Mitsubishi SRK18CL, SRK18CL-3, SRK18CL-6 Technical Manual

RESIDENTIAL AIR-CONDITIONING
TECHNICAL MANUAL & PARTS LIST
WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONER (Split system, air cooled cooling only type)
SRK18CL SRK18CL-3 SRK18CL-6
TECHNICAL MANUAL
-
1
-
'12 • SRK-T-125
CONTENTS
1. SPECIFICATIONS ........................................................................................ 3
(2) Outdoor units ....................................................................................... 6
(3) Wireless remote controller
................................................................... 6
............................................................................ 5
(1) Indoor units .......................................................................................... 5
2. EXTERIOR DIMENSIONS
3. ELECTRICAL WIRING ................................................................................. 7
(1) Indoor units .......................................................................................... 7
(2) Outdoor units ....................................................................................... 8
.......................................................... 10
5. RANGE OF USAGE & LIMITATIONS
4. PIPING SYSTEM ......................................................................................... 9
.................................................................................. 12
6. APPLICATION DATA
7. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ............... 21
(6) Timer operation
.................................................................................. 23
....................................................... 22
(1) Operation control function by remote controller
(5) Flap control ............................................................................................. 23
(4) Custom cord switching procedure
......................................................................... 22(3) Auto restart function
(2) Unit ON/OFF button
........................................................................... 22
.................................. 21
(8) Outline of automatic operation ........................................................... 24
(7) Outline of cooling operation ............................................................... 24
(9) Protective control function
................................................................... 25
..................... 27
.................................................................................. 26
(4) Troubleshooting procedure (If the air conditioner runs)
(3) Troubleshooting procedure
(If the air conditioner does not run at all)
........ 26
(1) Cautions
............................................................................................. 26
(2) Items to check before troubleshooting ................................................. 26
(5) Self-diagnosis table ............................................................................. 27
(6) Inspection procedures corresponding to detail of trouble .................... 28
8. MAINTENANCE DATA
-
2
-
'12 • SRK-T-125
'10 • SRK-T-099
(9) How to make sure of wireless remote controller .................................. 31
(7)
Phenomenon observed after shortcircuit, wire breakage on sensor
......... 29
(8) Checking the indoor electrical equipment
........................................... 30
How to read the model name
Example: SRK 18 C
Series code
For Indonesia
Cooling only type
Product capacity
Model name SRK : Wall mounted type
SRC : Outdoor unit
L -3
-
3
-
'12 • SRK-T-125
1. SPECIFICATIONS
Model
Item
SRK18CL (-3)
Indoor unit SRK18CL (-3) Outdoor unit SRC18CL (-3) Cooling capacity (1) W 5000 Power supply 1 Phase, 220/230/240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 1.70
Running current
Cooling
A
8.0/7.7/7.3 (220/230/240V)
Inrush current 37 COP Cooling 2.94 Noise level
Cooling
Sound level dB(A) Hi : 48 Me : 44 Lo : 42 50
Power level dB 64 65 Exterior dimensions (Height x Width x Depth) mm 309 x 890 x 251 640 x 850 (+65) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 12 37
Refrigerant equipment
Compressor type & Q'ty QJ292PBB(Rotary type) x 1 Motor (Starting method) kW 1.29 (PSC starting) Refrigerant oil 0.45 (SONISO 4GSI or ATMOS NM56) Refrigerant (3) kg R22 0.9 (Pre-Charged up to the piping length of 7m) Heat exchanger Louver fins & inner grooved tubing M fins & inner grooved tubing Refrigerant control Capillary tubes Deice control Microcomputer control
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 27 40 Air flow Cooling CMM 12.8 38 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless-Remote control — Room temperature control Microcomputer thermostat
Operation Display
RUN : Green, TIMER : Yellow, HI POWER : Green,
ECONO : Orange
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Fan motor error protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ15.88 (5/8") connecting method Flare connecting
Attached length of piping m
Liquid line : 0.55 Gas line : 0.49
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.10 (Outdoor unit is higher)
Max.10 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 20
Connection wiring
Size x Core number 1.5mm2 x 4 cores (Including earth cable) Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit
Optional parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230/240V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 7.5m connecting piping. (Purging is not required even for the short piping.)
The pipe length is 7.5m.
-
4
-
'12 • SRK-T-125
Model
Item
SRK18CL-6
Indoor unit SRK18CL-6 Outdoor unit SRC18CL-6 Cooling capacity (1) W 5000 Power supply 1 Phase, 220/230/240V, 50Hz
Operation data (1)
Power consumption
Cooling kW 1.72
Running current
Cooling
A
8.1/7.8/7.4 (220/230/240V)
Inrush current 37 COP Cooling 2.91 Noise level
Cooling
Sound level dB(A) Hi : 48 Me : 44 Lo : 42 50
Power level dB 64 65 Exterior dimensions (Height x Width x Depth) mm 309 x 890 x 251 640 x 850 (+65) x 290 Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight kg 12 37
Refrigerant equipment
Compressor type & Q'ty QJ292PBB(Rotary type) x 1 Motor (Starting method) kW 1.29 (PSC starting) Refrigerant oil 0.45 (SONISO 4GSI or ATMOS NM56) Refrigerant (3) kg R22 0.9 (Pre-Charged up to the piping length of 7m) Heat exchanger Louver fins & inner grooved tubing M fins & inner grooved tubing Refrigerant control Capillary tubes Deice control Microcomputer control
Air handling equipment
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1 Motor W 27 40 Air flow Cooling CMM 12.8 38 Fresh air intake Not possible — Air filter, Quality / Quantity Polypropylene net (washable) x 2
Shock & vibration absorber Cushion rubber (for compressor)
Operation control
Operation switch Wireless-Remote control — Room temperature control Microcomputer thermostat
Operation Display
RUN : Green, TIMER : Yellow, HI POWER : Green,
ECONO : Orange
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Fan motor error protection
Installation data
Refrigerant piping size (O.D) mm Liquid line: φ6.35 (1/4") Gas line: φ15.88 (5/8") connecting method Flare connecting
Attached length of piping m
Liquid line : 0.55 Gas line : 0.49
Insulation for piping Necessary (Both sides), independent Refrigerant line (one way) length
m
Max. 15
Vertical height difference between outdoor unit and indoor unit
Max.10 (Outdoor unit is higher)
Max.10 (Outdoor unit is lower) Drain hose Connectable (VP 16) — Power cable — Recommended breaker size A 20
Connection wiring
Size x Core number 1.5mm2 x 4 cores (Including earth cable) Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit
Optional parts
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature Outdoor air temperature
Standards
DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C ISO-T1, JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO. (3) The operation data are applied to the 220/230/240V districts respectively. (4) The refrigerant quantity to be charged includes the refrigerant in 7.5m connecting piping. (Purging is not required even for the short piping.)
The pipe length is 7.5m.
-
5
-
'12 • SRK-T-125
G
F
Space for installation and service when viewing from the front
Outlet for down piping
Refer to the above view
D C
A
E
B
Terminal block
881.9
59.926 20.9
59.9
46.5
61.5
46.5
61.5
890
309
9 61.5
3251
50 120 650 120 100
220 450 220
35 35
48.9222.5
48
48
5.7
295.4 7.9
15
Service space
70
Unit
54
46.5
Service space
Service space
Service space
Installation plate
491.1
520.8
559.1
58
61.5
2. EXTERIOR DIMENSIONS
(1) Indoor units
Model SRK18CL(-3) (-6)
Hole on wall for right rear piping
Hole on wall for left rear piping
Gas piping
Outlet for pipingon both side
Drain hose
Outlet for wiring
Liquid piping
F
G
E
CDB
Symbol
A
ø65
VP16
ø6.35(1/4")(Flare)
Content
ø15.88(5/8")(Flare)
ø65
Wireless remote controller
Unit:mm
60
150
17.3
-
6
-
'12 • SRK-T-125
Drain holes
286.4
12
50
290
49.6
43.5
850
203.1
510 136.9
476
Elogated hole (2-12 x16)
314
12
328
Terminal block
Service valve (Liquid) ø6.35 (1/4'')
Service valve (Gas) ø15.88 (5/8'')
Ground terminal
124
34.6
20 °
20
°
42.7
100.3
15
640
14
(2) Outdoor unit
Model SRC18CL(-3) (-6)
Unit: mm
(3) Wireless remote controller
Unit: mm
60
17.3
150
-
7
-
'12 • SRK-T-125
3. ELECTRICAL WIRING
(1) Indoor units
Model SRK18CL(-3) (-6)
250V
FUSE
3.15A
S/N
VARISTOR
FAN MOTOR
CNU
U
M
1 3 4 5 6
TO OUTSIDE
T
TERMINAL
1
2/N
3
UNIT
BLOCK
HEAT
EXCHANGER
BOARD
CIRCUIT
PRINTED
FLAP
CNX2
M
5
MOTOR
BLUE
WHITE
RED
WHITE
BLACK
BLUE
YELLOW
BLACK
CNG
CNE
DISPLAY
WIRELESS RECEIVER
BACK-UP SW
9
HEAT EXCHANGER SENSOR 1
ROOM TEMP. SENSOR
52C-4
52C-3
t
t
5
-
8
-
'12 • SRK-T-125
(2) Outdoor units
Model SRC18CL(-3) (-6)
Sh
WH
BL
OR
RD WH WH
WH
OR
OR
FMo
WH
BL
BL
WH
R
C
CM
S
RD
WH
BL
YGN
MARK
RD RED
COLOR
ORANGE
BLACK
BLUE
BK
OR
BL
WH WHITE
INDOOR UNIT
POWER SOURCE 220-240V 50Hz
YGN
YELLOW
GREEN
CFO
CC
2N
3
T
1L
RCR011G003BC
RUNNING CAPACITOR FOR COMPRESSOR RUNNING CAPACITOR FOR FAN MOTORCFO
CC
FAN MOTOR
COMPRESSOR MOTOR
FMo
CM
PARTS NAME
SYMBOL
MEANING OF MARK
CONNECTOR TERMINAL BLOCKT
Sh
G
RCR011G0 0 3 B C
-
9
-
'12 • SRK-T-125
4. PIPING SYSTEM
Model SRK18CL(-3) (-6)
Outdoor unitIndoor unit
Room temp. sensor
Heat exchanger
Flare connecting
Heat exchanger sensor
Piping (Liquid) ø
6.35
Piping (Gas)
ø15.88
Check joint
Service valve (Liquid)
Flare connecting
Heat exchanger
Compressor
Capillary tube Capillary tube
Accumulator
Service valve (Gas)
-
10
-
'12 • SRK-T-125
5. RANGE OF USAGE & LIMITATIONS
Net capacity = Capacity shown on specification Correction factors as follows.
(1) Coefficient of cooling capacity in relation to temperatures
All models
Models
Item
Indoor return air temperature (
Upper, lower limits
)
Outdoor air temperature (
Upper, lower limits
)
Refer to the selection chart
Refrigerant line (one way) length
Max. 15m
Max. 10m (Outdoor unit is higher
)
Max. 10m (Outdoor unit is lower
)
Min. 3 minutes
Max. 10 times/h
Min. 85% of rating
Vertical height difference between outdoor unit and indoor unit
Power source voltage
Voltage at starting
Frequency of ON−OFF cycle
ON and OFF interval
Rating 10%
16 18 20 22
21
25
30
35
40
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
43
24
ISO-T1 Standard ConditionIndoor air W.B. temperature ° C W.B.
Cooling
Applicable range
Coefficient of cooling
capacity in
relation to temperature
Cooling operation
Outdoor air D.B.
temperature
°C D.B.
-
11
-
'12 • SRK-T-125
(2) Correction of cooling capacity in relation to one way length of refrigerant piping
How to obtain the cooling capacity
=
Piping length [m]
Cooling
7
1.0
10
0.99
15
0.975
SRK18CL
5000 4875
-
12
-
'12 • SRK-T-125
6. APPLICATION DATA
Safety precautions
When installing the unit, be sure to check and satisfy the requirements in the selection of installation location, power supply specifica-
tions, usage limitation (piping length, height differences between indoor and outdoor units, power supply voltage and etc.) and installa­tion spaces.
Read the “SAFETY PRECAUTIONS” carefully first of all and strictly follow it during the installation work in order to protect yourself.
The precautionary items mentioned below are distinguished into two levels, WARNING and CAUTION .
WARNING : Wrong installation would cause serious consequences such as injuries or death. CAUTION : Wrong installation might cause serious consequences depending on circumstances.
Both mentions the important items to protect your health and safety so strictly follow them by any means.
Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the operating methods as well as the maintenance methods of this equipment to the user according to the owner’s manual.
Keep the installation manual together with owner’s manual at a place where any user can read at any time. Moreover if necessary, ask to hand them to a new user.
For installing qualified personnel, take precautions in respect to themselves by using suitable protective clothing, gloves, etc., and then perform the installation works.
Please pay attention not to fall down the tools, etc. when installing the unit at the high position.
If unusual noise can be heard during operation, consult the dealer.
The meanings of “Marks” used here are shown as follows:
Ne ve r do it un de r an y circumstances.
Always do it according to the instruction.
WARNING
Insta llation m ust be ca rried out by the qu alified i nstaller.
If you install th e sy stem by yourse lf, it m ay cause serious t rouble such as water leaks, ele ctric sh ocks, fir e and personal i njury, a s a resu lt of a system malfunct ion.
Insta ll the sy stem in f ull accor dance with the inst ruction m anual.
Incorrec t installa tion may ca use bursts , personal injury, wat er leaks, e lectric shocks a nd fire.
Be su re to use only for househol d and resi dence.
If this appliance is installed in inferi or en vironment suc h as mach ine shop and etc. , it can cause malfunction.
Use the ori ginal accessories and the specified components for ins talla-
tion.
If parts o ther than t hose prescribed by u s are used, It may caus e water le aks, electric shocks, fire and p ersonal i njury.
Insta ll the un it in a l ocation w ith good s upport.
Unsuitab le installa tion locati ons can cause the unit to fall and cause mate rial damage a nd personal injury.
Venti late the working area well in t he event of refr igerant leakage d ur-
ing inst allation.
If the refrigerant comes into contact with na ked flames, poisonous gas is produced .
When i nstalling in small ro oms, take p revention measures n ot to excee d
the density limit of refrigerant in the event of leakage, referred by th e formula (accordan ce with I SO5149).
If the densit y of refriger ant exc eeds th e limit , pleas e consu lt the dealer and install the ventilation system, otherw ise lack of oxyge n can occur, which can cause se rious acc ident.
After c ompleted installatio n, check tha t n o refrigera nt leaks from t he
system.
If refrigerant leaks into the roo m a nd comes int o contact with an oven or other ho t surface , poisonous gas is produced.
Tight en the fl are nut b y torque wrench wit h specifi ed method .
If the flare nut were tig htened with ex cess tor que, th is may cause burst and refriger ant leaka ge after a long per iod.
Do not ope n the operatio n valves for liquid line an d gas line u ntil com -
pleted r efrigeran t piping work, air tightness test and evacuati on.
If the c ompresso r is oper ated in state of opening operation valves before complete d connec tion of refrige rant piping wor k, air can be sucked into re­frigeran t circuit, whi ch can cause bus t or personal in jury due to anoma lously high pre ssure in the refrigerant.
Do not put the dr ainage pi pe directl y into dra inage chan nels where poi-
sonous g ases such as sulph ide gas ca n occur.
Poisonou s gases will fl ow into the roo m through dra inage pipe an d seriously affect t he user’s health and safety.
Ensur e that no air enters in the re frigerant circu it when the unit is in-
stalled and remove d.
If a ir en ters in th e ref rigerant circuit, the pressur e in the refr igerant circuit becomes too high, which can cause bu rst and p ersonal i njury.
Do not proces s, splice the power cord, or share a socket with other power
plugs.
This ma y cause fire or electric shock d ue to d efecting contact, defecting in­sulation and over-current e tc.
The electrical installation must be carr ied out by th e qu alified electri-
cian in accor dance with “t he norm for elect rical work” an d “ national wiring regulation”, and the s ystem must b e conn ected to the dedic ated circuit.
Power supply w ith ins ufficient capacit y and incorrec t functi on done by im ­proper w ork can c ause electric shock s and fir e.
Be su re to shu t off the power be fore start ing elect rical wor k.
Failure t o shut off the power can cause electric shocks, u nit failur e or incor ­rect fun ction of equipment.
Be sure to use the ca bles conf ormed to saf ety standa rd and cable
ampacity for powe r distrib ution wor k.
Unconfor mable cables can cause elect ric leak, anomalous heat prod uction or fire.
This appliance mu st be connected to main power supply by means o f a
circuit br eaker or swit ch (fuse:20 A) with a conta ct separati on of at least 3mm.
Wh en pl uggi ng th is ap pli anc e, a p lug con form ing t o th e nor m
IEC60884 -1 must b e used.
Use the prescribed cables for e lectrical connectio n, tighten the cab les
securely in terminal block a nd relieve the cab les correctly to p revent overload ing the t erminal b locks.
Loose conn ections or c able mounti ngs can cause anomalous h eat product ion or fire.
Arran ge the wirin g in the cont rol box so that it canno t be pushed up
further into the box. Inst all the se rvice pan el correc tly.
Incorrec t install ation may result in overheat ing and f ire.
Be su re to fix up the s ervice pa nels.
Incorrec t fixin g can cause electric shocks or f ire due to i ntrusion of dust or water.
Be sure to switch off the power supply in the event of instal lation, inspe c-
tion or servicing .
If the powe r s upply is not s hut off, there is a risk of elec tric shocks, unit failure or person al injury due to th e unexpec ted start of fan.
Stop the compressor before disconnecting refrigerant p ipes in cas e of
pump dow n operati on.
If disconnecting refri gerant pipe s in state of openi ng operatio n valves befor e compress or sto pping, air can be suc ked, which can ca use b urst o r pers onal injury d ue to ano malously high press ure in th e refrige rant circ uit
Only u se prescrib ed optional parts. The in stallatio n must be carr ied out
by the q ualified installer .
If you ins tall the sy stem by yourself, it ca n cause serious trouble such as water le aks, electric shock s, fire.
Do not bundle, wind or process for the power cord. Or, do not deform
the powe r plug du e to trea d it.
This may cause fi re or heating.
Do no t vent R 410A into the atm osphere : R410A is a fluor inated gr een-
house g as, cov ered by the Kyoto Pr otocol w ith Glo bal Warm ing Pote n­tial (GW P)=1975.
Do no t run the unit wit h removed panels or protecti ons.
Touching rotati ng equi pments, hot surfaces or high v oltage parts c an caus e personal injury d ue to entrapment, b urn or el ectric sh ocks.
Do not perfor m any change of pro tective devi ce itself or its setup conditi on.
The forced ope ration by short -circuiting protective device of pressur e switch and temp erature controller or the use of n on speci fied comp onent can cause fire or burst.
Carry out the electrica l work fo r ground l ead with care.
Do not connect the ground l ead to the gas line , water line, light ning cond uctor or t elephone line’s gr ound lead. Incorrec t groundi ng can ca use unit f aults suc h as elect ric shock s due to short-cir cuiting.