Mitsubishi Electronics MUY-D36NA, U1, MUY-D30NA, MUZ-D30NA, MUZ-D36NA User Manual

OUTDOOR UNIT
SERVICE MANUAL
Wireless type Models
MUZ-D30NA MUZ-D30NA-
U1
MUZ-D36NA MUZ-D36NA-
U1
MUY-D30NA MUY-D36NA
HFC
No. OBH502
utilized
R410A
Indoor unit service manual MSZ-D•NA Series (OBH501) MSY-D•NA Series (OBH501)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 3
3. SPECIFICATION ················································ 4
4. OUTLINES AND DIMENSIONS ························ 6
5. WIRING DIAGRAM ············································ 7
6. REFRIGERANT SYSTEM DIAGRAM ··············· 9
8. ACTUA TOR CONTROL ··································· 18
9. SERVICE FUNCTIONS ··································· 19
10. TROUBLESHOOTING ····································· 20
11. DISASSEMBLY INSTRUCTIONS ···················· 39
PARTS CATALOG (OBB502)
TM
2
1
TECHNICAL CHANGES
MUZ-D30NA MUZ-D30NA ­MUZ-D36NA MUZ-D36NA ­MUY-D30NA MUY-D36NA
1. New model
2
PART NAMES AND FUNCTIONS
MUZ-D30NA MUY-D30NA
U1
U1
MUZ-D36NA MUY-D36NA
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
33
3
Item Model MSZ-D30NA MSY-D30NA MSZ-D36NA MSY-D36NA
Capacity
Rated(Minimum~Maximum)
Capacity Rated Heating 17
Power consumption
Rated(Minimum~Maximum)
(TOTAL)
Power consumption Rated
EER 1 [SEER] 3 Cooling 8.0 [14.5] 9.1 [16.0]
HSPF IV(V) COP Heating 1 2.84 2.69
Outdoor unit model MUZ-D30NA MUY-D30NA MUZ-D36NA MUY-D36NA External fi nish Munsell 3Y 7.8/1.1
Power supply V , phase , Hz 208/230 , 1 , 60 Max. fuse size (time delay) A 25 Min. circuit ampacity A 21 Fan motor F.L.A 0.93
Compressor
Refrigerant control Liner expansion valve
Sound level 1
Defrost method Reverse cycle Reverse cycle
Dimensions
Weight Ib. 141 126 141 126 Remote controller Wireless type Control voltage (by built-in transformer) 12 - 24 VDC Refrigerant piping Not supplied
Refrigerant pipe size (Min. wall thickness)
Connection method
Between the indoor & outdoor units
Refrigerant charge (R410A) 4 lb. 10 oz. 4 lb. 4 lb. 10 oz. 4 lb. Refrigeration oil (Model) NE022
NOTE : Test conditions are based on ARI 210/240. 1 : Rating conditions (Cooling) — Indoor : 80 ˚FDB, 67 ˚FWB, Outdoor : 95 ˚FDB, (75 ˚FWB) Rated frequency (Heating) — Indoor : 70 ˚FDB, 60 ˚FWB, Outdoor : 47 ˚FDB, 43 ˚FWB Rated frequency 2 : (Heating) — Indoor : 70 ˚FDB, 60 ˚FWB, Outdoor : 17 ˚FDB, 15 ˚FWB Maximum frequency
SPECIFICATION
Cooling 1 Btu/h
Heating 47 1 Btu/h
2 Btu/h 20,800 — 22,800 —
Cooling
Heating 47 1W
Heating 17 2 W 2,620 3,000
4 Heating (8.2) — (8.2) —
Cooling dB(A) 55 55 56 56 Heating dB(A) 57 57
W in. 33-1/16 D in. 13 H in. 33-7/16
Liquid in. 3/8 (0.0315) Gas in. 5/8 (0.0394) Indoor Flared Outdoor Flared Height
difference Piping length ft. 100
1W
Model TNB220FMCHT R.L.A 16 L.R.A 20
ft. 50
30,700
(9,800 ~ 30,700)
32,600
(8,700 ~ 34,000)
3,850
(620 ~ 3,850)
3,360
(520 ~ 3,600)
30,700
(9,800 ~ 30,700)
3,380
(620 ~ 3,380)
32,000/33,200
(9,800 ~ 32,000) /
(9,800 ~ 33,200)
35,200
(8,700 ~ 36,000)
4,140/4,360
(620 ~ 4,140) /
(620 ~ 4,360)
3,840
(520 ~ 4,100)
7.7/7.6 [14.5]
33,200/34,600
(9,800 ~ 33,200) /
(9,800 ~ 34,600)
4,
(620 ~ 4,210) /
(620 ~ 4,240)
210/4,240
7.9/8.2 [15.1]
44
Test condition
3, 4
Mode Test
ARI
"A" Cooling Steady State at rated compressor Speed
"B-2" Cooling Steady State at rated compressor Speed
SEER
(Cooling)
HSPF
(Heating)
"B-1" Cooling Steady State at minimum compressor Speed
Low ambient Cooling Steady State at minimum compressor Speed
Intermediate Cooling Steady State at Intermediate compressor Speed
Standard Rating-Heating at rated compressor Speed
Low temperature Heating at rated compressor Speed
Max temperature Heating at minimum compressor Speed
High temperature Heating at minimum compressor Speed
Frost Accumulation at rated compressor Speed
Frost Accumulation at Intermediate compressor Speed
5
5
5 : At Intermediate compressor Speed
=("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".
Indoor air condition Outdoor air condition
Dry bulb (°F) Wet bulb (°F) Dry bulb (°F) Wet bulb (°F)
80 67 95 (75)
80 67 82 (65)
80 67 82 (65)
80 67 67 (53.5)
80 67 87 (69)
70 60 47 43
70 60 17 15
70 60 62 56.5
70 60 47 43
70 60 35 33
70 60 35 33
OPERATING RANGE
(1) POWER SUPPLY
Outdoor unit
(2) OPERATION
Mode Condition
Standard temperature 80 67 95
Cooling
Heating
Maximum temperature 90 73 115 — Minimum temperature 67 57 14 — Maximum humidity 78 % — Standard temperature 70 60 47 43 Maximum temperature 80 67 75 65 Minimum temperature 70 60 14 13
Rated voltage Guaranteed Voltage
208/230 V
1 phase
60 Hz
Min.187 V
DB WB DB WB
208 V 230 V Max.253 V
Intake air temperature (°F)
Indoor Outdoor
55
4
OUTLINES AND DIMENSIONS
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
REQUIRED SPACE
4 i
n. or more
Open as a rule 20 inch or more if the back, both sides and top are open
Unit: inch
Open as a rule 20 inch or more if the front and both sides are open
4 inch or more / 8 inch or more if there are obstacles to both sides
14 in. or more
6
6
5
MUZ-D30NA MUZ-D36NA
WIRING DIAGRAM
77
MUY-D30NA MUY-D36NA
88
6
REFRIGERANT SYSTEM DIAGRAM
MUZ-D30NA MUZ-D36NA
Refrigerant pipe (with heat insulator)
Refrigerant pipe 3/8 (with heat insulator)
5/8
Flared connection
Flared connection
4-way valve
Stop valve (with service port)
Receiver
Stop valve
Oil separator
Service port
Strainer
#100
Capillary tube
LEV
O.D. 0.142 I.D. 0.094
1-31/32
3.6 2.4 50
(
Strainer
#100
High-pressure Switch
Discharge temperature thermistor RT62
Compressor
Strainer
#100
)
Capillary tube
O.D. 0.071 x I.D. 0.024 x 39-3/8 ( 1.8 x 0.6 x 1,000)
Service port
Defrost thermistor RT61
Refrigerant flow in cooling Refrigerant flow in heating
Outdoor heat exchanger
Outdoor heat exchanger temperature thermistor RT68
R.V. coil heating ON cooling OFF
Ambient temperature thermistor RT65
Unit:inch
MUY-D30NA MUY-D36NA
Refrigerant pipe 5/8 (with heat insulator)
Flared connection
Flared connection
Oil separator
Capillary tube
O.D. 0.071 x I.D. 0.024 x 39-3/8 ( 1.8 x 0.6 x 1,000)
Stop valve (with service port)
Service port
Strainer
#100
Compressor
LEV
Service port
High-pressure Switch
Discharge temperature thermistor RT62
Strainer
#100
Outdoor heat exchanger
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Unit:inch
Refrigerant pipe 3/8 (with heat insulator)
Stop valve
Capillary tube
O.D. 0.142 x I.D. 0.094 x 1-31/32 ( 3.6 x 2.4 x 50)
99
Refrigerant flow in cooling
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping : ft. Piping size O.D : in.
Model
Max. Length
A
Max. Height difference
B
Gas Liquid
MUZ-D30NA MUZ-D36NA MUY-D30NA
100 50 5/8 3/8
MUY-D36NA
Indoor unit
Max. Height
difference
B
Max. length A
Outdoor unit
ADDITIONAL REFRIGERANT CHARGE (R410A:oz.)
Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
25 30 40 50 60 70 80 90 100
Refrigerant piping length (one way) : ft.
MUZ-D30NA MUZ-D36NA
4 lb. 10 oz. 0 2.96 8.88 14.80 20.72 26.64 32.56 38.48 44.40
Calculation : X oz. = 2.96/5 oz. / ft. x (Refrigerant piping length (ft.) - 25)
Model
MUY-D30NA MUY-D36NA
Outdoor unit
precharged
25 30 40 50 60 70 80 90 100
4 lb. 0 1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20
Refrigerant piping length (one way) : ft.
Calculation : X oz. = 1.08/5 oz. / ft. x (Refrigerant piping length (ft.) - 25)
NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
10
DATA7
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
7-1. PERFORMANCE DATA
1) COOLING CAPACITY
Indoor air Outdoor intake air DB temperature (˚F)
Model
MUZ-D30NA
MUZ-D36NA
MUY-D30NA
MUY-D36NA
(208 V)
MUY-D36NA
(230 V)
NOTE : 1. IWB : Intake air wet-bulb temperature
TC : Total Capacity (x10 SHC : Sensible Heat Capacity (x10 TPC : Total Power Consumption (kW)
2. SHC is based on 80 ˚F of indoor Intake air DB temperature.
IWB 75 85 95 105 115
(˚F) TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC
71 37.6 19.1 3.43 35.2 17.8 3.75 33.0 16.7 4.04 30.7 15.6 4.25 28.2 14.3 4.43 67 35.6 22.8 3.23 33.2 21.2 3.56 30.7 19.6 3.85 28.6 18.3 4.08 26.2 16.8 4.27 63 33.5 25.9 3.08 31.0 24.0 3.41 28.9 22.3 3.68 26.2 20.3 3.93 23.9 18.5 4.08 71 40.7 19.8 3.88 38.0 18.5 4.25 35.7 17.4 4.58 33.2 16.2 4.82 30.5 14.9 5.01 67 38.5 23.9 3.66 35.9 22.2 4.03 33.2 20.6 4.36 30.9 19.1 4.62 28.4 17.6 4.84 63 36.2 27.3 3.49 33.5 25.3 3.86 31.2 23.5 4.16 28.4 21.4 4.45 25.9 19.5 4.62 71 37.6 19.1 3.01 35.2 17.8 3.30 33.0 16.7 3.55 30.7 15.6 3.73 28.2 14.3 3.89 67 35.6 22.8 2.84 33.2 21.2 3.13 30.7 19.6 3.38 28.6 18.3 3.58 26.2 16.8 3.75 63 33.5 25.9 2.70 31.0 24.0 2.99 28.9 22.3 3.23 26.2 20.3 3.45 23.9 18.5 3.58 71 40.7 19.8 3.75 38.0 18.5 4.10 35.7 17.4 4.42 33.2 16.2 4.65 30.5 14.9 4.84 67 38.5 23.9 3.54 35.9 22.2 3.89 33.2 20.6 4.21 30.9 19.1 4.46 28.4 17.6 4.67 63 36.2 27.3 3.37 33.5 25.3 3.73 31.2 23.5 4.02 28.4 21.4 4.29 25.9 19.5 4.46 71 42.4 20.6 3.77 39.6 19.3 4.13 37.2 18.1 4.45 34.6 16.8 4.69 31.8 15.5 4.88 67 40.1 24.9 3.56 37.4 23.2 3.92 34.6 21.5 4.24 32.2 20.0 4.49 29.6 18.3 4.71 63 37.7 28.4 3.39 34.9 26.3 3.75 32.5 24.5 4.05 29.6 22.3 4.32 27.0 20.3 4.49
3
Btu/h)
3
Btu/h)
2) COOLING CAPACITY CORRECTIONS
Refrigerant piping length (one way : ft.)
25 (std.) 40 65 100
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
1.0 0.95 0.878 0.713
3) HEATING CAPACITY
Indoor air Outdoor intake air WB temperature (˚F)
Model
MUZ-D30NA
MUZ-D36NA
IDB 15 25 35 43 45 55 (˚F) TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC
75 18.9 2.50 23.6 2.94 28.2 3.28 31.8 3.44 32.8 3.49 37.2 3.63 70 20.0 2.42 24.5 2.87 28.9 3.19 32.6 3.36 33.6 3.43 38.0 3.56 65 20.5 2.32 25.6 2.77 29.8 3.11 33.6 3.28 34.6 3.33 38.8 3.49 75 20.4 2.86 25.5 3.36 30.4 3.74 34.3 3.94 35.4 3.99 40.1 4.15 70 21.6 2.76 26.4 3.28 31.2 3.65 35.2 3.84 36.3 3.92 41.0 4.07 65 22.2 2.65 27.6 3.17 32.2 3.55 36.3 3.74 37.3 3.80 41.9 3.99
NOTE : 1. IDB : Intake air dry-bulb temperature
TC : Total Capacity (x103 Btu/h) TPC : Total Power Consumption (kW)
2. Above data is for heating operation without any frost.
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on the remote controller.
11
7-2. PERFORMANCE CURVE Cooling
MUZ-D30NA
SHF at rating condition = 0.64
40 38 36 34
Indoor intake air WB temperature (°F)
32
Btu/h)
30
3
28
Total capacity
(10
26 24
4.5
4.3
4.1
3.9
3.7
(kW)
Indoor intake air WB temperat
3.5
3.3
3.1
Total power consumption
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
Airflow
MUY-D36NA
SHF at rating condition = 0.62
46
42
38
Ind
Btu/h)
3
Total capacity
(10
(kW)
Total power consumption
oor intake air WB temperature (°F)
34
30
26
5.0
4.6
4.2
oor intake air WB te
Ind
3.8
3.4
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
Airflow
mpe
= 763 CFM
ure (°F
= 763 CFM
rature (°F)
MUZ-D36NA
SHF at rating condition = 0.62
43 41 39 37
Indoor intake air WB temperature (°F)
35
Btu/h)
33
71 67 63
)
71 67 63
71
67
63
71
67
63
3
31
Total capacity
(10
29 27
5.2
4.8
4.4
(kW)
Indoor intake air WB temperat
4.0
3.6
Total power consumption
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
Airflow
= 763 CFM
ure (°F)
71 67 63
71 67 63
MUY-D30NA
SHF at rating condition = 0.64
40 38 36 34
Indoor intake air WB temperature (°F)
32
Btu/h)
30
3
28
Total capacity
(10
26 24
4.0
3.8
3.6
3.4
3.2
(kW)
Indoor intake air WB temperature (°F)
3.0
2.8
2.6
Total power consumption
65 75 85 95 105 115
Outdoor intake air DB temperature (°F)
Airflow
= 763 CFM
71 67 63
71 67 63
Heating
MUZ-D30NA
= 848 CFM
45
40
35
30
25
Btu/h)
3
20
Total capacity
(10
15
4.0
3.6
3.2
(kW)
2.8
2.4
Total power consumption
15 25 35 45 55
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity.
Airflow
Indoor intake air DB temperature (°F)
Indoor intake air DB temperature (°F
Outdoor intake air WB temperature (°F)
65 70 75
)
75 70 65
MUZ-D36NA
= 848 CFM
48
43
38
33
28
Btu/h)
3
23
Total capacity
(10
18
4.5
4.1
3.7
(kW)
3.3
2.9
Total power consumption
15 25 35 45 55
Airflow
oor intake air DB temperature (°F)
Ind
Indoor intake air DB temperature (°F)
Outdoor intake air WB temperature (°F)
1212
65 70 75
75 70 65
7-3. CONDENSING PRESSURE Cooling
Data is based on the condition of indoor humidity 50 %. Air flow should be set to High speed.
MUZ-D30NA
(PSIG)
580
540
500
460
420
380
Condensing pressure
340
300
260
68 70 75 80 85 90 95 100 105(°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
86 80 75 70
MUZ-D36NA
(PSIG)
580
540
500
460
420
380
Condensing pressure
340
300
260
68 70 75 80 85 90 95 100 105(°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
86 80 75 70
MUY-D30NA
(PSIG)
150
140
130
120
110
Suction pressure
100
90
68 70 75 80 85 90 95 100 105(°F)
(PSIG)
150
140
130
120
110
Suction pressure
100
90
68 70 75 80 85 90 95 100 105(°F)
Indoor DB temperature (°F
Outdoor ambient temperature
Indoor DB temperature (°F)
Outdoor ambient temperature
)
86
80
75
70
86
80
75
70
(PSIG)
580
540
500
460
420
380
Condensing pressure
340
300
260
68 70 75 80 85 90 95 100 105(°F)
Indoor DB temperat
Outdoor ambient temperature
ure (°F)
86 80 75 70
(PSIG)
150
140
130
120
110
Suction pressure
100
90
68 70 75 80 85 90 95 100 105(°F)
Indoor DB temperature (°F)
Outdoor ambient temperature
1313
86
80
75
70
MUY-D36NA
(PSIG)
580
86
540
500
460
Indoor DB temperature (°F)
80 75 70
420
380
Condensing pressure
340
300
260
68 70 75 80 85 90 95 100 105(°F)
Outdoor ambient temperature
Heating
Data is based on the condition of outdoor humidity 75 %. Air flow should be set to High speed. Data is for heating operation without any frost.
MUZ-D30NA
(PSIG)
150
140
130
Indoor DB temperature (°F)
120
110
Suction pressure
100
90
68 70 75 80 85 90 95 100 105(°F)
Outdoor ambient temperature
86
80
75
70
(PSIG)
500
480
460
440
420
400
380
360
340
320
300
Condensing pressure
280
260
240
220
200
14 20 25 30 35 40 45 50 55 60 65 70(°F)
MUZ-D36NA
(PSIG)
500
480
460
440
420
400
380
360
340
320
300
Condensing pressure
280
260
240
220
200
14 20 25 30 35 40 45 50 55 60 65 70(°F)
°F)
ure(
perat
oor DB tem
Ind
Outdoor ambient temperature
°F)
Indoor DB temperature(
Outdoor ambient temperature
58Hz
58Hz
(PSIG)
150
140
75
70
65
75
70
65
130
120
110
100
90
80
Suction pressure
70
60
50
14 20 25 30 35 40 45 50 55
(PSIG)
150
140
130
120
110
100
90
Suction pressure
80
70
60
50
14 20 25 30 35 40 45 50 55
Indoor DB temperature (°F)
Outdoor ambient temperature
Indoor DB temperature (°F)
Outdoor ambient temperature
58Hz
60 65 70(°F)
58Hz
60 65 70(°F)
75 70 65
75 70 65
14
7-4. STANDARD OPERATION DATA
Model MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA
Item Unit Cooling Heating Cooling Heating Cooling Cooling
Capacity Btu / h 30,700 32,600 32,000/33,200 35,200 30,700 33,200/34,000
SHF — 0.64 0.62 0.64 0.62
Total
Input kW 3.85 3.36 4.14/4.36 3.84 3.38 4.21/4.24
Rated frequency Hz 84 84 91 91 79 92 Indoor unit MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA
V,
Power supply
Input kW 0.058
Fan motor current A 0.45/0.42 Outdoor unit MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
Power supply
Electrical circuit
Input kW 3.792 3.302 4.082/4.302 3.782 3.322 4.152/4.182
Comp. current A 17.25/15.56 14.95/13.46 18.65/17.86 17.25/15.56 15.05/13.56 18.95/17.26
Fan motor current A 0.80/0.72
Condensing pressure PSIG 468 404 480 420 453 475
Suction pressure PSIG 126 96 122 94 125 119
Discharge temperature ˚F 186.8 169.7 198.7 168.8 191.3 197.1
Condensing temperature ˚F 126.5 114.3 128.5 117.0 123.8 127.4
Suction temperature ˚F 45.5 29.8 48.0 29.1 54.7 48.6
Comp. shell bottom temperature ˚F 175.6 156.4 187.0 155.7 177.4 182.7
Refrigerant circuit
Ref. pipe length ft. 25
Refrigerant charge (R410A) 4 lb. 10 oz. 4 lb.
Intake air temperature
Discharge air temperature
Indoor unit
Fan speed (High) rpm 1,100
Airfl ow (High) CFM 741 (Wet) 795 738 (Wet) 794 718 (Wet) 710 (Wet)
Intake air temperature
Fan speed rpm 800
Outdoor unit
Airfl ow CFM 1,941
phase,
Hz
V,
phase,
Hz
DB ˚F 80 70 80 70 80 80
WB ˚F 67 60 67 60 67 67
DB ˚F 53.9 112.2 53 114.9 53.7 51.7
WB ˚F 53 73.9 52.1 74.6 52.8 50.8
DB ˚F 95 47 95 47 95 95
WB ˚F — 43 — 43 — —
208/230 , 1 , 60
208/230 , 1 , 60
1515
7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY
MUZ-D30NA
Correction of Cooling capacity
1.5
Correction of Cooling total input
1.5
Correction of Heating capacity
1.5
Correction of Heating total input
1.5
1.0
0.5
Capacity correction factors
0 50 100 150
The operational frequency of compressor
MUZ-D36NA
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0 50 100 150
The operational frequency of compressor
MUY-D30NA
Correction of Cooling capacity
1.5
1.0
0.5
Input correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
Correction of Cooling total input
1.5
1.0
0.5
Input correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
Correction of Cooling total input
1.5
1.0
0.5
Capacity correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
Correction of Heating capacity
1.5
1.0
0.5
Capacity correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
1.0
0.5
Input correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
Correction of Heating total input
1.5
1.0
0.5
Input correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
(Hz)
(Hz)
1.0
0.5
Capacity correction factors
0 50 100 150
The operational frequency of compressor
MUY-D36NA
Correction of Cooling capacity
1.5
1.0
0.5
Capacity correction factors
0 50 100 150
The operational frequency of compressor
1.0
0.5
Input correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
Correction of Cooling total input
1.5
1.0
0.5
Input correction factors
(Hz)
0 50 100 150
The operational frequency of compressor
16
7-6. TEST RUN OPERATION (How to operate fixed-frequency operation)
1. Press EMERGENCY OPERATION switch to COOL or HEAT mode (COOL : Press once, HEAT : Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
17
8
ACTUATOR CONTROL
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
8-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds 15 seconds
ON
Compressor
OFF
ON
Outdoor fan motor
OFF
8-2. R.V. COIL CONTROL <MUZ>
Heating Cooling Dry
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
ON OFF OFF
<COOL>
5 seconds
<HEAT>
5 seconds
R.V.coil
Outdoor fan
motor
8-3. Relation between main sensor and actuator
Sensor Purpose
Discharge temperature thermistor Protection
Indoor coil temperature thermistor
Defrost thermistor Defrosting Fin temperature thermistor Protection Outdoor heat exchanger temperature Ambient temperature thermistor
ON
OFF
ON
OFF
ON or OFF
Cooling : Coil frost prevention Heating : High pressure protection
Protection Cooling : Low ambient temperature operation
ON or OFF
Actuator
Compressor
LEV
Outdoor
fan motor
R.V. coil
Indoor
fan motor
○○ ○ ○○○ ○○○○○ ○○ ○○○ ○○○
18
9
SERVICE FUNCTIONS
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
9-1. PRE-HEAT CONTROL
If moisture gets into the refrigerant cycle, or when refrigerant is liquefi ed and col- lected in the compressor, it may interfere the start-up of the compressor. To improve start-up condition, the compressor is energized even while it is not operating. This is to generate heat at the winding. The compressor uses about 50 W when pre-heat control is turned ON. Pre-heat control is ON at initial setting.
[How to activate pre-heat control]
1. Turn OFF the power supply for the air conditioner before making the setting.
2. Set the 2nd Dip Switch of SW1 on the outdoor electronic control P.C. board to ON to activate pre-heat control function.
The compressor is energized even while it is not operating. This is to generate heat at the winding to improve the compressor's start-up condition.
ON
1234
Power
Compressor
Outside temperature
Pre-heat
ON
OFF
ON
OFF
68 °F (20 °C)
ON
OFF
Breaker ON
30min.
Start operation
30min. 30min. 30min. 30min. 30min. 15min. 30min. 15min. 30min.
Stop operation
When outside temperature is above 68 °F (20 °C)
1. Pre-heat control is turned ON for 15 or 30 min. after the breaker is turned ON.
2. 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 min. and turned OFF for 30 min. This is repeated as shown in the graph until the breaker is turned OFF.
When outside temperature is 68 °F (20 °C) or below , pre-heat control is ON for 30 min.
When outside temperature is 70 °F (21 °C) or above, pre-heat control is ON for 15 min.
NOTE: When the unit is started with the remote controller, pre-heat control is turned OFF.
Compressor uses 50 W when pre-heat control is turned ON.
9-2. CHANGE IN DEFROST SETTING
Changing defrost finish temperature
1. Turn OFF the power supply for the air conditioner before making the setting.
2. Set the 4th Dip Switch of SW1 on the outdoor electronic control P.C. board to ON to change the defrost finish temperature. (Refer to 10-6-1.)
4th Dip Switch of SW1 Defrost fi nish temperature
OFF
(Initial setting)
ON 64.9 °F (18.3 °C)
49.5 °F (9.7 °C)
19
ON
1234
10
TROUBLESHOOTING
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
10-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after con­firming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring Housing point
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 10-2. and 10-3.
20
10-2. FAILURE MODE RECALL FUNCTION
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Operational procedure
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the
remote controller at the same time, press RESET button.
First, release RESET button.
And release the other two buttons after all LCD in operation display section of the
remote controller is displayed after 3 seconds.
This figures show about MSZ type.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-
ted at the same timing as the blinking of the left lamp of OPERATION INDICATOR lamp. 2
Yes
Judgment of indoor/outdoor abnormality
Releasing the failure mode recall function
Deleting the memorized abnormal condition
NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
Before blinking, does the left lamp of OPERATION INDICA­TOR lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the indoor unit failure mode table. (Refer to indoor unit service manual.) Make sure to check at least two consecutive blinking cycles.
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the defective parts.
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
(Blinks)
No
1
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnor-
No (OFF)
Yes
2
malities that can't be recalled with this way. Confi rm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 10-2.2)
The outdoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the outdoor unit failure mode table. (Refer to 10-2.3) Make sure to check at least two consecutive blinking cycles.
2. Blinking pattern when the indoor unit is abnormal:
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF
Blinking at 0.5-
second interval
ON
OFF
Repeated cycle Repeated cycle
Beeps
Beeps
Repeated cycle
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
3
Beeps
3.Blinking pattern when the outdoor unit is abnormal:
2.5-second OFF 3-second ON
ON
OFF
No beep Beeps
Repeated cycle
Blinking at 0.5­second interval
2.5-second OFF 3-second ON
No beep Beeps
Repeated cycle
21
Blinking at 0.5­second interval
Repeated cycle
2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
The outdoor unit might be abnormal. Confi rm if outdoor unit is abnormal according to the following procedures.
Confi rm that the remote controller is in the failure mode recall function.
With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 77 ˚F (25 ˚C).
1
Does left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of the left lamp of OPERATION INDICATOR lamp. 2
Yes
)
(Blinks
The outdoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the out- door unit failure mode table. (10-2.3.) Make sure to check at least two consecutive blinking cycles.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the defective parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (10-2.1.).
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
No (OFF)
2
1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
The outdoor unit is normal.
Release the failure mode recall function accord­ing to the left mentioned procedure.
2.Blinking pattern when outdoor unit is abnormal:
2.5-second OFF 3-second ON
ON
OFF
No beep
Repeated cycle
Blinking at 0.5­second interval
Beeps
2.5-second OFF 3-second ON
No beep Beeps
Repeated cycle
22
Blinking at 0.5-
second interval
Repeated cycle
3. Outdoor unit failure mode table
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
LED indication
The left lamp of OPERA-
TION INDICATOR lamp
(Indoor unit)
OFF Non (Normal)
2-time fl ash Outdoor power system Lighting Lighting
Abnormal point
(Failure mode / protection)
Discharge temperature thermistor Lighting Once
(Outdoor P.C.
board)
LED 1 LED 2
Condition Correspondence
IPM protection stop or lock protection stop is continuously performed 3 times within 1 minute after the compres­sor gets started, or converter protection stop or bus-bar voltage protection stop is continuously performed 3 times within 3 minutes after start-up.
Check the connection of the compressor connecting wire.
Refer to 10-5. inverter / compressor". Refer to 10-5. "Check of
• compressor start failure". Check the stop valve.
"How to check
Indoor/outdoor
unit failure mode
recall function
Defrost thermistor (MUZ) Lighting Once
3-time fl ash
4-time fl ash Overcurrent Once
5-time fl ash Discharge temperature Lighting Lighting
6-time fl ash High pressure Lighting Lighting
7-time fl ash
8-time fl ash Outdoor fan motor Lighting Lighting
9-time fl ash Nonvolatile memory data Lighting 5 times Nonvolatile memory data cannot be read properly.
10-time fl ash Discharge temperature Lighting Lighting
11-time fl ash
Ambient temperature thermistor Lighting Twice
Fin temperature thermistor Lighting 3 times
P.C. board temperature thermistor Lighting 4 times
Outdoor heat exchanger tempera­ture thermistor
Fin temperature 3 times
P.C. board temperature 4 times
Communication error between P.C. boards
Current sensor Lighting 7 times
Zero cross detecting circuit 5 times Goes out
Lighting 9 times
Goes
out
Goes
out
Goes
out
Lighting 6 times
Thermistor shorts or opens during compressor running.
28 A current fl ow into intelligent power module.
Temperature of discharge temperature thermistor exceeds 241 °F (116 °C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212 °F (100 °C) or less 3 minutes later.
The outdoor heat exchanger temperature exceeds 158 °F (70 °C) during cooling or the indoor gas pipe temperature exceeds 158 °F (70 °C) during heating (MUZ).
The fi n temperature exceeds 189 °F (87 °C) during opera- tion.
The P.C. board temperature exceeds 158 °F (70 °C) during operation.
Failure occurs continuously 3 times within 30 seconds after the fan gets started.
The frequency of the compressor is kept 80 Hz or more and the discharge temperature is kept under 102 °F (39 °C) for more than 20 minutes.
Communication error occurs between the electronic control P.C. board and power board for more than 10 seconds.
The communication between boards protection stop is continuously performed twice.
A short or open circuit is detected in the current sensor during compressor operating.
Current sensor protection stop is continuously performed twice.
Zero cross signal cannot be detected while the compres­sor is operating.
The protection stop of the zero cross detecting circuit is continuously performed 10 times.
Refer to 10-5. "Check of
• outdoor thermistors".
Replace the outdoor electronic
• control P.C. board.
Refer to 10-5. "Check of
• outdoor thermistors".
Reconnect compressor con-
• nector. Refer to 10-5. "How to check
• inverter/ compressor." Refer to 10-5. "Check of
• compressor start failure". Check the stop valve.
Check refrigerant circuit and
• refrigerant amount. Refer to 10-5. "Check of
• LEV".
Check refrigerant circuit and
• refrigerant amount. Check the stop valve.
Check around outdoor unit.
• Check outdoor unit air pas-
• sage. Refer to 10-5. "Check of
• outdoor fan motor".
Refer to 10-5. "Check of
• outdoor fan motor".
Replace the outdoor electronic
• control P.C. board.
Check refrigerant circuit and
• refrigerant amount. Refer to 10-5. "Check of
• LEV".
Check the connecting wire
• between outdoor electronic control P.C. board and power board.
Replace the power board.
Check the connecting wire
• among electronic control P.C. board, noise fi lter P.C. board and power board.
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).
23
The left lamp of OPERA-
TION INDICATOR lamp
(Indoor unit)
LED indication (Out-
Abnormal point
(Failure mode / protection)
Converter 5 times Goes out
Bus-bar voltage (1)
door P.C. board)
LED 1 LED 2
5 times Goes out
Condition Correspondence
A failure is detected in the operation of the converter dur­ing operation.
The bus-bar voltage exceeds 400 V or falls to 200 V or below during compressor operating.
Indoor/outdoor
unit failure mode
recall function
Replace the power board.
11-time fl ash
Bus-bar voltage (2)
Even if this protection stop
is performed continuously 3 times, it does not mean the abnormality in outdoor power system.
6 times Goes out
The bus-bar voltage exceeds 400 V or falls to 50 V or below during compressor operating.
24
10-3. TROUBLESHOOTING CHECK TABLE
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
No. Symptom
1
2 Lightning 3 times
3 Lightning 4 times
Outdoor unit does not oper-
4 Lightning 5 times
ate.
5 Lightning 6 times Serial signal
6 Lightning 7 times Nonvolatile memory data The nonvolatile memory data cannot be read properly. Replace the outdoor electronic control P.C. board.
7 Lightning 8 times Current sensor
8 Lightning 11 times
9 Lightning 12 times Zero cross detecting circuit
10
11 3 times Goes out
12 4 times Goes out
'Outdoor
13 5 times Goes out High-pressure protection
unit stops and restarts 3 minutes
14 8 times Goes out Converter protection
later' is repeated.
15 9 times Goes out
16 13 times Goes out Outdoor fan motor
17 Lighting 8 times Current sensor protection
18 Lighting 11 times
19 Lighting 12 times
NOTE 1. The location of LED is illustrated at the right figure. Refer to 10-6.1.
2. LED is lighted during normal operation.
Indication
LED1 (Red)
(Yellow)
Lightning Twice Outdoor power system
Twice Goes out
Abnormal point / Condition Condition Correspondence
LED2
Discharge temperature therm­istor
Fin temperature thermistor
P.C. board temperature therm­istor
Ambient temperature thermis­tor
Outdoor heat exchanger temperature thermistor
Defrost thermistor (MUZ)
Communication error between P.C. boards
IPM protection
Lock protection
Discharge temperature protec­tion
Fin temperature protection The fi n temperature exceeds 189 °F (87 °C) during operation.
P.C. board temperature pro­tection
Bus-bar voltage protection (1)
Bus-bar voltage protection (2)
Communication between P.C. boards protection
Zero cross detecting circuit protection
IPM protection stop or lock protection stop is continuously performed three times within 1 minute after the compressor gets started, or converter protection stop or bus-bar voltage protection stop is continuously performed 3 times within 3 minutes after start-up.
A short circuit is detected in the thermistor during opera­tion, or an open circuit is detected in the thermistor after 10 minutes of compressor start-up.
A short or open circuit is detected in the thermistor during operation.
A short or open circuit is detected in the thermistor during operation.
A short circuit is detected in the thermistor during operation, or an open circuit is detected in the thermistor after 5 minutes (in cooling) and 10 minutes (in heating (MUZ)) of compressor start-up.
A short circuit is detected in the thermistor during operation, or an open circuit is detected in the thermistor after 5 minutes of compressor start-up.
The communication fails between the indoor and outdoor unit for 3 minutes.
Current sensor protection stop is continuously performed twice.
The communication protection stop between boards is con­tinuously performed twice.
The protection stop of the zero cross detecting circuit is continuously performed 10 times.
Overcurrent is detected after 30 minutes of compressor start­up.
Overcurrent is detected within 30 minutes of compressor start-up
Temperature of discharge temperature thermistor exceeds 241 °F (116 °C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212 °F (100 °C) or less 3 minutes later.
The P.C. board temperature exceeds 158 °F (70 °C) during operation.
The outdoor heat exchanger temperature exceeds 158 °F (70 °C) during cooling or indoor gas pipe temperature exceeds 158 °F (70 °C) during heating (MUZ).
A failure is detected in the operation of the converter during operation.
The bus-bar voltage exceeds 400 V or falls to 200 V or below during compressor operating.
The bus-bar voltage exceeds 400 V or falls to 50 V or below during compressor operating.
Failure occurs continuously three times within 30 seconds after the fan gets started.
A short or open circuit is detected in the current sensor during compressor operating.
Communication error occurs between the outdoor electronic control P.C. board and power board for more than 10 sec­onds.
Zero cross signal cannot be detected while the compressor is operating.
Outdoor electronic control P.C. board(Parts side)
0.5-second ON
0.5-second ON
Check the connection of the compressor connect­ing wire.
Refer to 10-5. sor". Refer to 10-5. "Check of compressor start failure".
• Check the stop valve.
Refer to 10-5. "Check of outdoor thermistor".
Refer to 10-5. "Check of outdoor thermistor".
Replace the outdoor electronic control P.C. board.
Refer to 10-5. "Check of outdoor thermistor".
Refer to 10-5. "How to check miswiring and serial
• signal error.
Replace the power board.
Check the connecting wire between outdoor elec-
• tronic control P.C. board and power board.
Check the connecting wire among outdoor elec-
• tronic control P.C. board, noise fi lter P.C. board and power board.
Reconnect compressor connector.
Refer to 10-5. sor". Refer to 10-5. "Check of compressor start failure".
• Check the stop valve.
• Check the power module (PAM module).
Check the amount of gas and refrigerant circuit.
• Refer to 10-5. "Check of LEV".
Check refrigerant circuit and refrigerant amount.
• Refer to 10-5. "Check of LEV".
Check around of gas and the refrigerant circuit.
• Check of stop valve.
Replace the power board.
Replace the power board.
Refer to 10-5. "Check of outdoor fan motor".
Replace the power board.
Check the connecting wire between outdoor elec-
• tronic control P.C. board and power board.
Check the connecting wire among outdoor elec-
• tronic control P.C. board, noise fi lter P.C. board and power board.
"How to check inverter/compres-
"How to check inverter/compres-
LED1
LED2
Lighting
ON
OFF
2.5-second OFF
2.5-second OFF
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the flashing frequency is “2”.
25
No. Symptom
20
21 Twice Lighting
22 3 times Lighting
Outdoor unit oper­ates.
23 4 times Lighting
24 5 times Lighting
25
Outdoor unit oper­ates
26 Lighting Lighting Normal
Indication
LED1 (Red)
(Yellow)
Once Lighting
9 times Lighting Inverter check mode The unit is operated with emergency operation switch.
Abnormal point / Condition Condition Correspondence
LED2
Primary current protection The input current exceeds 15 A.
Secondary current protection The current of the compressor exceeds 15 A.
High-pressure protection (MUZ)
Defrosting in cooling
Discharge temperature protec­tion
Low discharge temperature protection
Cooling high-pressure protec­tion
The indoor gas pipe temperature exceeds 113 °F (45 °C) dur­ing heating.
The indoor gas pipe temperature falls 37 °F (3 °C) or below during cooling.
The discharge temperature exceeds 212 °F (100 °C) during operation.
The frequency of the compressor is kept 80 Hz or more and the discharge temperature is kept under 102 °F (39 °C) for more than 20 minutes.
The outdoor heat exchanger temperature exceeds 136 °F (58 °C) during operation.
These symptoms do not mean any abnormality of
• the product, but check the following points. Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short
• cycled.
Check refrigerant circuit and refrigerant amount.
Refer to 10-5. Refer to 10-5. "Check of outdoor thermistors".
Refer to 10-5. "Check of LEV".
• Check refrigerant circuit and refrigerant amount.
This symptom does not mean any abnormality of
• the product, but check the following points. Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short
• cycled.
"Check of LEV".
26
10-4. TROUBLE CRITERION OF MAIN PARTS
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
Part name Check method and criterion Figure
Defrost thermistor
(RT61) (MUZ)
Ambient temperature thermistor (RT65)
Outdoor heat ex­changer temperature thermistor (RT68)
Discharge tem­perature thermistor (RT62)
Fin temperature thermistor (RT64)
Measure the resistance with a tester.
Refer to 10-6. “Test point diagram and voltage”, 1. “Outdoor electron­ic control P.C. board”, the chart of thermistor.
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 10-6. “Test point diagram and voltage”, 1. “Outdoor electron­ic control P.C. board”, the chart of thermistor.
Compressor
Outdoor fan motor
R. V. coil (MUZ)
Linear expansion valve
Measure the resistance between terminals using a tester. (Winding temperature : 14 ~ 104 °F (-10 ~ 40 °C))
Normal
1.24 ~ 1.53 Ω
Measure the resistance between lead wires using a tester. (Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))
Color of lead wire Normal
RED – BLK
13 ~ 16 ΩBLK – WHT
WHT – RED
Measure the resistance using a tester. (Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))
Normal
1.20 ~ 1.55 kΩ
Measure the resistance using a tester. (Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))
Color of lead wire Normal
WHT – RED
RED – ORN YLW – BRN
38 ~ 50 Ω
BRN – BLU
V
WHT
WHT
RED
ORN
W
RED
U
BLK
RED
(W)
U
WHT
(V)
V
BLK
(U)
W
LEV
YLW
BRN
BLU
27
10-5. TROUBLESHOOTING FLOW
OPERATION / INDICATOR lamp flashes 5-times. Outdoor unit does not operate.
A How to check inverter/ compressor
Disconnect the terminal of the compressor. 3 minutes after turn­ing on the power supply, start EMERGENCY OPERATION.
Measure the voltage between each lead wire leading to the compressor. U (BLK) - V (WHT) V (WHT) - W (RED) W (RED) - U (BLK) Is voltage output on right table?
Yes
Is output balanced?
Yes
Is the input voltage to the outdoor electronic control P.C. board 370 V or more?
Yes
Turn off power supply of indoor and outdoor unit, and measure the compressor winding resistance between the compressor terminals. Is the resistance between each terminal normal?
Yes
•After the outdoor fan starts running, wait for 1 minute or more before measuring the voltage.
•The output voltage values have the tolerance of ±20 %.
No
No
Replace the power board.
No
No
Replace the compressor.
Reconnect the lead wire of compressor, and turn on power supply to indoor and outdoor unit. 3 minutes later, starts EMERGENCY OPERATION.
Clarify the causes by counting time until the inverter stops. 0 to 10 seconds: compressor rare short 10 to 60 seconds: compressor lock 60 seconds to 5 minutes: refrigerant circuit defective 5 minutes or more: normal
28
OPERATION INDICATOR lamp flashes 6-times. Thermistor is abnormal.
B Check of outdoor thermistors
Disconnect the connector of thermistor in the outdoor P.C. board (see below table), and measure the resistance of thermistor.
Is the thermistor normal? (Refer to 10-6.1.)
Yes
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
Yes
OK. (Cause is poor contact.)
Thermistor Symbol Connector, Pin No. Board
Defrost (MUZ) RT61 Between CN661 pin1 and pin2
Discharge temperature RT62 Between CN661 pin3 and pin4 Outdoor heat exchanger temperature RT68 Between CN661 pin7 and pin8 Ambient temperature RT65 Between CN663 pin1 and pin2 Fin temperature RT64 Between CN3 pin1 and pin2 Outdoor power board
No
No
Replace the thermistor except RT64. When RT64 is abnormal, replace the outdoor power board.
Replace the outdoor power board.
Outdoor electronic control P.C. board
29
The cooling operation or heating operation does not operate.
C Check of R.V. coil
MUZ-D30/36
Heating operation does not work.
Disconnect the lead wire leading to the compressor.
1. 3 minutes after turning on the power supply, start EMERGENCY
2. OPERATION in HEAT mode.
Is there voltage of 208 / 230 VAC between pin1 and pin 2 at connector CN912?
Yes
Turn OFF power supply of indoor and outdoor unit.
Disconnect the connec­tor CN912 in noise fi lter P.C. board. Is there normal resistance to R.V. coil?
Yes
Replace the 4-way valve.
Cooling operation does not work.
Disconnect the lead wire leading to the compressor.
1. 3 minutes after turning on the power supply, start EMERGENCY
2. OPERATION in COOL mode.
Is there voltage of 208 / 230 VAC between pin1 and pin 2 at connector CN912?
Replace the R.V. coil.
No
No
No
Turn off power supply of indoor and outdoor unit, and discon-
1. nect the connector CN781 in the outdoor electronic control P.C. board. 3 minutes after turning ON the power supply, start EMER-
2
.
GENCY OPERATION in HEAT mode.
Is there voltage 12 VDC be­tween the connector CN781 pin 5 (+) and pin 3 (-)?
Yes
Replace the noise fi lter P.C. board.
If the connector CN912 is not
connected or R.V. coil is open, voltage occurs between terminals even when the control is OFF.
Replace the 4-way valve.
Replace the electronic
No
control P.C. board.
Turn OFF power supply of indoor and outdoor unit, and
1. disconnect the connector CN781 in the outdoor electronic control P.C. board.
.
3 minutes after turning ON the power supply, start EMER-
2
GENCY OPERATION in COOL mode.
Is there voltage 12 VDC between the connector CN781 pin 5 (+) and pin 3 (-)?
Yes
Replace the outdoor electronic control P.C. board.
No
Replace the noise fi lter P.C. board.
30
Fan motor does not operate or stops operating shortly after starting the operation.
D Check of outdoor fan motor
Check the connection between the connector CN931 and CN932.
Is the resistance between each ter­minal of outdoor fan motor normal? (Refer to 10-4.)
No
Yes
Disconnect CN932 from outdoor electronic control P.C. board, and turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-)
(Fixed to either 5 or 0 VDC)
Replace the outdoor DC fan motor. Replace the outdoor electronic control P.C. board.
Outdoor unit does not operate.
Does the voltage between each terminal become 5 VDC
No
and 0 VDC repeatedly?
Yes
Does the outdoor fan motor rotate smoothly?
No
Yes
E Check of power supply
Check the connecting of parts of main power supply circuit.
Turn ON power supply.
Is there voltage of 208 / 230 VAC in the power supply terminal block?
Yes
Is the output voltage from the noise fi lter P.C. board 208 / 230 VAC?
Yes
No
No
Check the power supply cable.
Replace the noise fi lter P.C. board.
Is the input voltage to the power board 208 / 230 VAC?
Yes
Is the input voltage to the outdoor electronic control P.C. board 294 / 325 VDC?
Yes
Replace the outdoor electronic control P.C. board.
No
No
Replace the reactor.
Replace the power board.
31
F Check of compressor start failure
Confi rm that 1~4 is normal.
•Electrical circuit check Contact of lead wire leading to compressor
1. Output voltage of the outdoor electronic control P.C. board and balance of them
2. (See 10-5. ) Direct current voltage to the outdoor electronic control P.C. board
3. Voltage between outdoor terminal block S1-S2
4
.
Does the compressor run for 10 seconds or more after it starts?
Yes
Check the refrigerant circuit. Check the stop valve.
No
After the compressor is heated with a drier, does the compressor start? 1
No
Replace the compressor.
Yes
Compressor start failure. Activate pre-heat control. (Refer to 9-1. "PRE-HEAT CONTROL")
When cooling, heat exchanger of non-operating indoor unit frosts. When heating, non-operating indoor unit gets warm.
G Check of LEV
Turn ON power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.
1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part
Is "click - click" sound heard? Or, do you feel vibration of the LEV coil with a hand?
No
Disconnect the connector CN795. Is there normal resistance to LEV coil?
No
Replace the LEV coil.
32
Yes
Yes
Normal
Replace the outdoor electronic control P.C. board.
• Unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch. Indoor unit does not operate.
• OPERATION INDICATOR lamp flashes ON and OFF in every 0.5 seconds. Outdoor unit doesn’t operate.
H How to check miswiring and serial signal error
Turn OFF the power supply.
Outdoor electronic control P.C. board
Turn OFF inverter-controlled lighting
• equipment. Turn OFF the power supply and then
• turn ON again. Press EMERGENCY OPERATION
• switch.
Is serial signal error indicated 6 minutes later?
Yes
B
(Parts side)
LED1
LED2
A
No
BlinkingLighted
Reinstall either the unit or the light each other away. Attach a fi lter on remote control receiving section of the indoor unit.
Is there rated voltage in the power supply?
Yes
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICA­TOR lamp light up? <Confi rmation of the power to the indoor unit>
Is serial signal error indicated 6 minutes later?
Turn OFF the power supply. Check once more if the indoor/outdoor
B
connecting wire is not miswiring. Short-circuit outdoor terminal block S2 and S3.
Turn ON the power supply.
Does the LED on the inverter P.C. board or the outdoor electronic control P.C. board repeat "3.6-second-OFF and 0.8-second­ON quick blinking"? 3
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20 VDC between outdoor terminal block S2 and S3? <Confi rmation of serial signal>
Is there rated voltage between indoor terminal block S1 and S2? <Confi rmation of power voltage>
Replace the indoor electronic control P.C. board.
Be sure to release the failure-mode recall function after checking.
Yes
Yes
Yes
A
1
Yes
Yes
Yes
No
No
No
No
Check the power supply.
Check the wiring.
No
Is there any miswiring, poor contact, or wire disconnec­tion of the indoor/outdoor
No
connecting wire? Is fuse (F65) broken?
1. Miswiring may damage indoor electronic control P.C. board during the operation.
Be sure to confi rm the wiring is correct before the opera-
tion starts.
3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes.
Replace the inverter P.C. board or
No (Lighted or not lighted)
the outdoor electronic control P.C. board.
Is there any error of the in­door/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Is there any error of the in­door/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
2
2. Be careful to the residual voltage of smoothing capacitor.
No
No
Correct them.
Yes
Replace the indoor/ outdoor connecting
Yes
wire.
Replace the indoor/ outdoor connecting
Yes
wire.
33
The operation frequency does not go up from lowest frequency.
I Check of HPS
1. Disconnect the connector CN681 in the electronic control P.C. board.
2. Check the resistance of HPS 1 minute after the outdoor unit power supply was turned OFF.
Check the resistance between each terminal.
0 Ω
Reconnect CN681. Turn ON power supply to the indoor and outdoor unit. 3 minutes later, start EMERGENCY OPERATION.
Is HPS protection displayed immediately after compressor starts?
No
Normal
Infi nity
Yes
Replace HPS.
Replace the outdoor electronic control P.C. board.
34
J Electromagnetic noise enters into TV sets or radios
Is the unit grounded?
Yes
Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.91 ft.?
No
Is the distance between the TV sets or radios and the indoor unit within 3.28 ft., or is the distance between the TV sets or radios and the outdoor unit within 9.91 ft.?
No
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten­na wiring?
No
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
No
Yes
Yes
Yes
Yes
Ground the unit.
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Replace or repair the antenna. Replace or repair the coaxial cable.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir­ing of the antennas.
No
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the followings before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the elec­tromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
35
10-6. TEST POINT DIAGRAM AND VOLTAGE
1. Outdoor electronic control P.C. board
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
Discharge temperature thermistor (RT62)
700
600
500
400
300
200
Resistance (kΩ)
100
0
32 50 68 86 104 122 140 176 194 122 212 230 248
Temperature (°F)
(
CN932
20-90 VAC
(
To fan
motor
5 VDC
(
CN931
pulse wave
Defrost thermistor (RT61)
GND
5 V
(MUZ) CN661
(
Outdoor heat exchanger temperature
Discharge temperature thermistor (RT62)
CN661
(
(
Fin temperature thermistor (RT64)
200
180
160
140
120
100
80
Resistance (kΩ)
60
40
20
0
32 50 68 86 104 122 140 158 176
CN663
CN702
(
CN701
Signal transmission
(To power board)
5 VDC pulse wave
(
thermistor (RT68) CN661
Ambient temperature
thermistor (RT65)
(
(–)
(+)
(+)
Temperature (°F)
Signal reception
(From power board)
5 VDC pulse wave
GND
(–)
12 V
(
(–)
15 V
15 V
GND (power board)
Rush current relay
Defrost thermistor (RT61) Ambient temperature thermistor (RT65) Outdoor heat exchanger temperature thermistor (RT68)
100
90
80
70
60
50
Resistance (kΩ)
40
30
20
10
0
DC
R.V. coil (–)
-4 14 32 50 68 86 104
Temperature (°F)
CN781
LEV
CN795
12 VDC
pulse wave
(
(
(–)
(+)
(
(+)
LED 1
LED 2
CN801
294 ~ 370
VDC Input
F801
FUSE
3.15 A / 250 V
CN601
(
208/230 VAC 60 Hz Input
(
CN681 High pressure switch
(
for indoor
5~10 VDC
36
2. Noise filter P.C. board
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
CN901
MUZ
CN912 R.V. coil 208 / 230 VAC 60 Hz Output
208 / 230 VAC 60 Hz Output
{
To electronic control P.C. board
{
CN902 To power board
CN903 To power board
{
208 / 230 VAC 60 Hz Input
F64 FUSE 2 A / 250 V
NR64 VARISTOR
{
CN61
37
3. Outdoor power board
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
Connect to the compressor Voltage among phases: 180 V
Connect to the earth
294-370 VDC Output
(+)
(–)
(Red)
1
3
(White)
CN2 Connect to the controller board (+)1-5(–): Signal transmission (To electronic control P.C. board) 5 VDC pulse wave (+)2-5(–): Zero cross signal 3-4 : Not used (+)6-5(–): 15 V (+)7-5(–): 15 V
CN3 Fin temperature thermistor RT64
Signal reception (From electronic
)
control P.C. board) 5 VDC pulse wave
CN5 Primary current detection (Connect to the noise filter)
38
11
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve
Slide the sleeve.Pull the terminal while
Locking lever
pushing the locking lever.
(2) The terminal with this connector has the locking mechanism.
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Remove the screws of the cabinet. (8) Remove the cabinet. (9) Remove the screws of the back panel. (10)
Remove the back panel.
Photo 1
Screw of the top panel
Screws of the cabinet
Hold the sleeve, and pull out the terminal slowly.
Connector
Photo 3
Conduit plate
Screws of the back panel
Screw of the motor support
Set screws of the back panel
39
39
Screws of the cabinet
Photo 2
Screw of the service panel
Screws of the top panel
Set screws of the back panel
Screws of the cabinet
Screw of the valve cover
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, P.C. board and power board
(1) Remove the top panel, cabinet, service panel and the back
panel. (Refer to 1.)
(2) Disconnect the following connectors;
<Electronic control P.C. board>
CN931 and CN932 (Fan motor) CN795 (LEV) CN661 (Discharge temperature thermistor, defrost
thermistor (MUZ) and outdoor heat exchanger
temperature thermistor) CN663 (Ambient temperature thermistor) CN681 (High pressure switch) (MUZ)
<Noise filter P.C. board>
CN912 (4-way valve) (MUZ)
<Compressor>
<Reactor> (4) Remove the screws fixing the relay panel. (5) Remove the inverter assembly. (6) Disconnect all connectors and lead wires on the electronic
control P.C. board. (7) Remove the electronic control P.C. board from the inverter
assembly. (8) Remove the screws fixing the power board assembly. (9) Disconnect all connectors and lead wires on the power
board. (10)
Remove the power board from the inverter assembly.
(11)
Disconnect all connectors and lead wires on the noise filter
P.C. board. (12)
Remove the noise filter P.C. board from the inverter
assembly.
Photo 4
Screws of the reactor
HPS
Discharge temperature thermistor
Photo 5 (Inverter assembly)
Screws of the power board assembly
3. Removing R.V. coil (MUZ)
(1) Remove the top panel, cabinet, service panel and the back
panel. (Refer to 1.) (2) Disconnect the following connectors;
<Noise filter P.C. board>
CN912 (4-way valve)
(3) Remove the R.V. coil. (Photo 9)
Screws of the relay panel
Photo 6
Screws of the relay panel
Propeller
40
OPERATING PROCEDURE
PHOTOS
4. Removing the defrost thermistor (MUZ), discharge temperature thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor
(1) Remove the top panel, cabinet, service panel and the back
panel. (Refer to 1.)
(2) Disconnect the following connectors;
<Electronic control P.C. board>
CN661 (Discharge temperature thermistor, defrost therm-
istor (MUZ) and outdoor heat exchanger tem­perature thermistor)
CN663 (Ambient temperature thermistor) (3) Pull out the defrost thermistor from its holder. (Photo 7) (MUZ) (4) Pull out the discharge temperature thermistor from its hold-
er. (Photo 4)
(5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 7)
(6) Pull out the ambient temperature thermistor from its holder.
(Photo 7)
Photo 7
Outdoor heat exchanger temperature thermistor
Ambient temperature thermistor
Defrost thermistor (for MUZ)
5. Removing outdoor fan motor
(1) Remove the top panel, cabinet, service panel and the back
panel. (Refer to 1.)
(2) Disconnect the following connectors;
<Electronic control P.C. board>
CN931 and CN932 (Fan motor) (3) Remove the propeller. (4) Remove the screws fixing the outdoor fan motor. (5) Remove the outdoor fan motor.
41
Photo 8
Propeller
Screws of the outdoor fan motor
OPERATING PROCEDURE
PHOTOS
6. Removing the compressor and 4-way valve
(1) Remove the top panel, cabinet, service panel and the back
panel. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Remove the R.V. coil. (Refer to 3.) (4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure
gauge shows 0 PSIG. (5) Detach the welded part of the suction and the discharge
pipe connected with compressor. (Photo 9) (6) Remove the compressor nuts. (7) Remove the compressor. (8) Detach the welded part of 4-way valve and pipe. (Photo 8)
Photo 9
Photo 10
Welded parts of 4-way valve
Welded part of the discharge pipe
R.V. coil
7. Removing the reactor
(1) Remove the top panel, cabinet, service panel and the back
panel. (Refer to 1.) (2) Disconnect the reactor lead wire. (3) Remove the screws of the reactor, and remove the reactor.
Welded part of the suction pipe
42
43
TM
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Feb. 2008. No. OBH502 7 Made in Japan
New publication, effective Feb. 2008 Specifications subject to change without notice.
Loading...