pointing
Down
minimum inlet pressure (listed on data plate) at the maximum fl ow rate (BTU/hr). Undue pressure loss will occur if the pipe is too small.
When using copper of flex connectors use only fittings approved for gas connections. The gas control inlet is
Figure 33 - External Regulator with Vent Pointing
Down (Propane/LP Only)
26 54D0700
3
/8" NPT.
FIREPLACE INSTALLATION
Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.
A manual shutoff valve must be installed upstream of the appliance. Union tee
1
and plugged
/8" NPT pressure tapping
point should be installed upstream of
WARNING
NOTE : The gas line connection may be made using some municipalities have additional local codes it is always best to consult your local authorities and the current edition of the National Fuel Gas Code ANSI.Z223.1, NFPA54. In Canada CAN/CGA-B149 (1 or
2) Installation Code.
A listed manual shutoff valve must be installed upstream of the appliance. Union tee and plugged 1/8" NPT pressure tapping point should be installed upstream of the appliance. See Figure 34.
IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location. The main gas valve is for turning on or shutting off the gas to the fi replace.
Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged burner system valves.
1
/2" rigid tubing or an approved fl ex connector. Since
the appliance. See Figure 35.
CAUTION
Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
CAUTION
We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 34. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and burner system. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap collects moisture and contaminants and keeps them from going into the burner system gas controls. If sediment trap/drip leg is not installed or is installed wrong, burner system may not run properly.
Approved Flexible
Gas Line
Sediment Trap/Drip Leg
Tee Joint Pipe Nipple Cap
CSA Design-Certifi ed Equipment
Shutoff Valve with
3" Minimum
1
/8" NPT Tap*
Natural Gas
From Gas Meter
(4.5" W.C. to 10.5" W.C. Pressure)
Propane/LP
From External Regulator
(11" W.C. to 13" W.C. Pressure)
Figure 34 - Gas Connection
54D0700 27
CHECKING GAS PRES SURE AND ELECTRICAL INSTALLATION
1. Check gas type. The gas supply must be the same as stated on the appliance’s rating decal. If the gas supply is different from the fireplace, STOP! Do not install the appliance. Contact your dealer immediately.
2. To ease installation, a 30" (mm) flex line with manual shut-off valve has been provided with on this appliance. Install and attach
3. After completing gas line connection, purge air from gas line and test all gas joints from the gas meter to the fireplace for leaks. Use a solution of 50/40 water and soap or a gas sniffer.
4. To adjust flame height, turn HI/LO knob to HI to get maximum pressure to burner. Turn HI/LO knob to LO to get minimum pressure.
5. To check gas pressures at valve, turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point. Turn unit to high. See Figure 35. After taking pressure reading, be sure and turn captured screw clockwise firmly to reseal. Do not over torque. Check test points for gas leaks.
1
/2" gas line onto shut-off valve.
Pressure
Test “IN”
Pressure
Test “OUT”
HI/LO
Knob
Figure 35 - Gas Pressure Check at Gas Valve
Pilot Adjustment
Screw
Do not use open fl ame to check for gas leaks.
WARNING
ELECTRICAL WIRING
This fireplace will work without any electrical supply. Electricity is only needed to operate blower.
NOTE: If installed in mobile home, fi replace must be bolted securely to fl oor.
Electrical connections should only be performed by a qualifi ed, licensed electrician. Main power must be off when connecting to main electrical power supply or performing service. All wiring shall be in compliance with all local, city, and state codes. The appliance, when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code ANSI/ NFP A 70 (latest
WARNING
edition) and Canadian Electrical Code, CSA C22.1.
Label all wires before disconnecting when servicing controls. Wiring errors can cause improper and dangerous operation.
CAUTION
Verify proper operation after servicing.
28 54D0700
ELECTRICAL INSTALLATION
REMOTE WALL MOUNTED SWITCH
A remote wall switch and up to fifteen (15) feet of 18 Ga. wire may be used with this appliance. Attach the wall switch in a junc­tion box at the desired location on the wall. See Figure 36. Do not extend beyond the wall switch wire length provided.
NOTE: Extended lengths of wire may cause the fi replace not to function properly. Longer length of wire is permitted if the wire is made out of larger gauge (diameter) wire. Always check with local code.
Do not connect wall switch to heater (110V) circuit.
WARNING
OPTIONAL REMOTE
WALL SWITCH
ON
PILOT
HI
ON
OFF
O
L
TH TP
TH/TP
ON
OFF
RS
OFF
OPTIONAL REMOTE
WALL SWITCH
ON
OFF
Figure 36 - Wiring Diagram for Wall Switch
54D0700 29
ELECTRICAL INSTALLATION
ELECTRONIC PILOT IGNITION WIRING
Do not connect 110-120 VAC to the Remote Wall Switch. The appliance will malfunction.
WARNING
To Junction Box
Electronic Valve
RED #2 GRAY #1
EV1 EV2
RED #2
WHITE #3
HI
LO
15’ Wall Switch Wire
LACK
B
WHITE
REMOTE WALL SWITCH
Pilot Assembly
Spark Sense
MV/PV #2
MV #1
Ignition Module
PV #3
24V GND #5
GND (BURNER) #4
GREEN #4
24V #6
BLACK #6
SENSE #8
SPARK #9
ON OFF
Switch
RS
YELLOW YELLOW
Figure 37 - Remote Wall Switch Wiring Diagram
WHITE
WHITE
BLUE
GREEN BLACK
BLACK
Primary - 120V
Transformer
YELLOW
Secondary
24V
Position the wall switch. Do not extend beyond the 15 feet of wire.
OPTIONAL DC REMOTE SYSTEMS
These instructions replace the section entitled Hearth Mount in the Millivolt hand held remote instructions supplied with the remote.
1. Plug in remote connector wire to remote receiver.
2. Connect the wire terminal from the remote receiver. This replaces the 15' wall switch connection to the switch. See Figure 37.
3. Mount remote control receiver at junction box (for your wall switch).
30 54D0700
OPTIONAL FAN/BLOWER SYSTEMS
The junction box for the fan/blower systems has been factory installed. This system requires that 110-120 VAC to be wired to the factory installed junction box before the fireplace is permanently installed. See Figure 38.
120VAC
Receptacle
Junction
Box
BLACK
GREEN
BLACKBLACK
Speed Control
TANTANWHITE
Optional Thermostatic Switch
Figure 38 - Blower Wiring Diagram
54D0700 31
GLASS REMOVAL
GLASS FRAME REMOVAL
1. Release two clamps on bottom of fireplace. See Figure 39.
2. Tilt glass frame out and lift glass frame up until it clears three tabs on top of fireplace.
3. Set glass frame aside.
Glass Frame
Each clamp has a quick spring force. When reinstalling clamps, keep fi ngers clear. Remove control panel to operate middle clamp on 500 and 600 units.
CAUTION
Clamps
Two (2) on 300/400 Units
Three (3) on 500/600 Units
Figure 39 - Removing Glass Frame
Three
Tabs
32 54D0700
ROCK WOOL PLACEMENT
FINAL INSTALLATION
1. Place rock wool on burner to provide glowing
embers. For best results, pull the rock wool apart into pieces the size of a dime or smaller.
2. Distribute one layer of rock wool to cover the burner.
See Figure 40.
3. Place the logs on the burner. See Log Placement
below. Light unit and after 15 minutes, check burner flame and glow. See Burner Flame, page 38.
If the flame is blue and only in the center, turn off unit and let cool. After unit cools, remove logs. If the back holes are clear, add more rock wool to the center of the burner. Replace logs and check flame again. Save left over rock wool to refresh when cleaning later. Too much rock wool can disturb the flame and cause sooting on the glass or logs.
LOG PLACEMENT
1. Place rear log (#1) on grate assembly. Log should rest firmly on the two log mounting pins on the bars. See Figure 41.
Burner
Cover with
Rock Wool
Figure 40 - Placement of Rock Wool on Burner
Do not use the entire bag of rock wool to cover the burner. This could cause the fl ame to burn poorly and may lead to sooting.
WARNING
(#3) Top Left Log
(#2) Top
Right Log
2. Place top right log (#2) on the rear log. Rest the right back side of the log in the flat area of the rear log. Place the narrow front end of the log next to the center vertical grate bar. See
Figure 41.
3. Place the top left log (#3) on the rear log. Nest the forked end of the top left log into the fork or the rear log. Rest the narrow end of the top left log behind the center vertical grate bar. See Figure 41.
LAVA ROCK AND EMBER PLACEMENT
Sprinkle lava rock on the floor of the inner combustion chamber. Evenly distribute the rock. Do not pile the lava rock up in front of grate. Do not place lava rock on the burner. If desired, purchase optional embers to decorate the floor of the fireplace.
Do not sprinkle the lava rock or ember chunks on top of the burner. This may cause potential sooting, glass breakage and a fi re hazard.
WARNING
(#1) Rear
Log
Flat
Area
Log Mounting Pins
Left Vertical
Grate Bar
Center Vertical
Grate Bar
Right
Vertical
Grate Bar
Figure 41 - Log Placement
(BDV300, 400 shown)
54D0700 33
OPERATING INSTRUCTIONS (MILLI-VOLT)
FOR YOUR SAFETY READ BEFORE LIGHTING
If you do not follow these instruction exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
WARNING
A. This appliance is equipped with a pilot which must be lit with built-in piezo ignitor while following these
instructions exactly.
B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Turn off all gas to the appliance.
• Open windows.
Do not attempt to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in, or turn the gas control knob. Never use tools. If the knob will not push in or
turn by hand, don't try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part of it has been under water. Immediately call a qualified service tech-
nician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
LIGHTING PILOT FOR THE FIRST TIME
INITIAL LIGHTING
Purge air from the supply line as follows:
Open main shutoff valve.
Unscrew main pressure test point.
Leave inlet test screw open until gas comes in.
When gas is flowing, tighten inlet screw immediately.
LEAK TESTING
1. Follow the pipe from the gas supply line connection to the gas valve. Check connection for leaks with soap and water mixture.
2. Next check for gas leaks at the burner with soap and water mixture.
Never use an open fl ame to check for gas leak.
WARNING
3. Check the pilot for gas leaks with soap and water mixture.
34 54D0700
OPERATING INSTRUCTIONS (MILLI-VOLT)
LIGHTING PILOT FOR THE FIRST TIME
APPROVED LEAK TESTING METHOD
You may check for gas leaks with the following methods only:
• Soap and water solution
• An approved leak testing spray
• Electronic sniffer
Never check for gas leak with open fl ame!
DANGER
Check for gas leaks in each of the following locations:
• Pipe from the gas supply line connection to the gas valve
If using a soap and water solution to test for leaks, DO NOT spray solution onto control body.
WARNING
NOTE: Remove any excessive pipe compound from the connections. Excessive pipe compound can set off electronic sniffers.
• Burner connections • Field made joints / gas shutoff valve
• Pilot • Factory made joints
• Each joint or connection • All joints on valve and control body
LIGHTING PILOT
The control has an interlock device that does not allow the lighting of the fi replace up to the moment the safety device of the fl ame has not interrupted the gas fl ow. After that period of time (when the magnet is closed), it is possible to start the lighting operation.
The gas control knob is designed to be operated by hand. DO NOT use any tools
WARNING
during this operation. Damaged knobs may result in serious injury.
1. Depress and turn knob counterclockwise to pilot position.
2. Depress fully and hold pilot gas knob. Depress piezo igniter as many times as needed to ignite pilot. Keep knob fully depressed for a few seconds. Release and check that pilot continues to burn.
O
N
T
O
L
I
P
F
F
O
PILOT
If the pilot does not stay lit, repeat steps 1 and 2.
Figure 42 - Pilot Position
Continued on next page
54D0700 35
OPERATING INSTRUCTIONS (MILLI-VOLT)
LIGHTING BURNER
MAIN BURNER SWITCH
The “ON/OFF/RS” switch for the main burner can be found behind door of the fireplace. This switch allows you to turn on and to turn off the main burner without using the gas valve knob. Make sure the button is in the “ON” position to light the main burner. See Figure 43.
LIGHTING THE BURNER
Depress and turn the knob counterclockwise to the “ON” position. See
Figure 44.
PILOT POSITION
Depress and turn knob to pilot position to keep burner off while maintaining the pilot light. See Figure 45.
It will take less than four (4) seconds for the burner to ignite.
O
N
T
O
L
I
P
F
F
O
PILOT
ON
OFF
RS
Figure 43 -
On/Off/RS Switch
N
O
O
F
F
P
T
I
L
O
PILOT
Figure 44 - On Position
T
Depress and turn knob clockwise
Figure 45 - Pilot Position
TO TURN OFF GAS
to “OFF” position. See Figure 46.
P
I
L
O
T
F
F
O
O
N
PILOT
Figure 46 - Off Position
36 54D0700
OPERATING INSTRUCTIONS (ELECTRONIC)
FOR YOUR SAFETY READ BEFORE LIGHTING
A. This appliance is equipped with an ignition device
(Piezo) which automatically lights the pilot. Do NOT try to light the burner by hand.
B. BEFORE OPERATING smell all around the appli-
ance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Turn off all gas to the appliance.
• Open windows.
Do not attempt to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
C. Turn off all electric power to appliance. D. Do not use this appliance if any part of it has been under water. Immediately call a qualified service tech-
nician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
If you do not follow these instructions exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
WARNING
WARNING
Never use an open fl ame to check for gas leak.
LIGHTING ELECTRONIC IGNITION
1. STOP! Read the safety information above.
2. Make sure all power to unit is turned off.
3. Set thermostat to lowest setting.
4. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the
LO
HI
ON
OFF
PILOT
burner by hand.
5. Turn on all electric power to appliance.
Figure 47 - Electronic Gas Valve
6. Set thermostat to desired setting.
7. Turn RS-OFF-ON rocker switch to “ON”.
8. If the appliance will not operate, follow the instruction To Turn Off Gas below and call your service techni­cian or gas supplier.
TO TURN OFF GAS
1. Open lower door.
2. Turn RS-OFF_ON rocker switch to “OFF”.
3. Turn off all electric power to the appliance if service is to be performed.
4. Close lower door.
54D0700 37
CLEANING AND MAINTENANCE
Turn off gas before servicing fi replace. It is recommended that a qualifi ed service technician perform these check-ups at the beginning of each heating season
WARNING
BURNER, PILOT AND CONTROL COMPARTMENT
Keep the control compartment, logs, and burner areas surrounding the logs clean by vacuuming or brushing at least twice a year. Make sure the burner porting, pilot air opening and burner air opening are free of obstructions at all times.
PILOT FLAME
The flames from the pilot should be visually checked as soon as the heater is installed and periodically during normal operation. The pilot flame must always be present when the fireplace is in operation. See Figure 48. The pilot flame has three distinct flames, one engulfing the thermopile, one engulfing the thermocouple, and the other reaching to the main burner..
BURNER
Inspect area around the injector. Remove any lint or foreign material with a brush or vacuum.
BURNER FLAME
The flames from the burner should be visually checked as soon as the heater is installed and periodically during normal operation. In normal operation, at full rate, and after operating for about 15 to 30 minutes, the flame should be yellow and slightly taller than the rear log.
See Figure 49.
Thermocouple
Thermopile
Figure 48 - Pilot Flame
If the flame is blue and only in the center, turn off unit and let cool. After unit is cool, remove logs and check to make sure the back holes in the burner are not covered with rock wool. If the back holes are clear, add more rock wool to the center of the burner. Replace logs.
NOTE: The type of installation, vent system confi guration, and wind effects may cause the ame patterns to vary.
Figure 49 - Burner Flame Appearance
38 54D0700
CLEANING AND MAINTENANCE
VENT SYSTEM
The fireplace and venting system should be inspected before initial use and at least annually by a qualified field service person. Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the airflow. Inspect entire venting system to ensure proper function.
GLASS DOOR
Thoroughly clean the inside of the glass door after using the fireplace for ten hours. Periodically clean the glass door as necessary.
When cleaning the glass, remember:
Do not remove the glass when hot. Allow glass to cool before removal.
NEVER use abrasive materials.
Keep children and pets a safe distance away.
Never operate the fireplace without the glass door properly secured.
Never operate the fireplace if the glass is broken.
Replace any glass that is chipped, cracked, or broken. Replacement glass door assemblies MUST be supplied by the
fireplace manufacturer – No substitute materials may be used.
Handle glass door with care to avoid striking or scratching it on hard objects.
To clean glass door, follow “Glass Removal” procedure outlined in the Final Installation section. Film deposit on the inside of the glass should be cleaned off using a nontoxic, non-corrosive, non-abrasive, mild-cleaning solution. Simply apply an adequate amount to the glass and wipe off with a damp cloth. After all maintenance has been completed, re-install glass door.
LOGS
Leave logs installed in the fireplace for cleaning. Vacuum surface of the logs with a brush attachment. If logs must be removed for cleaning, handle carefully by holding gently at each end. Gloves are recommended to prevent skin irritation from ceramic fibers. If skin becomes irritated, wash gently with soap and water. Vacuum surface of logs with brush attachment or brush logs with a soft bristle brush (i.e. clean, dry paintbrush). To place logs back in the fireplace, see “Log Placement” found in the Final Installation section.
NOTE: Do not use fl uids to clean ceramic fi ber logs.
ROCK WOOL
Replace or add rock wool as required following installation instructions in the Final Installation section of this manual.
54D0700 39
TROUBLESHOOTING
STANDING PILOT IGNITION
SYMPTOM POSSIBLE CAUSE ACTION
1. Spark ignitor will not light pilot after repeated triggering of piezo.
2. Pilot will not stay lit after carefully follow­ing lighting instruc­tions.
. Pilot burning, valve
knob turned to “ON”, switch is turned to “ON” or “RS”, but burner will not ignite.
A. Wire disconnected.
B. Defective ignitor.
C. No gas or low gas pressure.
D. No Propane/LPG in tank
A. Defective thermocouple
B. Defective valve
A. Defective switch, wall
switch, remote control or wire
B. Pilot flame too small
C. Defective or malfunction-
ing thermopile
D. Defective valve
A. Open door and check to make sure wire is connected to ignitor. B. Check for spark at electrode and pilot. If no spark and electrode
wire is properly connected, replace pilot assembly.
C. Check remote/manual shut off valve from fireplace. Low pres-
sure can be caused by bent lines, restricted lines, low pressure line pressure. Consult with plumber or gas supplier.
D. Check Propane/LPG tank. Refill tank.
A. Check that thermocouple flame impinges on thermocouple.
Clean and/or adjust pilot for maximum flame impingement. Ensure that the thermocouple connection at the gas valve is fully inserted and tight.
Disconnect the thermocouple from the valve, place one millivolt
lead wire on the tip of the thermocouple and the other meter lead wire on the thermocouple copper lead. Start the pilot and hold the valve knob in. If the millivolt reading is less than 15 mV, replace pilot assembly.
B. If thermocouple is producing more than 15 mV, replace faulty
valve.
A. Check switch and wire for proper connection. Place jumper
wires across terminals of switch. If burner comes on, replace defective switch.If the switch is OK, repeat the same procedure on remote control If burner comes on, replace remote control.
Place jumper wire across wire at gas valves (terminals marked
TH and TP/TH). If burner comes on, wires are faulty or connec­tions are bad. Replace wire.
B. If pilot flame is not close enough to the thermopile, adjust pilot
flame.
C. Check thermopile wire connections to make sure all are tight
and that the thermopile is fully inserted into pilot assembly. Check thermopile with a millivolt meter. Connect leads to TP and TP/TH terminals on the control valve. If meter reading is below 325 mV, replace pilot assembly.
D. Turn valve knob to “On” and switch to “ON.” Take a reading at
the thermopile leads (TP & TP/TH) on the valve. If the meter reads greater than 175 mV and the burner does not light, replace defective valve.
40 54D0700
STANDING PILOT IGNITION
SYMPTOM POSSIBLE CAUSE ACTION
TROUBLESHOOTING
4. Frequent pilot outage problem.
5. The pilot and main burner extinguish while in operation
6. Glass Soots
7. Flame burn blue and lifts off burner (ghost­ing)
A. Pilot flame may be too high or
too low, causing pilot safety to drop out
A. Inner vent pipe leaking
exhaust gases back into system
B. Horizontal vent improperly
pitched
C. Improper vent cap installation
A. Flame impingement on logs
A. Insufficient oxygen being
supplied
A. Clean and adjust the pilot flame for maximum flame impinge-
ment on thermocouple.
A. Check for flue product leak. Replace defective pipe section.
B. Check horizontal-venting piping is running upward 1/4" per foot.
Do not run the pipe level or downward.
C. Check for proper installation and freedom from debris or block-
age.
A. Install log set per the instructions Inspect the injector and air intake area. Make sure this area does
not have any blockage from debris and clean.
Check gas supply.
A. Ensure that the vent cap is installed properly and free of debris.
Ensure that the vent system joints are tight and have no leaks. Ensure that no debris has been blocking the inner air intake at the bottom back of the combustion chamber. Ensure that the glass is properly secure and latch.
54D0700 41
ILLUSTRATED PARTS LISTS
FIREBOX COMPONENTS
3
2
9
5
7
6
8
1
10
4
42 54D0700
ILLUSTRATED PARTS LISTS
FIREBOX COMPONENTS
Item Description Qty BDV300 BDV400 BDV500 BDV600
Standard Features
1 Junction Box Assembly 1 26D2128K 26D2128K 26D2128K 26D2128K 2 Black Louver 6 54D0246 26D0695 26D0697 26D0699 3 Glass Frame Assembly 1 54D0294 54D0340 54D0195 54D0443
Factory Installed Options
2 Brass Louver 6 54D0249K 26D0701K 26D0703K 26D0705K 4 Thermostat Sensor 1 26D2870 26D2870 26D2870 26D2870 5 Standard Firebrick Center CC 1 26D7069 26D7077 26D7083 26D7089 6 Standard Firebrick Right CC 1 26D7068 26D7076 26D7076 26D7076 7 Standard Firebrick Left CC 1 26D7068 26D7075 26D7075 26D7075 5 Standard Firebrick Center CR 1 26D7097 26D7105 26D7111 26D7117 6 Standard Firebrick Right CR 1 26D7096 26D7104 26D7104 26D7104 7 Standard Firebrick Left CR 1 26D7096 26D7103 26D7103 26D7103 8 Blower Motor 1 54D0281 26D0748 26D0748 26D0748
Accessories/Field Installed Options
2 Brass Louver 1 L30BR L32BR L36BR L42BR 2 Pewter Louver 1 L30PW L32PW L36PW L42PW
5,6,7 Cottage Clay Firebrick Walls 1 FB300CCW FB400CCW FB500CCW FB600CCW
8 Cottage Clay Firebrick Floors 1 FB300CCF FB400CCF FB500CCF FB600CCF
5,6,7 Cottage Red Firebrick Walls 1 FB300CRW FB400CRW FB500CRW FB600CRW
8 Cottage Red Firebrick Floors 1 FB300CRF FB400CRF FB500CRF FB600CRF 9 Curved Design - Brass 1 BRTK30C BRTK32C BRTK36C BRTK42C 9 Curved Design - Pewter 1 PWTK30C PWTK32C PWTK36C PWTK42C 9 Curved Design - Black 1 BLTK30C BLTK32C BLTK36C BLTK42C 9 Black Trim 1 BLMTK30 BLMTK32 BLMTK36 BLMTK42 9 Pewter Trim 1 PWMTK30 PWMTK32 PWMTK36 PWMTK42 9 Brass Trim 1 BRMTK30 BRMTK32 BRMTK36 BRMTK42
10 T-stat Blower with Speed Control 1 BLOTS BLOT BLOT BLOT
CC=Cottage Clay
CR=Cottage Red
54D0700 43
ILLUSTRATED PARTS LISTS
STANDING PILOT — MILLIVOLT CONTROL
1
3
2C
4
2I
2T
2
5
6
7
8
8
11,12,13, 14
10
44 54D0700
ILLUSTRATED PARTS LISTS
STANDING PILOT – MILLIVOLT CONTROL
Item Description Qty BDV300NV BDV300PV BDV400NV BDV400PV BDV500NV BDV500PV BDV600NV BDV600PV
1 Gas Valve Assembly 1 37D0117 37D0118 37D0117 37D0118 37D0117 37D0118 37D0117 37D0118 2 Pilot Assembly 1 37D0018 37D0019 37D0018 37D0019 37D0018 37D0019 37D0018 37D0019
2C Replacement Thermocouple 1 37D1067 37D1067 37D1067 37D1067 37D1067 37D1067 37D1067 37D1067 2I Replacement Igniter and Wire 1 37D1069 37D1069 37D1069 37D1069 37D1069 37D1069 37D1069 37D1069
2T Replacement Thermopile 1 37D1068 37D1068 37D1068 37D1068 37D1068 37D1068 37D1068 37D1068 3 Burner Tube 1 54D0288 54D0288 54D0194 54D0194 54D0194 54D0194 54D0194 54D0194
4 Flexhose with Shutoff Valve 1 23D6046 23D6046 23D6046 23D6046 23D6046 23D6046 23D6046 23D6046
5 Rocker Switch 1 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 6 Piezo Igniter 1 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 7 Injector 1 62D3006 20H3146 62D3004 20H3143 20H3145 57D0210 20H3145 57D0210 8 Burner Assembly 1 54D0200 54D0200 54D0001 54D0001 54D0329 54D0329 54D0329 54D0329 9 Venturi 1 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 10 Wire Assembly 1 44D0500 44D0500 44D0500 44D0500 44D0500 44D0500 44D0500 44D0500 10 Wire Assembly 1 44D0501 44D0501 44D0501 44D0501 44D0501 44D0501 44D0501 44D0501
Accessories
11 Thermostatic Remote Control 1 RCT/TRC RCT/TRC RCT/TRC RCT/TRC RCT/TRC RCT/TRC RCT/TRC RCT/TRC
12 Remote Control On/Off 1 RCM/MRC RCM/MRC RCM/MRC RCM/MRC RCM/MRC RCM/MRC RCM/MRC RCM/MRC 13 Wall Switch Kit 1 MVWS MVWS MVWS MVWS MVWS MVWS MVWS MVWS 14 Wall Thermostat Kit 1 MVWTS MVWTS MVWTS MVWTS MVWTS MVWTS MVWTS MVWTS
Conversion Kit (Not Shown)
300 Conversion NG to LPG 1 300 Conversion LPG to NG 1 — 400 Conversion NG to LPG 1 — 400 Conversion LPG to NG 1 — 500 Conversion
NG to LPG 1 — 500 Conversion
LPG to NG 1 600 Conversion NG to LP 1 600 Conversion LP to NG 1
BCK300CKPA
— — — — — — —
BCK300CKNA
— —
BCK400CKPA
BCK400CKNA — — — —
BCK500CKPA — — —
BCK500CKNA
BCK500CKPA —
BCK500CKNA
54D0700 45
ILLUSTRATED PARTS LISTS
ELECTRONIC IGNITION
1
LO
HI
5
3
4
6
2
8
7
10
11
9
6
'.$"52.%2
6'.$
3%.3%
30!2+
06
-606
-6
46 54D0700
ILLUSTRATED PARTS LISTS
ELECTRONIC IGNITION
Item Description Qty BDV300NE BDV300PE BDV400NE BDV400PE BDV500NE BDV500PE BDV600NE BDV 600PE
1 Gas Valve Assembly 1 37D0016 37D0017 37D0016 37D0017 37D0016 37D0017 37D0016 37D0017 2 Pilot Assembly 1 37D0020 37D0021 37D0020 37D0021 37D0020 37D0021 37D0020 37D0021 3 Burner Tube 1 54D0288 54D0288 54D0194 54D0194 54D0194 54D0194 54D0194 54D0194
4 Flexhose with Shutoff Valve 1 23D6046 23D6046 23D6046 23D6046 23D6046 23D6046 23D6046 23D6046
5 Rocker Switch 1 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 6 Injector 1 62D3006 20H3146 62D3004 20H3143 20H3145 57D0210 20H3145 57D0210 7 Burner Assembly 1 54D0200 54D0200 54D0001 54D0001 54D0329 54D0329 54D0329 54D0329 8 Venturi 1 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 9 Wire Assembly 1 54D2001 54D2001 54D2001 54D2001 54D2001 54D2001 54D2001 54D2001 10 Ignition Module 1 37D0325 37D0325 37D0325 37D0325 37D0325 37D0325 37D0325 37D0325 11 Transformer 1 37D0027 37D0027 37D0027 37D0027 37D0027 37D0027 37D0027 37D0027
54D0700 47
ILLUSTRATED PARTS LIST
VENT COMPONENTS
1
3
HOT
4
7
8
9
5
11
2
6
Simpson
Duravent Item Qty/Box Description or MHS P/N Selkirk P/N
1 1 Simpson Horizontal High Wind Termination Cap 985 4DT-HC 1 1 Horizontal Square Termination Cap with Built-In Vinyl Siding Standoff, Heat Defl ector and Firestop. Instructions are included with kit. BHRTK 1 1 Horizontal Rigid Pipe Termination Kit with Horizontal Termination Cap with Built-In Vinyl Siding Standoff, Heat Defl ector, Firestop, 90° Elbow and 11"x145/8" Adjustable Pipe. Instructions are included with kit. BHSTK — 1 1 Horizontal Flexible Pipe Termination Kit with Horizontal Termination Cap with Built-In Vinyl Siding Standoff, Heat Defl ector, Firestop, 20" to 40" Flexible Pipe Adapter. Instructions are included with kit. BHSFTK — 2 1 Vertical Termination 980 4DT-VC 3 6 6” Pipe Length 908 4DT-06 3 6 9” Pipe Length 907 4DT-09 3 6 12” Pipe Length 906 4DT-1 3 6 24” Pipe Length 904 4DT-4 3 6 36” Pipe Length 903 4DT-36 3 6 48” Pipe Length 902 4DT-48 4 6 11” To 14 5/8” Pipe, Adjustable 911 4DT-AJ 4 6 17” To 24” Pipe, Adjustable 917 4DT-AJ14 5 6 45° Elbow 945 4DT-EL45 5 6 45° Swivel Elbow 945G 4DT-EL45 6 6 90° Elbow 990 4DT-EL90 6 6 90° Swivel Elbow 990G 4DT-EL90 7 6 Flashing, 0/12 To 6/12 Roof Pitch 943 4DT-AF6 8 6 Storm Collar 953 4DT-SC 9 6 Firestop 963 4DT-FS 10 1 Vinyl Siding Standoff 950 4DT-VS 11 1 Ristrictor Disk 45D0551
10
48 54D0700
LOGS
Item Description Qty BDV300 BDV400 BDV500 BDV600
1 Rear Log 1 54D0121 54D0181 54D0339 54D0039 2 Right Log 1 54D0147 54D0116 54D0361 54D0361
3 Left Log 1 54D0146 54D0115 54D0360 54D0360
3
2
ILLUSTRATED PARTS LISTS
1
54D0700 49
NOTES
MASSACHUSETTS RESIDENTS ONLY:
PLEASE READ AND FOLLOW THESE
SPECIAL REQUIREMENTS
NOTE REGARDING VENTED PRODUCTS
This product must be installed by a licensed plumber or gas fi tter when installed within the Commonwealth of Massachu- setts.
Any residence with a direct vent product must have a CO detector installed in the residence. Installation of the fi replace or vented gas log in the State of Massachusetts requires the damper to be permanently removed
or welded in the fully open position. In addition, a naturally vented gas log may not be installed in a bedroom or bathroom in the State of Massachusetts. Flex line installation must not exceed 36 inches and must have a T shutoff valve.
NOTE REGARDING VENT FREE PRODUCTS
This product must be installed by a licensed plumber or gas fi tter when installed within the Commonwealth of Massachu- setts.
In addition, vent free products may not be installed in a bedroom or bathroom regardless of size or type in the State of Mas­sachusetts.
Flex line installation must not exceed 36 inches and must have a T shutoff valve.
CARBON MONOXIDE DETECTOR REQUIREMENTS
(2) Revise 10.8.3 by adding the following additional requirements: (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above fi nished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfi ed:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber or gasfi tter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the fl oor level where the gas equipment is to be installed. In addition, the installing plumber or gasfi tter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualifi ed licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent oor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation,
the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be in­stalled.
50 54D0700
SPECIAL REQUIREMENTS CONTINUED
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certifi ed.
3. SIGNAGE. A metal or plastic identifi cation plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required T o Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer
of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
NOTES
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the
manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the fl ue gases, but identifi es “special venting systems,” the following requirements shall be satisfi ed by the manufacturer:
1. The identifi cation of each “special venting system” shall include either the listing of the website, phone number or manufacturer's address where the venting system installation instructions can be obtained; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions provided with that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for the Product Approved side wall horizontally vented gas fueled equipment and
all the venting instructions, parts lists, and/or all design instructions for the venting system shall remain with the appli­ance or equipment at the completion of the installation.
54D0700 51
LIMITED LIFETIME WARRANTY POLICY
LIFETIME WARRANTY
The following components are warranted for life to the original owner, subject to proof of purchase: Firebox, Combustion Chamber, Heat Exchanger, Grate and Stainless Steel Burners.
FIVE YEAR WARRANTY
The following components are warranted five (5) years to the original owner, subject of proof of purchase: Ceramic Fiber Logs.
BASIC WARRANTY
Monessen Hearth Systems (MHS) warrants the components and materials in your gas appliance to be free from manufacturing and material defects for a period of two years from date of installation. After installation, if any of the components manu­factured by MHS in the appliance are found to be defective in materials or workmanship, MHS will, at its option, replace or repair the defective components at no charge to the original owner. MHS will also pay for reasonable labor costs incurred in replacing or repairing such components for a period of two years from date of installation. Any products presented for warranty repair must be accompanied by a dated proof of purchase.
This Limited Lifetime Warranty will be void if the appliance in not installed by a qualified installer in accordance with the installation instructions. The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance, and does not extend to (1) firebox/burner assembly damage by accident, neglect, misuse, abuse, alterations, negligence of others, including the installation thereof by unquali­fied installers, (2) the costs of removal, reinstallation or transportation of defective parts on the appliance, or (3) incidental or consequential damage. All service work must be performed by an authorized service representative.
This warranty is expressly in lieu of other warranties, express or implied, including the warranty of merchantability of fitness for purpose and of all other obligations or liabilities. MHS does not assume for it any other obligations or liabilities in con­nection with sale or use of the appliance. It states that do not allow limitations on how long an implied warranty lasts, or do not allow exclusion of indirect damage, those limitations of exclusions may not apply to you. You may also have additional rights not covered in the Limited Lifetime Warranty.
MHS reserves the right to investigate any and all the claims against the Limited Lifetime Warranty and decide upon method of settlement.
For information about this warranty, contact:
Technical Services
Monessen Hearth Systems
149 Cleveland Drive
Paris, Kentucky 40361
MAY 2008 P/N 54D0700 • Rev. 11