Mitsubishi SRK21CNS-S6, SRK26CNS-S6, SRK19CNS-S, SRK25CNS-S Technical Manual

Page 1
RESIDENTIAL AIR-CONDITIONING
TECHNICAL MANUAL & PARTS LIST
WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS (Split system, air cooled cooling only type)
SRK21CNS-S6 SRK26CNS-S6
Page 2
Page 3
-
1
-
'14•SRK-T-164
TECHNICAL MANUAL
Page 4
-
2
-
'14•SRK-T-164
gs32+4
CONTENTS
1. SPECIFICATIONS .................................................................................... 4
(2) Outdoor units ...................................................................................... 8
(3) Wireless remote control
...................................................................... 10
........................................................................ 6
(1) Indoor units ......................................................................................... 6
2. EXTERIOR DIMENSIONS
3. ELECTRICAL WIRING ............................................................................. 11
(1) Indoor units ......................................................................................... 11
(2) Outdoor units ...................................................................................... 13
....................................................... 15
5. RANGE OF USAGE & LIMITATIONS
4. PIPING SYSTEM ..................................................................................... 14
............................................................................... 17
6. APPLICATION DATA
7. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ........... 28
(6) 3D auto operation
............................................................................. 32
4IMEROPERATION
................................................................................. 33
(5) Flap and louver control ..................................................................... 31
...................................................... 30(4) Custom cord switching procedure
........................................................................ 30(3) Auto restart function
(2) Unit ON/OFF button

(1) Operation control function by remote control ..................................... 28
(8) Installation location setting ................................................................. 33
(10) Outline of automatic operation .......................................................... 34
/UTLINEOFCOOLINGOPERATION .............................................................. 34
(11) Protective control function
.................................................................. 35
.............................................................................. 37
.................... 38
4ROUBLESHOOTINGPROCEDURE)FTHEAIRCONDITIONERRUNS
4ROUBLESHOOTINGPROCEDURE
(If the air conditioner does not run at all)
....... 37
(1) Cautions
............................................................................................ 37
(2) Items to check before troubleshooting ................................................ 37
3ELFDIAGNOSISTABLE 
(6) Inspection procedures corresponding to detail of trouble ................... 40
8. MAINTENANCE DATA
Page 5
-
3
-
'14•SRK-T-164
gs32+4
(OWTOMAKESUREOFWIRELESSREMOTECONTROL ..................................... 45

0HENOMENONOBSERVEDAFTERSHORTCIRCUITWIREBREAKAGEONSENSOR
........ 43
#HECKINGTHEINDOORELECTRICALEQUIPMENT
.......................................... 44
How to read the model name
Example: SRK 21 C
Series code
Cooling only type
Product capacity
Model name SRK : Wall mounted type
SRC : Outdoor unit
NS-S6
Page 6
-
4
-
'14•SRK-T-164
1. SPECIFICATIONS
Model
Item
SRK21CNS-S6
Indoor unit SRK21CNS-S6 Outdoor unit SRC21CNS-S6 Cooling capacity (1) W 5300 Power supply 1 Phase, 220-240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 1.46
Running current
Cooling
A
6.4
Inrush current 3.6 COP Cooling 3.63 Noise level
Cooling
Sound level dB(A) Hi : 47 Me : 42 Lo : 39 50
Power level dB 60 65 Exterior dimensions (Height x Width x Depth) mm 309 x 890 x 251 640 x 850 (+65) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 12 44.5
Refrigerant equipment
Compressor type & Q'ty PA190M2AS-4KTL1 (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil 0.62 (ESTER OIL VG74) Refrigerant (4) kg R410A 1.34 (Pre-Charged up to the piping length of 7.5m) Heat exchanger Louver fins & inner grooved tubing Louver fins & inner grooved tubing Refrigerant control Capillary tubes + Electronic expansion valve Deice control Microcomputer control
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 30 40 Air flow Cooling m3/min 15 38 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat
Operation Display
RUN : Green, TIMER : Yellow, HI POWER : Green,
3D AUTO : Green
Safety devices
Compressor overheat protection,
Frost protection, Serial signal error protection, Fan motor error protection,
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ15.88 (5/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.55 Gas line : 0.49
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 25
Vertical height difference between outdoor unit and indoor unit
Max.15 (Outdoor unit is higher)
Max.15 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable 2m (3 Cores wih Earth) Recommended breaker size A 20
Connection wiring
Size x Core number 1.5mm2 x 4 cores (Including earth cable) Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit
Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 7.5m connecting piping. (Purging is not required even for the short piping.) If the piping length is 7.5m to 15m, additional refrigerant is not required.
The pipe length is 7.5m.
Page 7
-
5
-
'14•SRK-T-164
Model
Item
SRK26CNS-S6
Indoor unit SRK26CNS-S6 Outdoor unit SRC26CNS-S6 Cooling capacity (1) W 7400 Power supply 1 Phase, 220-240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 2.065
Running current
Cooling
A
9.2
Inrush current 43.7 COP Cooling 3.58 Noise level
Cooling
Sound level dB(A) Hi : 50 Me : 46 Lo : 43 55
Power level dB 60 67 Exterior dimensions (Height x Width x Depth) mm 318 x 1098 x 248 750 x 880 (+88) x 340 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 14.5 53
Refrigerant equipment
Compressor type & Q'ty PA270G2CS-4MUL1 (Rotary type) x 1 Motor (Starting method) kW PSC Refrigerant oil 0.85 (ESTER OIL VG74) Refrigerant (4) kg R410A 1.05 (Pre-Charged up to the piping length of 7m) Heat exchanger Louver & inner grooved tubing Aluminium heat-exchanger Refrigerant control Capillary tubes + Electronic expansion valve Deice control Microcomputer control
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 56 90 Air flow Cooling m3/min Hi : 20.0 Me : 17.0 Lo : 14.0 60 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless remote control — Room temperature control Microcomputer thermostat
Operation Display
RUN : Green, TIMER : Yellow, HI POWER : Green,
3D AUTO : Green
Safety devices
Compressor overheat protection,
Frost protection, Serial signal error protection, Fan motor error protection,
Installation data
Refrigerant piping size (O.D) mm Liquid line :φ6.35 (1/4") Gas line :φ15.88 (5/8") Connecting method Flare connecting
Attached length of piping m
Liquid line : 0.70 Gas line : 0.63
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 25
Vertical height difference between outdoor unit and indoor unit
Max.15 (Outdoor unit is higher)
Max.15 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable 2m (3 Cores wih Earth) Recommended breaker size A 20
Connection wiring
Size x Core number 1.5mm2 x 4 cores (Including earth cable)
Connecting method Terminal block (Screw fixing type) Accessories (included) Mounting kit Option parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 230V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 7.5m connecting piping. (Purging is not required even for the short piping.) If the piping length is 7.5m to 15m, additional refrigerant is not required.
The pipe length is 7.5m.
Page 8
-
6
-
'14•SRK-T-164
G
F
Space for installation and service when viewing from the front
Outlet for down piping
Refer to the above view
D C
A
E
B
Terminal block
881.9
59.926 20.9
59.9
46.5
61.5
46.5
61.5
890
309
9 61.5
3251
50 120 650 120 100
220 450 220
35 35
48.9222.5
48
48
5.7
295.4 7.9
15
Service space
100
Unit
54
46.5
Service space
Service space
Service space
Installation plate
491.1
520.8
559.1
58
61.5
2. EXTERIOR DIMENSIONS
(1) Indoor units
Model SRK21CNS-S6
Hole on wall for right rear piping
Hole on wall for left rear piping
Gas piping
Outlet for pipingon both side
Drain hose
Outlet for wiring
Liquid piping
F
G
E
CDB
Symbol
A
ø65
VP16
ø6.35(1/4")(Flare)
Content
ø15.88(5/8")(Flare)
ø65
Wireless remote control
Unit:mm
60
150
17.3
Page 9
-
7
-
'14•SRK-T-164
Model SRK26CNS-S6
Outlet for down piping
Refer to the above view
Hole on wall for right rear piping
Hole on wall for left rear piping
Gas piping
Outlet for pipingon both side
Drain hose
Outlet for wiring
Liquid piping
F
G
E
CDB
Symbol
A
ø65
VP16
ø6.35(1/4")(Flare)
Content
ø15.88(5/8")(Flare)
ø65
D
C
B
A
E
Wireless remote control
G
F
Unit:mm
7753.5
633.5
703.5 792
15
7.7
44.5
44.5
301.8 8.5
5050
450349 299
106886106
100
100
50
49.5
221.5
25
25
Service space
Service space
Service space
Unit
Installation plate
Space for installation and service when viewing from the front
6-5X17.5Slot hole
43
412X18(Slot hole)
Service space
244 610 244
225
46
1098
318
3
248
410904
60
55
19
55
55
43.564
9
60
150
17.3
Page 10
-
8
-
'14•SRK-T-164
(2) Outdoor units
Model SRC21CNS-S6
φ15.88(58")(Flare
Content
C Pipecable draw-out hole
D
E Anchor bolt hole
Drain discharge hole
Symbol
B
A Service valve connection(gas side)
M10×4places
φ20×3places
Service valve connection(liquid side)
φ6.35(14")(Flare
Minimum installation space
Notes
.sedisruofehtnosllawybdednuorrusebtontsumtI1
 (2 The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm.
 (3 Where the unit is subject to strong winds, lay it in such
a direction that the blower outlet faces perpendicularly
to the dominant wind direction.
 (4 Leave 1m or more space above the unit.
 (5 A wall in front of the blower outlet must not exceed the units height.
 (6 The model name label is attached on the right side of the unit.
L2
L3
L4
L1 600
100
100
Examples of
Dimensions
installation
15
640
100.3 39.7
40
40
125.4 33.3
Terminal block
43.549.6
153
476.3
203.1 510 136.9
850 65
17.9
21.9
286.4
50
12
14 312.5
340
13.5
103.2
385.9
Outlet
Intake
L3
L1
L2
Intake
Service
space
( )
L4
Open
2-16x12
240
290
320
Center of gravity
A
C
B
D
E
Unit:mm
Page 11
-
9
-
'14•SRK-T-164
Model SRC26CNS-S6
φ15.88(58")(Flare
Content
C Pipecable draw-out hole
D
E Anchor bolt hole
Drain discharge hole
Symbol
B
A Service valve connection(gas side)
M10×4places
φ20×3places
Service valve connection(liquid side)
φ6.35(14")(Flare
Unit:mm
Minimum installation space
Notes
.sedisruofehtnosllawybdednuorrusebtontsumtI1
 (2 The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm.
 (3 Where the unit is subject to strong winds, lay it in such
a direction that the blower outlet faces perpendicularly
to the dominant wind direction.
 (4 Leave 1m or more space above the unit.
 (5 A wall in front of the blower outlet must not exceed the units height.
 (6 The model name label is attached on the right side of the unit.
L2
L3
L4
L1 600
100
100
Examples of
Dimensions
installation
Outlet
Intake
L3
L1
L2
Intake
Service
space
( )
L4
Open
150 580 150
88
223
533
61
25.8
29.8
61
47.5
60
15
380 1919
2-φ15
742
30
30
Terminal block
165.5 25
418
375
Center of gravity
150
880
340
D
E
B
C
A
24
103.4 48.5
278
Page 12
-
10
-
'14•SRK-T-164
(3) Wireless remote control
Unit: mm
60
17.3
150
Unit: mm
17.3
150
Page 13
-
11
-
'14•SRK-T-164
3. ELECTRICAL WIRING
(1) Indoor units
Model SRK21CNS-S6
250V
FUSE
3.15A
S/N
VARISTOR
FAN MOTOR
CNU
CNS
J
U
M
1 3 4 5 6
TO OUTSIDE
T
TERMINAL
1
2/N
3
UNIT
BLOCK
L
HEAT
EXCHANGER
BOARD
CIRCUIT
PRINTED
CNR
CNX2
CNX1
RED
WHITE
RED
WHITE
BLACK
BLUE
YELLOW
BLACK
CNG
CNE
DISPLAY
WIRELESS RECEIVER
CNF
BACK-UP SW
2
9
HEAT EXCHANGER SENSOR 1
ROOM TEMP. SENSOR
HUMIDITY
SENSOR
FLAP
MOTOR
MOTOR
LEFT
LOUVER
LOUVER
RIGHT
MOTOR
5 5
3
5
INTERFACE KIT
SC-BIKN
5
3
2
7
M
M
M
Page 14
-
12
-
'14•SRK-T-164
Model SRK26CNS-S6
250V
FUSE
3.15A
S/N
VARISTOR
FAN MOTOR
CNU
CNS
INTERFACE KIT
SC-BIKN
J
M
1 3 4 5 6
5
TO OUTSIDE
T
TERMINAL
1
2/N
3
UNIT
BLOCK
L
HEAT
EXCHANGER
BOARD
CIRCUIT
PRINTED
FLAP
LOUVER
RIGHT
MOTOR
LEFT
CNX2
CNX1
M
M
M
5
5
5
LOUVER
MOTOR
MOTOR
RED
WHITE
RED
WHITE
BLACK
BLUE
YELLOW
BLACK
CNG
CNE
DISPLAY
WIRELESS RECEIVER
CNF
BACK-UP SW
2
8
HUMIDITY SENSOR
HEAT EXCHANGER SENSOR 1
ROOM TEMP. SENSOR
t
t
U
Page 15
-
13
-
'14•SRK-T-164
PRINTED CIRCUIT
BOARD
PRINTED CIRCUIT
BOARD
ELECTRIC EXPANSION VALVE(COIL) HEAT EXCHANGER SENSOR OUTDOOR AIR TEMP. SENSOR DISCHARGE PIPE TEMP. SENSOR
RUNNING CAPACITOR FOR FAN MOTOR
RUNNING CAPACITOR FOR COMPRESSOR
COMPRESSOR MOTOR
DIODE STACK
FAN MOTOR
CFO
Th3 D.S CC
EEV
Th2
Th1
FMo
CM
TERMINAL BLOCKT
MEANING OF SYMBOLS
PARTS NAME
SYMBOL
Y/GN
T
ELECTRIC EXPANSION VALVE(COIL) HEAT EXCHANGER SENSOR OUTDOOR AIR TEMP. SENSOR DISCHARGE PIPE TEMP. SENSOR
RUNNING CAPACITOR FOR FAN MOTOR
RUNNING CAPACITOR FOR COMPRESSOR
COMPRESSOR MOTOR
DIODE STACK
FAN MOTOR
CFO
Th3 D.S CC
EEV
Th2
Th1
FMo
CM
TERMINAL BLOCKT1,T2
MEANING OF SYMBOLS
PARTS NAME
SYMBOL
Y/GN
Y/GN
WH
(2) Outdoor units
Model SRC21CNS-S6
Model SRC26CNS-S6
BL
RD
OR
SYMBOL
BK
BLUE
ORANGE
RED
BLACK
COLOR COLOR
WH
SYMBOL
WHITE
WH
RD
BK
N
J
L
D.S
VARISTOR
+
-
CNG
Th2
EEV
CNE
Th1
Th3
CC
WH
CM2
CM1
BK
R
WH
RD
C
N
3
2
L
1
INDOOR UNIT
POWER SOURCE 220-240V 50Hz
S
YELLOW/
GREEN
Y/GN
FMo
OR
BL
WH
CFO
OR
WH
52X1
CM
BL
RD
OR
SYMBOL
BK
BLUE
ORANGE
RED
BLACK
COLOR COLOR
WH
SYMBOL
WHITE
YELLOW/
GREEN
Y/GN
WH
RD
BK
N
J
L
D.S
VARISTOR
+
-
CNG
Th2
EEV
CNE
Th1
Th3
CC
WH
CM2
CM1
BK
R
WH
RD
C
S
250V 3.15A
FUSE
FMo
OR
BL
WH
CFO
OR
WH
52X1
CM
N
3
2
1
L
N
BK
T1
T2
INDOOR UNIT
POWER SOURCE 220-240V 50Hz
250V 3.15A
FUSE
4
4
52X1
52X1
Page 16
-
14
-
'14•SRK-T-164
4. PIPING SYSTEM
Model SRK21CNS-S6
Model SRK26CNS-S6
Outdoor unitIndoor unit
Room temp. sensor
Humidity sensor
Heat exchanger
Flare connecting
Heat exchanger sensor
Liquid pipe
ø
6.35
Gas pipe
ø15.88
Check joint
Service valve (Liquid)
Flare connecting
Discharge pipe temp. sensor
Outdoor air temp. sensor
Heat exchanger
Heat exchanger sensor
Compressor
Capillary tube
Strainer
Accumulator
Service valve (Gas)
Electronic expansion valve
Outdoor unitIndoor unit
Room temp. sensor
Humidity sensor
Heat exchanger
Flare connecting
Heat exchanger sensor
Liquid pipe ø
6.35
Gas pipe
Check joint
Service valve (Liquid)
Flare connecting
Discharge pipe temp. sensor
Outdoor air temp. sensor
Heat exchanger
Heat exchanger sensor
Compressor
Capillary tube
Strainer
Strainer
Accumulator
Service valve (Gas)
Electronic expansion valve
ø
15.88
Cooling cycle
Cooling cycle
Page 17
-
15
-
'14•SRK-T-164
5. RANGE OF USAGE & LIMITATIONS
Net capacity = Capacity shown on specification Correction factors as follows.
(1) Coefficient of cooling capacity in relation to temperatures
All models
Models
Item
Indoor return air temperature (
Upper, lower limits
)
Outdoor air temperature (
Upper, lower limits
)
Refer to the selection chart
Refrigerant line (one way) length
Max. 25m
Max. 15m (Outdoor unit is higher
)
Max. 15m (Outdoor unit is lower
)
Min. 3 minutes
Max. 10 times/h
Min. 85% of rating
Vertical height difference between outdoor unit and indoor unit
Power source voltage
Voltage at starting
Frequency of ON−OFF cycle
ON and OFF interval
Rating 10%
14 16 18 20 22
15
20
25
30
35
40
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
43
24
ISO-T1 Standard ConditionIndoor air W.B. temperature °C W.B.
Cooling
Applicable range
Coefficient of cooling
capacity in relation
to temperature
Cooling operation
Outdoor air D.B.
temperature
°C D.B.
Page 18
-
16
-
'14•SRK-T-164
(2) Correction of cooling capacity in relation to one way length of refrigerant piping
How to obtain the cooling capacity
=
Piping length [m]
Cooling
7
1.0
10
0.99
15
0.975
20
0.965
25
0.95
SRK21CNS-S6
SRK21CNS-S6
5300 5168
Page 19
-
17
-
'14•SRK-T-164
6. APPLICATION DATA
Safety precautions
WALL TYPE AIR CONDITIONER
R410A REFRIGERANT USED
Read the “Safety precautions” carefully first of all and strictly follow it during the installation work in order to protect yourself.v The precautionary items mentioned below are distinguished into two levels,v
WARNING
and
CAUTION
.
WARNING
: Wrong installation would cause serious consequences such as injuries or death.
CAUTION
: Wrong installation might cause serious consequences depending on circumstances.
Both mentions the important items to protect your health and safety so strictly follow them by any means. Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the operating methods as v well as the maintenance methods of this equipment to the user according to the user’s manual. Keep the installation manual together with user’s manual at a place where any user can read at any time. Moreover if necessary, ask v to hand them to a new user. For installing qualified personnel, take precautions in respect to themselves by using suitable protective clothing, groves, etc., and then v perform the installation works. Please pay attention not to fall down the tools, etc. when installing the unit at the high position.v If unusual noise can be heard during operation, consult the dealer.v The meanings of “Marks” used here are shown as follows:v
Never do it under any circumstances.
Always do it according to the instruction.
WARNING
Installation must be carried out by the qualified installer.v
If you install the system by yourself, it may cause serious trouble such as water leaks, electric shocks, fire and personal injury, as a result of a system malfunction. Do not carry out the installation and maintenance work except the by qualified installer.
Install the system in full accordance with the installation v manual.
Incorrect installation may cause bursts, personal injury, water leaks, electric shocks and fire.
Be sure to use only for household and residence.v
If this appliance is installed in inferior environment such as machine shop and etc., it can cause malfunction.
Use the original accessories and the specified components forv installation.
If parts other than those prescribed by us are used, it may cause water leaks, electric shocks, fire and personal injury.
Install the unit in a location with good support.v
Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury.
Ensure the unit is stable when installed, so that it can withstand v earthquakes and strong winds.
Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury.
Ventilate the working area well in the event of refrigerantv leakage during installation.
If the density of refrigerant exceeds the limit, please consult the dealer and install the ventilation system, otherwise lack of oxygen can occur, which can cause serious accident.
When installing in small rooms, take prevention measures not v to exceed the density limit of refrigerant in the event of leakage, referred by the formula (accordance with ISO5149).
If the density of refrigerant exceeds the limit, please consult the dealer and install the ventilation system, otherwise lack of oxygen can occur, which can cause serious accident.
After completed installation, check that no refrigerant leaks v from the system.
If refrigerant leaks into the room and comes into contact with an oven or other hot surface, poisonous gas is produced.
Use the prescribed pipes, flare nuts and tools for R410A.v
Using existing parts (for R22 or R407C) can cause the unit failure and serious accidents due to burst of the refrigerant circuit.
Tighten the flare nut by torque wrench with specified method.v
If the flare nut were tightened with excess torque, this may cause burst and refrigerant leakage after a long period.
Do not open the operation valves for liquid line and gas line v until completed refrigerant piping work, air tightness test and evacuation.
If the compressor is operated in state of opening operation valves before completed connection of refrigerant piping work, air can be sucked into refrigerant circuit, which can cause burst or personal injury due to anomalously high pressure in the refrigerant.
The electrical installation must be carried out by the qualifiedv electrician in accordance with “the norm for electrical work” and “national wiring regulation”, and the system must be connected to the dedicated circuit.
Power supply with insufficient capacity and incorrect function done by improper work can cause electric shocks and fire.
Be sure to shut off the power before starting electrical work.v
Failure to shut off the power can cause electric shocks, unit failure or incorrect function of equipment.
Be sure to use the cables conformed to safety standard and v cable ampacity for power distribution work.
Unconformable cables can cause electric leak, anomalous heat production or fire.
This appliance must be connected to main power supply byv means of a circuit breaker or switch (fuse 21 series: 20A, 26 series: 25A) with a contact separation of at least 3mm.
When plugging this appliance, a plug conforming to the norm v IEC60884-1 must be used.
Use the prescribed cables for electrical connection, tighten v the cables securely in terminal block and relieve the cables correctly to prevent overloading the terminal blocks.
Loose connections or cable mountings can cause anomalous heat production or fire.
Arrange the wiring in the control box so that it cannot be v pushed up further into the box. Install the service panel correctly.
Incorrect installation may result in overheating and fire.
Be sure to fix up the service panels.v
Incorrect fixing can cause electric shocks or fire due to intrusion of dust or water.
Be sure to switch off the power supply in the event of v installation, inspection or servicing.
If the power supply is not shut off, there is a risk of electric shocks, unit failure or personal injury due to the unexpected start of fan.
Stop the compressor before removing the pipe after shutting v the service valve on pump down work.
If the pipe is removed when the compressor is in operation with the service valve open, air would be mixed in the refrigeration circuit and it could cause explosion and injuries due to abnormal high pressure in the cooling cycle.
Only use prescribed option parts. The installation must be v carried out by the qualified installer.
If you install the system by yourself, it can cause serious trouble such as w
ater leaks, electric shocks, fire.
Be sure to wear pr
otective goggles and gloves while at work.v
Earth leakage breaker must be installed.v
If the earth leakage breaker is not installed, it can cause electric shocks.
Do not put the drainage pipe directly into drainage channelsv where poisonous gases such as sulphide gas can occur.
Poisonous gases will flow into the room through drainage pipe and seriously affect the user’s health and safety. This can also cause the corrosion of the indoor unit and a resultant unit failure or refrigerant leak.
Ensure that no air enters in the refrigerant circuit when the unit v is installed and removed.
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit becomes too high, which can cause burst and personal injury.
Do not bundling, winding or processing for the power cord. Or,v do not deforming the power plug due to tread it.
This may cause fire or heating.
Do not processing, splice the power cord, or share a socketv with other power plugs.
This may cause fire or electric shock due to defecting contact, defecting insulation and over-current etc.
Do not vent R410A into the atmosphere : R410A is a fluorinatedv greenhouse gas, covered by the Kyoto Protocol with Global Warming Potential (GWP)=1975.
Do not run the unit with removed panels or protections.v
Touching rotating equipments, hot surfaces or high voltage parts can cause personal injury due to entrapment, burn or electric shocks.
Do not perform any change of protective device itself or its v setup condition.
The forced operation by short-circuiting protective device of pressure switch and temperature controller or the use of non specified component can cause fire or burst.
When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces.
Page 20
-
18
-
'14•SRK-T-164
Safety precautions
CAUTION
Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting.
Use the circuit breaker of correct capacity. Circuit breaker should be the one that disconnect all poles under over current.
Using the incorrect one could cause the system failure and fi re.
Install isolator or disconnect switch on the power supply wiring in accordance with the local codes and regulations.
The isolator should be locked in OFF state in accordance with EN60204-1.
Be sure to install indoor unit properly according to the instruction manual in order to run off the drainage smoothly.
Improper installation of indoor unit can cause dropping water into the room and damaging personal property.
Install the drainage pipe to run off drainage securely according to the installation manual.
Incorrect installation of the drainage pipe can cause dropping water into the room and damaging personal property.
Be sure to install the drainage pipe with descending slope of 1/100 or more, and not to make traps and air-bleedings.
Check if the drainage runs off securely during commissioning and ensure the space for inspection and maintenance.
After maintenance, all wiring, wiring ties and the like, should be returned to their original state and wiring route, and the necessary clearance from all metal parts should be secured.
Secure a space for installation, inspection and maintenance specifi ed in the manual.
Insuffi cient space can result in accident such as personal injury due to falling from the installation place.
Take care when carrying the unit by hand.
If the unit weights more than 20kg, it must be carried by two or more persons. Do not carry by the plastic straps, always use the carry handle when carrying the unit by hand. Use gloves to minimize the risk of cuts by the aluminum fi ns.
Dispose of any packing materials correctly.
Any remaining packing materials can cause personal injury as it contains nails and wood. And to avoid danger of suffocation, be sure to keep the plastic wrapper away from children and to dispose after tear it up.
For installation work, be careful not to get injured with the heat exchanger, piping fl are portion or screws etc.
Be sure to insulate the refrigerant pipes so as not to condense the ambient air moisture on them.
Insuffi cient insulation can cause condensation, which can lead to moisture damage on the ceiling, fl oor, furniture and any other valuables.
When perform the air conditioner operation (cooling or drying
operation) in which ventilator is installed in the room. In this case, using the air conditioner in parallel with the ventilator, there is the possibility that drain water may backfl ow in accordance with the room lapse into the negative pressure status. Therefore, set up the opening port such as incorporate the air into the room that may appropriate to ventilation (For example; Open the door a little). In addition, just as above, so set up the opening port if the room lapse into negative pressure status due to register of the wind for the high rise apartment etc.
Be sure to perform air tightness test by pressurizing with nitrogen gas after completed refrigerant piping work.
If the density of refrigerant exceeds the limit in the event of refrigerant leakage in the small room, lack of oxygen can occur, which can cause serious accidents.
Do not install the unit in the locations listed below.
Locations where carbon fi ber, metal powder or any powder is fl oating.
Locations where any substances that can affect the unit such as sulphide gas, chloride gas, acid and alkaline can occur. Vehicles and ships. Locations where cosmetic or special sprays are often used. Locations with direct exposure of oil mist and steam such as kitchen and machine plant. Locations where any machines which generate high frequency harmonics are used. Locations with salty atmospheres such as coastlines. Locations with heavy snow (If installed, be sure to provide base fl ame and snow hood mentioned in the manual). Locations where the unit is exposed to chimney smoke. Locations at high altitude (more than 1000m high). Locations with ammonic atmospheres. Locations where heat radiation from other heat source can affect the unit. Locations without good air circulation. Locations with any obstacles which can prevent inlet and outlet air of the unit. Locations where short circuit of air can occur (in case of multiple units installation). Locations where strong air blows against the air outlet of outdoor unit.
Locations where something located above the unit could fall. It can cause remarkable decrease in performance, corrosion and damage of components, malfunction and fi re.
Do not install the indoor unit in the locations listed below (Be
sure to install the indoor unit according to the installation manual for each model because each indoor unit has each limitation).
Locations with any obstacles which can prevent inlet and outlet air
of the unit.
Locations where vibration can be amplifi ed due to insuffi cient
strength of structure.
Locations where the infrared receiver is exposed to the direct
sunlight or the strong light beam (in case of the infrared
specifi cation unit).
Locations where an equipment affected by high harmonics is placed
(TV set or radio receiver is placed within 1m).
Locations where drainage cannot run off safely. It can affect performance or function and etc.
Do not install the outdoor unit in the locations listed below.
Locations where discharged hot air or operating sound of the
outdoor unit can bother neighborhood.
Locations where outlet air of the outdoor unit blows directly to
plants. The outlet air can affect adversely to the plant etc.
Locations where vibration can be amplifi ed and transmitted due to
insuffi cient strength of structure.
Locations where vibration and operation sound generated by the outdoor
unit can affect seriously (on the wall or at the place near bed room).
Locations where an equipment affected by high harmonics is placed
(TV set or radio receiver is placed within 1m).
Locations where drainage cannot run off safely. It can affect surrounding environment and cause a claim.
Do not install the unit where corrosive gas (such as sulfurous acid gas etc.) or combustible gas (such as thinner and petroleum gases) can accumulate or collect, or where volatile combustible substances are handled.
Corrosive gas can cause corrosion of heat exchanger, breakage of plastic parts and etc. And combustible gas can cause fi re.
Do not install the unit near the location where leakage of combustible gases can occur.
If leaked gases accumulate around the unit, it can cause fi re.
Do not use the indoor unit at the place where water splashes may occur such as in laundries.
Since the indoor unit is not waterproof, it can cause electric shocks and fi re.
Do not install nor use the system close to the equipment that generates electromagnetic fi elds or high frequency harmonics.
Equipment such as inverters, standby generators, medical high frequency equipments and telecommunication equipments can affect the system, and cause malfunctions and breakdowns. The system can also affect medical equipment and telecommunication equipment, and obstruct its function or cause jamming.
Do not place any variables which will be damaged by getting wet under the indoor unit.
When the relative humidity is higher than 80% or drainage pipe is clogged, condensation or drainage water can drop and it can cause the damage of valuables.
Do not install the remote control at the direct sunlight.
It can cause malfunction or deformation of the remote control.
Do not use the unit for special purposes such as storing foods, cooling precision instruments and preservation of animals, plants or art.
It can cause the damage of the items.
Do not install the outdoor unit in a location where insects and small animals can inhabit.
Insects and small animals can enter the electric parts and cause damage or fi re. Instruct the user to keep the surroundings clean.
Do not use the base fl ame for outdoor unit which is corroded or damaged due to long periods of operation.
Using an old and damage base fl ame can cause the unit falling down and cause personal injury.
Do not use any materials other than a fuse with the correct rating in the location where fuses are to be used.
Connecting the circuit with copper wire or other metal thread can cause unit failure and fi re.
Do not touch any buttons with wet hands.
It can cause electric shocks.
Do not touch any refrigerant pipes with your hands when the system is in operation.
During operation the refrigerant pipes become extremely hot or extremely cold depending the operating condition, and it can cause burn injury or frost injury.
Do not touch the suction or aluminum fi n on the outdoor unit.
This may cause injury.
Do not put anything on the outdoor unit and operating unit.
This may cause damage the objects or injury due to falling to the object.
Do not use the unit for special purposes such as storing foods, cooling precision instruments and preservation of animals, plants or art.
Do not clean up the unit with water.
Page 21
-
19
-
'14•SRK-T-164
A place where good air circulation can be obtained and where rain,
snow or sunshine will not directly strike the unit.
A place where discharged hot air or unit’s operating sound will not be
a nuisance to the neighborhood.
A place where servicing space can be secured.A place where vibration will not be enlarged.
*Avoid installing in the following places.
sA place near the bedroom and the like, so that the operation noise
will cause no trouble.
s
A place where there is possibility of flammable gas leakage.
sA place exposed to strong wind. sIn a salt-laden atmosphere or a place where the generation of oil
mist, vapor or fume is expected.
Blowing out port and suction port on the back side of the unit can be
installed at a distance of 10cm from walls.
In case the barrier is 1.2m or above in height, or is overhead, the sufficient space between the unit and wall shall be secured.
When the unit is installed, the space of the following dimension and
above shall be secured.
OUTDOOR UNIT
Note (1) If the wall is higher than 1.2 m or a ceiling
is present, distances larger than indicated in the above table must be provided.
Selection of installation location
Where there is no obstructions to the air flow and where the cooled
air can be evenly distributed.
A solid place where the unit or the wall will not vibrate.A place where there will be enough space for servicing. (Where
space mentioned right can be secured)
Where wiring and the piping work will be easy to conduct.The place where receiving part is not exposed to the direct rays of
the sun or the strong rays of the street lighting.
A place where it can be easily drained.
A place separated at least 1m away from the television or the radio. (To prevent interfence to images and sounds.)
A place that home appliance and household goods, etc. aren’t below
unit.
INDOOR UNIT
10 cm
5 cm
10 cm
Left side
60 cm MIN
Air intake
10 cm MIN
10 cm MIN
Air outlet
Air intake
No obstacles (Service space for electrical parts)
Right side
)(
Standard accessories
(Installation kit)
Accessories for indoor unit
Q'ty
Installation board (Attached to the rear of the indoor unit)
1
Wireless remote control 1
Remote control holder
Tapping screws (for installation board 4dia. by 25mm)
5 (21)
10 (26)
Wood screw (for remote control switch holder 3.5dia. by 16mm)
2
Baterry [R03 (AAA, Micro) 1.5V] 2
Air-cleaning fi 2sretl
Filter holders (Attached to the front panel of the indoor unit)
2
Option parts Q'ty
Sealing plate 1
Sleeve 1
Inclination plate 1
Putty 1
Drain hose (extention hose) 1
Piping cover (for insulation of connection piping)
1
Necessary tools for the installation work
1 Plus headed driver (Phillips screwdriver)
2 Knife
3 Saw
4 Tape measure
5 Hammer
6 Spanner wrench
7 Torque wrench
(
14.0 ~ 82.0N · m (1.4 ~ 8.2kgf · m)
)
8 Hole core drill (65mm in diameter)
9 Wrench key (Hexagon) [4m/m]
10 Vacuum pump
11
Vacuum pump adapter (Anti-reverse flow type)
(
Designed specifically
for R410A
)
12 Gauge manifold
(
Designed specifically
for R410A
)
13 Change hose
(
Designed specifically
for R410A
)
14 Flaring tool set
(
Designed specifically
for R410A
)
15 Gas leak detector
(
Designed specifically
for R410A
)
16
Gauge for projection adjustment (Used when flare is made by using conventional flare tool)
17 Pipe bender
1
Page 22
-
20
-
'14•SRK-T-164
Installation of indoor unit
Installation of installation board
s Adjustment of the installation board in the horizontal direction
is to be conducted with four screws in a temporary tightened state.
s Adjust so that board will be level by turning the board with the
standard hole as the center.
Standard hole
Mating mark for level surface
450
610
Look for the inside wall structures (Intersediate support or pillar and firaly install the unit after level surface has been checked.)
Drain hose 792 ( 16)
INSTALLATOIN SPACE (INDOOR UNIT) (FRONT VIEW)
Indoor unit
Installation board
Space
for service
Space
for service
Piping for Gas 633.5
Piping for Liquid
703.5
Piping hole ( 65)
Piping hole ( 65)
Space for service
For bolt anchor and nut anchor
Space
for service
100
Limitations for one way piping length and vertical height difference
Total one way piping length ( )
Max. 25 m
Vertical height difference (h)
Max. 15 m
Total one way piping length ( )
Max. 25 m
Vertical height difference (h)
Max. 15 m
h
21 Series
21 Series
26 Series
26 Series
Look for the inside wall structures (Intersediats support or pillar and finally install the unit after level surface has been checked.)
450
Level position (2 locations)
Mating mark for level surface
Fixing on concrete wall
Nut (M6)
Mounting board
Mounting board
Max.10
Bolt (M6 12)
Standard hole
Nothing is connected to this hole on the back of indoor unit.
Adjustment of the installation plate in the horizontal direction is to be conducted with four screws in a temporary tightened state.
Adjust so the plate will be level by turning the board with the standard hole as the center.
INSTALLATION SPACE (INDOOR UNIT) (FRONT VIEW)
Space for service
Piping for Gas
Piping for Liquid
Piping hole ( 65)Piping hole ( 65)
Piping for Liquid : 6.35 Piping for Gas :
12.7
50
120
220
35
58
54
35
7.7
48
5.6
295.7
650 450
220
120
Space for service
100 Space for service
15 Space for service
Indoor unit
Installation board
49
48
222.5
100
491.1
559.1
Drain hose (
16)
520.8
Use of nut anchor Use of bolt anchor
Page 23
-
21
-
'14•SRK-T-164
Drilling of holes and fixture sleeve (Option parts)
(Inserting sleeve)
Note (1) Drill a hole with incline of 5 degree from
indoor side to outdoor side.
Indoor side Outdoor side
Cut off the sleeve col lar in case of dr aw in g pi pi ng out to rear.
Cut off the sleeve collar that c an b e seen from beneath the unit.
Wall thic kness
+ 1.5 cm
Indoor side Outdoor side
Turn t o tighten
Paste
View of sleeve when installed
In cl ined flange
Seal ing plate
Sleeve
Indoor side Outdoor side
(*Sleeve + *Inclined + *Sealin g plate)
Drill a hole with 65 whole core drill Adjusting sleeve length
Install the sleeve
Preparation of indoor unit
Mounting of connecting wires
Open the air inlet panel.Remove the lid.Remove the wiring clamp.Connect the connecting wire securely to the terminal block.
Use cable for interconnection wiring to avoid loosening of the wires. CENELEC code for cables Required field cables.
H05RNR4G1.5 (Example) or 245IEC57
H Harmonized cable type
05 300/500 volts
R Natural-and/or synth. rubber wire insulation N Polychloroprene rubber conductors insulation R Standed core
4or5 Number of conductors
G One conductor of the cables is the earth conductor (yellow/green)
1.5 Section of copper wire (mm
2
)
Connect the connection wire securely to the terminal block. If the wire is not affixed completely, contact will be poor, and it is danger-
ous as the terminal block may heat up and catch fire.
Take care not to confuse the terminal numbers for indoor and outdoor connections.
Earth lead wire shall be longer than the other lead wires for the electrical safety in case of the slipping out of the cord from the anchor-
age.
The earth line of power cord must be properly earthed.
Affix the connection wire using the wiring clamp.
Fix the connecting wire by wiring clamp.Attach the lid.Close the air inlet panel.
Page 24
-
22
-
'14•SRK-T-164
Left Side Piping Right Side Piping
Pipe
Drain hose
Shaping the pipe Taping of the exterior
Hold the bottom of the pipe and change its direction before stretching it and shaping it.
Tape only the portion that runs through the wall. Always tape the crossover wires with the pipe.
Cautions when piping from the left and the rear center of the unit
[ TopView ]
Right rear piping
Left rear piping
Left side piping
Right side piping
Left downward
Right
Rear
Downward
Left rear
Left
Piping is possible in the rear, left, left rear, left downwar d, right or downward direction.
Terminal block
1 3
2 N
Lid
Wiring Clam
p
21 Series 26 Series
Service panel
Terminal block
Clamp
The screw of the service panel is tightened securely.
Page 25
-
23
-
'14•SRK-T-164
1. Remove the drain hose. 2. Remove the drain cap. 3. Insert the drain cap. 4. Connect the drain hose.
Remove the screw and
drain hose, making it rotate.
Remove it with hand
or pliers.
Insert the drain cap which was removed at procedure “2” securely using a hexagonal wrench etc.
Note: Be careful that If it is not Inserted
securely, water leakage may occur.
Insert the drain hose securely,
making rotate. And install the screw.
Note: Be careful that If it is
not Inserted securely, wate r leakage may occur.
[Drain hose changing procedures]
Do not place t he power s upply cords above t he gutter,
because the air conditioner is structured in a way where condensation on the back side is collected in to the drain pan before drainage.
Do not make traps in the drain hose line.
Wall
Gutter
Pipes storage area
Declining slope
Inverted slipe
Trap
Installing steps
1.Hook the upper part of the indoor unit to the installation board.
2.The unit can be installed simply by gently push­ing in the lower part.
5 Securing the indoor unit to the installation board
Wall
Indoor unit base latch
Installation board
Latch (2 locations)
Installation board
Indoor unit
How to remove the indoor unit from the installation board
1 Push up at the marked portion of the indoor unit base
lower latch, and slightly pull it toward you.
(both right and left hand sides)
(The indoor unit base lower latch can be removed from
the installation board)
2
Push up the indoor unit upward. So the indoor unit will be removed from the installation board.
The marked portion of the Indoor unit bese lower latch
Page 26
-
24
-
'14•SRK-T-164
Removal and installation of the front panel
Open/close and detachment/attachment of air inlet panel
Removing
Remove the air inlet panel.
Remove the screw(A) 2pcs/screw(B) 3pcs fixing to
the front panel.
Remove the 3 latches in the upper section of the front
panel and then remove the front panel from the unit.
Installing
Remove the air filter.
Cover the unit with the front panel.
Tighten the screw(A) 2pcs/screw(B) 3pcs to fix the
front panel.
Install the air filter.
Install the air inlet panel.
Removing
Remove the air inlet panel.
Remove the 5 set screws.
Remove the 4 latches in the upper section.
Move the lower part of the panel forward and puch
upwards to remove.
Installing
Remove the air filter.
Cove the unit with the front panel.
Install the 4 latches in the upper section.
Tighten the 5 set screws.
Install the air filter.
Install the air inlet panel.
To open, pull the panel at both ends of lower part and release
latches, then pull up the panel until you feel resistance. (The air inlet panel stops at approx. 60˚ open position.)
To close, hold the panel at both ends of lower part to lower
downward and push it slightly until the latch works, then push the center portion slightly.
To remove, pull up the panel to the position shown in right il-
lustration and pull it toward you.
To install, insert the air inlet panel arm into the slot on the front
panel from the position shown in right illustration, hold the panel at both ends of lower part, lower it downward slowly, then push it slightly until the latch works and further push the center portion slightly.
Air inlet panel
Air filter
Screw (B) Screw (B) Screw (B)
Screw (A)
Screw (A)
Front panel
Latch
Approx. 80
To remove / To install
21 Series
26 Series
Set screws
latch
Page 27
-
25
-
'14•SRK-T-164
Installation of outdoor unit
Make sure that the unit is stable in installation. Fix the unit to stable base.When installing the unit at a higher place or where it could be toppled by strong winds, secure the unit firmly with foundation
bolts, wire, etc.
Perfrom wiring, making wire terminal numbers conform to terminal numbers of indoor unit terminal block.Earth lead wire shall be longer than the other lead wires for the electrical safety in case of the slipping out of the cord from the
anchorage. Connect using ground screw located near
mark.
Connection of refrigerant pipings
2/N
3
2/N
1/L
1/L
Outdoor unit
breaker
Safety
Earth
leakage
20A
circuit breaker
Earth
Power supply
When wire length exceeds 30m, use 2.0-mm wires.
1
2/N
3
Indoor unit
Outdoor unit
breaker
Safety
Earth
leakage
20A
circuit breaker
Earth
Power supply
When wire length exceeds
SRC21CNS-S SRC26CNS-S
30m, use 2.0-mm wires.
1
2/N
L
N
3
123
Indoor unit
(POWER SUPPLY CODE)
CENELEC code for cables requiring fields cables.
H05RNR3G2.5
A
90± 0.5°
Preparation
Connection of refrigerant piping
Keep the openings of the pipes covered with tapes etc. to prevent dust, sand, etc. from entering them.
Connect the pipes on both liquid and gas sides. Tighten the nuts to the following torque.
N·m (kgf·m)
Liquid side
(F 6.35)
14.0 ~ 18.0 (1.4~1.8)
Gas side
(F 9.52)
34.0 ~ 42.0 (3.4~4.2)
(F 12.7)
49.0 ~ 61.0 (4.9~6.1)
(F 15.88)
68.0 ~ 82.0 (6.8~8.2)
Flaring workv
CAUTION
Do not apply excess torque to the v flared nuts.
Otherwise, the flared nuts may crack depending on the conditions and refrigerant leak may occur.
Measurement B
Copper pipe
Flaring block
Copper pipe diameter
Measurement B (mm)
Use a flare tool designed for R410A or a conventional flare tool. Please note that measurement B (protrusion from the flaring block) will vary depending on the type of a flare tool in use. If a conventional flare tool is used, please use a copper pipe gauge or a similar instrument to check protrusion so that you can keep measurement B to a correct value.
Clutch type flare
tool for R410A
Conventional (R22) flare tool
Clutch type Wing nut type
F 6.35
0.0~0.5 1.0~1.5 1.5~2.0
F 9.52
0.0~0.5 1.0~1.5 1.5~2.0
F 12.7
0.0~0.5 1.0~1.5 2.0~2.5
F 15.88
0.0~0.5 1.0~1.5 2.0~2.5
Indoor Outdoor
Liquid side Gas side
(Do not turn)
Liquid side Gas side
Remove the flared nuts. (on both liquid and gas sides)
Remove the flared nuts. (on both liquid and gas sides)
Install the removed flared nuts to the pipes to be connected, then flare the pipes.
CAUTION
Do not apply v
refrigerating machine oil to the flared surface.
roodtuOroodnI
(Do not turn)
evomeRevomeR
sserPsserP
Dimension A Liquid side : ø6.35: 9.1 Gas side ø9.52: 13.2
ø12.7: 16.6 ø15.88: 19.7
(Unit : mm)
Page 28
-
26
-
'14•SRK-T-164
Insulation of connecting portion
Cover the connection portion of the refrigerant piping with the
pipe cover and seal them.
If neglecting to do so, moisture occurs onthe piping and water will drip out.
Finishing and fixing
ⓐ Tie up the piping with wrapping tape, and shape it so that it conforms
to which the pipe is attached.
ⓑ Fix them with clamps as right figure.
Vinyl tape
To cover the connecting portion with insulation materials, cut u pper porti on and then sea l it with insulation materials.
Cover the exterior portion with cov­ering tape and shape the piping so it will match the contours of the route that the piping to take. Also fix the wiring and pipings to the wall with clamps.
Insulation Refrigerant piping Electrical wiring Covering tape
Drain hose
Tapping screw
Additional refrigerant charge
Air purge
Additional refrigerant
Less than 15m : Not required More than 15m : 20g/m
How to relocate or dispose of the unit
In order to protect the environment,be sureto pumpdown (recovery of refrigerant).
Pump down is the method of recovering refrigerant from the indoor unit to the outdoor unit when the pipes are removed from the unit.
<How to pump down>
Connect charge hose to check joint.Liquid side : Close the liquid valve with hexagon wrench key.
Gas side : Fully open the gas valve. Carry out cooling operation. (If indoor temperature is low, operate
forced cooling operation.)
After low pressuregauge become 0.01MPa, close thegas valve then
stop cooling operation.
Forced cooling operation
Turn on a power supply again after a while after turn off a power supply. Then press continually the ON/OFF button 5 seconds or more.
21 Series
26 Series
Unit ON/OFF button
Unit ON/OFF button
Securely tighten the operation valve cap and the check joint blind nut after adjustment.
Operation valve size
(mm)
Operation valve cap
tightening torque (N·m)
Check joint blind nut
tightening torque (N·m)
φ
6.35 (1/4") 20 ~ 30
10 ~ 12
φ
9.52 (3/8")
φ
12.7 (1/2") 25 ~ 35
φ
15.88 (5/8") 30 ~ 40
Compound pressure gauge
Operation valve cap
Operation valve (three-way valve)
Operation valve cap
-0.1MPa
(-76cmHg)
Handle Lo
Pressure gauge
Handle Hi Charge hose (Designed specifically for R410A)
Vacuum pump adapter
(Anti-reverse flow type)
(Designed specifically for R410A)
Vacuum pump
Charge hose (Designed specifically for R410A)
Check joint
Operation valve (two-way valve)
Gauge manifold
(Designed specifically for
R410A)
Tighten all flare nuts in the pipings both indoor and outside wall so as not to cause leak. Connect operation valve, charge hose, manifold valve and vacuum pump as is illustrated right. Open manifold valve handle Lo to its full width, and perform vacuum or evacuation. Continue the vacuum or evacuation operation for 15 minutes or more and check to see that the vacuum gauge reads -0.1MPa. After completing vacuum operation, close the Lo handle and stop operation of the vacuum pump. After completing vacuum operation, fully open operation valve (Both gas and liquid sides) with hexagon headed wrench. Check for possible leakage of gas in the connection parts of both indoor and outdoor.
Since the system uses check joints differing in diameter from those found on the conventional models, a charge hose (for R22) presently in use is not applicable. Please use one designed specifically for R410A. Please use an anti-reverse flow type vacuum pump adapter so as to prevent vacuum pump oil from running back into the system. Oil running back into an air-conditioning system may cause the refrigerant cycle to break down.
Page 29
-
27
-
'14•SRK-T-164
Installation of remote control switch
Mounting method of battery
Earthing work
+
+
-
-
Uncover the remote control switch, and mount the batter­ies [R03(AAA, Micro)×2 pieces] in the body regularly.
(Fit the poles with the indication marks, , & . without
fail)
Earth work shall be carried out without fail in order to prevent electric shock and noise generation.
The connection of the earth cable to the following substances causes dangerous failures, therefore it shall never be done.
City water pipe, Town gas pipe, TV antenna, lightning conductor, telephone line, etc.
Trial run and operation
1 Conduct trial run after confi rming that there is no gas leaks. 2 When conducting trial run set the remote control thermostat to continuous operation position. However when the power source is
cut off or when the unit’s operation switch is turned off or was turned to fan operation position, the unit will not go into operation in order to protect the compressor.
3 Explain to the customer on the correct usage of the air-conditioner in simple layman’s terms. 4 Make sure that drain fl ows properly.
Battery
Cover
Fixing to pillar or wall
Conventionally, operate the wireless remote control by
holding in your hand.
Avoid installing it on a clay wall etc.
Screws
CAUTION
Do not use new and old batteries together.
Installations test check points
Check the following points again after completion of the installation, and before turning on the power. Conduct a test run again and ensure that the unit operates properly.
At the same time, explain to the customer how to use the unit and how to take care of the unit following the instruction manual.
After installation
The power supply voltage is correct as the rating.
No gas leaks from the joints of the operation valve.
Operation valve is fully open.
The pipe joints for indoor and outdoor pipes have been insulated.
Test run
Air conditioning operation is normal.
No abnormal noise.
Water drains smoothly.
Protective functions are not working.
The remote control is normal.
Operation of the unit has been explained to the customer.
(Three-minute restart preventive timer) When the air conditioner is restarted or when changing the operation, the unit will not start operating for approximately 3 minutes.
This is to protect the unit and it is not a malfunction.
Page 30
-
28
-
'14•SRK-T-164
Remote control
7.
OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
(1) Operation control function by remote control
Operation section
Unit display section
Unit indication section
21 Series
3D AUTO light (green)
Illuminates during 3D AUTO operation.
HI POWER light (green)
Illuminates during HIGH POWER operation.
TIMER light (yellow)
Illuminates during TIMER operation.
In emergencies, this button can be used for turning on/off the unit
when remote control is not available.
Remote control signal receiver
Unit ON/OFF button
RUN light (green)
Illuminates during operation.
Blinks at the ‘CLEAN operation’.
ON
OFF
1 sec.
CLEAN operation
3 sec.
Page 31
-
29
-
'14•SRK-T-164
Unit indication section
3D AUTO light (green)
Illuminate s during 3D AUTO opera tion.
HI POWER light (green)
Unit ON/OFF button
Remote control signal receiver
Illuminate s during HI GH POWER op eration.
TIMER light (yellow)
Illuminate s during TI MER operati on.
1 sec.
RUN TIME R H I PO W ER 3D AUTO
ON/ OFF
In emergen cies, this button can be used fo r turning on /off the un it when rem ote control is not available.
RUN light (green)
Illuminates dur ing operati on.
Blinks a t the ‘CLEA N operation ’.
3 sec.
OFF
ON
CLEAN oper ation
21 Series
26 Series
3D AUTO light (green)
Illuminates during 3D AUTO operation.
HI POWER light (green)
Illuminates during HIGH POWER operation.
TIMER light (yellow)
Illuminates during TIMER operation.
In emergencies, this button can be used for turning on/off the unit
when remote control is not available.
Remote control signal receiver
Unit ON/OFF button
RUN light (green)
Illuminates during operation.
Blinks at the ‘CLEAN operation’.
ON
OFF
1 sec.
CLEAN operation
3 sec.
(2)  Unit ON/OFF button
(a) Operation
(b) Details of operation
Function
operation mode
Room temperature
setting
Fan speed
Flap/Louver
Timer Switch
COOL
About 24
DRY
Unit ON/OF F button
Unit ON/OF F button
21 Series 26 Series
Page 32
-
30
-
'14•SRK-T-164
Auto restart function
(a)
(b)
(i)
(ii)
(J170)
(4)  Custom cord switching procedure
(a) Modifying the indoor printed circuit board
(b) Modifying the wireless remote control
(i)
(ii)
(J171)
Jumper wire (J170)
Jumper wire (J171)
Cut
(3)
Page 33
-
31
-
'14•SRK-T-164
(5) Flap and louver control
(a) Flap
(b) Louver
(c) Swing
(i)
(ii)
(d) Memory flap (Flap or Louver stopped)
(e) When not operating
COOL , DRY, FAN
Remote control display
Approx. 5°(10°)
Approx.30°
(Swing)
(Flap stopped)
Approx.45° Approx.60°
Angle of Flap from Horizontal
Center installation
Remote control display
Right end installation
Left end installation
Angle of Louver
Left
Note (1) Values in ( ) are for the 26 Series.
Approx.45°
Left Approx
.
45°
Left Approx
.
20°
Left Approx
.
30°
Center
Left Approx.20°
Right Approx.20°
Center
Right Approx.45°
Right Approx
.
20°
Left Approx.20°
Center
Right Approx.20° Right Approx.30° Right Approx.45°
(Louver stopped)
(Swing) (Spot) (Wide)
In COOL, DRY, FAN operation
Approx.
10°
Approx. 60°
Approx. 15°(20°)
Page 34
-
32
-
'14•SRK-T-164
(6)  3D auto operation
(a)
(i)
(ii)
(b)
Cooling
Air flow selection
Operation mode
AUTO HI MED LO
Indoor temp. – Setting temp. >5°C
Indoor temp. – Setting temp. 5°C
HIGH POWER AUTO
HI MED LO
< =
Flap Louver
Cooling
Up/down Swing
Wide (Fixed)
Flap Louver
Cooling
Left/right Swing
Horizontal blowing (Fixed)
Flap Louver
Cooling
Up/down Swing
Center (Fixed)
Wide (Fixed)
Flap Louver
Cooling
Horizontal blowing (Fixed)
Operation mode
Indoor temp. – Setting temp. 2°C
Cooling
Air flow direction contorol
2°C <
Indoor
temp.
Setting temp. 5°C
Indoor temp. – Setting temp. > 5°C
The control in 4) continues. Control returns to the control in 2). Control returns to the control in 1).
< =
< =
Wide (Fixed)
Flap Louver
Horizontal blowing (Fixed)
1)
2)
3)
4)
5)
3
4
Page 35
-
33
-
'14•SRK-T-164
(i) , (iv)
(ii)
(iii)
(b) Sleep timer operation
(7) Timer operation
(a) Comfortable timer setting (ON timer)
(c) OFF timer operation
(8) Installation location setting
(a) Setting
(i)
If the air conditioning unit is running, press the ON/OFF button to stop.
(ii) Press the AIR FLOW (UP/DOWN) button and the
AIR FLOW (LEFT/RIGHT) button together for 5 seconds
or more.
(iii) Setting the air-conditioning installation location.
(iv) Press the ON/OFF button.
Airf low range Airflow rangeAirf low range
(Left End Installation) (Center Installation) (Right End Installation)
(Center Installation) (Right End Installation) (Left End Installation)
Page 36
-
34
-
'14•SRK-T-164
(b)
The unit checks the temperature every 30 minutes after the start of operation and, if the result of check is not same as
the previous operation mode, changes the operation mode.
(c)
When the unit is started again within one hour after the stop of automatic operation or when the automatic operation is
selected during cooling or dehumidifying operation, the unit is operated in the previous operation mode.
(d)
Setting temperature can be adjusted within the following range. There is the relationship as shown below between the
signals of the wireless remote control and the setting temperature.
Signals of wireless remote control (Display)
–6 –5 –4 –3 –2 –1
±
0 +1 +2 +3 +4 +5 +6
Setting
Cooling
18 19 20 21 22 23 24 25 26 27 28 29 30
temperature
Dehumidifying
18 19 20 21 22 23 24 25 26 27 28 29 30
(9) Outline of cooling operation
(a) Operation of major functional components in Cooling mode
(b) Fan speed switching
ON OFF OFF
ON
OFF
(few minutes ON)
OFF
(few minutes ON)
ON ON ON
Thermostat ON Thermostat OFF Failure
Cooling
Compressor
Indoor fan motor
Outdoor fan motor
Auto fan control
Speed 8
Speed 6
Speed 4
Model
Fan speed
All models
Auto
MED
HI
LO
(10) Outline of automatic operation
(a) Determination of operation mode
The unit checks the indoor air temperature and the outdoor air temperature, determines the operation mode, and then
begins in the automatic operation.
27.5
25.5
19.5
18
30
Dehumidifying
Cooling
Indoor air temperature (˚C)
Outdoor air temperature (˚C)
Room temperature
25.5
25.5
℃≦
Room temperature
Operation mode Dehumidifying Cooling
21 Series
26 Series
Page 37
-
35
-
'14•SRK-T-164
(11) Protective control function
(a) Frost prevention for indoor heat exchanger (During cooling or dehumidifying)
(i) Operating conditions
1) Indoor heat exchanger temperature (Th2) is lower than 2.5ºC.
2) 3 minutes elapsed after the start of operation.
(ii) Detail of frost prevention operation
Compressor OFF
Indoor fan Protects the fan tap just before frost prevention control.
Outdoor fan Depending on the stop mode
(iii) Reset condition: Indoor heat exchanger temperature (Th2) is higher than 15ºC.
(b) Dew condensation prevention control [Cooling (including auto), cooling oriented dehumidifying operation]
(i) Operating condition: When the following conditions are met after 5 minutes or more of continuous
operation after operation starts.
s The humidity sensor value is 68% or higher
(ii) Operation contents
1) Command of the electronic expansion valve.
2) When such a command is continued for 30 minutes or more, air direction
controls will be as listed below:
Humidity (%)
63 68
Reset
Prevention control
(c) Indoor fan motor protection
When the airconditioner is operating and the indoor fan motor is turned ON, if the indoor fan motor has operated at 300
min
-1
(rpm) or under for more than 30 seconds, the unit enters first in the stop mode and then stops the entire system.
TIMER light illuminates simultaneously and the RUN light flashing 6-time at each 8-second.
(d) 3 minutes forced operation
When the compressor begins operating the thermal operation is not effective for 3 minutes, so operation continues as
is in the operation mode. (After 3 minutes has passed the thermal operation is effective.)
However, stopping the compressor via a stop signal or protection control has priority.
(e) Abnormality of outdoor unit
When an abnormal stop occurs 3-time with automatic recovery within 20 minutes after the outdoor unit’s power supply
was turned on.
(iii) Reset condition: When the following condition is satisfied.
s The humidity sensor value is less than 63%.
UP/ DOWN air flow
Flap swing Executes the command to the left.
Situations besides the ones described above Controls the level of the UP/DOWN flap.
LEFT/ RIGHT air flow
Louver swing Executes the command to the left.
Situations besides the ones described above
Controls the front of the LEFT/RIGHT louver .
Page 38
-
36
-
'14•SRK-T-164
(g) Serial signal transmission error protection
(i) Purpose: Prevents malfunction resulting from error on the indoor outdoor signals.
(ii) Detail of operation: If the compressor is operating and a serial signal cannot be received from the indoor control with
outdoor control having serial signals continuously for 1 minute and 55 seconds, the compressor is
stopped.
After the compressor has been stopped, it will be restarted after the compressor start delay if a serial
signal can be received again from the indoor control.
(RUN light: ON, TIMER light: 6-time flash)
(h) Sensor disconnection (room temperature, indoor heat exchanger, outdoor heat exchanger, outdoor tempera-
ture, discharge pipe)
(i) Room temperature sensor
If the temperature detected by the room temperature sensor is –45ºC or lower continuously for 15 seconds or longer while
operation is stopped, an error indication is displayed. (RUN light: 2-time flash, TIMER light: ON)
(ii) Indoor heat exchanger temperature sensor
If the temperature detected by the indoor heat exchanger temperature sensor is –28ºC or lower continuously for 15 seconds
or longer while operation is stopped, an error indication is displayed.
(RUN light : 1-time flash, TIMER light : ON)
(iii) Outdoor heat exchanger temperature sensor
–55ºC or lower is detected for 5 seconds continuously 3-time within 40 minutes after initial detection of this anomalous
temperature.
Or –55ºC or lower is detected for within 20 seconds after power ON.
(RUN light : keep flashing, TIMER light : 2-time flash)
(iv) Outdoor air temperature sensor
(v) Discharge pipe temperature sensor
–25ºC or lower is detected for 5 seconds continuously 3-time within 40 minutes after initial detection of this anomalous
temperature.
–55ºC or lower is detected for 5 seconds continuously 3-time within 40 minutes after initial detection of this anomalous
temperature.
Or –55ºC or lower is detected for within 20 seconds after power ON.(RUN light : keep flashing, TIME Rlight : 1- time
flash)
Or –25ºC or lower is detected for within 20 seconds after power ON.(RUN light : keep flashing, TIME Rlight : 4- time
flash)
(f) Compressor overheat protection
If the discharge pipe temperature (sensed by Th3) exceeds the set temperature value, the compressor stops. If the temperature is 95ºC
or lower after a 3-minute delay, it starts again, but if this function is reactivated again within 60 minutes, it results in an abnormal stop.
(RUN light : ON, TIMER light : 5-time flash)
Discharge pipe temperature (°C)
Operation possible
Abnormal stop
11021 type: 95 11526 type: 95
Page 39
-
37
-
'14•SRK-T-164
8. MAINTENANCE DATA
(1) Cautions
(a) If you are disassembling and checking an air conditioner, be sure to turn off the power before beginning. When work
-
ing on indoor units, let the unit sit for about 1 minute after turning off the power before you begin work. When work
-
ing on an outdoor unit, there may be an electrical charge applied to the main circuit (electrolytic condenser), so begin
work only after discharging this electrical charge (to DC 10 V or lower).
(b) When taking out printed circuit boards, be sure to do so without exerting force on the circuit boards or package
components.
(c) When disconnecting and connecting connectors, take hold of the connector housing and do not pull on the lead wires.
(2) Items to check before troubleshooting
(a) Have you thoroughly investigated the details of the trouble which the customer is complaining about?
(b) Is the air conditioner running? Is it displaying any self-diagnosis information?
(c) Is a power supply with the correct voltage connected?
(d) Are the control lines connecting the indoor and outdoor units wired correctly and connected securely?
(e) Is the outdoor unit’s service valve open?
(3) Troubleshooting procedure (If the air conditioner does not run at all)
If the air conditioner does not run at all, diagnose the trouble using the following troubleshooting procedure. If the air
conditioner is running but breaks down, proceed to troubleshooting step (4).
Important
When all the following conditions are met, we say that the air conditioner will not run at all.
(a)
The RUN light does not light up.
(b)
The aps do not open.
(c)
The indoor unit fan motors do not run.
(d)
The self-diagnosis display does not function.
YES
YES
YES
NO
NO
NO
NO
YES
Troubleshooting procedure (If the air conditioner does not run at all)
Is the cor rec t v olt age connected for the power supply?
With the power off, do
the aps open manually,
then close again when the power is turned on?
Is the r e a re c e pt i o n sound emitted from the unit when it is operated by the remote control?
Replace the indoor PCB and perform an operation check.
Make sure the correct volt­age is connected, then per­form an operation check.
Is the current fuse on the in­door unit PCB blown?
Proceed to the indoor PCB check.
Proceed to the wireless remote control troubleshooting proce­dure.
If the package components are not damaged, replace the fuse and perform an op­eration check again.
* If the voltage is correct, it will be
within the following voltage range.
AC 198 ~ 242 V
Page 40
-
38
-
'14•SRK-T-164
(4) Troubleshooting procedure (If the air conditioner runs)
NO
YES
39.
Page 41
-
39
-
'14•SRK-T-164
gs32+$"$
Indoor unit display panel
TIMER
6-time
flash
ON
ON
ON
RUN
light
Keeps
flashing
Keeps
flashing
Keeps
flashing
(5) Self-diagnosis table
When a heat exchanger sensor 1 wire disconnection is detected while operation is stopped. (If a temperature of –28ºC or lower is detected for 15 seconds, it is judged that the wire is disconnected.) (Not displayed during operation.)
When a room temperature sensor wire disconnection is detected while operation is stopped. (If a temperature of –45ºC or lower is detected for 15 seconds, it is judged that the wire is disconnected.) (Not displayed during operation.)
• Broken heat exchanger sensor
1 wire, poor connector connection
• Indoor PCB is faulty
• Broken room temperature
sensor wire, poor connector connection
• Indoor PCB is faulty
Heat exchanger sensor 1 error
Room temperature sensor error
When conditions for turning the indoor unit’s fan motor on exist during air conditioner operation, an indoor unit fan motor speed of 300min
-1
(rpm) or
• Defective fan motor, poor connector connection
Indoor fan motor error
–55ºC or lower is detected for 5 seconds continuously 3 times within 40 minutes after initial detection of this anomalous temperature. Or –55ºC or lower is detected for within 20 seconds after power ON. (The compressor is stopped.)
–55ºC or lower is detected for 5 seconds continuously 3 times within 40 minutes after initial detection of this anomalous temperature. Or –55ºC or lower is detected for within 20 seconds after power ON. (The compressor is stopped.)
• Broken heat exchanger sensor
wire, poor connector
connection
• Outdoor main PCB is faulty
Outdoor heat exchanger sensor error
–25ºC or lower is detected for 5 seconds continuously 3 times within 40 minutes after initial detection of this anomalous temperature.
(The compressor is stopped.)
• Broken discharge pipe sensor wire, poor connector connection
• Outdoor main PCB is faulty
Discharge pipe
sensor error
gency stop caused by trouble in the outdoor unit, When there is an emer
or the input current value is found to be lower than the set value.
(The air conditioner stops.)
• Broken compressor wire
• Compressor blockage
Trouble of outdoor unit
When the value of the discharge pipe sensor exceeds the set value.
(The air conditioner stops.)
• Gas shortage, defective discharge pipe sensor, service valve is closed
Over heat of
compressor
When there is no signal between the indoor PCB and outdoor PCB for
10 seconds or longer (when the power is turned on), or when there is no signal for 7 minute 35 seconds or longer (during operation)(the compressor is stopped).
• Defective power supply, Broken signal wire, defective indoor/outdoor sub PCB
Error of signal transmission
Description
of trouble
Cause Display (flashing) condition
• Broken outdoor air temp.
sensor wire, poor connector connection
• Outdoor main PCB is faulty
Outdoor air temperature sensor error
lower is measured for 30 seconds or longer. (The air conditioner stops.)
1-time
flash
2-time
flash
ON
ON
ON
5-time
flash
6-time
flash
light
2-time
flash
4-time
flash
2-time
flash
1-time
flash
Or –25ºC or lower is detected for within 20 seconds after power ON.
Page 42
-
40
-
'14•SRK-T-164
(6) Inspection procedures corresponding to detail of trouble
Sensor error
[Broken sensor wire, connector poor connection]
Is connector connection good?
YES
YES
NO
NO
Replace PCB.
Correct connection.
Replace sensor.
Is sensor resistance value good?
Indoor fan motor error
[Defective fan motor, connector poor connection, defective indoor PCB]
Is connector connection good?
YES
NO
NO
Is the output of the indoor unit PCB normal?
Power supply reset
NO
YES
YES
Correct connector connection
Is DC fan motor resistance value good?
Replace indoor PCB
Replace indoor fan motor
Notes (1) See page 44 for the DC fan motor and indoor PCB check
procedure.
(2) After making sure the DC fan motor and indoor PCB are
normal, connect the co nnectors and confirm that the fan motor is turning.
(If power is turned on while one or the other is broken down,
it could cause the other to break down also.)
* Disc onne ct the fan mo to r
connec tor, then investigate the DC fan motor and indoor PCB separately.
(Short circuit)
(Broken wire)
S ensor tempe r atur e char a cteri s tics
(Room temp., indoor heat exchanger temp., outdoor heat exchanger temp., outdoor air temp.)
Temperature (˚C)
Resistance (k
)
30
25
20
15
10
5
30
20
10
40 50 60
70
0
-
10
Discharge pipe sensor temperature characteristics
0
0 20 40 60 80 100 120 135
20
40
60
80
100
120
140
160
180
(Short circuit)
(Broken wire)
Temperature (˚C)
Resistance (k
)
Is normal state restored?
Malfunction by temporary noise
NO
Replace fan motor (If anomaly persiste after replacing fan motor, replace indoor PCB)
YES
Page 43
-
41
-
'14•SRK-T-164
'09•SRK-DB-087D
Over heat of compressor
Gas shortage, defective discharge pipe sensor
Error of signal transmission
Wiring error including power cable, defective indoor/ outdoor PCB
② ③
② ③
① ②
40)
main
indoor
indoor
outdoor sub
Page 44
-
42
-
'14•SRK-T-164
Trouble of outdoor unit
Insufficient refrigerant amount, Faulty power transistor, Broken compressor wire Service valve close, Defective EEV, Defective outdoor PCB
◆ (1)
(1)
main
AC
AC AC
Does 52X1 relay operate properly?
'09•SRK-SM-087D
(b) Outdoor unit
Compressor stop.
Sensor
Operation mode
Phenomenon
Shortcircuit Disconnected wire
Heat exchanger sensor
Cooling
Ourdoor air temperature sensor
Cooling
Discharge pipe sensor
All modes
Page 45
-
43
-
'14•SRK-T-164
'09•SRK-DB-087D
Outdoor fan motor error
Rotor lock
(7) Phenomenon observed after shortcircuit, wire breakage on sensor
(a) Indoor unit
Defective fan motor, connector poor connection, defective outdoor PCB
Defective compressor, defective outdoor PCB
Sensor
Operation mode
Phenomenon
Shortcircuit Disconnected wire
Room temperature sensor
Cooling
Heat exchanger sensor
Cooling
Humidity sensor
Cooling
Humidity sensor operation
Failure mode Control input circuit resding
Air conditioning system operation
① ② ①②
See pages 53.
main
'09•SRK-SM-087D
(b) Outdoor unit
Compressor stop.
Sensor
Operation mode
Phenomenon
Shortcircuit Disconnected wire
Heat exchanger sensor
Cooling
Ourdoor air temperature sensor
Cooling
Discharge pipe sensor
All modes
Page 46
-
44
-
'14•SRK-T-164
'09•SRK-SM-087D
(8) Checking the indoor electrical equipment
(a) Indoor PCB check procedure
(b) Outdoor unit
Is there voltage between terminal blocks ① and ② ? (AC 220V)
Indoor electrical components are normal.
Is the voltage between terminal blocks ② and ③ oscillating between DC 0 and 20V?
Inspect
If th e p ackag e com pon en ts are not damaged, replace the fuse and perform an operation check again.
Compressor stop.
power source
for outdoor unit.
Replace indoor PCB.
Is the fuse burnt out? (3.15 A)
NO
YES
YES
NO
YES
NO
(b) Indoor unit fan motor check procedure
(i) Indoor PCB output check
① ④
(ii) Fan motor resistance check
FM
I
DC15V
Indoor PCB
DC 308~336V
DC several V (4~6 V)
CNU
(–)
GND
Blue
Yellow
White
Black
Red
Sensor
Operation mode
Phenomenon
Shortcircuit Disconnected wire
Heat exchanger sensor
Cooling
Ourdoor air temperature sensor
Cooling
Discharge pipe sensor
All modes
Measuring point Resistance when normal
−
−
Measuring point
Resistance when normal
−
k
1)
2)
3)
several V (4~6V)
Page 47
-
45
-
'14•SRK-T-164
gs32+$"$
(9) How to make sure of wireless remote control
(C) Power transistor inspection procedure
[Use a tester with a needle indicator for the inspection. (Do not use a digital tester. Check in the AC 300 volt range.)] (1) If there is a self-diagnosis display, inspect the compressor system (burns, wiring mistakes, etc.) If no problems are found, check the
output of the power transistor.
(2) Output inspection procedure
Disconnect the terminals for the compresseor. If an output such as the one shown in the figure on the below can be measured, the power transistor and the circuit board for the outdoor unit are normal.
(Example) RUN light : ON TIMER light: 2 time flash
Measure in this sectionOperation SW ON
8~10 sec.
1 sec. 1 sec.
3 min. 3 min.
1 sec.
0
Output voltage
(ACV)
The figare below shows the SRK series.
of
indoor unit
Replace the display of indoor unit.
reset (ACL) button
Page 48
-
46
-
'14•SRK-T-164
Page 49
-
47
-
'14•SRK-T-164
PARTS LIST
INDOOR UNI
T
SRK21CNS-S6 SRK26CNS-S6
OUTDOOR UNIT
SRC21CNS-S6 SRC26CNS-S6
Page 50
-
48
-
'14•SRK-T-164
CRAE0288
44
5
5
44
42
6
32
36
33
43
31
7
34
2
2
39
39
40
41
37
38
40
30
35
8
29
28
20
19
22
9
15
15
10
27
18
24
26
25
23
14
12
17
16
22
21
11
13
13
11
15
15
4
3
1
PANEL & FAN ASSY
Page 51
-
49
-
'14•SRK-T-164
SRK21CNS-S6
END ITEM NO. : RMA002F062AH
10 30 50 100 500 1000
17 RMA 102A 101C PANEL ASSY,FRONT 1 1 1 1 2
1 RKY 122A 002B PANEL ASSY,FRONT 1 1 1 1 2
2 RKY 435A 003 GRILLE,AIR IN(TOP) 2 1 1 2 3
3 RMA 435A 010D PANEL ASSY,AIR IN 1 1 1 2 3
4 RKY 437A 001 FILTER,AIR 2 2 2 4 8 W348.5×H339(t2)
5 RKY 129A 012 CAP 2 1 1 1 2
6 RKY 133A 008C PLATE ASSY,ORNAMENT 1 1 1 1 2
7 RMA 011G 007 LABEL WIRING 1
829 RMA 435A 009C GRILLE ASSY,AIR OUT 1 1 1 2 3
8 RKY 435A 002 GRILLE,AIR OUT 1 1 1 2 3
9 RMA 436A 001 FLAP ASSY(U) 1 1 1 2 2 UPPER
10 RMA 436A 003 FLAP ASSY(L) 1 1 1 2 2 LOWER
1112 RKY 436A 009 LOUVER ASSY 1 1 1 2 2
11 RKY 436A 011 LOUVER 6 1 1 2 2
12 RKY 129A 011 PLATE,CONNECTING 1 1 1 1 2
1314 RKY 436A 009A LOUVER ASSY 1 1 1 2 2
13 RKY 436A 011 LOUVER 6 1 1 2 2
14 RKY 129A 011 PLATE,CONNECTING 1 1 1 1 2
15 RKW 935C 200 COLLAR 4
1622 RKY 144A 010 LINK ASSY(R) 1 1 1 1 2
16 RKY 129A 009 JOINT(R) 1 1 1 1 2
17 RKY 129A 005 BRACKET,MOTOR(R) 1 1 1 1 2
18 RKY 144A 001 LINK 1 1 1 1 2
19 RKY 144A 002 CRANK(A) 1 1 1 1 2
20 RKY 144A 003 CRANK(B) 1 1 1 1 2
21 RKY 144A 004 CRANK(C) 1 1 1 1 2
22 SSA 512T 096 MOTOR,STEPPING 2 1 1 1 2
FOR LOUVER(RIGHT),FLAP
2326 RKY 144A 011A LINK ASSY(L) 1 1 1 1 2
23 RKY 129A 010 JOINT(L) 1 1 1 1 2
24 RKY 129A 006 BRACKET,MOTOR(L) 1 1 1 1 2
25 RKY 144A 004 CRANK(C) 1 1 1 1 2
26 SSA 512T 096 MOTOR,STEPPING 1 1 1 1 2 FOR LOUVER(LEFT)
27 RMA 504A 013 HARNESS ASSY 1 1 1 1 2
28 SSA 423A 102 HOSE,DRAIN 1
29 SSA 326A 047 PLUG 1
30 RKY 111A 001A BASE ASSY 1 1 1 1 2
31 RKY 129A 002A PLATE,BASE 1 1 1 1 2
32 RKY 129A 037 BRACKET ASSY(U) 1 1 1 1 2
33 RKY 129A 038 BRACKET ASSY(L) 1 1 1 1 2
34 SSA 923C 114 BEARING,PLANE 1 1 1 1 2
35 SSA 431G 050A IMPELLER 1 1 1 2 4
36 SSA 512T 127A MOTOR,DC 1 1 1 1 2 FOR IMPELLER
37 RKY 032A 001 PLATE,INSTALLATION 1 1 1 1 2
No. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Note
Page 52
-
50
-
'14•SRK-T-164
SRK21CNS-S6
END ITEM NO. : RMA002F062AH
10 30 50 100 500 1000
No. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Note
3840 RKY 129A 023B FILTER UNIT ASSY 1 1 1 1 2
38 RKY 129A 036 HOLDER ASSY(B) 1 1 1 1 2
39 RKY 129A 025 HOLDER,FILTER(R) 2 1 1 1 2
40 RKY 129A 028 HOLDER,FILTER 2 1 1 1 2
41 RKY 129A 034A COVER ASSY(PIPE) 1 1 1 1 2
42
RKY 132A 001C LID(R)
1
1 1 1 2
43
RKY 132A 002A LID(L)
1
1 1 1 2
44
SSA 913A 007 SCREW,TAP
2 4×12
Page 53
-
51
-
'14•SRK-T-164
MEMO
Page 54
-
52
-
'14•SRK-T-164
CRAE0289
3
1
2
7
5
4
6
8
9
10
12
13
11
25
17
23
16
28 31
22
21
30
20
18
15
14
19
24
32
34
33
26
27
29
36
35
HEAT EXCH. & CONTROL
Page 55
-
53
-
'14•SRK-T-164
SRK21CNS-S6
END ITEM NO. : RMA002F062AH
10 30 50 100 500 1000
110 RMA 301A 012 HEAT EXCH ASSY(AIR) 1 1 1 1 2
2 RMA 315D 008 HEADER ASSY 1
3 RKY 129A 035 BRACKET ASSY(L) 1 1 1 1 2
410 RKY 315A 002 DISTRIBUTOR ASSY 1
1113 RMA 321A 138 PIPE ASSY 1
12 SSA 323F 012F UNION,SOLDER 1 FOR GAS
13 SSA 323F 088A UNION(SLD) 1 FOR LIQ.
14 RKY 142A 001 BOX,CONTROL(R) 1
15 RKY 142A 002 BOX,CONTROL(L) 1
16 RKY 132A 003 LID,CONTROL 1
17 RKY 129A 015 HOLDER,SENSOR 1
18 RKY 129A 014 COVER,BEND 1
19 RKY 132A 004 COVER,CONTROL(R) 1
20 RKY 132A 005 COVER,CONTROL(L) 1
21 SSA 551A 223A SENSOR ASSY 1 1 1 2 4
INCL.SENSOR (ROOM TEMP.& HEAT EXCH.)
22 SSA 551B 017A SENSOR(HUMIDITY) 1 1 1 2 4
23 RMA 504A 012 HARNESS ASSY 1
24 SSA 561B 702B BLOCK,TERMINAL 1 1 1 2 2 T1
2527
RKY 505A 001JK
PWB ASSY 1 2 2 4 8
26
SSA 555B 058AD
VARISTOR 1 1 1 1 2 Z
27 SSA 564A 132 FUSE(CURRENT) 1 1 1 1 2 F 3.15A
28
RKY 503A 001D
DISPLAY ASSY 1 1 1 2 4
29
RKY 505A 003D
PWB ASSY 1 2 2 4 8
30 RKJ 941F 001A SPRING,LEAF 1
31
RMA 008A 012D
PARTS,STANDARD 1
32 RMA 012A 078 MANUAL,INSTRUCTION 1
33 RKT 437A 011B FILTER,CLEAN 1
34 RKT 437A 005C FILTER,LIGHT CLEAN 1
35 RKX 502A 001 CONTROL ASSY,REMOTE 1 2 3 5 10
36
RKN 032A 002C
HOLDER(REMO-CON) 1 1 1 1 2
(37)
RMA 011F 016BA
LABEL,MODEL NAME 1
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 56
-
54
-
'14•SRK-T-164
CRAE0240
1
35
41
34
14
14
14
13
18
16
19
14
5
21
20
45
45
46
42
43
32
38
10
11 23
25
12
17
15
27
22
24
26
12
10
33
36
44
39
40
37
7
31
30
28
29
6
4
46
46
4
4
3
9
8
3
2
PANEL & FAN ASSY
Page 57
-
55
-
'14•SRK-T-164
SRK26CNS-S6
END ITEM NO. : RMA002F063AH
10 30 50 100 500 1000
16
RKW 102A 400H
PANEL ASSY,FRONT 1 1 1 1 2
1
RKW 122A 400C
PANEL,FRONT 1 1 1 1 2
2
RKW 435A 401F
PANEL ASSY,AIR IN 1 1 1 2 3
3 RKW 437A 400 FILTER,AIR 2 1 1 2 3 W458.5×H345.3(t2)
4
RKW 129A 214A
CAP 3 1 1 1 2
5 RKW 133A 401 PLATE,ORNAMENT 1 1 1 1 2
6
RKW 011G 400C
LABEL,WIRING 1
731
RKW 435A 202G
GRILLE ASSY,AIR OUT 1 1 1 2 3
7
RKW 435A 203B
GRILLE,AIR OUTLET 1 1 1 2 3
8
RKW 436A 200A
FLAP(A) 1 1 1 2 2 UPPER
9
RKW 436A 201A
FLAP(B) 1 1 1 2 2 LOWER
1011
RKW 436A 202B
LOUVER ASSY 1 1 1 2 2
10
RKW 436A 203A
LOUVER 6 1 1 2 2
11
RKW 129A 209A
PLATE,CONNECTING 1 1 1 1 2
1213
RKW 436A 202C
LOUVER ASSY 1 1 1 2 2
12
RKW 436A 203A
LOUVER 6 1 1 2 2
13
RKW 129A 209A
PLATE,CONNECTING 1 1 1 1 2
14 RKW 935C 200 COLLAR 8
1521
RKW 144A 200A
LINK ASSY 1 1 1 1 2
15
RKW 129A 208A
JOINT(L) 1 1 1 1 2
16 RKW 129A 210 BRACKET,MOTOR(A) 1 1 1 1 2
17 RKW 144A 201 LINK 1 1 1 1 2
18 RKW 144A 202 CRANK(A) 1 1 1 1 2
19 RKW 144A 203 CRANK(B) 1 1 1 1 2
20 RKW 144A 204 CRANK(C) 1 1 1 1 2
21 SSA 512T 049 MOTOR,STEPPING 2 1 1 1 2
FOR LOUVER(LEFT),FLAP
2225
RKW 144A 205A
CRANK ASSY 1 1 1 1 2
22
RKW 129A 207A
JOINT(R) 1 1 1 1 2
23 RKW 129A 211 BRACKET,MOTOR(B) 1 1 1 1 2
24 RKW 144A 204 CRANK(C) 1 1 1 1 2
25 SSA 512T 049 MOTOR,STEPPING 1 1 1 1 2 FOR LOUVER(RIGHT)
26 RKW 504A 401 HARNESS ASSY 1 1 1 1 2 FOR FLAP MOTOR
27 RKW 504A 402 HARNESS ASSY 1 1 1 1 2 FOR LOUVER MOTOR
28 SSA 423A 102A HOSE,DRAIN 1
29 SSA 326A 043 PLUG 1
30 RKW 116A 400 BRACKET,PANEL(R) 1 1 1 1 2
31 RKW 116A 401 BRACKET,PANEL(L) 1 1 1 1 2
32
RKW 111A 200C
BASE ASSY 1 1 1 1 2
33 SSA 512T 099 MOTOR,DC 1 1 1 1 2 FOR IMPELLER
34
SSA 431G 043B
IMPELLER 1 1 1 2 4
35 SSA 923C 114 BEARING,PLANE 1 1 1 1 2
36 RKW 129A 201 BRACKET,MOTOR(U) 1 1 1 1 2
37 RKW 129A 202 BRACKET,MOTOR(L) 1 1 1 1 2
No. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Note
Page 58
-
56
-
'14•SRK-T-164
SRK26CNS-S6
END ITEM NO. : RMA002F063AH
10 30 50 100 500 1000
No. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Note
38
RKW 032A 200A
PLATE,INSTALLATION 1 1 1 1 2
39 PHA 129A 302A COVER ASSY(PIPE) 1 1 1 1 2
40 RKW 132A 400 LID(R) 1 1 1 1 2
41 RKW 132A 401 LID(L) 1 1 1 1 2
4243 RKW 132A 403 LID ASSY(TERMINAL) 1 1 1 1 2
43
RSA 011H 027 LABEL,NOTICE
1
1 1 1 2
44
RKW 129A 405 COVER,PIPE
1
1 1 1 2
45
RKW 129A 213 HOLDER,FILTER
2
1 1 1 2
46 SSA 913A 007A SCREW,TAP 3 4×14
Page 59
-
57
-
'14•SRK-T-164
MEMO
Page 60
-
58
-
'14•SRK-T-164
CRAE0290
28
25
30
29
33
26
32
31
14
27
15
2
5
6
7
9
8
10
4
17
21
20
19
18
22
24
23
1
3
13
12
11
16
HEAT EXCH. & CONTROL
Page 61
-
59
-
'14•SRK-T-164
SRK26CNS-S6
END ITEM NO. : RMA002F063AH
10 30 50 100 500 1000
110 RMA 301A 008 HEAT EXCH ASSY(AIR) 1 1 1 1 2
2 RMA 315D 003 HEADER ASSY 1
3 RKW 129A 410 BRACKET ASSY(L) 1 1 1 1 2
410 RMA 315A 006 DISTRIBUTOR ASSY 1
4 RSA 315A 005 DISTRIBUTOR 1
5 RMA 321A 015 PIPE ASSY 1
2.8×ĭ 4.0 L100
6 RMA 315B 004 CAPILLARY 1
2.8×ĭ 4.0 L100
7 RMA 315B 005 CAPILLARY 1
2.8×ĭ 4.0 L100
8 RMA 321A 016 PIPE ASSY 1
2.8×ĭ 4.0 L100
9 RMA 321A 018 PIPE ASSY 1
2.8×ĭ 4.0 L100
10 RMA 321A 020 PIPE ASSY 1
2.8×ĭ 4.0 L100
1113 RMA 321A 030 PIPE ASSY 1
12 SSA 323F 012F UNION,SOLDER 1 FOR GAS
13 SSA 323F 088A UNION(SLD) 1 FOR LIQ.
14 RKW 129A 411 HOLDER ASSY,FILTER 1
1516 RKW 142A 400 BOX ASSY,CONTROL(R) 1
15 RKW 142A 402 BOX,CONTROL(R) 1
16 RKW 132A 404 COVER,CONTROL(R) 1
17 RKW 142A 401 BOX ASSY,CONTROL(L) 1
18 RKW 129A 407 HOLDER,SENSOR 1
19 SSA 551A 223H SENSOR ASSY 1 1 1 2 4
INCL.SENSOR (ROOM TEMP.& HEAT EXCH.)
20 SSA 551B 017C SENSOR(HUMIDITY) 1 1 1 2 4
21 SSA 561B 702B BLOCK,TERMINAL 1 1 1 2 2 T1
2224
RKY 505A 001JL
PWB ASSY 1 2 2 4 8
23
SSA 555B 058AD
VARISTOR 1 1 1 1 2 Z
24 SSA 564A 132 FUSE(CURRENT) 1 1 1 1 2 F 3.15A
25
RKW 503A 400A
DISPLAY ASSY 1 1 1 2 4
26
RKW 505A 400A
PWB ASSY(DISPLAY) 1 2 2 4 8
27 RKJ 941F 001A SPRING,LEAF 1
28
RMA 008A 016B
PARTS,STANDARD 1
29 RKX 502A 001 CONTROL ASSY,REMOTE 1 2 3 5 10
30 RMA 012A 078 MANUAL,INSTRUCTION 1
3132
RKW 437A 201A
FILTER ASSY,CLEAN 1
31 RKT 437A 005D FILTER,LIGHT CLEAN 1
32 RKT 437A 011D FILTER,CLEAN 1
33
RKN 032A 002C
HOLDER(REMO-CON) 1 1 1 1 2
(34)
RMA 011F 016BG
LABEL,MODEL NAME 1
NoteNo. Part No. Part Name
RE.Q
Recommendable Purchased Q'ty
Page 62
-
60
-
'14•SRK-T-164
CRBE0393
14
2
5
3
6
7
8
9
11
13
4
17
12
15
15
16
15
15
10
1
18
PANEL & FAN ASSY
Page 63
-
61
-
'14•SRK-T-164
END ITEM NO. : RMC003F062AH
10 30 50 100 500 1000
1
RWC 122A 004A
PANEL ASSY,FRONT 1 1 1 1 2
2
RWC 123A 005F
PANEL ASSY,SIDE(R) 1 1 1 1 2
3 RWC 123A 008 PANEL,SIDE(L) 1 1 1 1 2
4 RWC 124A 004 PANEL ASSY,TOP 1 1 1 1 2
5 RWC 132A 007 PANEL ASSY,SERVICE 1 1 1 1 2
6 RWC 435A 002 GRILLE,AIR OUTLET 1 1 1 2 3
7 SSA 944B 036B HANDLE 1
8 RWC 131A 004 GUARD,FIN 1
9
RWC 116A 04103
BRACKET,MOTOR 1
10 SSA 511B 818A MOTOR,AC 1 1 1 1 2
11 SSA 431B 233 PROPELLER 1 1 1 2 4
12 SSA 913A 034F SCREW,TAP 4 4×8
13
SSA 914B 007AD
NUT,TH 1
14 RMC 116A 002 BRACKET 1
15 W011D04X008 TAP-SCREW,CRS-TRS 2 5 4×8
16 RWC 141A 002 PLATE,BAFFLE 1
17 SSA 947B 019 GROMMET 1 1 1 2 4
18
RWC 111A 005R
BASE ASSY 1 1 1 1 2
SRC21CNS-S
6
RE.Q
Recommendable Purchased Q'ty
NoteNo. Part NO. Part Name
Page 64
-
62
-
'14•SRK-T-164
CRBE0394
1
2
20
22
14
13
12
10
11
9
5
6
8
23
18
19
7
3
4
(GAS)
(LIQ.)
CONTROL ASSY
151617
2125
2124
21
(TH3)
(TH2)
(TH1)
HEAT EXCH. & CONTROL
Page 65
-
63
-
'14•SRK-T-164
END ITEM NO. : RMC003F062AH
10 30 50 100 500 1000
1
RMC 301A 009A
HEAT EXCH ASSY(AIR) 1 1 1 1 2
2 RCK 116A 002 BRACKET(VALVE) 1
3 RCP 381A 001A VALVE,SERVICE(1/4") 1 1 1 1 2 LIQ.
4 RWC 381A 017 VALVE,SERVICE(5/8") 1 1 1 1 2 GAS
57 RWC 304A 137 PIPING ASSY(EXPAN) 1 1 1 1 2
5 SSA 387F 052 VALVE,BODY(EXP) 1 1 1 1 2 EEV
6 SSA 357A 005A STRAINER 1
7 RWC 315B 098 CAPILLARY,SUB 2
2.6×ĭ 4.0 L300
8 SSA 382F 210L COIL,SOLENOID 1 1 1 1 2 FOR EEV
9 RMC 201A 061 COMPRESSOR ASSY 1 1 2 3 8
10 RMC 941C 051 CUSHION,RUBBER 3
11 SSA 914C 013A NUT,FLANGE 3
12 RMC 932C 004 GASKET,COVER 1
13 RMC 947K 004 COVER,TERMINAL 1 1 1 2 4
14 RMC 914C 002 NUT,FLANGE 1
1517 RCR 505A 040F PWB ASSY 1 2 2 4 8
16
SSA 555B 058AD
VARISTOR 1 Z
17 SSA 564A 132 FUSE(CURRENT) 1 1 1 2 4 F 3.15A
18 SSA 561B 702B BLOCK,TERMINAL 1 1 1 2 2 T1
19 SSA 561B 665 BLOCK,TERMINAL 1 1 1 2 2 T2
20 RCP 504A 500A HARNESS ASSY 1 FOR COMP.
21 SSA 551A 185K SENSOR ASSY 1 1 1 2 4 TH1,TH2,TH3
22 SSA 552A 178F CAPACITOR,RUNNING 1 1 1 2 4 440VAC 45ȝF
23 SSA 552A 836A CAPACITOR,RUNNING 1 1 1 2 4 500VAC 2ȝF
24 RKJ 941F 001A SPRING,LEAF 1 FOR TH1
25 RCJ 941F 001 SPRING,LEAF 1 FOR TH2
(26)
RMC 011F 021CG
LABEL,MODEL NAME 1
SRC21CNS-S
6
RE.Q
Recommendable Purchased Q'ty
NoteNo. Part NO. Part Name
Page 66
-
64
-
'14•SRK-T-164
CRBE0395
11
7
1
2
8
12
20
4
20
13
10
6
5
3
13
9
13
15
14
16
17
21
18
19
20
PANEL & FAN ASSY
Page 67
-
65
-
'14•SRK-T-164
END ITEM NO. : RMC003F063AH
10 30 50 100 500 1000
1 RCR 122A 001 PANEL ASSY,FRONT 1 1 1 1 2
23
RCR 125A 002G
PANEL ASSY,REAR 1 1 1 1 2
3 SSA 944B 031A HANDLE 1
4
RCR 124A 002M
PANEL ASSY,TOP 1 1 1 1 2
56
RCR 122A 004A
PANEL ASSY,SERVICE 1 1 1 1 2
5
RCR 122A 006B
PANEL,SERVICE 1 1 1 1 2
6 SSA 944B 031A HANDLE 1
7
RCR 115A 002A
SUPPORT,CORNER 1
8 RCR 435A 001 GRILLE,AIR OUTLET 1 1 1 2 3
9
RCR 132A 004B
COVER ASSY,SERVICE 1
10 RCR 131A 002 GUARD,FIN(B) 1
11 RCR 132A 002 COVER,TERMINAL 1
12 SSA 913A 034F SCREW,TAP 20 4×8
13 SSA 913A 034G SCREW,TAP 6 4×12
14
RCR 116A 001A
BRACKET,MOTOR 1
15 SSA 511B 819 MOTOR,AC 1 1 1 1 2
16
RCR 141A 00102
PLATE,BAFFLE 1
17 SSA 431B 247A FAN,PROPELLER 1 1 1 2 4
18
SSA 914B 007AD
NUT,TH 1
19 W200H10 WASHER 1
20 W011D04X008 TAP-SCREW,CRS-TRS 2 4 4×8
21
RCR 111A 001D
BASE ASSY 1 1 1 1 2
SRC26CNS-S
6
RE.Q
Recommendable Purchased Q'ty
NoteNo. Part NO. Part Name
Page 68
-
66
-
'14•SRK-T-164
CRBE0396
1
2
8
9
21
23
24
16
15
14
13
12
10
6
6
5
7
11
20
4
(GAS)
3
(LIQ.)
CONTROL ASSY
171819
2226
(TH3)
22
(TH2)
2225
(TH1)
HEAT EXCH. & CONTROL
Page 69
-
67
-
'14•SRK-T-164
END ITEM NO. : RMC003F063AH
10 30 50 100 500 1000
1 RMC 301A 041 HEAT EXCH ASSY(AIR) 1 1 1 1 2
2 RCR 116A 003 BRACKET(VALVE) 1
3
RCR 381A 003B
VALVE,SERVICE(1/4") 1 1 1 1 2 LIQ.
4 RCR 381A 004 VALVE,SERVICE(5/8") 1 1 1 1 2 GAS
57 RMC 304A 025 PIPING ASSY(EXPAN) 1 1 1 1 2
5 SSA 387F 052 VALVE,BODY(EXP) 1 1 1 1 2 EEV
6 SSA 357A 005A STRAINER 2
7 RMC 315B 016 CAPILLARY 1
2.6×ĭ 4.0 L300
8 RMC 154D 013 INSULATION,COMP 1
9 RMC 154D 014 INSULATION 1
10 SSA 382F 210L COIL,SOLENOID 1 1 1 1 2 FOR EEV
11 RMC 201A 060 COMPRESSOR ASSY 1 1 2 3 8
12 RMC 941C 051 CUSHION,RUBBER 3
13 SSA 914C 013A NUT,FLANGE 3
14 RMC 932C 004 GASKET,COVER 1
15 RMC 947K 004 COVER,TERMINAL 1 1 1 2 4
16 RMC 914C 002 NUT,FLANGE 1
1719
RCR 505A 040G
PWB ASSY 1 2 2 4 8
18
SSA 555B 058AD
VARISTOR 1 Z
19 SSA 564A 132 FUSE(CURRENT) 1 1 1 2 4 F 3.15A
20 SSA 561B 723A BLOCK,TERMINAL 1 1 1 2 2 T
21 RMC 504A 012 HARNESS ASSY 1 FOR COMP.
22 SSA 551A 229 SENSOR ASSY 1 1 1 2 4 TH1,TH2,TH3
23 SSA 552A 178D CAPACITOR,RUNNING 1 1 1 2 4 440VAC 60ȝF
24 SSA 552A 836C CAPACITOR,RUNNING 1 1 1 2 4 450VAC 5ȝF
25 RKJ 941F 001A SPRING,LEAF 1 FOR TH1
26 RCJ 941F 001 SPRING,LEAF 1 FOR TH3
(27)
RMC 011F 021CL
LABEL,MODEL NAME 1
SRC26CNS-S
6
RE.Q
Recommendable Purchased Q'ty
NoteNo. Part NO. Part Name
Page 70
RESIDENTIAL AIR-CONDITIONING
TECHNICAL MANUAL & PARTS LIST
Copyright MITSUBISHI HEAVY INDUSTRIES, LTD.
Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice.
C
Loading...